Jandy AquaPure APURE700, AquaPure APURE1400 Installation And Operation Manual

Installation and Operation Data
Installation and Operation Manual
Jandy® AquaPure
Electronic Chlorine Generator
Patent Pending
FOR YOUR SAFETY - This product must be installed and serviced by a pro fes sion al pool/spa service technician. The procedures in this manual must be followed ex act ly. Failure to follow warning notices and instructions may result in property damage, serious injury, or death.
H0282600B
WARNING
Table of Contents
Page 3
Section 1. Safety Information ...........................4
Section 2. System Description ...........................6
2.1 Electrical Specifi cations ....................................7
Section 3. Installation Instructions Model
APURE700 and APURE1400 ..........8
3.1 Materials and Tools ...........................................8
3.2 Plumbing Confi gurations ...................................8
3.2.1 Recommended Cell and Sensor
Orientation .............................................9
3.2.2 Recommended Plumbing Confi guration 10
3.3 Installing APURE700 and APURE1400
Control Center ...................................................11
3.4 Earth Bonding (Grounding) ...............................12
3.5 Installing the APURE700 and APURE1400
Cell and Flow/Temp/Salinity Sensor .................12
3.6 Connection to an AquaLink® RS Control
System ...............................................................14
3.6.1 Wiring to a Jandy AquaLink RS ............15
3.6.2 Wiring Multiple AquaPure Units to
a Jandy AquaLink RS ............................15
Section 4. Pool Water Preparation ...................16
4.1 Determining Pool Size (m3 of Water in
Your Pool) ..........................................................16
4.2 Determining Pool Size (Gallons of Water in
Your Pool) ..........................................................16
4.3 Selecting Model Size .........................................17
4.4 Chemistry You Need to Know ...........................17
4.5 Optimum Pool Water Conditions ....................18
4.6 Chlorine Testing ..............................................18
4.7 Salt (NaCl sodium chloride) ............................18
4.7.1 When to Add Salt? .................................18
4.7.2 What Type of Salt to Use? .....................18
4.7.3 How Much Salt to Use? .......................19
4.7.4 How to Add Salt to the Pool? ................19
Section 5. Operating Instructions ....................23
5.1 Using the Front Panel Controls .........................23
5.2 Reading the Display ..........................................25
5.3 Operation .........................................................26
5.4 Startup................................................................27
5.4.1 Shocking ................................................27
5.4.2 Apply Power ..........................................27
5.5 Operating in Winter .........................................28
5.6 Recommendations .............................................28
Section 6. User Maintenance Instructions .....29
6.1 Daily ..................................................................29
6.2 Weekly ...............................................................29
6.3 Monthly .............................................................29
6.4 Electrolytic Cell Cleaning - As Needed .............29
6.6 Winterizing ........................................................31
Section 7. Troubleshooting ................................32
7.1 Problems and Corrective Action ........................32
7.2 Service Codes ....................................................35
7.3 Additional Letter Codes ....................................35
Section 8. Temperature Conversion .................36
Section 9. APURE700 and APURE1400
Exploded Views and Replacement
Kits ....................................................37
9.1 Control Center Replacement Parts ....................37
9.2 3-Port Electrolytic Cell and Sensor Replacement
Parts with Universal Unions (2”-2½”) ..............38
9.3 2-Port Electrolytic 2” Cell and Sensor
Replacement Parts (PVC Black Unions) ...........39
9.4 2-Port Electrolytic 1½” Cell and Sensor
Replacement Parts (ABS White Unions) ..........39
Page 4
Section 1. Safety Information
IMPORTANT SAFETY INSTRUCTIONS PERTAINING TO A RISK OF FIRE,
ELECTRIC SHOCK, OR INJURY TO PERSONS
READ AND FOLLOW ALL INSTRUCTIONS
When installing and using this electrical equipment, basic safety precautions should always be followed, including the following:
WARNING
To reduce the risk of injury, do not permit children to use this product unless they are closely supervised at all times.
WARNING
When mixing acid with water, ALWAYS ADD ACID TO WATER. NEVER ADD WATER TO ACID.
WARNING
To reduce the risk of electric shock, fi re or injury, service should only be attempted by a qualifi ed Pool Service Professional.
