JENN-AIRTM36"(91.4CM) WALL-MOUNT
CANOPY RANGEHOOD
HOTTEDECUISINII:REJENN-AIRTMPOUR
II
MONTAGEMURAL36 (91,4 CM)
InstallationInstructionsandUse&Care Guide
For questions about features, operation/performance, parts, accessories, or service in the U.S.A., call:
1-800-JENNAIR (1-800-536-6247), or visit our website at www.jennair.com.
In Canada, call: 1-800-807-6777, or visit our website at www.jennair.ca.
Instructionsd'installationet Guide d'utilisationetd'entretien
Au Canada, pour assistance, installation ou service, composez le 1-800-807-6777 ou visitez notre site web _]www.jennair.ca.
Table of Contents/Table des mati_res ..................... 2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION RI_SIDENTIELLE UNIQUEMENT.
JENN-AIR°
LI3UUB/W102743200
TABLEOF CONTENTS
TABLEDESMATIERES
RANGE HOOD SAFETY ................................................................. 3
INSTALLATION REQUIREMENTS ................................................ 4
Tools and Parts ............................................................................ 4
Location Requirements ................................................................ 5
Venting Requirements .................................................................. 6
Electrical Requirements ............................................................... 7
INSTALLATION INSTRUCTIONS .................................................. 8
Prepare Location.......................................................................... 8
Install Range Hood ....................................................................... 9
Connect Vent System .................................................................. 9
Install Vent Covers ..................................................................... 10
Complete Installation ................................................................. 10
RANGE HOOD USE ...................................................................... 10
Display ........................................................................................ 10
Light............................................................................................ 11
Timer ........................................................................................... 11
Fan Speed Buttons .................................................................... 11
RANGE HOOD CARE ................................................................... 12
Cleaning ...................................................................................... 12
WIRING DIAGRAM ...................................................................... 13
ASSISTANCE OR SERVICE ......................................................... 14
WAR RANTY .................................................................................. 15
SI_CURITI_ DE LA HOTTE DE CUlSINII_RE ............................... 17
EXIGENCES D'INSTALLATION ................................................... 19
Outils et pieces ........................................................................... 19
Exigences d'emplacement ......................................................... 19
Exigences concernant I'evacuation ........................................... 20
Specifications electriques .......................................................... 22
INSTRUCTIONS D'INSTALLATION ............................................. 23
Preparation de I'emplacement ................................................... 23
Installation de la hotte ................................................................ 24
Raccordement du circuit d'evacuation ...................................... 24
Installation des cache-conduits ................................................. 25
Achever I'installation .................................................................. 25
UTILISATION DE LA HOI-I'E ....................................................... 25
Affichage ..................................................................................... 25
Eclairage ..................................................................................... 26
Minuterie ..................................................................................... 26
Boutons de vitesse du ventilateur .............................................. 26
ENTRETIEN DE LA HOTTE .......................................................... 27
Nettoyage ................................................................................... 27
SCHI_MA DE CABLAGE .............................................................. 28
ASSISTANCE OU SERVICE ......................................................... 29
GARANTIE ..................................................................................... 30
2
RANGE HOOD SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow
instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
iMPORTANT SAFETY iNSTRUCTiONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
• Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
• Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
• Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
• Do not operate any fan with a damaged cord or plug.
Discard fan or return to an authorized service facility for
examination and/or repair.
• Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
• When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
• Ducted fans must always be vented outdoors.
CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
[] Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
[] Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flamb6).
[] Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
[] Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING: =
[] SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
[] NEVER PICK UP A FLAMING PAN - you may be burned.
[] DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
[] Use an extinguisher ONLY if:
- You know you have a class ABC extinguisher, and you
already know how to operate it.
- The fire is small and contained in the area where it
started.
- The fire department is being called.
- You can fight the fire with your back to an exit.
=Based on "Kitchen Fire Safety Tips" published by NFPA.
[] WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control
device.
