Pool/Spa Combination Systems and
Pool/Spa Only Systems
FOR YOUR SAFETY - This product must be installed and serviced by a professional pool/
spa service technician. The procedures in this manual must be followed exactly. Failure to
follow warning notices and instructions may result in property damage, serious injury, or
death.
Sheet #6594, Rev. K
WARNING
Table of Contents
Page 3
Section 1. Important Safety Instructions ...........4
Section 2. System Overview .............................
Spa Only .........................................38
Aux Labels .......................................39
40
CONTROl PANEl MODEl SERIAl NUMBER
NOTES:
Page 4
Section 1. Important Safety Instructions
READ AND FOllOW All INSTRUCTIONS
lire la notice technique.
All electrical work must be performed by a licensed electrician and conform to all national, state, and
local codes. When installing and using this electrical equipment, basic safety precautions should always be
followed, including the following:
DANGER
To reduce the risk of injury, do not remove the suction fittings of your spa or hot tub. Never operate a spa or hot
tub if the suction fittings are broken or missing. Never replace a suction fitting with one rated less than the flow rate
marked on the equipment assembly.
WARNING
Prolonged immersion in hot water may induce hyperthermia. Hyperthermia occurs when the internal temperature
of the body reaches a level several degrees above the normal body temperature of 98.6° F. The symptoms of
hyperthermia include dizziness, fainting, drowsiness, lethargy, and an increase in the internal temperature of the
body. The effects of hyperthermia include: 1) unawareness of impending danger; 2) failure to perceive heat; 3)
failure to recognize the need to exit spa; 4) physical inability to exit spa; 5) fetal damage in pregnant women; 6)
unconsciousness resulting in a danger of drowning.
WARNING
To Reduce the Risk of Injury -
a) The water in a spa should never exceed 104°F (40°C). Water temperatures between 100°F (38°C) and
104°F (40°C) are considered safe for a healthy adult. Lower water temperatures are recommended for young
children and when spa use exceeds 10 minutes.
b) Since excessive water temperatures have a high potential for causing fetal damage during the early months of
pregnancy, pregnant or possibly pregnant women should limit spa water temperatures to 100°F (38°C).
c) Before entering a spa or hot tub, the user should measure the water temperature with an accurate
thermometer since the tolerance of water temperature-regulating devices varies.
d) The use of alcohol, drugs, or medication before or during spa or hot tub use may lead to unconsciousness with
the possibility of drowning.
e) Obese persons and persons with a history of heart disease, low or high blood pressure, circulatory system
problems, or diabetes should consult a physician before using a spa.
f) Persons using medication should consult a physician before using a spa or hot tub since some medication
may induce drowsines while other medication may affect heart rate, blood pressure, and circulation.
WARNING
Risk of electric shock - Install the power center at least five (5) feet (152.4cm) from the inside wall of the pool
and/or hot tub using non-metallic plumbing. Canadian installations must be at least three (3) meters (10 feet) from
the water.
Children should not use spas or hot tubs without adult supervision.
Do not use spas or hot tubs unless all suction guards are installed to prevent body and hair entrapment.
People using medications and/or having an adverse medical history should consult a physician before using a spa
or hot tub.
Danger d'electrocution - Les installations Canadiennes doivent se trouver à au moins trois (3) mètres de l’eau.
Ne pas laisser les enfants utiliser une cuve de relaxation sans surveillance.
Pour éviter que les cheveux ou une partie du corps puissent être aspirés, ne pas utiliser une cuve de relaxation si
les grilles de prise d'aspiration ne sont pas toutes en place.
Les personnes qui prennent des médicaments ou ont des problèmes de santé devraient consulter un médecin
avant d’utiliser une cuve de relaxation.
AVERTISSEMENT
Page 5
WARNING
People with infectious diseases should not use a spa or hot tub.
To avoid injury, exercise care when entering or exiting the spa or hot tub.
Do not use drugs or alcohol before or during the use of a spa or hot tub to avoid unconsciousness and possible
drowning.
Pregnant or possibly pregnant women should consult a physician before using a spa or hot tub.
Water temperature in excess of 100°F/38°C may be injurious to your health.
Before entering a spa or hot tub measure the water temperature with an accurate thermometer.
Do not use a spa or hot tub immediately following strenuous exercise.
