JENN-AIR_ 86 (91,4 ©M) WALL-MOUNT
CANOPY RANGE HOOD
HOWE DE CUISINIERE JENN-AIR ®POUR
MONTAGE MURAL 36 (9 ,40M)
_ 1
For questions about features, operation/performance, parts, accessories, or service in the U.S.A., call:
1-800-JENNAIR (1-800-536-6247} or visit our website at www.jennair.com.
In Canada, call: 1-800-JENNAIR (1-800-536-6247}, or visit our website at www.jennair.ca.
Au Canada, pour assistance, installation ou service, composez le 1-800-JENNAIR (1-800-536-6247) ou visitez notre site web
www.jennair.ca.
Table of Contents/Table des mati@res............. 2
iMPORTANT: READ AND SAVE THESE iNSTRUCTiONS.
FOR RESiDENTiAL USE ONLY.
iMPORTANT : LiRE ET CONSERVER CES iNSTRUCTiONS.
POUR UTILISATION Rf-ZSIDENTIELLE UNIQUEMENT.
JENN-AIR °
2845/W10640309B
TABLE OF CONTENTS
RANGE HOOD SAFETY ................................................................. 3
INSTALLATION REQUIREMENTS ................................................ 5
Tools and Parts ............................................................................ 5
Location Requirements ................................................................ 5
Venting Requirements .................................................................. 6
Electrical Requirements ............................................................... 7
INSTALLATION INSTRUCTIONS .................................................. 9
Prepare Location .......................................................................... 9
Install Range Hood ..................................................................... 11
Connect Vent System ................................................................ 11
Reinstall Motor ........................................................................... 12
Make Electrical Connection ....................................................... 12
Install Chimney Covers .............................................................. 13
Complete Installation ................................................................. 14
Range Hood Use ........................................................................ 14
Controls and Features ................................................................ 14
RANGE HOOD CARE ................................................................... 15
Cleaning ...................................................................................... 15
WIRING DIAGRAM ...................................................................... 17
ASSISTANCE OR SERVICE ......................................................... 18
In the U.S.A................................................................................ 18
Accessories ................................................................................ 18
In Canada ................................................................................... 18
WAR RANTY ................................................................................. 19
TABLE DES MATIERES
SI_CURITI_ DE LA HOTTE DE CUlSINII_RE ................................ 20
EXIGENCES D'INSTALLATION ................................................... 22
Outils et pieces ........................................................................... 22
Exigences d'emplacement ......................................................... 22
Exigences concernant I'evacuation ........................................... 23
Specifications electriques .......................................................... 25
INSTRUCTIONS D'INSTALLATION ............................................. 27
Preparation de I'emplacement ................................................... 27
Installation de la hotte ................................................................ 29
Raccordement du circuit d'evacuation ...................................... 29
Remontage du moteur ............................................................... 30
Raccordement electrique ........................................................... 30
Installer les cache-conduits ....................................................... 31
Achever I'installation .................................................................. 32
UTILISATION DE LA HOTTE ....................................................... 32
Commandes et caracteristiques ................................................ 32
ENTRETIEN DE LA Ho'n'E .......................................................... 34
Nettoyage ................................................................................... 34
SCHI_MA DE CABLAGE .............................................................. 36
ASSISTANCE OU SERVICE ......................................................... 37
Au Canada .................................................................................. 37
Accessoires ................................................................................ 37
GARANTIE .................................................................................... 38
2
RANGE HOOD SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow
instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
State of California Proposition 65 Warnings:
WARNING: This product contains one or more chemicals known to the State of California to cause cancer.
WARNING: This product contains one or more chemicals known to the State of California to cause birth defects or other
reproductive harm.
iMPORTANT SAFETY iNSTRUCTiONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
m Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
m Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
m Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
m Do not operate any fan with a damaged cord or plug.
Discard fan or return to an authorized service facility for
examination and/or repair.
m Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
m When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
m Ducted fans must always be vented outdoors.
CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
m Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
m Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flamb6).
m Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
m Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING: a
m SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
m NEVER PICK UP A FLAMING PAN - you may be burned.
m DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
m Use an extinguisher ONLY if:
- You know you have a class ABC extinguisher, and you
already know how to operate it.
- The fire is small and contained in the area where it
started.
- The fire department is being called.
