JennAir JXI8536HS User Guide & Installation Manual

JENNAIR® 36" (91.4 CM) ISLAND CANOPY
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONL
IMPOR
POUR UTILISA
.
RANGE HOOD
HOTTE DE CUISINIÈRE JENNAIR
36" ET (91,4 CM)
®
POUR ÎLOT DE
Installation Instructions and Use & Care Guide
1-800-JENNAIR (1-800-536-6247) or visit our website at www.jennair.com.
In Canada, call: 1-800-JENNAIR (1-800-536-6247) or visit our website at www.jennair.ca.
Instructions d’installation et Guide d’utilisation et d’entretien
Au Canada, pour assistance, installation ou service, composez le 1-800-JENNAIR (1-800-536-6247) ou visitez notre site web
Table of Contents/Table des matières ..................................... 2
Y.
TANT : LIRE ET CONSERVER CES INSTRUCTIONS.
TION RÉSIDENTIELLE UNIQUEMENT
LI32KD/W11244201B
à www.jennair.ca.
TABLE OF CONTENTS TABLE DES MATIÈRES
TABLE DES MATIÈRES ..................................................................2
INSTALLATION REQUIREMENTS .................................................4
Tools and Parts .............................................................................4
Location Requirements ................................................................4
Venting Requirements ..................................................................5
Electrical Requirements ...............................................................6
INSTALLATION INSTRUCTIONS ...................................................7
Prepare Location ..........................................................................7
Assemble and Install Range Hood ..............................................7
Make Electrical Connection .......................................................10
Install Duct Covers .....................................................................10
Complete Installation .................................................................12
RANGE HOOD USE ......................................................................12
Controls and Features ................................................................12
RANGE HOOD CARE ...................................................................13
Cleaning .....................................................................................13
WIRING DIAGRAM .......................................................................14
ASSISTANCE OR SERVICE .........................................................15
In the U.S.A. ...............................................................................15
In Canada ...................................................................................15
Accessories ................................................................................15
RANGE HOOD SAFETY
SÉCURITÉ DE LA HOTTE DE CUISINIÈRE ...............................16
EXIGENCES D'INSTALLATION ...................................................18
Outils et pièces ...........................................................................18
Exigences d'emplacement .........................................................18
Exigences concernant l'évacuation ...........................................19
Spécications électriques ..........................................................20
INSTRUCTIONS D’INSTALLATION .............................................21
Préparation de l’emplacement ...................................................21
Assemblage et installation de la hotte .......................................22
Raccordement électrique ...........................................................24
Installation des cache-conduits .................................................25
Achever l'installation ..................................................................27
UTILISATION DE LA HOTTE .......................................................27
Commandes et caractéristiques ................................................27
ENTRETIEN DE LA HOTTE .........................................................29
Cleaning .....................................................................................29
SCHÉMA DE CÂBLAGE ...............................................................30
ASSISTANCE OU SERVICE .........................................................31
Au Canada ..................................................................................31
Accessoires ................................................................................31
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
follow instructions.
You
can be killed or seriously injured if you don't
instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
Ducted fans must always be vented to the outdoors.
For General Ventilating Use Only. Do Not Use
To Exhaust Hazardous Or Explosive Materials And Vapors.
READ AND SAVE THESE INSTRUCTIONS
To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control Device.
This appliance is not intended for use by people (including children) whose physical, sensory or mental capacities are different or impaired or who lack the necessary experience or knowledge/expertise to do so, unless such persons are supervised or are trained to operate the appliance by a person who accepts responsibility for their safety.
3
INSTALLATION REQUIREMENTS
12
"
)
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tools needed
■ Level
■ Drill with 1¼" (3 cm), 3/8" (9.5 mm), 7/64" (2.75 mm) and
1/8" (3 mm) drill bits
■ Pilot hole drill bits (determined by chimney support
attachment method)
■ Pencil
■ Wire stripper or utility knife
■ Tape measure or ruler
■ Pliers
■ Caulking gun and weatherproof caulking compound
■ Vent clamps
■ Jigsaw or keyhole saw
■ Flat-blade screwdriver
■ Metal snips
■ Phillips screwdriver
Parts needed
■ Home power supply cable
■ 1/2" (12.7 mm) UL listed or CSA approved strain reliefs (2)
■ UL listed wire connectors (3)
For vented installations, you will also need:
■ Wall or roof cap
■ Metal vent system
For non-vented (recirculating) installations, you will also need:
■ Recirculating Kit for non-vented (recirculating) installations
only. See “Assistance or Service” section to order.