Prolonged immersion in a spa or hot tub may be injurious to your health.
Do not permit any electric appliance (such as a light, telephone, radio, or television) within 5 feet (1.5 m) of a spa
or hot tub.
The use of alcohol, drugs or medication can greatly increase the risk of fatal hyperthermia in hot tubs and spas.
Water temperature in excess of 100°F/38°C may be hazardous to your health.
AVERTISSEMENT
Les personnes atteintes de maladies infectieuses ne devraient pas utiliser une cuve de relaxation.
Pour éviter des blessures, user de prudence en entrant dans une cuve de relaxation et en sortant.
Pour éviter l’évanouissement et la noyade éventuelle, ne prendre ni drougue ni alcool avant d’utiliser une cuve de
relaxation ni quand on s’y trouve.
Les femmes enceintes, que leur grossesse soit conrmée ou non, devraient consulter un médecin avant d’utiliser
une cuve de relaxation.
Il peut être dangereux pour la santé de se plonger dans de l’eau à plus de 38°C/100°F.
Avant d’utiliser une cuve de relaxation mesurer la témperature de l’eau à l’aide d’un thermomètre précis.
Ne pas utiliser une cuve de relaxation immédiatement après un exercice fatigant.
L’utilisation prolongée d’une cuve de relaxation peut être dangereuse pur la santé.
Ne pas placer d'appareil électrique (luminaire, téléphone, radio, téléviseur, etc) à moins de 1.5m de cette cuve de
relaxation.
La consommation d’alcool ou de drogue augmente considérablement les risques d’hyperthermie mortelle dans
une cuve de relaxation.
Il peut etrê dangereux pour la santé de se plonger dans de l’eau à plus de 38°C/100°F.
To avoid injury ensure that you use this control system to control only packaged pool/spa heaters which have builtin operating and high limit controls to limit water temperature for pool/spa applications. This device should not be
relied upon as a safety limit control.
A terminal bar marked "GROUND" is provided within the power center. To reduce the risk of electrical shock,
connect this terminal bar to the grounding terminal of your electric service or supply panel with a continuous
copper conductor having green insulation and one that is equivalent in size to the circuit conductors supplying this
equipment, but no smaller than no. 12 AWG (3.3mm). In addition, a second wire connector should be bonded with
a no. 8 AWG (4.115mm) copper wire to any metal ladders, water pipes, or other metal within five (5) feet (1.52m)
of the tub.
A ground-fault circuit-interrupter must be provided if this device is used to control underwater lighting fixtures. The
conductors on the load side of the ground-fault circuit-interrupter shall not occupy conduit, boxes, or enclosures
containing other conductors unless the additional conductors are also protected by a ground-fault circuitinterrupter. Refer to local codes for complete details.
Attention installer: Install to provide drainage of compartment for electrical components.
WARNING
CAUTION
CAUTION
SAVE ThESE INSTRUCTIONS
Page 6
Section 2. System Overview
2.1 Package Contents
Package contents will depend on which AquaLink RS System you are installing. All Jandy AquaLink RS
Systems come complete with the appropriate number of 3HP relays needed.