WARNING
Do not operate electrolytic cell without proper fl ow or water circulation. A buildup of fl ammable gases would result in hazardous conditions.
WARNING
Installation must be done in accordance with the National Electric Code (NEC, NFPA-70) and/or any other applicable local and national installation codes.
RISK OF ELECTRIC SHOCK, FIRE, PERSONAL INJURY, OR DEATH. Connect only to a circuit that is protected by a ground-fault circuit-interrupter (GFCI). Such a GFCI should be provided by the installer and should be tested on a routine basis. To test the GFCI, push the test button. The GFCI should interrupt power. Push the reset button. Power should be restored. If the GFCI fails to operate in this manner, there is ground current fl owing, indicating the possibility of an electric shock. Do not use this unit. Disconnect this unit and contact a qualifi ed service representative before using.
A green colored terminal (or a wire connector marked “G”, “GR”, “Ground” or “Grounding”) is provided within the terminal compartment. To reduce risk of electric shock, connect this terminal or connector to the grounding terminal of your electric service or supply panel with a conductor equivalent in size to the circuit conductors supplying this equipment.
Power supply must be interconnected with Pool Pump motor power source. This ensures the chlorinator and pool pump will turn on and off together.
Use of chemicals other than those recommended may be hazardous. Follow the Chemical Manufacturers Instructions.
It is recommended that the water Flow/Temp/Salinity Sensor is installed in the same piping as the electrolytic cell, without any valves or diverters between them. (See page 5 Figure 1).
The Flow/Temp/Salinity Sensor must be mounted as shown on page 12 Figure 8.
Page 5
CAUTION
It is important to note that certain materials used in and around swimming pools and spas may not be compatible with chemicals commonly used to purify pool and spa water (e.g. acids, chlorine, salt, stabilizers, etc.).
As such, Jandy Pool Products, Inc. does not warrant or guarantee that the chlorinated water generated by the AquaPure will not damage or destroy certain types of plants, decking, coping and other materials in and around your pool and/or spa. Before selecting materials to be used in and around your pool and/ or spa, please discuss all options with your contractor to assess the compatibility of such materials and chemicals.
Some helpful considerations may include:
• Choosing plants that can withstand splash out of pool water containing chlorine and/or salt and other water purifi cation chemicals.
• All metal components used in and around a pool should be of a high grade, quality stainless steel.
• Careful selection of masonry products. The porosity and hardness of natural stones varies greatly. Therefore we recommend you consult with your builder or stone contractor on the best choice for stone materials around your pool or spa.
• Sealing all masonry products. Professionals in the stone industry specify that even natural stone, especially when used outdoors, be sealed to prevent weathering, staining, and premature degradation. Consult with your stone or deck contractor for the proper sealer for the masonry products you have selected to use around your pool or spa.
• For the optimal results, sealers should be reapplied on a regular basis. Reapply the protective sealer on a schedule per the manufacturer’s instructions
.
SAVE THESE INSTRUCTIONS
Page 6
Section 2. System Description
Options List
1. ORP/External Control Interface
2. ORP/Freeze Control Unit
3. Heater
Heater
Cell with
Flow/Temp/Salinity Sensor
ORP Unit (Control Signal from ORP Unit to ORP Interface/Aux Board)
AquaPure
Control
Center
Pump
Filter
Spa IntakePool Intake
Spa ReturnPool Return
Figure 1. Typical AquaPure Installation With Options
A TTENTION INST ALLER: Various application notes (more detailed instructions) are
available from the Dealer covering installation, operation, maintenance, and plumbing of the chlorinator system.
The AquaPure uses a process known as electrolysis to produce sodium hypochlorite (liquid chlorine) from a low concentration of salt added to the pool water. Hypochlorite kills bacteria, oxidizes organic material, and kills algae then reverts back to salt. The AquaPure then reuses the salt and the process starts over again. The AquaPure system is comprised of the following three component parts and an optional pool pump timer.
