SEALEDGASCOOKTOPS
Models: JGC1430 & JGC1536
403WESTFOURTHSTREET,NORTH• NEWTON,
IMPORTANT: Dimensions Shown in Both Inches and Centimeters.'
IMPORTANT: Be sure the appliance being installed is equipped for the gas to be supplied. Refer to serial plate on
underside of burner box for this information. Do not attempt to convert this appliance for use with a gas other than the type
specified.
DIMENSIONS
inches cm
E
A 281/2 + 1/16 72.4 + 0,2
B 1915/16 + 1/16 50,6 + 0.2
C 21/8 + 1/16 5.4 + 0.2
D 51/4 + 1/16 13,3 + 0.2
E 291/2 + 1/16 74,9 + 0.2
F 21 1/2 + 1/16 54,6 + 0.2
G 313/16 + 1/16 9,7 + 0,2
H 12 1/4 + 1/16 31,1 + 0,2
TI .. ,, _I__
G_--' __L_J_
DIMENSIONS
inches cm
A 341/2 + 1/16 87,6 + 0,2
B 1915/16 + 1/16 50,6 + 0,2
C 21/8 + 1/16 5,4 + 0.2
D 5 1/4 + 1/16 13,3 + 0,2
E 36 + 1/16 91,4 + 0,2
F 21 + 1/16 53,3 + 0,2
G 313/16 + 1/16 9,7 + 0.2
H 151/4 + 1/16 38,7 + 0,2
CUTOUT DIMENSIONS
ARE CRITICAL
C
SPECIAL WARNING:
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE, MAINTENANCE
OR USE OF RANGE CAN RESULT IN SERIOUS INJURY OR PROPERTY DAMAGE.
NOTICE TO INSTALLER: Leave these instructions with the appliance.
NOTICE TO CONSUMER: Retain these instructions for future reference.
8101 P736-60
(lO-O6-0o)
Location Of Your Jenn-Air Appliance
Locate this appliance away from combustible materials
such as window curtains and combustible wall
decorations.
Minimum horizontal clearance between the edge of the
appliance and combustible construction extending from
the cooking surface to 18" (45.72 cm) above the cooking
surface is:
1.0" (2.54 cm) at rear
6" (15.24 cm) at sides
(Dimensions apply to both 30" and 36" wide models),
2.54 cm
6
15,24 cm
FIGURE1
,," 18"
/ 45.72 cm
Installing Cabinetry Over Your
Jenn-Air Cooktop
A = 30" (76.2 cm) minimum
vertical clearance
between cooking surface
and construction above
the appliance. This
clearance may be
reduced to not less than
24 inches (60.96 cm) by
protecting the underside
of the combustible
material or metal cabinet
above the cooking
surface with not less than
1/4 inch (.635 cm)
insulating millboard
covered with sheet metal
not less than 0.0122 inch
thick.
B = 13" (33.02 cm) maximum depth of cabinets installed
above cooktop.
Avoid use of cabinets above cooktop for storage space to
eliminate associated potential hazards such as reaching
over open flames,
A
FIGURE2
Preparation Of Countertop
The countertop cutout must be prepared according to the
illustration on page 1 of these instructions.
CAUTION: Cutout dimensions are critical. Dimensions
must be measured and cut accurately to within + 1/16"
(.159 cm) to ensure proper fit.
Important Preparation Suggestions
1. Chamfer all exposed edges of decorative laminate to
prevent damage from chipping.
2. Radius corners of cutout and file to insure smooth
edges and prevent corner cracking, Recommend
1/4" or 3/8" diameter drill in each corner,
3. Rough edges, inside corners which have not been
rounded and forced fits can contribute to cracking of
the countertop laminate.
4. Countertop must be supported within 3" (7.62 cm) of
cutout.
_ ROBLEMSWITHTHE GAS
ART $ 9215-252
NOTE:THEFIGUREMAYNOTACCURATELYREPRESENT
YOURRANGEORCOOKTOP;HOWEVER,THISWARNING
APPLIESTOALL GASCOOKINGPRODUCTS.
