IMPORTANT - SAVE FOR THE LOCAL ELECTRICAL INSPECTOR'S USE
IMPORTANT: Installation should be performed only by an authorized Jenn-Air Service Contractor or other qualified
installer. Read safety precautions in the Use & Care Manual before using this appliance.
(Dimensions shown in both inches and centimeters)
FOUR-ELEMENT RADIANT COOKTOPS
DIMENSIONS
inches cm
A 29-1/16+ 1/16 74.0+ 0.2
B 20-3/8 + 1/16 51.9 +0.2
C 2-1/8 min. 5.4
D 4-1/8 min.clear 10.5
E 29-15/16 76.0
F 21-1t2 54.6
G 3-3/4 9.5
NOTE: "D" is clearance needed for unit depth measure down from top of countertop. Typical for all units.
FIVE-ELEMENT RADIANT COOKTOPS
DIMENSIONS
inches cm
A 34-9/16+ 1/16 87.9 + 0.2
B 20-3/8 + 1/16 51.9 +0.2
C 2-1/8 min. 5.4
D 4-1/8 min.clear 10.5
E 35-5/16 89.7
F 21-1/2 54.6
G 3-3/4 9.5
CUTOUT DIMENSIONS
ARE CRITICAL
UNITS PROVIDED WITH 1/2" (1.3 cm) I.D. FLEXIBLE CABLE 48" (121.9 cm) LONG WITH 6" (15.2 cm) WIRE LEADS
AT END, FURNISHED AND INSTALLED BY MANUFACTURER (CONNECT TO 240/120 VOLT ELECTRICAL SERVICE
INSTRUCTIONS TO INSTALLER:
= Side Clearance - unit may be safely installed as near as 0" (0 cm) from a side wall if space limitations requires.
Notice To Installer: Leave these instructions with the appliance.
Notice To Consumer: Retain these instructions for future reference.
8101 P503-60
(10-02-00)
Installing Cabinetry Over Your Cooktop
A = 30" (76.2 cm) minimum clearance between the top of
the cooktop and the bottom of an unprotected wood or
metal cabinet.
A = 24" (60.96 cm) minimum when bottom of wood or
metal cabinet is protected by not less than 1/4" (0.635
cm). FLAME RETARDANT millboard covered with not
less than no. 28 MSG sheet steel, 0.015" (0.038 cm)
stainless steel, 0.024" (0.061 cm) aluminum or copper.
To eliminate the risk of burns or
fire by reaching over heated
surface units, cabinet storage
space located above the surface
units should be avoided. If
cabinet storage is to be provided,
the risk can be reduced by
installing a range hood that
projects horizontally a minimum
of 5 inches beyond the bottom of
the cabinets.
t
I
L...---._.--.._
Important Installation Suggestions
1. Chamfer all exposed edges of decorative laminate to
prevent damage from chipping.
2. Radius corners of cutout and file to insure smooth edges
and prevent corner cracking.
3. Rough edges, inside corners which have not been
rounded and forced fits can contribute to cracking of the
countertop laminate.
4. Countertop must be supported within 3" (7.62 cm) of
cutout.
CAUTION
warranty is void On equipmen t installed Other than as re_
commended by manufacturer:
Electrical Wiring Information
The neutral of this unit is grounded to the frame through the
solid copper grounding wire. If used on new branch-circuit
installations (1996 NEC), mobile homes, recreational
vehicles, or in an area where local codes prohibit grounding
through the neutral conductor, untwist or disconnect the
solid copper wire and connect the ground wire to ground in
accordance with local code. Connect the white neutral to
the service neutral. Connect all wires to the branch circuit
with approved connectors. Use copper or aluminum wire. If
aluminum wire is used, use connectors recognized for
joining aluminum to copper.
ProperElectricalSupply
You must provide an adequate electrical supply system as
required for your cooktop. All wire connections must be in
accordance with local codes and properly insulated. Check
with local utility for governing electrical codes and
ordinances. In the absence of local electrical codes, the
National Electrical Code, NFPA No. 70, governing electric
range installations must be followed. A copy of the National
Electrical Code, NFPA No. 70, can be obtained by writing
to:
National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
A three-wire, single phase, A.C. 120/240 volt 60 cycle
electrical system (properly circuit protected to meet Local
Codes of NFPA No. 70) must be provided. Unit must be
properly grounded in accordance with local wiring code. The
chart below recommends the minimum circuit protector and
wire size if the appliance is the only unit on the circuit• If
smaller sizes of wire are used, the unit efficiency will be
reduced and a fire hazard may be created. It is advisable
that the electrical wiring and hookup be accomplished by a
competent electrician.
RECOMMENDEDMINIMUM
K.W.RATING
ONSERIALPLATE
0 4.8
4.9 6.9
7.0 9.9
10.0 - 11.9
12.0 - 14.9
CIRCUITPROTECTION
INAMPRES
2O
3O
4O
5O
6O
WIRESIZE
(AWG)
12
10
8
8
6
Notice To Installer
Follow accompanying instruction carefully.
CAUTION
Never use a metal bla_b off: If knob cannot I
be easily removed, tuck folds of a dish- towel under kn0 b I
skirt and pull upward with steady, even pressure. I
Preparation Of Countertop
The cutout in the countertop into which the appliance is to
be installed should be prepared according to the cutout
dimensions given on page 1 of these instructions.
CAUTIO.__ ___NN
CutoUt dimensi0ns are critical. Dimensions must be
measured and cut accurately to within _ 1/16 (.16 cm) I
to insure proper fit,
Installation Of Appliance
1. Remove the cooktop from the carton and place it upside
down over two soft pads making sure control knobs do
not interfere with any surface.
2. Provide cutout in countertop as required per page 1.
3. Place unit in the cutout.
4. Make electrical wire connection to unit. Consult local
codes for proper power hook-up.
5. Test to insure control knobs operate all elements
properly.