- You can fight the fire with your back to an exit.
aBased on "Kitchen Fire Safety Tips" published by NFPA.
m WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control
device.
READ AND SAVE THESE INSTRUCTIONS
INSTALLATION REQUIREMENTS
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools needed
• Level
• Drill with 11¼'' (3.0 cm) and 3/le" (5.0 mm) drill bits
• Pencil
• Wire stripper or utility knife
• Tape measure or ruler
• Pliers
• Caulking gun and weatherproof caulking compound
• Vent clamps
• Jigsaw or keyhole saw
• Flat-blade screwdriver
• Metal snips
• Phillips screwdriver
• T20®tTorx®bit or driver
Parts needed
For hard wire installations, you will also need:
• Home power supply cable
• 1/2"(12.7 mm) UL listed or CSA approved strain relief
For vented installations, you will also need:
• 1 wall or roof cap
• Metal vent system
For non-vented (recirculating) installations, you will also
need:
• Recirculation Kit Part Number W10646866 for non-vented
(recirculating) installations only. See "Assistance or Service"
section to order.
• Charcoal Filter Kit Part Number W10272069. See "Assistance
or Service" section to order.
IMPORTANT: Observe all governing codes and ordinances.
Have a qualified technician install the range hood. It is the
installer's responsibility to comply with installation clearances
specified on the model/serial rating plate. The model/serial rating
plate is located behind the left filter on the rear wall of the vent
hood.
Canopy hood location should be away from strong draft areas,
such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given
dimensions provide minimum clearance.
The canopy hood mounting location must be capable of
supporting 100 Ibs (45.4 kg).
This range hood is recommended for use with cooktops with a
maximum total rating of 78,000 BTUs or less.
Grounded electrical outlet is required. See "Electrical
Requirements" section.
The canopy hood is factory set for venting through the roof or
wall. For non-vented (recirculating) Installation see "For non-
vented (recirculating) installation only" in the "Connect Vent
System" section. Recirculation Kit Part Number W10646866 and
Charcoal Filter Kit Part Number W10272069 are available from
your dealer or an authorized parts distributor.
All openings in ceiling and wall where canopy hood will be
installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local
codes.
Product Dimensions
Parts supplied
Remove parts from packages. Check that all parts are included.
• Hood canopy assembly with ventilator and lights installed
• Vent mounting boss (attached to hood canopy assembly)
• Damper
• 3 - 3.5 x 9.5 mm screws damper to mounting boss
• Metal grease filter installed in hood canopy
• Chimney cover support bracket
• 2-piece chimney cover
• 2 - 8 x 80 mm hanger bolts (T20®TORX®drive)
• 2-8mmnuts
• 2- flat washers
• 2 - 5 x 40 mm T20 ®Torx®drive screws for chimney bracket
mounting.
• 2 - 5 mm wall anchors
• 1/2"(13 mm) special nut tightening tool
• 2 - Plastic spacers for lower chimney
1"®T20 and TORX are registered trademarks of Acument Intellectual Properties, LLC.
A. 12_" (31.4 cm)
B. 13 _" (33.4 cm)
C. 36" (91.4 cm)
D. 193//' (50.1 cm)
E
& 2_" (6.0cm)
F.25_/' (65.0cm)
G.33z_'' (86.0 cm) min.
55Y2"(141.0cm)max.
Cabinet Dimensions
10" (25.4 cm) rain.
13" (33.0 max.
"X"
bottom of I
canopy
to cooking I
SILll'faoe
2" (5.1 cm) rain.
)" (22.9 cm) rain.*
Vent and power
Side
cabinet
_ly came
, location
)Centerline
surface
*For non-vented (recirculating) installations
IMPORTANT:
Minimum distance "X": 24" (61.0 cm) from electric cooking
surface.
Minimum distance "X": 30" (76.2 cm) from gas cooking
surface.
Suggested maximum distance "X": 36" (91.4 cm)
NOTE: For best performance of the Auto Sense feature, the
range hood should be installed at 24" (61.0 cm) from an electric
cooking surface and 30" (76.2 cm) from a gas cooking surface.
The chimneys can be adjusted for different ceiling heights. See
the following chart.