WARNING
THISPRODUCTSHOULDNOT
BEINSTALLEDBELOWA
VENTILATIONTYPEHOOD
SYSTEMTHATDIRECTSAIR
INADOWNWARDDIRECTION.
(SEEFIGURE)
THESESYSTEMSMAYCAUSE
IGNITIONANDCOMBUSTION
BURNERSRESULTINGIN
PERSONALINJURYANDMAY
AFFECTTHE COOKING
PERFORMANCEOFTHEUNIT.
Required Adjustments At Time Of Installation
The installation of this appliance must conform with local codes, or in the absence of local codes, with the latest edition
of the National Fuel Gas Code ANSI Z223.1 USA or current CAN 'CGA-B149 INSTALLATION CODE.
[] This appliance was manufactured for use with Natural Gas. If LP gas is the fuel of choice, follow the conversion to
LP procedure found in the installation instructions.
[] Test all external connections for gas leaks. Never test for gas leaks with an open flame.
[] Test all electrical connections.
Checkthecooktopserialplatetoseeifthecooktopis
approvedforinstallationinmobilehomesand/or
recreationalparktrailers.Serialplateislocatedonthe
bottomoftheunit.
All supply piping, except as noted, should use common
National Pipe Thread (N.ET.). For all pipe connections
use an approved pipe joint compound resistant to the
action of LP gas.
Ifapproved,thefollowingitemsareapplicable:
Mobile Homes
The installation of a range designed for mobile home
installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part
3280 [formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24 HUD, (Part 280)] or,
when such standard is not applicable, the Standard for
Manufactured Home Installations, ANSI A225.1/NFPA
501A, or with local codes.
In Canada the range must be installed in accordance with
the current CSA Standard C22.1 - Canadian Electrical
Code Part 1 and Section Z240.4.1 - Installation
Requirements for Gas Burning Appliances in Mobile
Homes (CSA Standard CAN/CSA - Z240MH).
Recreational Park Trailers
The installation of a range designed for recreational park
trailers must conform with state or other codes or, in the
absence of such codes, with the Standard for
Recreational Park Trailers, ANSI All 9.5-latest edition.
In Canada the range must be installed in accordance with
CAN/CSA - Z240.6.2 - Electrical Requirements for R.V.'s
(CSA Standard CAN/CSA - Z240 RV Series) and Section
Z240.4.2 - Installation Requirements for Propane
Appliances and Equipment in R.V.'s (CSA Standard
CAN/CSA - Z240 RV Series).
Installation Of Appliance
The installation of this appliance must conform with local
codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1-Latest Edition, or, in
Canada, CAN/CGA-B149 Installation Code, Latest
Edition.
This appliance, when installed, must be electrically
grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code
ANSI/NFPA No. 70-Latest Edition, or, in Canada, current
CSA Standard C22.1 Canadian Electrical Code, Part 1.
In The Commonwealth Of Massachusetts
This product must be installed by a licensed plumber or
gas fitter when installed within the Commonwealth of
Massachusetts.
A "T" handle type manual gas valve must be installed in
the gas supply line to this appliance.
CAUTION: Warranty is void on Jenn-Air equipment
installed other than as recommended by manufacturer.
This appliance is designed for use with the appliance gas
pressure regulator supplied with this appliance. It must be
installed in the gas line ahead of the gas manifold
entrance. It is preset for use with natural gas and must be
converted, as described on pages 8 and 9, for use with
LP gas. (See figures 7 - 12).
This appliance is designed to operate at a pressure of 5
inches of water column (36" models), 4 inches of water
column (30" models) on natural gas or, if converted for
use with LP gas (propane or butane), 10 inches water
column. Make sure this appliance is supplied with and
adjusted for the type of gas for which it is designed.
This appliance was adjusted at the factory for use with
natural gas. If, at any time, this appliance is to be used
with a different type of gas, all of the conversion
adjustments described on pages 8 and 9 must be made
by a qualified service technician before attempting to
operate the cooktop on that gas. Natural gas should be
supplied to the appliance pressure regulator at a line
pressure between 6 and 14 inches of water column or, if
converted for LP gas, between 11 and 14 inches.
