Jenn-Air JES8850AAS Installation Guide

INSTALLER: LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE
INSTALLATION MANUAL
Electric 30-inch Wide
Jenn-Air Radiant Element Range
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
THE MANUAL IS INTENDED TO ASSIST IN THE INITIAL INSTALLATION AND ADJUSTMENTS OF THE RANGE.
SPECIAL WARNING
Only qualified personnel should install or service this range.
Read “Safety Instructions” in Use & Care book before using range.
Improper installation, adjustment, alteration, service, maintenance or use of range can result in serious injury or property damage.
· ALL RANGES CAN TIP AND CAUSE INJURIES TO PERSONS.
CLEARANCE DIMENSIONS
For complete information in regard to installation of Jenn-Air range, see figures 1, 2, 3 and 4. For SAFETY CONSIDERATIONS, do not install a range in any combustible cabinetry which is not in accord with the installation clearances shown in figure 1.
CAUTION: This range has been designed in
accordance with the requirements of various safety agencies and complies with the maximum allowable wood cabinet temperatures of 194°F. If this range is installed with cabinets that have a lower working temperature than 194°F, discoloration, delamination or melting may occur.
Your range may not be equipped
with some of the features referred
to in this manual.
· INSTALL ANTI-TIP DEVICES PACKED WITH RANGE.
· FOLLOW ALL INSTALLATION INSTRUCTIONS.
ENGLISH '''' PP. 1-8 ESPAÑOL '''' pág. 9-16 FRANCAIS '''' p. 17-24
8101P429-60
(03-02-01)
INSTALLATION DRAWINGS (Pages 2, 3 & 4)
IMPORTANT
PLEASE KEEP FOR THE USE OF THE LOCAL ELECTRICAL INSPECTOR.
FIGURE 1
NOTE: Figure may not be representative of actual unit.
The 30 inches (76.2 cm) minimum clearance between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet can be reduced to 24 inches (61 cm) minimum when bottom of wood or metal cabinet is protected by not less than 1/4-inch (6.4 mm) thick flame-retardant millboard covered with not less than No. 28 MSG sheet steel, 0.015-inch (0.381 mm) thick stainless steel, 0.024-inch (0.610 mm) thick aluminum, or
0.020-inch (0.508 mm) thick copper.
To eliminate the risk of burns or fire by reaching over heated surface units, cabinet storage space located above the surface units should be avoided. If cabinet storage is to be provided, the risk can be reduced by
installing a range hood that projects horizontally a minimum of 5 inches (13 cm) beyond the bottom of the cabinets.
FIGURE 1
1 COMBUSTIBLE BACK WALL....
2 COMBUSTIBLE SIDE WALL....
3 COMBUSTIBLE WALL CABINET....
DIMENSION “A” ISTOBEA MINIMUM OF 3 INCHES (7.5 CM).
A SLIDE-IN RANGE, IF EQUIPPED WITH OPTIONAL BACKGUARD KIT, MAY BE INSTALLED ZERO INCHES FROM COMBUSTIBLE WALL 1 (SEE FIGURE 1).
-2-
30²
²
²²
JENN-AIR RANGES
FIGURE 2
FIGURE 3
Notes:
1. Provide for either a 3-wire or 4-wire 120/208, 120/240 volt outlet per applicable cord in shaded area shown. Refer to installation instructions for proper positioning of outlet.
2. Dimension K (figure 4, page 4) is from the wall to the side edge of the oven door. It does not include the curvature of the glass or the depth of the handle.
3. Dimension L (figure 4, page 4) is with the leveler legs adjusted all the way in. This may vary slightly upon leveling leg a djustment.
4. Do not use grout, epoxy, etc., to install this unit. Installation must allow for removal of this appliance from the installed location for purposes of servicing.
-3-
30²
²
²²
JENN-AIR RANGES
Unity II Slide-In Range
Dimensions
FIGURE 4
JJJJ
A B C D E
F G H
J
2*
K
3*
L M
* SEE NOTES ON PAGE 3
Inches
25 24 30
36 23 5/8 23 1/4
51/2
10 29 7/8
26 3/16
35 3/4
2/1/4
Centimeters
63.5
61.0
76.2
91.4
60.0
59.1
14.0
25.4
75.9
66.5
90.8
5.7
-4-
MOBILE HOMES
LOCATING THE RANGE
The installation of a range designed for mobile home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24 HUD, Part 280) or, when such standard is not applicable, the Standard for Manufactured Home Installations 1982 (Manufactured Home Sites, Communities and Set-Ups), ANSI A225.1-latest edition, or with local codes.