Control System Sub-Assemblies
All ButtonOneTouchWireless OneTouch
All Button Control Panel,
Power Center PCB,
Two (2) Temp Sensors,
Additional Relays,
Two (2) JVAs (Pool/Spa Combo
Systems)
Standard Power Center
(with mounting brackets)
OneTouch Control Panel,
Power Center PCB,
Two (2) Temp Sensors,
Additional Relays,
Two (2) JVAs (Pool/Spa Combo
Systems)
Power Centers
Sub-Panel Power Center
(with mounting brackets)
Wireless OneTouch Control Panel,
Outdoor Transceiver J-box,
Power Center PCB,
Two (2) Temp Sensors,
Additional Relays,
Two (2) JVAs
PureLink Power Center
(with mounting brackets)
2.2SystemComponentSpecicationsandDimensions
Table 1
Specifications (USA and Canada)
Power Supply120 VAC; 60 Hz; 3 A
Contact RatingHigh voltage - 25 A; 3HP @ 240 VAC
1½ HP @120 VAC
1500 Watts Incandescent
Low Voltage - Class Two, 1 A @ 24 VAC
Service SwitchAll Circuits (located at Power Center in Service Mode)
Specifications (European)
Power Supply230-240VAC; 50/60 Hz; 3 A
Contact RatingHigh voltage - 25 A; 3HP @ 240 VAC
Low Voltage - Class Two, 1 A @ 24 VAC
Service SwitchAll Circuits (located at Power Center in Service Mode)
Dimensions
Page 7
1¼"
All Button
Control Panel
5"
14½"
8"
5"
1¼"
5"
4½"
OneTouch
Control Panel
14½"
5"
1½"
4½"
5½"
Wireless Control
Panel
13¾"
Standard
Power Center
20"
Sub-Panel
Power Center
Page 8
2.3 Basic Plumbing
2.3.1 PlumbingforPoolandSpaCombination
The following plumbing diagrams illustrate
simplified versions of standard plumbing setups
for a pool and spa that share the same filter pump,
filter, and heater. The intake and return JVA’s
turn simultaneously so when the Spa button
is pressed on the AquaLink RS Control Panel,
water circulation switches between pool and spa
(consult the Jandy Valve Actuator Installation and Operation Manual to ensure that the JVA’s are
synchronized and rotate properly). Please consult
the Jandy Valve Plumbing Manual for further
examples of pool/spa plumbing.
From Solar
heat Pump
For Pool Only/Spa Only or Dual Equipment
plumbing, please refer to the Jandy Valve Plumbing
Manual for further examples.
NOTE When the filter system is shared (a Pool/Spa
Combo), the spa water must be able to overflow
back to the pool.
To Solar
heater
Check
Valve
Make-up
Spa
Check
Valve
Spa ReturnPool Return
Filter
Pump
Filter
Pool Drain
Spa Drain
SkimmersSkimmers
2.3.2 Booster Pump Pool Cleaner Plumbing
Page 9
heater
Booster
Spa Make-up
Pump
Spa ReturnPool Return
2.3.3 Non-Booster Pump Pool Cleaner Plumbing
Filter
Pump
Filter
Check
Valve
Pool IntakeSpa Intake
heater
Pool Return
Spa Make-up
Filter
Check
Valve
Spa Return
Cleaner
line
Filter
Pump
Energy
Filter
Pool IntakeSpa Intake
Page 10
Section 3. Installation
3.1 Power Center Mounting
1. The Power Center should be located at or
near the equipment pad. Locate the Power
Center at least five (5) feet or more away
from pool/spa and five (5) feet off the
ground. All national, state, and local codes
are applicable.
NOTE For Canadian installations, the Power Center
must be at least three (3) meters (9.8 feet)
away from the pool/spa and 1.5 meters (5 feet)
above the ground.
2. Use the mounting brackets and instructions
provided with the Standard Power Center
and/or Sub-Panel Power Center.
3. Sub-Panel Power Centers have special
code requirements. Be sure to follow all
applicable local and state codes to insure
safe installation.
appropriate wire for equipment. Each piece of
equipment requires its own high voltage relay.
Connect 120 volts to the Power Center terminals.
Connect equipment ground(s). See Figures 1 and 2.
Transformer
Black
Primary
White
low voltage raceway, do not run high voltage in this compartment
Neutral
Wire nut to
120 VAC power
Earth Ground
NOTE The Power Center is not to be considered
as suitable for use as Service Equipment.
Therefore, it is required to have the appropriate
means of disconnection, circuit isolation, and/or
branch circuit protection installed upstream of
the Power Center.
3.2 High Voltage Wiring
3.2.1 System Power
WARNING
Potentially high voltages in the AquaLink RS
Power Center can create dangerous electrical
hazards, possibly causing death, serious injury
or property damage. Turn off power at the main
circuit of the AquaLink RS Power Center to
disconnect the Power Center from the system.
To properly and safely wire the system, be sure
to carefully follow the applicable requirements
of the National Electrical Code (NEC), NFPA 70
or the Canadian Electrical Code (CEC), CSA
C22.1. All applicable local installation codes
must also be adhered to.
Depending on the amount of equipment being
controlled, run ½" or ¾" conduit from the power
supply panel to the bottom of the Power Center.