■ 6" (15.2 cm) round metal vent duct. Length required is
determined by ceiling height.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances. Have a qualied technician install the range hood. It is the
installer's responsibility to comply with installation clearances specied on the model/serial/rating plate. The model/serial rating plate is located behind the left lter on the rear wall of the vent hood.
Canopy hood location should be away from strong draft areas, such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance.
Grounded electrical outlet is required. See “Electrical Requirements” section.
Because of the size and weight of this island hood, the chimney support must be securely attached to the ceiling.
■ For plaster or drywall ceilings, the chimney support must be
attached to joists. If this is not possible, you must build a support structure behind the plaster or drywall. The support structure must be able to support 100 lbs (45.4 kg).
This range hood is recommended for use with cooktops with a maximum total rating of 78,000 BTUs or less.
The range hood is factory set for venting through the roof. For non-vented (recirculating) installation, see “Non-vented
(recirculating) Installations” in “Assemble and Install Range Hood” section. Recirculation Kit Part Number W10692909 is available from your dealer or an authorized parts distributor.
All openings in ceiling and wall where range hood will be installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local codes.
Parts Supplied
Remove parts from packages. Check that all parts are included.
■ Hood canopy assembly with ventilator and LED light installed
■ Filter - installed in hood canopy
■ Levelling screws (2)
■ Nuts (2)
■ 4.2 x 8 mm screws (60)
■ 5 x 45 mm screws (4)
■ Mounting template
■ Upper vent covers (2)
■ Lower vent covers (2)
■ Vent transition with back draft damper installed
■ 3.5 x 9.5 mm mounting screws (2)
■ Plastic vent clips (4)
■ Upper horizontal support bracket
■ Horizontal support
■ Vertical supports (8)
■ 3.5 x 6.5 mm screws (4)
■ 2.9 x 3 mm screws (2)
■ T10® Torx®† adapter
■ T20® Torx® adapter
†®TORX, T10 and T20 are registered trademarks of Acument Intellectual Properties, LLC.
4
Product Dimensions
¹⁄₄
(31.0 cm)
13³⁄₁₆"
(33.5 cm)
36" (91.2 cm)
*Vented installations only **Non-vented (recirculating) installations only
*32¹⁄₂"
(82.6 cm)
*46¹⁄₂"
(118.0 cm)
min.
max.
27" (68.6 cm)
**32¹⁄₂"
(82.6 cm)
min.
**52⁹⁄₁₆"
(133.5 cm
max.
Installation Dimensions
B
C A
D
A. Ceiling height B. Hood height from ceiling to bottom of the
range hood: A - C - D = B
C. 24" (61.0 cm) minimum to 36" (91.4 cm)
maximum suggested hood height
D. Countertop height
IMPORTANT:
Minimum distance “C”: 24" (61.0 cm) from electric cooking surface.
Minimum distance “C”: 27" (68.6 cm) from gas cooking surface.
Suggested maximum distance “C”: 36" (91.4 cm) The chimneys can be adjusted for different ceiling heights. See
the following chart.
Vented Installations
Min. ceiling height Max. ceiling height
Electric cooking surface
Gas cooking surface
Non-vented (Recirculating) Installations
Electric cooking surface
Gas cooking surface
*NOTE: The range hood chimneys are adjustable and designed
to meet varying ceiling or soft heights depending on the distance “C” between the bottom of the range hood and the cooking surface. For higher ceilings, a Stainless Steel Chimney Extension Kit Part Number W10688278 is available from your dealer or an authorized parts distributor. The chimney extension replaces the upper chimney shipped with the range hood.
7' 9" (2.3 m) 9' 10" (3.0 m)
8' (2.44 m) 9' 10" (3.0 m)
Min. ceiling height Max. ceiling height 7' 9" (2.36 m) 10' 4" (3.15 m)
8' (2.44 m) 10' 4" (3.15 m)
Venting Requirements
■ Vent system must terminate to the outside, except for non-
vented (recirculating) installations.
■ Do not terminate the vent system in an attic or other
enclosed area.
■ Do not use 4" (10.2 cm) laundry-type wall caps.
■ Use metal vent only. Rigid metal vent is recommended. Do
not use plastic or metal foil vent.