WARNING
If the line pressure supplying the appliance pressure
regulator exceeds 14" water column (any gas), an
external regulator must be installed in the gas line ahead
of the appliance regulator to reduce the pressure to no
more than 14" water column. Failure to do this can result
in malfunction and damage to the appliance.
Insure this appliance is adjusted for the type of gas
supplied to it and that the gas supply pressure to the
appliance regulator is within the proper pressure range.
- If no other appliance is to be installed in the cabinetry
below this unit, proceed as instructed under paragraph
1, page 4.
If this unit is to be installed over a Jenn-Air Model
JJW9530, JJW9130, JJW8530 or JJW8130 Series
Electric Wall Oven proceed as instructed under
paragraph 2, page 5.
NOTE: In Canada, gas utilization codes prohibit use of
street elbows. Use standard pipe elbows and make
modifications to these instructions as necessary.
A flexible gas connector, when used. must not exceed a
length of three (3) feet / 36 inches.
Connecting Appliance To Gas Supply
A QUALIFIED SERVICE TECHNICIAN OR GAS
APPLIANCE INSTALLER MUST MAKE THE GAS
SUPPLY CONNECTION. Leak testing of the
appliance shall be conducted by the installer
according to the instructions given.
Gas supply piping MUST conform to all local,
municipal and state building codes and local utility
regulations.
1. IF NO OTHER APPLIANCE IS TO BE INSTALLED
BELOW THIS COOKTOP
Join the appliance pressure regulator supplied with this
appliance to the entrance threads of the Gas Manifold.
The appliance regulator is marked with a directional
arrow indicating correct direction of gas flow. Ensure
the appliance regulator is installed with the arrow
pointing toward the gas manifold entrance. Tighten the
appliance regulator to 20 to 30 ft-lbs of torque.
Never tighten to more than 35 ft-lbs of torque. Always
use an approved pipe joint compound resistant to the
action of LP gas.
Apply a non-corrosive leak detection fluid to all joints and
fittings in the gas connection between the supply line
shut-off valve and the cooktop. Include gas fittings and
joints in the cooktop if connections were disturbed
during installation. Check for leaks! Bubbles appearing
around fittings and connections will indicate a leak. If a
leak appears, turn off supply line gas shut-off valve,
tighten connections, turn on the supply line gas shut off
valve, and retest for leaks. Never test for gas leaks with
an open flame.
ILLUSTRATIVE GAS SUPPLY PIPING
BURNER BOX
i (NO OTHER APPLIANCE BELOWCOOKTOP)
_J (3/8"N.P.T.)
I
(REAR OF APPLIANCE)
MANIFOLD
ENTRANCE
Install the appliance in its counter cutout.
Make the gas connection to the inlet of the appliance
pressure regulator with 1/2" NPT male pipe threads.
Install a manual shut-off valve in an accessible location in
the gas line ahead of the appliance pressure regulator
and external to this appliance for the purpose of turning
on or shutting off gas to the appliance.
Make additional pipe connections as necessary ahead of
the shut-off valve to the gas supply source. Assure all
pipe joint connections are gas tight.
APPLIANCEPRESSURE
!
I
I
P_
!
ELBOW
ALL SUPPLY SIDE
PIPE JOINTS
REGULATOR
1/2" N.P.T.
MANUAL
SHUTOFF
VALVE
INLET
FIGURE3
WARNING
Gas leaks may occur in your system and result in a
dangerous situation. Gas leaks may not be detected by
smell alone. Gas suppliers recommend you purchase and
install an UL approved gas detector. Install and use in
accordance with the manufacturer's instructions.
2,IFTHISUNITWILLHAVEA JENN-AIRMODEL
WALLOVENINSTALLEDBELOWTHISCOOKTOP.
NOTE1:Thisapplianceanditsgasandelectricalsupply
sourcesmustbeinstalledbeforethewallovenisinstalled.
Seeillustration(ElectricalWiringInformation- page7;
figure6)forrecommendedelectricalsupplysource
locations.