Place range in a well lit area. Do not set range over holes in the floor or other locations where it may be subject to strong drafts. Any opening in the wall behind the range and in the floor under the range should be sealed. Make sure the flow of cooling/ventilation air is not obstructed below the range.
NOTE: A range should NOT be installed over kitchen carpeting.
ANTI-TIP DEVICE INSTALLATION INSTRUCTIONS
WARNING: A risk of range tip-over exists if the appliance
is not installed in accordance with the provided installation instructions. The proper use of this device minimizes the risk of TIP-OVER. In using this device the consumer must still observe the safety precautions as stated in the USE and CARE MANUAL and avoid using the oven doors as a step stool.
Installation instructions are provided for wood and cement in either floor or wall. Any other type of construction may require special installation techniques as deemed necessary to provide adequate fastening of the ANTI-TIP bracket to the floor or wall. The bracket may be installed to engage the LEFT or RIGHT rear leveling foot.
NOTE: The bracket provided is designed for use with flush mount and non-flush mount outlet receptacles.
Install the bracket with the orientation hole in the longer leg against the wall as shown in figure 5.
STEP 1 - Locating The Anti-tip Bracket (See Figure
A. Determine where either the right or left “EDGE” of the
range will be located and mark the floor or wall.
B. Place the BRACKET 15/16² (24mm) from the marked
“EDGE” toward center of opening and against the back wall as shown in figure 5, with orientation hole against wall.
C. Use the bracket as a template and mark the required
holes, as shown in figure 5, for the type of construction you will be using.
D. Anti-tip bracket may be secured to either floor or wall.
See Step 2 on page 6 for bracket installation options.
5)
FIGURE 5
-5-
STEP 2 - Anti-Tip Bracket Installation A. Wood Construction:
1. Floor:Locatethecenterofthetwoholesidentifiedin figure 5 as “HOLES FOR FLOOR.” Drill a 1/8² (3 mm) pilot hole in the center of each hole (a nail or awlmaybeusedifa drillisnotavailable).Securethe ANTI-TIP bracket to the floor with the two screws provided. Proceed to STEP 3.
Options
STEP 3 - Range
A. A Jenn-Air range may be installed by one person. B. Align the range to its designated location and slide it
back into position. Note: A minimum clearance of 1/4² (6 mm) is required between the range and the leveling foot that will engage the ANTI-TIP bracket, see figure
6.
Installation
2. Wall:Locate the center of the two holes identified in figure 5 as “HOLES FOR WALL.” Drill an angled 1/8² (3 mm) pilot hole in the center of each hole as showninfigure 6. (A nailorawlmaybe used if adrill isnotavailable).SecuretheANTI-TIPbracket tothe wallwiththetwo screws provided as shown in figure
6. Proceed to STEP 3.
B. Cement or Concrete Construction:
1. Suitable screws for concrete construction can be obtained at the hardware store. Drill the required size hole for the hardware obtained into the concreteatthecenteroftheholesidentifiedinfigure 5 as “HOLES FOR FLOOR”. Secure the ANTI-TIP bracket to the floor. Proceed to STEP 3.
C. All Jenn-Air ranges have a non lift-up top. D. For SAFETY CONSIDERATIONS as well as optimum
performance adjust the range so that it is level. This may be checked by placing a spirit level or a large pan of water on the cooktop or the oven rack. If an adjustment is required pull the range forward, tip the range and rotate the leveling feet as required.
E. To check the range for proper installation of the
anti-tip bracket: Use a flashlight and look underneath the bottom of the range to see that one of the rear leveling feet is engaged in the bracket slot.
F. Proceed with the remainder of the installation
instructions provided with the range.
FIGURE 6
-6-
CONNECTING THE RANGE
ELECTRIC SUPPLY
The range must be installed in accordance with Local and National Electric Code (NEC) ANSI/NFPA No. 70-latest edition. See rating plate for total connected KW rating.
ELECTRIC SUPPLY (Canada)
The range must be installed in accordance with Local and Canadian Electric Code CSA STD.C22.1 latest edition. See rating plate for total connected KW rating.