Control Center The control center converts AC electrical current to a low voltage DC current which
is required by the cell to perform the electrolysis. The control center is connected with the pool circulation pump electrical source so that the electrolytic cell only operates when the pool pump is on. The fl ow portion of the Flow/Temp/Salinity
Sensor
Electrolytic Cell The AquaPure electrolytic cell contains bipolar electrodes which perform the
is a backup device only.
electrolysis and produce chlorine when energized with DC current. Chlorine is generated as pool water containing salt passes through the cell. The chlorine production can be varied by either adjusting the Chlorine Production Level on the
power center or by varying the number of hours the AquaPure is on each day. The
AquaPure automatically cleans the Cell electrodes once every 3 hours by reversing polarity. This does not interrupt the production of Chlorine.
Page 7
Flow/Temperature/Salinity Sensor The Flow/Temp/Salinity Sensor only allows the Cell to operate if
there is adequate water fl ow through the Cell. The salinity portion of the Flow/Temp/ Salinity Sensor detects the level of salt in the pool water. This salt level is displayed in grams per liter (gpl) on the Liquid Crystal Display (LCD) whenever the salinity button is pressed. This eliminates the need for manual pool water salinity testing. Pool Temperature is now available on all models by pressing the
Pool Pump Timer A Pool Pump Timer is not included as part of your AquaPure. It is recommended that
Temperature button.
a timer or an AquaLink RS control system be used to save on energy and prolong the service life of your pool pump and the AquaPure.
2.1 Electrical Specifi cations Circuit Protection 2 pole 20 AMP device at the Electrical Panel.
Model APURE700 Model APURE1400
Input: 120 VAC, 50/60 Hz, 1.5 AMPS
240 VAC, 50/60 Hz, 0.75 AMPS
Input: 120 VAC, 50/60 Hz, 2.5 AMPS
240 VAC, 50/60 Hz, 1.25 AMPS Output: 22-30 VDC @ 3 AMPS maximum Output: 22-30 VDC @ 6 AMPS maximum Chlorine: 0.625 lb. / 24 Hr. (283 gm / 24 Hr.) Chlorine: 1.25 lb. / 24 Hr. (567 gm / 24 Hr.) External
Control:
ORP/External Control Connector AquaLink
®
RS485 Connector
External Control:
ORP/External Control Connector
AquaLink® RS485 Connector
CAUTION
Factory wired for 240 VAC service. If available electrical service is 120 VAC, the power supply
wiring must be changed to operate on 120 VAC as shown in the wiring diagram below. (Figure 2.)
Use Copper Conductors Only – Rated for 90°C Minimum
Line 1
Line 2
Pool Pump Timer
12
9
3
6
Transformer
Factory Wired for
240 VAC
Load 2 Load 1 Ground (Chassis)
To Earth Bonding Point
~
Wire Nut Connections
Load 1 to Blk Load 2 to Blk/Yel Blk/Red to Blk/Wht
Blk/Yel Blk/Red
Blk/Wht
Blk
Ribbon Cable
To Back PCB
Stripe
Flow/Temp/Salinity
Sensor
Circuit Breaker
Panel
240
VAC
50/60 Hz
3 wire
Ground
Tes t
Switches
Test Points
A to K
Test Points
Common
Aux Board
Front PCB
Reverse Side
Flow
Sensor
RS
H ORP
24 VAC
Figure 2. APURE700 and APURE1400 Wiring Diagram
RED BLK YEL GRN
AquaLink RS
Test Points
L to U
Pool Pump
Blue to Blue - 75 VAC (pin 1 to 8)
-L
Blk/Green to BLK/Green - 65 VAC (pin 2 to 7)
-U
From Transformer
1
1-8
A
8
B
Ribbon
Cable
From Front
PCN
Stripe
Test Points
Transformer
Back
PCB
A B
Re-wired for
120 VAC
Load 1 (Hot)
Load 2 (Neutral)
Ground (Chassis)
To Earth Bonding Point
Green
DC Cord
22 - 30 VDC
Black / White
Wire Nut Connections
Load 1 to Blk/Wht and Blk/Yel
~
Load 2 to Blk/Red and Blk
Blk/Yel Blk/Wht
Blk
Blk/Red
Page 8
Section 3. Installation Instructions Model APURE700 and APURE1400
3.1 Materials and Tools
NOTE Salt not included. See pages 17 - 20.