NOTE2"Itmaybenecessarytoextendgassupplypiping
forthisapplianceintoadjacentunder-countercabinetry
whena wallovenisinstalledbelowthisappliance.
Joina3/8"NPTpipeelbow(locallyavailable)tothemale
threadsatthemanifoldentrance.Whenjoined,ensure
openthreadsoftheelbowfacetowardtherightsideof
theappliance.Installtheapplianceinitscountercutout.
Joina3/8"NPTpipenippletotheelbowusingapipe
sectionof sufficientlengthtoextend,horizontally,beyond
therightsideofthewalloven.(Toaccomplishthisitmay
benecessarytoextendthepipesectionintoadjacent
cabinetry.)Joinadditional3/8"NPTelbow(s)andpipe
nipples,asnecessary,toaccomplishthefollowing:
Jointheoutletoftheappliancepressureregulator
suppliedwiththisappliancetothemalethreadsofthe
newlyinstalledgassupplypiping.Installtheappliance
regulatorinalocationwhichwillbeaccessiblebesideor
belowthewalloven.Insuretheapplianceregulatoris
installedwithitsdirectionalarrowpointinginthedirection
ofgasflow.Tightentheapplianceregulatorto20to30
ft-lbsoftorque.
ILLUSTRATIVE GAS SUPPLY PIPING
(WALL OVEN INSTALLED BELOW 30" COOKTOP)
_1 -'/ BURNER BOX
_:I I / _ (REAR OF APPLIANCE)
_i_I/" _:::::'.
:::::::::::::::::::::::::::::::::::::::::::: MANIFOLD ,,
: 'i':':+: .","_:':" _ (3/8N PT)
:l_i.;:::i_:_;.:::_ LJ ENTRANCE "'"
iii! iiiiill ii! iiii_"__ _gE"-- ELBOW_PTAPI;R_-_AS_sE
APPLIANCE MANUAL
PRESSURE SHUTOFF
REGULATOR VALVE
k iNkEr
ALL UNIT StDE APPROXIMATE CROSS SECTION ALL SUPPLY SIDE
PiPE JOINTS PROFILE OF WALL OVEN PIPEJOINTS
318" N.P.T. 1/2" N.P.T.
FIGURE4
Never tighten to more than 35 ft-lbs of torque. Always
use an approved pipe joint compound resistant to the
action of LP gas.
Locate and join a manual shut-off valve in an accessible
location in the gas line ahead of the appliance regulator
and external to the appliance for the purpose of turning on
or shutting off gas to the appliance.
Make additional pipe connections as necessary ahead of
the shut-off valve to the gas supply source. Assure all
pipe joint connections are gas tight.
II [e] I;tll/T;51#I li
Apply a non-corrosive leak detection fluid to all joints and
fittings in the gas connection between the supply line
shut-off valve and the cooktop. Include gas fittings and
joints in the cooktop if connections were disturbed during
installation. Check for leaks! Bubbles appearing around
fittings and connections will indicate a leak. If a leak
appears, turn off supply line gas shut-off valve, tighten
connections, turn on the supply line gas shut off valve,
and retest for leaks. Never test for gas leaks with an open
flame.
Note, regarding Figure 4, above:
° For convenience in service a union (not shown: locally
available) should be included in the piping illustrated in
figure 4, in a location most practical for the installation.
Generally, a practical location is in the cabinet below
this appliance, near the manifold entrance, rather than
in an adjoining cabinet.
If the alternative piping method shown in figure 5 is
selected for the installation, no union is required. (The
flexible appliance connector illustrated provides the
union joints necessary for servicing.) When a dividing
wall is present and a flexible connector is used, it is
recommended for convenience in both installation and
service, that the flexible connector pass through the
dividing wall. Any flexible connector used with this
appliance must satisfy all requirements stated in
the text accompanying figure 5.