OUTSIDE WIRING
Your local utility company will tell you whether the present electric service to your home is adequate. It may be necessary to increase the size of the wiring to the house and service switch to take care of the electrical load demanded by the range. The kilowatt rating for the range is specified on the rating plate located on the front of the range.
HOUSE WIRING
Most local Building Regulations and Codes require that all electrical wiring be done by licensed electricians. All wiring should conform to Local and National Electrical Codes. This range requires a single phase three wire 120/240 or a 120/208 volt, 60 Hz, AC circuit. Wiring codes require a separate circuit be run from the main entrance panel to the range and that it be equipped with separate disconnect switch and fuses, either in the main entrance panel or in a separate switch and fuse box. In some communities, a solid or flexible continuous armored conduit must be used from main entrance panel to the terminal box on the rear of the range. Others will permit the termination of the range circuit at a polarized three or four wire plug-in outlet placed at a convenient point near the back of the range. The range is then connected to this outlet through an approved range connector (pigtail) fastened securely to the terminal block with proper strain relief at the range and a three or four pronged plug at the opposite end.
RANGE CONNECTIONS
Some models are shipped direct from the factory with service cords (pigtails) attached. There are no range connections necessary on these models. Just plug into the range outlet. On models not provided with a service cord, connection to the power supply is necessary. REMEMBER - only a 4-conductor cord is to be used on new branch-circuit installations (1996 NEC), mobile homes, recreational vehicles, or in an area where local codes prohibit grounding through the neutral conductor. Hence, 4-wire service MUST be provided for such installations. 3-wire service may be used when permitted by local code. USE COPPER OR ALUMINUM CONDUCTORS. Main terminal block is recognized for Copper or Aluminum conductors. If a flexible power cord is required, it is recommended a cord no longer than 4 ft. be used. Make connections as explained below and with reference to the appropriate illustration (see figures 8 and
9). After installation, insure tightness of all electrical connections and replace all covers.
Remove terminal block access cover from range back. (See figure 7).
RANGE CONNECTIONS (Canada)
This model was shipped direct from the factory with service cord (pigtail) attached. There are no range connections necessary. Just plug into the range outlet. See figure 2 on page 3 for outlet location.
NOTE: Cord replacement - ONLY a power supply cord rated at 240 volts minimum, 40 amperes or 50 amperes power supply cord that is marked for use with nominal 13/8² (34.93 mm) diameter connection opening, with closed loop terminals and marked for use with ranges shall be used.
-7-
FIGURE 7
3-WIRE SERVICE CORD OR CONDUIT INSTALLATION
1. Insure that the copper ground strap IS CONNECTED between the middle post of the main terminal connection block and the range chassis.
2. The middle wire of the service cord or ground lead of 3-wire conduit MUST connect to the neutral (middle) post of the main terminal block. The other two wires of the service cord or conduit connect to the outside posts of the main terminal connection block. Polarity is unimportant.
3. A appropriate strain relief for service cord or conduit must be attached to the conduit plate.
4-WIRE SERVICE CORD OR CONDUIT INSTALLATION
(MOBILE HOMES OR AS REQUIRED BY CODES)
1. The copper ground strap connected between the neutral (middle) post of the main terminal block and the chassis MUST be cut off as shown in figure 9. Save the green ground screw to attach the ground from the 4 wire cord. Only a 4 wire cord or conduit should be used.
2. The ground wire from the service cord or conduit must connect to the range chassis using the green ground screw.
3. The white wire of the service cord or conduit must connect to the neutral (middle) post of the main terminal block. The other two wires of the service cord or conduit connect to the red and black posts of the main terminal block, respectively.
4. An appropriate strain relief for service cord or conduit must be attached to the conduit plate.
CONVERSION FROM 3-WIRE TO 4-WIRE SERVICE
(Model With 3-Wire Service Cord Attached)
Disconnect range from power. Remove the access cover on back of range and remove the 3-wire service cord from the main terminal block. Follow instructions as outlined in figure 9 to connect the 4-wire service cord.
FIGURE 8
ACCEPTABLE 3-WIRE PLUG INSTALLATION
NOTE: Cord replacement - ONLY a power supply cord rated at 240 volts minimum, 40 amperes or 50 amperes power supply cord that is marked for use with nominal 13/8² (34.93 mm) diameter connection opening, with closed loop terminals and marked for use with ranges shall be used.
FIGURE 9
ACCEPTABLE 4-WIRE PLUG INSTALLATION
-8-
Loading...
+ 16 hidden pages