If you are using the Sub-Panel Power Center,
wire power to the appropriate breakers. Pull in
Breaker Panel
Figure 1. Standard Power Center
Transformer
Black
Primary
White
White
low voltage raceway, do not run high voltage in this compartment
White
Earth Ground
Figure 2. Sub-Panel Power Center
Black
Black
To 120 VAC
Breaker
Ground
From Main
Power
Page 11
3.2.2 3HP(Standard)Relays
For each piece of 240 volt equipment to be
controlled, connect line power to the two (2) line
terminals and connect equipment power to the two
(2) load terminals on the same relay.
For each piece of 120 volt equipment, connect
power to a line terminal and connect equipment to
a load terminal on the same relay.
NOTE The following are the contact ratings for 3HP
(Standard) Relay. DO NOT exceed any ratings.
3 HP @ 240 VAC; 1½ HP @ 120 VAC; 25
Amps; 1500 Watts.
3.2.3 BondingthePowerCenter
Install a bonding lug to the Power Center
enclosure. Connect the bond lug, using a #8 solid
copper core wire, to an approved earth ground (an
approved ground stake, grid, or conducting metal
water pipe buried to a sufficient depth). See Figure
3.
Filter
Pump (240
VAC)
24 VAC
Transformer
Primary
Earth
Ground
Bonding lug
Blower (120
VAC)
Figure 3. Standard Power Center - Bonding
Breaker
Panel
Page 12
OPTIONAL
OPTIONAL
3.2.4 UnderwaterLightingGFCIWiring
CAUTION
A Ground Fault Circuit Interrupter (GFCI) must be
provided in high voltage pool/spa lights. Do not
use a GFCI circuit breaker.The conductors on
the load side of the GFCI circuit shall not occupy
conduit, boxes, or enclosures containing other
conductors unless the other conductors are also
on the load side of a GFCI. Refer to local codes
for complete details.
1. For a Standard Power Center, install a GFCI
receptacle next to the breaker panel. For
a Sub-Panel Power Center install a GFCI
receptacle in the Power Center (use the
knockout provided on the right side of the
Sub-Panel Power Center). See Figure 4.
2. Connect neutral and hot wire (from circuit
breaker) to the LINE side of the GFCI.
3. Connect neutral (white wire) and the hot
(black wire) from the light to the LOAD
side of the GFCI.
3.2.5 JandyPoolandSpaLightsWiring
The JandyPoolandSpaLights can be wired into
the Jandy AquaLink RS control system to ensure
simplified operation of the lights, as well as a
means to synchronize the color change function.
Connect the lights to one of the auxiliary relays in
the Power Center.
NOTE It is recommended to connect one light per
relay so each light can be controlled separately.
However, up to four lights can be connected on
a single relay. If there are more than four lights
installed on one AquaLink RS system, ensure
there is more than one auxiliary relay available
in the Power Center.
Refer to Figures 5 and 6 to connect the Jandy Pool
and Spa Lights to the Power Center.
NOTE The Jandy Pool and Spa Lights are available
in 120-volt and 12-volt versions. If installing a
12-volt light, a 120-volt/12-volt step-down (AC)
transformer must be used. For more information
about 12-volt installations, refer to the Jandy
Digital,Color Changing,Underwater Pool and
Spa Lights Installation and Operation Manual.
4. Connect ground from the light to the
grounding bar inside the Power Center.
GFCI
Outlet
Standard Power Center
GFCI Outlet
(Optional)
Sub-Panel Power Center
Figure 4. GFCI Installation for Underwater
lighting
Page 13
GFCI
Black
White
Green
120V
Jandy
Light
Ground
Ground
Neutral
120 VAC
Power Supply
Junction
Box
GFCI
Ground
Ground
Neutral
Black
White
Green
12V
Jandy
Light
Black
White
Green
120V/12V
Transformer
120 VAC
Power Supply
Junction
Box
Figure 5. 120-Volt Jandy Pool and Spa light Wiring Diagram
Figure 6. 12-Volt Jandy Pool and Spa light Wiring Diagram
Page 14
3.3LowVoltageWiring
Minimum wire size should be 22 AWG. If wire run
is more than 300 feet, larger wire should be used.
3.3.1 Bezel Connection
Plug the 24 VAC power plug from the transformer
into its 3-pin terminal on the back of the Power
Center PCB (see Figure 7). Mount the Bezel to
the Power Center using the screws provided. Keep
battery wires from pinching.