Alternative Piping Methods To
Connect Appliance To Gas Supply
A TRAINED SERVICE TECHNICIAN OR GAS
APPLIANCE INSTALLER MUST MAKE THE GAS
SUPPLY CONNECTION, Leak testing of the
appliance shall be conducted by the installer
according to the instructions given,
Unless prohibited by local codes or ordinances, a new
A.G.A. - Certified, flexible metal appliance connector may
be used to connect this appliance to its gas supply. The
connector must be no more than 5 feet in length. Per
figure 5, use appropriate flare union adapter at each end
of the flexible connector. If a flexible connector is used
assure that both the appliance pressure regulator and
manual shut-off valve are joined solidly to other
permanent hard piping (either gas supply or the appliance
manifold) so as to be physically stationary. See
illustrations below.
CAUTION: DOnot attemp t to attach the flexible
connector directly to an external pipe thread.
connection requires flare union adapters: I
Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 pounds
per square inch (3.5 kPa).
This appliance, as well as its individual shut-off valve,
must be disconnected from the gas supply piping system
during any pressure testing of the system at test
pressures in excess of 1/2 pounds per square inch (3.5
kPa).
When checking appliance regulator function, make certain
pressure of natural gas supply is between 6 and 14
inches of water column or, if converted for LP gas,
between 11 and 14 inches of water column.
ILLUSTRATIVE ALTERNATIVE PIPING
Manifold_] )
Entrance _1
I I
I
Apply a non-corrosive leak detection fluid to all joints and
fittings in the gas connection between the supply line
shut-off valve and the range. Include gas fittings and
joints in the range if connections were disturbed during
installation. Check for leaks! Bubbles appearing around
fittings and connections will indicate a leak. If a leak
appears, turn off supply line gas shut-off valve, tighten
connections, turn on the supply line gas shut off valve,
and retest for leaks. Never test for gas leaks with an open
flame.
_-,It--- AppliancePressure
I
I_1- FlareUnionAdaptor
I
_ 1/2" N.P.T.Flexible
I
0-,91- Flare UnionAdaptor
!
!
NO APPLIANCE
MOUNTED BELOW
THIS COOKTOP
WALL OVEN MOUNTED
IN CABINETRY BELOW
THIS COOKTOP
(Observedirectionality
Regulator,SuppIied _,,,,_"'u
of GasFlow)
(A5Pf_'.ianaCe.)C°nnect°r
.,91-Gas Shut-Off Valve
"4-112" N.P.T.Pipe
(Stationary Supply Pipe)
FlareUnion Elbow
_ Adaptor
"_ _ql- 3/8" N.P.T.Flexible
_ ApplianceConnector
.._ (5ft. max.)
I
i_ ,,,qI- FlareUnion
I
_I-- ppliancePressure
I Flow)
I
,_ Gas Shut-Off Valve
I
t-1/2" N.P.T.Pipe
(StationarySupply
Pipe)
FIGURE5
\ 3/8" NIPIT.
Adaptor
Regulator,Supplied
(Observe
directionalityofGas
1/2" N.P.T. Pipe
Nipple
Electrical Wiring Information
This appliance is equipped with a grounded type power
cord. A grounded outlet must be provided. It is
recommended, for convenience, the outlet be located
(with reference to figure 6) as in A or B, below:
A. If no other appliance is to be installed below this
appliance: within either the shaded area or the cross
hatched area shown infigure 6.
B. If a Jenn-Air Model Wall Oven is to be installed below
this appliance, either:
1. within the cross hatched area of figure 6, or,
2. within an adjacent cabinet.
If a wall oven is to be installed below this appliance and
the counter units outlet is to be mounted within the cross
hatched area of figure 6:
1. The cabinet's lower front panel, below the oven, must
be made removable for access to the outlet.
2. A clearance hole for the power cord's plug (1-1/4" (3.18
cm) dia is recommended) must be provided through the
oven's floor support shelf and, if necessary, through the
slats supporting the shelf. The clearance hole should
be located as near as practical to the rear of the shelf.
can be located as is convenient in this left wall or in the
corresponding right wall.
In planning any installation, note that the free length of
this appliance's power cord, extending beyond a point
3-3/4" (9.53 cm) left of the nominal center of the rear wall
of the burner box, when viewed from the front of the unit,
is approximately 46" (117 cm).
