JCC JC71746, JC71746EM, JC71741, JC71745, JC71743 User Manual

...
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
BS EN ISO9001 - 2015 - Registered Firm Certificate No. GB 1552
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 5-years if registered within the first year of pu (2 year on batteries). Please register at jcc.co.uk/warranty (Terms and conditions apply).
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chas Product Code/Date Code.
Skypack™ QR Range
N
1
2
Installation instructions for Skypack™ LED Battens
Warnings & Cautions
To avoid electric shock, serious injury or property damage, isolate power before installing, removing or servicing the product.
It is recommended that luminaires are installed by a qualied electrician to ensure the installation complies with the local current wiring regulations.
It may be necessary to upgrade your MCBs to allow for increased inrush current.
This luminaire is suitable for indoor use only.
a company
This product cannot be covered with insulation material - do not cover.
Any broken or damaged parts should be replaced as soon as possible. JCC will not accept responsibility for
claims arising from sub-standard installations; which will void the warranty.
Emergency product routine inspection and tests must be undertaken at times of least risk and in
accordance with EN 50172:2004. A copy of this report must accompany any tting returned to JCC for
any reason.
INSTALLATION
1. To remove the diffuser and LED tray from the body press both the release buttons at each end of the tting as shown in Fig. 1.
2. The diffuser and LED tray is secured to the body with security tabs, which will support the diffuser when installing the body.
3. Secure the tting in the desired postion either using the xing points or BESA plates for conduit mounting.
4. Terminate the wiring into the press t terminal as shown in Fig. 2 or into fused terminal for the emergency version as shown in Fig. 3.
5. Connect DALI or 1-10V dimming controls indicated as per Fig. 2(A)
6. Connect batteries on emergency version (allow a full 24 hours for batteries to charge prior to testing). Please refer to periodic test
procedure on page two.
7. Ret the front cover by aligning the diffuser with the body and click into place.
8. Turn on the mains supply and check operation.
N.B This luminaire is suitable for surface, BESA mounting or with conduit end entry to both ends.
Note: DO NOT carry out insulation tests with the driver connected to the circuit.
1-10V+
1-10V-
N
Figure 2(A).
DA +
DA -
Diffuser release buttons
Emergency version connection
220-240V 50/60Hz / Class I
Figure 3.
L1 = Unswitched live
L = Switched Live = earth
neutral
L
N =
L1
L
N
Dimming control input
1-10V control wires DALI control wires
Standard version connection
220-240V 50/60Hz / Class I
Figure 2.
N = neutral
= earth L = Live
Figure 1.
ENGLISH
Specications Colour temp: 4000K Ra: 80
Skypack™ Product
code
4ft Single JC71741 23 2760 120
4ft Single EM JC71741EM 25 2760 110
4ft Twin JC71742 40 4800 120
4ft Twin EM JC71742EM 42 4800 114
5ft Single JC71743 37 4440 120
5ft Single EM JC71743EM 39 4440 113
5ft Twin JC71744 60 7200 120
5ft Twin EM JC71744EM 62 7200 116
6ft Single JC71745 54 6480 120
6ft Single EM JC71745EM 56 6480 116
6ft Twin JC71746 82 9800 120
6ft Twin EM JC71746EM 84 9800 117
Total
circuit
wattage
Lumens LpcW
sis:
RoHS
Compliant
IP20
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT
jcc.co.uk
V9_July_2022_RS
Emergency range routine inspection and test
76.5
76.5
76.5
6ft single/twin
Prole & Dimensions
All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:
Daily: Indicators of central power supply shall be visually inspected for correct operation.
Monthly: (in addition to the daily check) If automatic testing devices are used, the results of the short
duration tests shall be recorded. Test shall be carried out as follows:
a) Switch the luminaire over to emergency mode to operate from the batteries by simulating a failure
of supply to the normal lighting for a period sufcient to ensure correct luminaire operation
NOTE: The period of simulation failure should be sufcient for the purpose of this clause whilst
minimising damage to the system components e.g lamps. During this period, all luminaires and signs shall be checked to ensure that they are present, clean and functioning correctly. At the end of this test period, the supply to the normal lighting should be restored and any
indicator lamp or device should be checked to ensure that is showing that the normal supply has been restored.
Annually: If automatic testing devices are used, the results of the short duration tests shall be recorded.
For all other systems the monthly inspection shall be carried out and the following additional
tests made:
a) Each luminaire and internally illuminated sign shall be tested monthly as above but for its full
duration in accordance with the manufacturer’s information.
b) The normal supply for the luminaire should be restored and any charge indicator lamp or
device should be checked to ensure that it shows the normal supply has been restored. The charging arrangements should be checked for proper functioning.
c) The date of the test and its results shall be recorded in the system logbook.
A copy of this report must accompany any tting returned to the manufacturer for any reason.
General Information
Our products are designed to comply with the requirements of UK law and the relevant industry
national and international standards and should not be modied in any way. All emergency lighting systems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency
Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring regulations. Before installing any type of Emergency Lighting always seek the advice and approval of
the local Fire Prevention Ofcer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced immediately. These units
are designed especially for a long and trouble free life. Under normal conditions, will require no routine
maintenance or service beyond the inspection and test regime of BS5266-1.
Both mains supply and battery protection fusing is incorporated internally. Should access to these or any other part of the circuitry be required this must be undertaken only by a suitably qualied person. Special care must be taken when removing the cover to circuitry and battery. Only replacement
components authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.
You can help protect the environment. Please remember to respect the local regulations: hand in the non-working
electrical equipment to an appropriate waste disposal centre. The packaging material is recyclable. Dispose of the packaging in an environmentally friendly manner and make it available for the recyclable material collection service.
6ft single/twin
182870
5ft single/twin
5ft single/twin
152370
4ft single/twin
70
Month Test Type First Year Second Year Third Year Fourth Year Fifth Year
January Functional
February Functional
March Functional
April Functional
May Functional
June Functional
July Functional
August Functional
September Functional
October Functional
November Functional
December 3 hour
4ft single/twin
1220
All dimensions in millimetres
Emergency test record sheet
Sign Date Sign Date Sign Date Sign Date Sign Date