■ The vent system must have a damper. If the roof or wall
cap has a damper, do not use the damper supplied with the range hood.
For the most efficient and quiet operation:
■ Use a straight run or as few elbows as possible.
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61.0 cm) of straight
vent between the elbows, if more than 1 elbow is used.
■ Do not install 2 elbows together.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
■ The size of the vent should be uniform.
Cold Weather Installations
An additional back draft damper should be installed to minimize backward cold air ow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems when using ventilation systems greater than specied CFM of air movement. The specied CFM varies from locale to locale. Consult your HVAC professional for specic requirements in your area.
Venting Methods
This island hood is factory set for venting through the roof. An 6" (15.2 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 6" (15.2 cm) round. NOTE: Flexible vent is not recommended. Flexible vent
creates back pressure and air turbulence that greatly reduce performance.
Vent system can terminate either through the roof or wall. To vent through a wall, a 90° elbow is needed.
5
For Non-Vented (recirculating) Installations
A
Wall cap
If it is not possible to vent cooking fumes and vapors to the outside, the hood can be used in the non-vented (recirculating) version, tting a charcoal lter and the deector. Fumes and vapors are recycled through the top grille.
Roof venting Non-vented (recirculating)
A
B
A. Roof cap B. 6" (15.2 cm) round vent
B
A. Deector B. 6" (15.2 cm) round vent
NOTE: Wall venting can be an option for 2-story homes.
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft
90° elbow 5.0 ft
(0.8 m)
(1.5 m)
Electrical Requirements
Observe all governing codes and ordinances. Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
■ A 120 V, 60 Hz, AC only, 15 A, fused electrical circuit is
required.
■ If the house has aluminum wiring, follow the procedure
below: Connect the aluminum wiring using special connectors
and/or tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended procedure. Aluminum/copper connection must conform with local codes and industry accepted wiring practices.
■ Wire sizes and connections must conform with the rating of
the appliance as specied on the model/serial/rating plate. The model/serial/rating plate is located behind the left lter on the rear wall of the range hood.
■ Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
Maximum equivalent vent length is 35 ft (10.7 m).
Example Vent System
90 elbow
2 ft
(0.6 m)
The following example falls within the maximum vent length of 35 ft (10.7 m).
1 - 90° elbow = 5 ft (1.5 m) 1 - wall cap = 0 ft (0.0 m) 8 ft (2.4 m) straight = 8 ft (2.4 m) System length = 13 ft (3.9 m)
6
6 ft (1.8 m)
INSTALLATION INSTRUCTIONS
A
Prepare Location
■ It is recommended that the vent system be installed before
the range hood is installed.
■ Before making cutouts, make sure there is proper clearance
within the ceiling for exhaust vent.
■ Range hood is to be installed 24" (61.0 cm) min. for electric
cooking surfaces, 27" (68.6 cm) min. for gas cooking surfaces, to a suggested maximum of 36" (91.4 cm) above the cooking surface.
■ Check your ceiling height and the range hood height
maximum before you select your hood.
1. Disconnect power.
2. Determine which venting method to use: roof, wall,
or non-vented.
3. Select a at surface for assembling the range hood. Place covering over that surface.
WARNING
Excessive Weight Hazard
Use two or more people to move and install range hood.
Failure to do so can result in back or other injury.
4. Using 2 or more people, lift range hood onto covered surface.
3. For vented installations only: Using a jigsaw or keyhole saw, cut a 6½" (16.5 cm) diameter hole for the vent duct.
Install In-Line Smart Kit - Optional
NOTE: Your range hood can work with either an internal or an in-line (external) blower motor system. An optional In-Line Smart Kit (purchased separately) allows the blower motor that comes with this range hood to be installed in a location other than inside the range hood cavity.
CAUTION: To reduce the risk of re and electric shock, install this range hood only with the In-Line Smart Kit manufactured by Whirlpool, W10692945.
For installation see the In-Line Smart Kit installation instructions. See the “Assistance or Service” section to order.
Assemble and Install Range Hood
1. Install transition on top of hood (if removed for shipping) with 2 - 3.5 x 9.5 mm sheet metal screws.
B
Range Hood Mounting Screws Installation
1. Determine and mark the centerline on the ceiling where the range hood will be installed, considering the requirements for ceiling support structures. See the “Location Requirements” section. Make sure the range hood is centered over the cooking surface.
2. Tape template in place on the ceiling at the marked centerline. The line for the front of the range hood should be parallel to the front of the cooktop.