Vented Installations
Min. ceiling height Max. ceiling height
Electric cooking 7' 10" (2.39 m) 10' 4" (3.24 m)
surface
Gas cooking 8' 4" (2.54 m) 10' 4" (3.24 m)
surface
Non-vented (recirculating) Installations
Min. ceiling height Max. ceiling height
Electric cooking 7' 10" (2.39 m) 10' 4" (3.24 m)
surface
Gas cooking 8' 4" (2.54 m) 10' 4" (3.24 m)
surface
*NOTE: The range hood chimneys are adjustable and designed
to meet varying ceiling or soffit heights depending on the
distance "X" between the bottom of the range hood and the
cooking surface. For higher ceilings from 10' 4" to 12' (3.24 m to
3.66 m), a Stainless Steel Chimney Extension Kit Part Number
W10646864 is available from your dealer or an authorized parts
distributor. The chimney extension replaces the upper chimney
shipped with the range hood.
(_ye_ste_I _:_e_e s e_s_y_}
Vent system must terminate to the outdoors, except for non-
vented (recirculating)installations.
Do not terminate the vent system in an attic or other enclosed
area.
• Do not use 4" (10.2 cm) laundry-type wall cap.
• Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
• The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
• Use no more than three 90 ° elbows.
• Make sure there is a minimum of 24" (61.0 cm) of straight
vent between the elbows if more than 1 elbow is used.
• Do not install 2 elbows together.
• Use clamps to seal all joints in the vent system.
• The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
• Use caulking to seal exterior wall or roof opening around the
cap.
• The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This canopy hood is factory set for venting through the roof or
wall.
A 6" (15.2 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 6" (15.2 cm) round.
A 6" to 8" (15.2 cm to 20.3 cm) vent adapter is available for 8"
(20.3 cm) vent systems. See the "Assistance or Service" section
to order.
Vent system can terminate either through the roof or wall. To vent
through a wall, a 90° elbow is needed.
Rear discharge
A 90° elbow may beinstalled immediately above the hood.
6
For Non-Vented (recirculating) Installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting a charcoal filter and the deflector. Fumes and
vapors are recycled through the upper chimney cover louvers.
To order the charcoal filter and recirculation kit, see
"Accessories" in the "Assistance and Service" section.
RoofVenting Wall Venting Non-vented
(recirculating)
Example vent system
90°elbow I_ 6t't(1.8m)_l .....Wall cap
The following example falls within the maximum recommended
vent length of 35 ft (10.7 m).
A. Roof cap A. Wall cap A. Deflector
B. 6" (15.2 cm) B. 6" (15.2 cm) B. 6" (15.2 cm)
round vent round vent round vent
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft
(0.8m)
1 - 90° elbow
1 - wall cap
8 ft (2.4 m) straight
Length of system
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
• A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
= 13.0 ft (3.9 m)
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
90° elbow 5.0 ft
(1.5m)
Maximum equivalent vent length is 35 ft (10.7 m).
For 3 Prong Grounded Power Cord:
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
This range hood is equipped with a power supply cord having
a 3 prong grounding plug.
To minimize possible shock hazard, the cord must be
plugged into a mating, 3 prong, grounding-type outlet,
grounded in accordance with local codes and ordinances. If a
mating outlet is not available, it is the responsibility of the
customer to have the properly grounded outlet installed by a
qualified electrician.
The grounded 3 prong outlet is to be located above the range
hood at a maximum distance of 40" (101.6 cm) from where
the power cord exits the hood. See illustration.
T
40"
(101.6 cm)
GROUNDING INSTRUCTIONS
• For a grounded, cord-connected range hood:
This range hood must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing an escape wire for the electric current.
This range hood is equipped with a cord having a grounding
wire with a grounding plug.The plug must be plugged into
an outlet that is properly installed and grounded.
WARNING: Improper grounding can result in a risk of
electric shock.
Consult a qualified electrician if the grounding instructions
are not completely understood, or if doubt exists as to
whether the range hood is properly grounded.
Do not use an extension cord. Ifthe power supply cord is too
short, have a qualified electrician install an outlet near the
range hood.
SAVE THESE INSTRUCTIONS
For Hard Wire from Home Power Supply:
• If the house has aluminum wiring, follow the procedure
below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial rating plate.
The model/serial plate is located behind the filter on the rear
wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22.1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
8
INSTALLATION INSTRUCTIONS
• It is recommended that the vent system be installed before 5. Remove the motor from the range hood.
hood is installed.