READ AND SAVE THESE INSTRUCTIONS
INSTALLATIONREQUIREMENTS
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools needed
• Level
• Drill with 1W' (3.0 cm), 3/8"(9.5 mm), and 8Ad'(7.9 mm)
drill bits
• Pencil
• Wire stripper or utility knife
• Tape measure or ruler
• Pliers
• Caulking gun and weatherproof caulking compound
• Vent clamps
• Jigsaw or keyhole saw
• Flat-blade screwdriver
• Metal snips
• Phillips screwdriver
• Metric Allen wrench set
Parts needed
For vented installations, you will also need:
• 1 wall or roof cap
• Metal vent system
For non-vented (recirculating) installations, you will also
need:
• Recirculation Kit Part Number W10272063 for non-vented
(recirculating) installations only. See "Assistance or Service"
section to order.
• 6" (15.2 cm) dia. round metal vent duct - length required is
determined by ceiling height.
Parts supplied
Remove parts from packages. Check that all parts are included.
• Hood canopy assembly with ventilator and light bulbs
installed
• Vent transition with back draft dampers installed
• Metal grease filter(s)
• Vent cover support bracket
• Mounting template
• 2-piece vent cover
• 2 - 3.5 x 6.5 mm screws
• 2 - 2.9 x 6.5 mm screws
• 6- 5 x 45 mm mounting screws
• 2 - 8 x 40 mm wall anchors
• 4- 10 x 50 mm wall anchors
Product Dimensions
81/16" 81/8"
(20.4 cm) (20.7 cm)
141/8. 42%o" (107.2 cm) max.
(3_.9cm) I
36" (91.4 cm)
*For non-vented (recirculating) installations
**For vented installations
Cabinet Dimensions
20" (50.8 cm)
*281%o" (73.4 cm) rain.
*'287/8" (73.3 ore) rain.
387/16"(97.6 cm) max.
IMPORTANT: Observe all governing codes and ordinances.
Have a qualified technician install the range hood, It is the
installer's responsibility to comply with installation clearances
specified on the model/serial rating plate. The model/serial rating
plate is located behind the left filter on the rear wall of the vent
hood.
Canopy hood location should be away from strong draft areas,
such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given
dimensions provide minimum clearance.
Grounded electrical outlet is required. See "Electrical
Requirements" section.
The canopy hood is factory set for venting through the roof or
wall. For non-vented (recirculating) Installation see "For Non-
vented (recirculating) Installations Only" in "Connect Vent
System" section. Recirculation Kit Part Number W10272063 is
available from your dealer or an authorized parts distributor.
All openings in ceiling and wall where canopy hood will be
installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local
codes.
power
supply cable
entry location
"/ I "-.. 15" (38.1 cm)
Side
cabinet
-- _ 36" (71.4 cm)
//*+// "%".%_
x i
bottom of
canopy
to cooking I
surface
iCenterline
Cookinq surface
*For non-vented (recirculating) installations
*NOTE: The range hood chimneys are adjustable and designed
to meet varying ceiling or soffit heights depending on the
distance "X" between the bottom of the range hood and the
cooking surface. For higher ceilings, a Stainless Steel Chimney
Extension Kit Part Number W10272070 is available from your
dealer or an authorized parts distributor. The chimney extension
replaces the upper chimney shipped with the range hood.
IMPORTANT:
Minimum distance "X": 27" (68.6 cm) from electric cooking
surface.
Minimum distance "X": 30" (76.2 cm) from gas cooking
surfaces.
Suggested maximum distance "X": 36" (91.4 cm)
For vented installations, the chimneys can be adjusted for
ceilings between 7' 11" (2.4 m) and 8' 8" (2.6 m).
For non-vented (recirculating) installations, the chimneys can
be adjusted for ceilings between 7' 11" (2.4 m) and 9' 0" (2.7 m).
Ventsystemmustterminatetotheoutdoors,exceptfornon-
vented (recirculating) installations.
Do not terminate the vent system in an attic or other enclosed
area.
• Do not use 4" (10.2 cm) laundry-type wall cap.
• Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
• The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
• Use no more than three 90° elbows.
• Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
• Do not install 2 elbows together.
• Use clamps to seal all joints in the vent system.
• The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
• Use caulking to seal exterior wall or roof opening around the
cap.
• The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Roof Venting
Wall Venting Non-vented
(recirculating)
B
A. Roof cap A. Wall cap A. Deflector
B. 6" (15.2 cm) B. 6" (15.2 cm) B. 6" (15.2 cm)
round vent round vent round vent
B
A
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft ....