3. Use a pencil to mark the mounting screws, wire access and duct hole locations on the ceiling.
NOTE: Mounting hole locations should be into a ceiling support structure capable f holding 100 lbs (45.4 kg).
Remove the template.
4. Drill (4) 3⁄16" (4.8 mm) pilot holes for mounting the upper horizontal support
Complete Preparation
1. Determine the required location for the home power supply cable and drill a 1/2" (1.3 cm) diameter hole for wire access.
2. Run wire through the home power supply cable according to the National Electrical Code or CSA Standards and local codes and ordinances. There must be enough 1/2" conduit and wires from the fused disconnect (or circuit breaker) box to make the connection in the hood’s electrical terminal box.
NOTE: Do not reconnect power until installation is complete.
2. Mark with a pencil the hole locations for screws and duct on
the ceiling.
3. Fix the upper horizontal support with 4 wood screws.
A. Vent transition B. 3.5 x 9.5 mm screw
7
4. Install the lower horizontal support with 8 - 4.2x8 mm
A
screws.
6. Install the structure to the upper horizontal support with 16
- 4.2x8 mm screws.
A
B
A. Lower horizontal support B. 8 - 4.2x8 mm screws
5. Install the 4 upper vertical supports with 16 - 4.2x8 mm screws.
A
B
B.
A. Upper horizontal support B. 16 - 4.2x8 mm screws
7. Using 2 or more people, lift the range hood assembly under the structure.
B
A
B
A. 4- Upper vertical supports B. 16 - 4.2x8 mm screws
A. Range hood assembly B. Lower vertical supports
8
8. Attach the range hood assembly to the lower vertical
A
B
supports with 2 leveling screws and 2 nuts.
A
B
Make Electrical Connection
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Remove terminal box cover.
3. Remove the knockout in the terminal box, and then install a
UL listed or CSA approved 1/2" (12.7 mm) strain relief.
C
D
A. 2 - Leveling screws B. Lower vertical support C. Place leveling screws
through the structure
D. Nut
9. Install the 4 lower vertical supports with 16 - 4.2x8 mm screws. Make sure all screws are securely tightened
A
C
A. Knockout B. Terminal box C. Terminal box cover
B
A. 4 - Lower vertical supports B. 16 - 4.2 x 8 mm screws
9
4. Run home power supply cable through strain relief and into
D
E
B
A
B
C
the terminal box.
A
B
C
F
A. Home power supply cable B. UL listed or CSA approved
strain relief
C. Black wires
D. UL listed wire connectors E. White wires F. Green (or bare) and yellow-
green ground wires
Install Duct Covers
NOTE: Remove the lm from the duct covers.
1. Assemble the upper duct covers together, and then install
the duct covers around the support frame. The larger hole in the anges of the upper duct cover must be outside the smaller hole in the mating ange of the other upper duct cover.
2. Secure the upper duct covers together with two 3.5 x 6.5 mm screws at the top and two 2.9 x 3 mm screws at the bottom. Install 1 screw on each side at the top and bottom of the assembled duct covers.
A
C
5. Use UL listed wire connectors and connect black wires (C) together.
6. Use UL listed wire connectors and connect white wires (E) together.
WARNING
Electrical Shock Hazard
Electrically ground blower.
Connect ground wire to green and yellow ground wire in terminal box.
Failure to do so can result in death or electrical shock.
7. Connect green (or bare) ground wire from home power supply to yellow-green ground wire (F) in terminal box using UL listed wire connectors.
8. Tighten strain relief screw.
9. Install terminal box cover.
10. Check that all light bulbs are secure in their sockets.
11. Reconnect power.
A
C
A. 3.5 x 6.5 mm screws (2) B. Assembly holes (larger hole outside of
smaller hole on both sides)
C. 2.9 x 3 mm screws (2)
NOTE: For non-vented (recirculating) installation, the slotted holes in the upper duct covers will be visible when assembled. For vented installations, the slotted holes will be hidden down inside the lower duct covers.
Optional Power Cord Kit Installations
For optional power cord kit installations, follow the instructions supplied with the power cord kit. See the “Assistance or Service” section for information on ordering.
NOTE: Use only with range hood cord connection kits that have been investigated and found acceptable for use with this model range hood.
A. Top toward ceiling B. Slots installed up for non-vented installations C. Slots installed down for vented installations
10
Loading...
+ 22 hidden pages