Installation Materials Furnished Tools Needed for Installation
(1 ea.) Electrolytic Cell with 2”-2.5” Universal Unions (1 ea.) Port Plug with 16 ft (4.88 m) Sensor and O-Ring (3 ea.) Universal Union Nut (1 ea.) 16 ft (4.88 m) DC Power Cord (1 ea.) Power Supply/Control Center (4 ea.) Anchors and Screws (2 ea.) Wire Nuts (1 ea.) Owner’s Manual - Warranty Information
Tape Measure Phillips & Flathead Screwdrivers Pliers Hacksaw Voltmeter to determine line voltage of AC wiring to power supply Electric Drill Motor and 1/4 “ masonry drill bit for mounting power supply on
block or stucco wall
®
approved All Purpose Cleaner Primer
An NSF
®
approved All Purpose Cement (such as Weld-On 794, 793)
An NSF
3.2 Plumbing Confi gurations
WARNING
When using electrical products, basic precautions should always be followed, including the following:
• DANGER: RISK OF ELECTRIC SHOCK WHICH CAN RESULT IN SERIOUS INJURY OR DEATH. Before attempting installation or service, ensure that all power to the device is disconnected/turned off at the circuit breaker. Connect only to a circuit protected by a ground-fault circuit-interrupter (GFCI).
• Grounding is required. The unit should be installed by a qualifi ed service representative and should be properly grounded. (See Earth Bonding, page 11).
• Install to permit access for servicing.
• Read Cautions and Important Instructions on page 4. Before attempting any electrical wiring, be
sure to read and follow Safety Instructions. Wiring should only be attempted by a qualifi ed professional.
Page 9
3.2.1 Recommended Cell and Sensor Orientation
Shown below are four different cell and sensor orientations. The third port on the cell is designed for installation of the sensors and for quick viewing of the cell plates. The Minimum Flow Rate is 30 GPM (114 LPM).
Flow
Sensor
A
A
Flow
Sensor
B
Figure 3. Chlorine Generator Cell and Sensor Orientation with Flow Direction
C
Sensor
Flow
Page 10
3.2.2 Recommended Plumbing Confi guration
The preferred installation is that the Cell and Sensors are plumbed in the return line to the pool after (downstream of) all the pool equipment (fi lter, heater, solar, etc.). The Cell and Sensor fi tting are designed to be plumbed into 2” PVC pipe. Adapters can be used for systems with 1½” plumbing. Figure 3 shows cell and sensor confi guration with fl ow direction. Figures 4 and 5 illustrates the recommended plumbing confi gurations, which result in the most reliable operation.
Note The AquaPure is powered from the LOAD SIDE of the pool circulation pump relay or the time clock. This
ensures that the Cell only operates when the pool pump is ON. The Flow Sensor serves as a protection device to ensure there is suffi cient fl ow for the Cell to operate.
AquaLink RS
Control System
AquaPure/
Clormatic
Cell
Heater
Heater
Sensor
Spa Bypass for Spillover
JANDY
Pool
Spa
Figure 4. Recommended Plumbing Confi guration for Pool/Spa Combination Systems
AquaLink RS
Control
Heater
System
Cell
Pool
Return
Sensor
Figure 5. Alternate Plumbing Confi guration for Pool or Dual Equipment Systems
AquaPure/
ClorMatic
Note The AquaPure is powered from the LOAD SIDE of the pool circulation pump relay or the time clock. This
ensures that the Cell only operates when the pool pump is ON. The Flow Sensor serves as a protection device to ensure there is suffi cient fl ow for the Cell to operate.
Page 11
3.3 Installing APURE700 and APURE1400 Control Center
1. Locate the control center as close to the pump and fi ltration system as possible. Make sure that the DC power cord and the Flow/Temp/Salinity Sensor cable can reach that section of pipe selected for the Cell
and Flow/Temp/Salinity Sensor installation. Do not install the Control Center within 10 ft (3 m) of the
pool edges.
2. Use hardware provided and mount the control center at eye level. Leave suffi cient clearance on all sides of the chassis backplate. If possible, leave a minimum of 9½ inch (241 mm) on the left side. Position the backplate on the mounting surface. Mark screw centers and drill four ¼ inch (6.35 mm) holes spaced 10
3
8
/
inches (264 mm) on the horizontal center and 6
3
8
/
inches (162 mm) on the vertical
center. Install the anchors (provided) into the mounting surface. See Figure 6.