User may experience occasional circuit tripping if Ground
Fault Circuit Interrupter (GFCI) outlet or breaker is in use.
WARNING
Electrical Grounding Instructions
This appliance is equipped with a (three-prong)
grounding plug for your protection against shock
hazard and should be plugged directly into a
properly grounded receptacle. Do not cut or
remove the grounding prong from this plug.
WARNING
If the outlet is to be mounted in either a left or right
adjacent cabinet, a clearance hole, as described above,
must be provided in the dividing wall between the
cabinets. Figure 4; page 5, illustrates a typical (left side)
dividing wall. The clearance hole (not shown in figure 4)
!iiiiiiiii!!iiiiiiiiiiiiiiiiiiiiiiiiiiiii!ii!i!i!!ii!iiiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiii_iiiiiiiiiiii_!iiiiii!iiii
!!!!_!_!_iiii_i_ii_i_i_!i_i_i_i_ii!!i_!!!!!!!!_!!!!!!!!!!!!_!i_ii!_i_
i!_!!!!!!!i!i_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiiiiiii_iii_iiii!ii_!i!!!!i_!!!i!ii_!i!!!i!!!i!!!!!iiiiiit
_i_i_iiiiiiiii_iii_iiiiiiiiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiiii_iii_i_i_i_i!ii_iiiiiiiiiiiiiiiiil
!!!!!iiiiiiiii!i_!!!!!!!!ii!!i_iiiiiiiiiiiiiiiiii_iiiiii_iiiiiiiiiiiiiiiiiii!!i_i!iiiiiiiii!iiii!iii_!iiii_i
iiii_!!!!!!!ii!_iii_ii_i_i_iiii_iiiiii_i_i_;_ii_i_iii_i_ii_i_i_;_
iiiiiiiiiiiiiiiii_;_;_i_;;_i_iii_i_i_ii_ii_i_i_i_i_i_ii_iii!ii!!!!_
i!!!!!i!!iiiiiiiiiiiiiiiiiiiii_ii_;_Z_iii_i_ii_i_i_i_i_i_iiii_i_ii_i_I
i_i_iiiiiiiiiiiiiiiiiiiii_iiiiii_iiiiiiiiiiiii_!iii_ii_i_iiii_ii_i_iiiii_i_iii_iii_i_i_ii_ii_i_I
i_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!iiiiiiiiiiiii!iiiiiii_ii_i_iiiiiiiiii_iii_i_i_i_iii_
iiiiiii!!i!!!i!!_ii_i_i_i_ii_i_iii_iiiiiiiiiiiiiiii_!!!!!!!_
iiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiiiiiii_iiiii_iiiii_iiiiiiiiiiiii_iiii_!_!!!!!!!!!!!!ii!!!!I
i_i_iiii_ii_iiii_iiiiiiiii_iiiiiii_iiiiii_iiiii_iiiiiiiiiiiiiiii_ii_i_ii_iii_i_!_i=
_!!!!!!!i!ii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiiiiiiiiii_iii_iii_iiii_i_!!!!!!!_
_!!!!!!!!!i_!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_i_ii_!_!!!!_!_!i!i_!_!_
ii_iiiiiiiiii_iii_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii_iiiiiiiiiiiiiiiii_i_
!iiiiiiiiiiiiiiii_i_!__iiiiiiiiiiiiiiiii_i_i_iiii_iii_
3 1/2" (8.89 cm) WIDE
SLATS WHEN A WALL
OVEN IS INSTALLED
BELOW 30" MODEL
THIS APPLIANCE MUST BE DISCON-
NECTED FROM ITS ELECTRICAL SUPPLY
AT THE WALL RECEPTACLE BEFORE
SERVICING THE APPLIANCE.
3 13/16"
9.7 cm
I
29 3/8"
74.61 cm
37 3/16"
94.46 cm
4" MAX.
10.16 cm ,
CABINET BOTTOM
FIGURE 6
Converting Appliance For Use
With LP Gas
WARNING
Propane conversion is to be performed by a JENN-AIR
AUTHORIZED SERVICER (or other qualified agency) in
accordance with the manufacturer's instructions and all
codes and requirements of the authority having
jurisdiction. Failure to follow instructions could result in
serious injury or property damage. The qualified agency
performing this work assumes responsibility for this
conversion,
Installation Of LP Orifice Spud
1.01 0.64 0.91
oN- oN.