Before making cutouts, make sure there is proper clearance
within the ceiling or wall for exhaust vent.
Check your ceiling height and the hood height maximum
before you select your hood.
1.
Disconnect power.
2.
Determine which venting method to use: roof, wall, or non-
vented.
3.
Select a flat surface for assembling the range hood. Place
covering over that surface.
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
A. Blower housing
B. Keyhole slots (4)
C. Motor assembly
D. Motor plate
4. Using 2 or more people, lift range hood onto covered surface.
5. Remove the motor from the canopy assembly (see the "Motor
Removal" section in this section).
Motor Removal
To remove motor:
1. Remove the filter cover and metal grease filter (see the "Metal
Grease Filters" section in the "Range Hood Care" section).
2. Disconnect the blower motor wiring at the 9 pin connector.
3. Locate the special _/2"(13 mm) tool inside the range hood
blower housing in the left front corner behind the insulation
pad. Use it to loosen the 4 nuts located inside the blower
housing that mounts the motor to the module top cover.
4. Grasp the motor plate and slide the motor toward the back of
the module housing to the large openings in the keyhole slots.
A
B
D
A. Special Y2"(13 mm) tool
B. Motor assembly
C. Keyhole slots (large opening) (4)
D. V2"(13 mm) motor mounting nuts (4)
E. Motor plate
F. Module top cover
Range Hood Mounting Screws Installation
1=
Determine and mark the centerline on the wall where the
canopy hood will be installed.
2.
Select a mounting height between a minimum of 24"
(61.0 cm) for an electric cooking surface, a minimum of 30"
(76.2 cm) for a gas cooking surface, and a suggested
maximum of 36" (91.4 cm) above the range to the bottom of
the hood. Mark a horizontal reference line on the wall.
3.
Measure up from the horizontal mounting height reference
line 21_5/ld'(55.7 cm) and draw a parallel horizontal line.
Measure from the centerline 4%" (11.8 cm) in each direction
along the upper horizontal line. Mark the centers for the
fastener locations.
=
i
y=A
i
B I ' I
(11.8cm) ,, (11.8cm)
A. Centerline
B. Fastener locations
C. Mounting height reference
IMPORTANT: All screws must be installed into wall wooden
support structure. If there is no wooden support structure to
screw into, additional wall framing supports will be required.
This mounting structure must be capable of supporting
100 Ibs (45.4 kg).
4=
Drill 3Ad'(4.8 mm) pilot holes at all locations where screws are
being installed into wood.
=
=
=
' 21_%d' (55.7 cm)
=
C
(hood bottom line)
/
5,
Using a T20®Torx®bit and driver, install the 2 - 8 x 80 mm
hanger bolts. Leave a 11¼'' (31.8 mm) gap between the wall
and the end of the hanger bolt for sliding the range hood into
place.
Vent Cover Bracket Installation
1. Use chimney cover mounting bracket centered on the center
line of the wall and flush to the ceiling to mark the center
points of the outermost holes for mounting screws. Mark and
drill 2 - 3/16"(4.8 mm) holes.
2. Install the 5 mm wall anchors.
For Vented Installations Only:
1. Attach the chimney cover bracket to the wall using 2 - 5 x
40 mm screws (D).
A. Ceiling
B. Wall
C. Centerline
D. 5 x 40 mm screws (2)
For Non-Vented (recirculating) Installations Only:
1. Attach the chimney cover bracket and air deflector bracket to
the wall using the (2) 5 x 40 mm screws (D).
A
/
/
\
2.
Install the 5 x 40 mm screw through the top of the air
deflector bracket into the ceiling.
NOTE: To use the optional 5 mm wall anchor supplied with
the recirculation kit in the ceiling, locate and mark the hole
through the top of the air deflector bracket. Remove the
bracket and drill a 3/16"(4.8 mm) hole and install the 5 mm wall
anchor.
C B
A. Ceiling C. Air deflector bracket
B. Wall D. 5 x 40 mm screw
Complete Preparation
1. Determine and make all necessary cuts in the wall for the vent
system. Install the vent system before installing the hood. See
"Venting Requirements" section.
For Vented Installations Only:
• Using a jigsaw or keyhole saw, cut a 61/2"(16.5 cm) diameter
hole in the wall or ceiling for the vent duct.