(0.8 m)
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This canopy hood is factory set for venting through the roof or
wall.
A 6" (15.2 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 6" (15.2 cm) round.
NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that greatly reduce
performance.
Vent system can terminate either through the roof or wall. To vent
through a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may be installed immediately above the hood.
For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting a charcoal filter and the deflector. Fumes and
vapors are recycled through the top grille.
90° elbow 5.0 ft
(1.5m)
Maximum equivalent vent length is 35 ft (10.7 m).
Example vent system
,oo I o. ....W°,,
The following example falls within the maximum recommended
vent length of 35 ft (10.7 m).
1 - 90 ° elbow = 5.0 ft (1.5 m)
1 - wall cap = 0.0 ft (0.0 m)
8 ft (2.4 m) straight = 8.0 ft (2.4 m)
Length of system = 13.0 ft (3.9 m)
6
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
IMPORTANT: The range hood must be electrically grounded in
accordance with local codes and ordinances, or in the absence
of local codes, with the National Electrical Code, ANSI/NFPA 70
(latest edition) or Canadian Electrical Code, CSA C22.1
No. 0-M91 (latest edition).
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
• A 120 volt, 60 Hz, AC only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this range hood be provided.
• This range hood is equipped with a power supply cord having
a 3 prong grounding plug.
• To minimize possible shock hazard, the cord must be
plugged into a mating, 3 prong, grounding-type outlet,
grounded in accordance with local codes and ordinances. If a
mating outlet is not available, it is the personal responsibility
and obligation of the customer to have the properly grounded
outlet installed by a qualified electrician.
• The grounded 3 prong outlet is to be located above the range
hood at a maximum distance of 337_e'' (85.0 cm) from where
the power cord exits the hood. See illustration.
T
337/%"
(85 cm)
[
GROUNDING INSTRUCTIONS
• For a grounded, cord-connected range hood:
This range hood must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing an escape wire for the electric current.
This range hood is equipped with a cord having a grounding
wire with a grounding plug.The plug must be plugged into
an outlet that is properly installed and grounded.
WARNING: Improper grounding can result in a risk of
electric shock.
Consult a qualified electrician if the grounding instructions
are not completely understood, or if doubt exists as to
whether the range hood is properly grounded.
Do not use an extension cord. Ifthe power supply cord is too
short, have a qualified electrician install an outlet near the
range hood.
SAVE THESE INSTRUCTIONS
INSTALLATIONINSTRUCTIONS
• It is recommended that the vent system be installed before 8. Mark centers of the fastener locations through the template
hood is installed, to the wall.
• Before making cutouts, make sure there is proper clearance
within the ceiling or wall for exhaust vent.
• Check your ceiling height and the hood height maximum
before you select your hood.
1. Disconnect power.
2. Determine which venting method to use: roof, wall, or non-
vented.
3. Select a flat surface for assembling the range hood. Place
covering over that surface.
IMPORTANT: All screws must be installed into wood. If there
is no wood to screw into, additional wall framing supports
may be required.
Remove the template.
g=
Drill 3Ad'(4.8 mm) pilot holes at all locations where screws are
being installed into wood.
10.
Install the 2 - 5 x 45 mm mounting screws. Leave a
1/4"(6.4 mm) gap between the wall and the back of the
screw head to slide range hood into place.
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
4. Using 2 or more people, lift range hood onto covered surface.
Range Hood Mounting Screws Installation
5. Determine and mark the centerline on the wall where the
canopy hood will be installed.
6. Select a mounting height between a minimum of
27" (68.6 cm) for an electric cooking surface, a minimum
of 30" (76.2 cm) for a gas cooking surface, and a suggested
maximum of 36" (91.4 cm) above the range to the bottom
of the hood. Mark a reference line on the wall.
7. Tape template in place, aligning the template centerline and
bottom of template with hood bottom line and with the
centerline marked on the wall.
=
i
:......................................A
i
i.
(6.4rnrn) _
Vent Cover Support Bracket Installation
Installations using telescoping upper and lower vent cover
assembly
1. Position vent cover bracket on wall about 1/8"(3.0 mm) away
from the ceiling.