Electrical power and gas must be turned
WARNING off
prior to conversion.
This appliance was adjusted at the factory for use with
natural gas. To convert it for use with LP gas (propane or
butane), each of the following modifications must be
performed: (A, B, and C)
A. REPLACE ALL ORIFICE SPUDS
Step 1: Remove the grates and burner caps.
Step 2: Remove burner base by removing 2 screws.
(See figure 7).
Step 3: Firmly press 9/32" (or 7mm) nut driver over the
orifice spud (figures 7 and 8) and loosen spud
by turning counter- clockwise. Carefully lift nut
driver out of burner throat. Orifice spud must be
captured in the nut driver. Repeat steps 2 & 3
for each burner.
REMOVAL OF ORIFICE SPUD
Step 4:
Step 5:
Step 6:
Step 7:
0.64
Locate the LP orifice spud packet included in
the literature packet. The spuds have small
numbers stamped on the side. This number
codes the orifice diameter and its correct
burner location. Figure 9 and 10 show the
correct LP orifice spud location.
Carefully install the orifice spud in the
appropriate burner throat by turning clockwise
to tighten. Tighten to a torque of 15 to 20
inch-lbs.
Replace burner base, caps, and grates.
Tighten screws (do not cross thread) to 25-30
in Ibs.
Save the orifices removed from the appliance
for future use.
0.91
Head
Orifice
Locatin
Ring
FIGURE7
Orifice.__
Holder O
AEf #921_156-0
FIGURE8
1.01
FIGURE10
B. INVERT CAP IN APPLIANCE PRESSURE
REGULATOR (See figure 11)
With the appliance installed, the appliance regulator
should be located as shown in figure 3, 4 or 5,
CONVERSION OF APPLIANCE APPLYDOWNWARD
PRESSURE REGULATOR FINGERPRESSURE
CONVERTE APPLYSIDEWARD
_;_A CAP i
NAT I i'_
C. LOW FLAME ADJUSTMENT (See figure 12)
This appliance is shipped from the factory with low and
high flame settings adjusted for use with natural gas.
To set for use with LP proceed as follows:
1, Remove control knob from valve stem,
R_LP REPLACEPININCAR
,,_ FINGERPRESSURE
ND PIN .J
./
TOREMOVEPIN
FROMCAP
NATT I LiP
FIGURE11
ATDISCEDGESTO
After adjusting the screw the burner should produce a
stable, steady blue flame of minimum size. The setting
should be checked by turning knob from high to low
several times without extinguishing the flame.
This operation will automatically provide the proper flame
size at medium setting.
After Conversion Steps A, B and C have been completed,
check the appearance of each burner flame at the Hi and
Lo settings against figure 13. If the flames appear too
large or too small, review each step to make sure it was
completed correctly.
FLAME APPEARANCE AT HI, MED AND LOW
OFF
CAUTION: NEVER USE A METAL B_DE TOPRY
KNOB OFR IF KNOB CANNOT BE EASILY REMOVED,
TUCK THE FOLDS OFA CLOTH DISHTOWEL UNDER
THE KNOB AND PULL THE TOWEL UPWARD W!TH
STEADY, EVEN PRESSURE.
2. Carefully remove rubber grommet.
3. Locate the valve adjustment screw. See figure 12.
4. Insert a slender, thin-blade screwdriver into knob
hole and engage blade with slot in adjusting screw.
5, Turn the adjusting screw clockwise until tight (5-7
in-lbs max.). Do not over tighten.
6, Replace rubber grommet and control knob,
7, Repeat for remaining burners.
KNOB
FIGURE12 OFF FIGURE13
lOW
LIGHT
OFF
LOW
LIGHT
SCREW
KNOB HOLE
(KNOB AND GROMMET
REMOVED)
High Altitude Notice
The specified gas burner ratings typically apply to
elevations up to 2000 feet. For higher altitudes, the rates
may need to be reduced to achieve satisfactory operation,
A local certified gas servicer will be able to advise if a
reduction is necessary.
