JCC JC71831, JC71833, JC71832, JC71830 Installation Instructions

company
Toughbay™ Range
Live (+)
Installation guide for Toughbay™ LED Highbay
Important information
a
It is recommended that luminaires are installed by a qualied electrician to ensure the installation complies with the local current wiring regulations.
It is recommended that the ambient room temperature should not exceed 45°C.
Caution. Risk of electric shock
The external exible cable or cord of this luminaire cannot be replaced; if the cord is damaged the luminaire shall be destroyed.
INSTALLATION
Standard version connection
220-240V~ 50/60Hz / Class I
Figure 1. Mains input
brown
Earth
yellow/green
Neutral (-)
blue
1-10V Dimming control input Figure 3.
Dim - (white)
These products are designed for connection to a 220-240V~50/60Hz supply.
The light source of this luminaire is not replaceable by the end user. The light source contained in this this luminaire shall only be replaced by the
manufacture or their service agent or a similar qualied person.
This luminaire is suitable for indoor and outdoor use.
It may be necessary to upgrade your MCBs to allow for increased inrush current.
This luminaire should be installed out of arms reach.
Terminal block not included. Installation may require advice from a
qualied person.
ENGLISH
Specications Colour temp: 5700K Ra: 80
Toughbay™
Base
100W 12300 123 60°/90°
150W 18400 123 60°/90°
200W 24500 123 60°/90°
Toughbay™
Plus
100W 14500 145 60°/90°
150W 21200 141 60°/90°
200W 28000 140 60°/90°
Lumens LpcW Beam
Lumens LpcW Beam
Dim + (Black)
Terminal block must comply to
EN 60998-2-1 or EN 60998-2-2
Terminal block specication: Number of Ways 3
Mounting Type Through Hole Pitch 8mm Current Rating 24A Termination Method Screw Down
Wire Size 2.5 mm² Material Nylon Voltage Rating 380 V
Maximum Operating Temperature +125°C Contact Material Brass
Contact Plating Nickel
Termianl block must be IP65 waterproof for
outdoor installation.
Available nishes: Black(BLK)only
Read instructions and check that you have all of the tools and accessories required to complete the installation correctly. Isolate power supply before starting the installation.
Standard dimmable version installation procedure
1. The luminaire comes with a xed eye(s) for suspension as standard.
2. For surface mounting please order correct bracket separately (see
table below for deatails). Fit the bracket to a at surface ensuring that xings are suitable to hold the weight of the luminaire. Fit the
luminaire to the bracket using the bolts supplied.
3. Connect the mains input as shown in Fig.1, using a suitable
connector to maintain the IP rating for the location. Alternatively
connect using accessory JC71851 waterproof IP65 connector (not supplied). Please ensure that 3-core H07 RN-F cable is used.
4. This luminaire is 1-10V dimmable as standard, if you wish to dim this
tting ensure that you connect the 1-10V dimming control wires as shown in Fig.3 to a 1-10V dimming system only. If no dimming is
required please leave the terminals isolated.
Accessories
JC71840 Bracket for Toughbay Base 100W
JC71841 Bracket for Toughbay Base 150W
JC71842 Bracket for Toughbay Base 200W
JC71843 Bracket for Toughbay Plus 100W
JC71844 Bracket for Toughbay Plus 150W
JC71845 Bracket for Toughbay Plus 200W
RoHS
Compliant
IP65
jcc.co.uk
V5_NOV_2017_RS
Prole & Dimensions
171 270
176 296
193 338
234 270
242 320
Toughbay™ Base
100W 150W 200W
100W
Toughbay™ Plus
150W 200W
All dimensions in millimetres
Important warranty information
Toughbay™ Plus is supported by a 7 year extended warranty. Toughbay™ Base is supported by a 5 year extended warranty; which must be registered online at jcc.co.uk/warranty.
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chassis: Product Code/Batch Code.
JCC Lighting Products Ltd., Innovation Centre, Beeding Close, Southern Cross Trading Estate, Bognor Regis, West Sussex, PO22 9TS , United kingdom
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
Loading...