3. Install the screws (provided) into the anchors, leaving approximately ¼” of the screw shaft exposed. Position the backplate keyhole slots over the four mounting screws. Press the control center chassis down fi rmly so that the screws are secure in the keyhole slots. Tighten the screws until snug.
4. Remove the four screws that secure the control center front cover. Remove the front cover.
Install Anchors (4)
and Screws (4) into
mounting surface
Drill two (2) holes
spaced 6
Drill two (2) holes spaced 10 3/8” on
Figure 6. Mounting the Control Center Chassis Backplate
3
/8” on the
vertical center.
the horizontal center.
Lower Chassis Keyhole on
to screws and tighten.
5. Using two of the four front cover screws, attach the cover to the chassis backplate. Please note that the chassis backplate has side mounting holes on both sides that allow you to secure the cover to either side of the backplate while you make all wire connections (see Figure 7).
Front cover secured to
available mounting holes.
Figure 7. Securing the Control Center Front Cover to the Chassis Backplate
Mounting holes
for front cover.
Page 12
6. Check source voltage. (All units are factory wired for 240 VAC). In order to use on 120 VAC, the internal factory wiring of the control center must be changed. (See wiring diagram page 6 Figure 2).
7. Use #12/3 insulated wire and conduit. Wire control center transformer to pool pump power source. The control center should be connected to the pump motor switch or automatic timer (Pool Pump
Timer) as shown in the diagram on page 6 Figure 2. The ow portion of the Flow/Temp/Salinity Sensor is a backup device only. Attach the third wire (Ground) from the electrical panel to the ground point inside the Control Center. Earth bonding in Section 3.4 must also be accomplished to ensure
personal safety and safety of equipment.
3.4 Earth Bonding (Grounding)
2
A solid, copper # 8 AWG (8.4 mm
) wire is recommended for connecting the control center to a Permanent
Earth Ground connection that is acceptable to the local inspection authority. Refer to your local codes for the acceptable grounding wire gauge. Attach the bonding point located on bottom of the chassis backplate to a Common Earth Bonding Point. Do not use the AquaPure as the Common Bonding Point. Each piece of non-AquaPure related pool equipment requiring a ground should be bonded to the Common, Approved
Earth Bonding Point. Never ground pool pump to the chassis backplate.
3.5 Installing the APURE700 and APURE1400 Cell and Flow/Temp/Salinity Sensor
NOTE: Maximum Operating Pressure is 345 kPa or 50 PSI - Minimum Flow Rate is 30 GPM (114 LPM).
1. Be sure pool pump is turned off.
WARNING
ATTENTION INSTALLER: If The Flow/Temp/Salinity Sensor is not installed properly, it may allow the Cell to operate without water fl ow. This would cause a buildup of fl ammable gases which can result in FIRE or EXPLOSION.
Mount as shown in Figure 8. This will result in the most reliable operation.
The Flow/Temp/Salinity Sensor must be mounted: (1) in the same line as the Electrolytic Cell. (2) with no valves or diverters between the Flow/Temp/Salinity Sensor and Cell.
Anytime the Flow/Temp/Salinity Sensor is connected or disconnected and reconnected, the AC power to the unit must be turned off and back on (Cycle Power). If power is not cycled, unreliable operation of the Flow/Temp/Salinity Sensor will result.
2. It is recommended that the Flow/Temp/Salinity Sensor and Electrolytic Cell be installed in the pool return line after the fi lter and heater. The Cell can be installed in either a horizontal (as shown in Figure 3) or a vertical position.
3. Position the Flow/Temp/Salinity Sensor and Cell in the recommended position (see page 8 Figure 3, page 9 Figures 4 and 5, and page 5 Figure 1).
4. Locate a suitable section of pipe, approximately 17 inches (432 mm) long or follow the recommended plumbing diagrams beginning on page 9, Figures 4 and 5. The Flow/Temp/Salinity Sensor cable and
Cell DC cord must be able to reach from the control center to this section.
Loading...
+ 28 hidden pages