To Convert Appliance For Use With
Natural Gas
4 BURNER MODEL(30" WIDE)
1.10 1.42
Electrical power and gas must be turned
WARNING off
prior to conversion.
If this appliance has been converted for use with LP gas,
each of the following modifications must be performed to
convert the unit back to natural gas.
A. REPLACE ALL ORIFICE SPUDS,
1. Perform Steps 1and 2 on page 8.
2. Perform Step 3 on page 8.
3. For Step 4: Locate the brass natural gas orifice
spuds that were originally installed in this appliance
before its conversion for use with LP gas. Observe
the number on each of the spuds and note the
correct burner location for each spud as shown in
figures 14 and 15.
Installation Of Natural Gas Orifice Spuds
5 BURNER MODEL(36" WIDE)
1.61 1.10 1.42
1.61 2.00
FIGURE15
4. Complete Steps 5, 6 and 7 on page 8 to complete
the installation of natural gas main spuds in their
correct locations.
5. Save the orifices removed from the appliance for
future use. They will be needed if this appliance is
again converted for use with LP gas.
ao
INVERT CAP IN APPLIANCE PRESSURE
REGULATOR, (See figure 11).
With the appliance installed the appliance regulator
should be located as shown in either figure 3, 4 or 5
(pages 4, 5 & 6). Identify the type of appliance
regulator and follow the instructions in the appropriate
illustration.
FIGURE14
Co
RESET THE VALVES FOR NATURAL GAS
1. Light one burner, and set on low.
2. Remove the knob.
3,
Remove the rubber grommets.
4.
Locate the valve adjustment screw. See figure 12.
5.
Insert a slender, thin-blade screwdriver into knob
hole and engage blade with slot in adjusting screw.
6,
Starting from the LP position (see #5 on page 9,
under C. LOW FLAME ADJUSTMENT), turn the
screw counter clockwise until the flame stabilizes
and matches the pictured "low" setting on figure 13.
Proper adjustment will produce a stable, steady blue
flame of minimum size. The final adjustment should
be checked by turning the knob from high to low
several times without extinguishing the flame.
After Steps A, B and C have been completed, check
the appearance of each burner's flame at the Hi and Lo
settings against figure 13. If the flames appear too
large or too small, make sure all steps were completed
correctly.
10
Burner Performance
CAUTION: Never cover control knobs or surrounding
control surface with utensils, towels, or other objects.
Never obstruct free air passage past the control knobs.
The knob openings have been sized to properly control air
entry to the interior of the appliance during operation.
This appliance has no air shutters. Primary air
adjustments are unnecessary. The burners are designed
to provide optimum aeration for all gases without air
shutters. When operating properly, burners should
produce clearly defined, even blue flames. Ifthe flames
have yellow tips or are hazy and otherwise appear to
have insufficient air, obtain the services of a qualified
service technician. Some yellow tipping on LP gas is
normal.
Specified input rates are as shown in figures 16 and 17
below.
5 BURNERMODEL(36"Wide)
FIGURE 16
JENN-AIR 36"
INPUTRATES- NATURALGAS/ LP GAS (BTU/HR)
BURNERLOCATION Hi Lo
RightFront
RightRear
LeftFront
LeftRear
Center
17,000/ 14,000
9,200 / 9,100
9,200 / 9,200
12,000/ 10,500
5,000 / 4,000
2,200/2,200
1,500/ 1,500
1,500/ 1,500
1,500/ 1,500
1,100/ 1,100
4 BURNER MODEL (30" Wide)
FIGURE17
JENN-AIR30"
INPUT RATES- NATURALGAS / LP GAS (BTU/HR)
BURNERLOCATION Hi Lo
RightFront
RightRear
Left Front
Left Rear
Center
17,000/ 14,000
9,200 / 9,100
12,000/ 10,500
5000 / 4000
1,800/ 1,800
1,300/ 1,300
1,300/ 1,300
650/ 650
11