2. Mark the hole locations.
3. Drill 3/8"(9.5 mm) holes for wall anchors and insert anchors
flush with the wall.
A. 8 x 40 mm drywall anchors
B. Centerline on wall
C. Vent cover support bracket
D. 5 x 45 mm screws
4. Attach vent cover support bracket to wall.
Complete Preparation
1. Determine and make all necessary cuts in the wall for the vent
system. Install the vent system before installing the hood. See
"Venting Requirements" section.
2. Use caulk to seal all openings.
i7
B
A. Centerline
B. Fastener locations
C. Mounting height reference
d,! ..........
C
8
1.
Using 2 or more people, hang range hood on 2 mounting
screws through the mounting slots on back of hood.
A I
C
A. Mounting screws
B. Mounting slots
C. Lower mounting screws
2. Remove the grease filter. See "Range Hood Care" section.
3. Level the range hood and tighten upper mounting screws.
4. Install 2 - 5 x 45 mm lower mounting screws and tighten.
For non-vented (recirculating) installation only:
1. Assemble the air deflector with the duct cover bracket with
2 - assembly screws provided with the Recirculation Kit.
B
C
A. Ventcover bracket
B.2.9 x 6.5 mm screws
C.Deflector
2.
Measure from the bottom of the air deflector to the bottom of
the hood outlet.
g ................................
D
X---------------------C
E .............
1.
Install transition on top of hood (if removed for shipping) with
2 - 3.5 x 6.5 mm sheet metal screws.
A
A. Vent transition
B. 3.5 x 6.5 mm screw
For vented installations only:
1. Fit vent system over transition piece.
2. Seal connection with clamps.
3. Check that back draft dampers work properly.
A.Air deflector
B. Ventclamp
C.X = length to cut vent duct
D. Ventduct
E.Exhaustoutlet
3.
Cut the duct to the measured size (X).
4.
Remove the air deflector.
5.
Slide the duct onto the bottom of the air deflector.
6.
Place the assembled air deflector and duct over the exhaust
outlet from the hood.
7.
Reassemble the air deflector to the duct cover bracket with
2 assembly screws.
8. Sealconnectionswithventclamps.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to folow these instructions can result in death,
fire, or electrical shock.
RANGE HOOD USE
The range hood is designed to remove smoke, cooking vapors
and odors from the cooktop area. For best results, start the hood
before cooking and allow it to operate several minutes after the
cooking is complete to clear all smoke and odors from the
kitchen.
The range hood controls are located on the front side of the
canopy.
\
9. Plug 3 prong power cord into a grounded 3 prong outlet
located above the range hood.
n C
When using both upper and lower vent covers, push lower cover
down onto hood and lift upper cover to ceiling and install with
two 2.9 x 6.5 mm screws.
NOTE: For vented installations, the upper vent cover may be
reversed to hide slots.
A. Upper vent cover
B. Lower vent cover
C. 2.9 x 6.5 mm screws
D. Bracket
G
D
A. Louver holes (non-vented
[recirculating] installations only)
B.Duct covers
C. Canopy
Control Panel
The range hood controls are located on the front side of the
canopy.
A B C D E
:_ IIJENN-AIR BSBB
[_o.........................
Q Clean grease fll er
A.Power decrease
B.Power increase
C.Display
D.Light
E.Timer
D. Grease filters
E. Lamp housings
F. Grease filter handles
G. Control panel
1. For non-vented (recirculating) installations only, install
charcoal filters over grille on blower housing. See the "Range
Hood Care" section.
2. Install metal filters. See the "Range Hood Care" section.
3. Check the operation of the range hood blower and light. See
the "Range Hood Use" section.
NOTE: To get the most efficient use from your new range hood,
read the "Range Hood Use" section.
10
Grease Filter Saturation Alarm
After 30 hours of fan function, the display will show "Clean
Grease Filter" when the fan is active. When this icon shows in the
display, the installed grease filters should be washed. See
"Range Hood Care" section.
• To reset the grease filter saturation alarm, press and hold the
POWER INCREASE button for 5 seconds. The "Clean Grease
Filter" icon will no longer be displayed.