• Install the vent duct system through the hole.
Seal all connections with vent clamps.
For use with Grounded Power Supply Cord:
• This range hood is equipped with a power supply cord having
a 3 prong grounding plug.
A 3 prong receptacle is required to be located at a maximum
distance of 40" (101.6 cm) above the range hood terminal
box. If a mating outlet is not available, it is the responsibility
of the customer to have a properly grounded outlet installed
by a qualified electrician.
For use with a Hard Wire Home Power Supply Cable:
• Determine the required height for the home power supply
cable and drill a 11¼"(3.2 cm) hole at this location.
Run the home power supply cable according to the National
Electrical Code or CSA Standards and local codes and
ordinances. There must be enough 1/2"conduit and wires from
the fused disconnect (or circuit breaker) box to make the
connection in the hood's electrical terminal box.
NOTE: Do not reconnect power until installation is complete.
2. Use caulk to seal all openings.
C
D
A. Ceifing D. 5 x 40 mm screws (2)
B. Wall E.Air deflector bracket
C. Centerline for range hood F. Chimney cover bracket
10
1.
Using 2 or more people, hang range hood on the 2 mounting
screws through the mounting slots on the back of the hood.
For Non-Vented (recirculating) Installations:
1. Mount the air deflector and flexible duct assembly to the air
deflector bracket using (4) 3.5 x 9.5 mm screws supplied with
the Recirculation Kit.
A
B
C
A. Mounting hanger bolts
B. Mounting slots
C. Flat washers and nuts
2. Install the flat washers and nuts to the hanger bolts. Level the
range hood and tighten the nuts.
For Vented Installations:
1. Assemble the damper (if needed) to the mounting boss using
(3) 3.5 x 9.5 mm screws.
2. Assemble the vent system to the damper (if used) or the
mounting boss.
3. Secure all of the connections with vent clamps.
A
C
A. Air deflector bracket
B.Air deflector/flexible duct assembly
C. 3.5 x 9.5 mm screws (4)
2. Loosen the 4 nuts on the mounting boss. The back flange of
each nut should be approximately 3/_e"(5 mm) from the face of
the mounting boss.
3. Expand the flexible section of vent duct to the top of the
range hood top plate.
4. Check the mounting boss handle for alignment. The
mounting boss handle must align parallel with the front of the
range. If alignment is needed, loosen one of the vent clamps
and adjust as necessary. Retighten any vent clamps that are
loosened.
5.
Secure all of the connections with vent clamps.
6.
Reach inside the range hood cavity and grasp the handle of
the mounting boss. Pull down to align the nuts through the
cutout holes in the module top cover. Push back into the half-
slots to assemble. Tighten the 4 nuts using the 1/2"(13 mm)
special tool or W' (13 mm) socket and driver with extension.
A
Front of range hood
B
A. Metal duct
B. Vent clamps
C. Mounting boss
4. Check that the back draft damper (if used) works properly.
D
A. Inside of range hood cavity
B. Mounting boss handle
C. Half slots in module top cover (4)
D. Nuts (4)
NOTE: For ceiling heights above 9 ft (1.8 m), an appropriate
length of 6" (15.2 cm) ducting (not supplied) will be required.
11
1. Place the motor into the module housing positioning it with
the large keyholes in motor mounting plate towards the back
of the canopy.
2. Grasping the motor plate, push the motor up into the module
housing. Locate the large keyholes over the motor mounting
nuts, push up against the module top cover and pull the
motor forward to lock into the small keyholes slots.
3. Use the special 1/2"(13 mm) tool and tighten the (4) nuts to
secure the motor.
For 3 Prong Grounded Power Cord:
For Hard Wire from Home Power Supply:
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Remove the terminal box cover.
A
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
1. Plug 3 prong power cord into a grounded 3 prong outlet
located above the range hood.
B
A. Screws
B. Terminal box cover
3. Disconnect grounded power cord wires from terminal block.
Loosen the screws labeled "L," "N," and "Ground Symbol."
4. Remove power cord strain relief from terminal box and
remove power cord.
12
®
A. Power cord
B. Power cord strain relief
C. Location "L" (black wire)
D. Location "N" (white wire)
E. Location ground symbol (green or bare ground wire)
5. Install a UL listed or CSA approved V2"strain relief.