CAUTION
DO NOT INSTAll BATTERY
power up system.
24 VAC Power Plug
Connection
until ready to
low Voltage
Raceway
Conduit Knockout for low Voltage
Control Panel Wire
Figure 7. Power Center PCB (back view)
3.3.2 Control Panel Cable to Power Center
PCB
Make provision for the cable to be run between
the indoor Control Panel and the Power Center.
Never run high voltage and low voltage in the
same conduit. Pull cable through the knockout
with the Heyco fitting and into the low voltage
compartment. Strip back jacket 6". Strip each wire
a ¼" and connect to the red, 4-pin connector on
the Power Center PCB. A multiplex kit may be
required if there are more than two cables running
to a red, 4-pin connector. See Figure 8.
heyco Fittings for
low Voltage JVA
and Sensor Wires
Figure 8. Control panel Cable to Power Center
PCB
high Voltage
Knockouts for
Conduit
(DO NOT run any low
Voltage wires through
these knockouts)
Page 15
OPTIONAL
4 3 2 1
4 3 2 1
RED
BLK
YEL
GRN
RED
BLK
YEL
GRN
®
JANDYAquaLink RS
FILTERPUMP OFF
AIR79°
06/26/04MON
6:00PM
EQUIPMENTON/OFF
ONETOUCH ON/OFF
MENU/ HELP
3.4 Heater Connection
The heater connection section applies to all
heaters or heat pumps with thermostatic circuitry
of 24 VAC or less (see pages 15 thru 17 for brand
specific installation).
NOTE If you are connecting a heater with thermostatic
circuitry of 120 VAC or greater, do not connect
to the green, 10-pin Terminal Bar. Instead
connect the heater to a high voltage relay in the
Power Center and plug the spare relay into the
Electric Heater relay socket on the back of the
Power Center PCB.
3.4.1 JandyHeaterConnections
1. Connect two #14 gauge wires, designed for
use in hot environments, to the #1 and #2
terminals on the green, 10-pin Terminal Bar.
2. Connect the other ends of the #14 gauge
wires from Step 1 to the Fireman's Switch
terminal bar in place of the factory installed
wire loop.
2. Confirm the LX and AquaLink RS software
revisions are compatible (see table).
3. Run a 4-conductor cable from the LX GUI
red, 4-pin connector to the RS power Center
red, 4-pin connector (see Figure 10).
lX Software RevisionAqualink RS Software
Revision
C04 to C08h or hh
C10, C11 or laterI, JJ, K or later
NOTE If connecting more than two (2) items to the RS
Power Center red, 4-pin connector, a Multiplex
PCB is required.
3. Do not disconnect high limit or pressure
switches.
4. Turn the heater thermostat(s) to maximum
setting.
5. Turn the heater switch to the ON position.
OR
For dual thermostat heaters turn switch to
Spa position.
Green 10-pin
Terminal Bar
Power Center PCB/Bezel
Factory
Installed
heater
Thermostat To
Wire loop
Max.
Terminal 1
Terminal 2
Jandy heater Fireman's
Switch Connection
Figure 9. Jandy heater Connection
#14
Gauge
Wire
heater Toggle
Switch To On
Figure 10. Jandy lX heater Connection to Power
heater
Wiring
4-Conductor
Wire
lX GUI
Center
RS Power
Center
Page 16
3.4.3 GuidelinesforHaywardHeaters
1. Remove heater service door.
2. Remove factory-installed wire nut between
two (2) red wires labeled "CONNECTION
FOR FIELD INSTALLED CONTROL
SWITCH" (see Figure 11).
3. Wire nut two (2) heater wires from
AquaLink RS P.C. Board to the two (2) red
wires of the heater (see Figure 12).
4. Set the thermostat selector switch to
ON, HIGH, or SPA, and set the heater
thermostat(s) to maximum.
limit Switch
limit Switch
4. Turn the heater toggle switch on, and the
heater thermostat(s) to max.
5. When connecting an AquaLink RS Control
to a Pentair Heater, Pentair requires that
you install the low voltage thermostat wires
in conduit separate from ANY line voltage
wires.
VIO
BlK
BlK
V
R
R
Pressure Switch
Factory
Installed
Wire Nut
Bl
OFFON
Figure 11. hayward heater Wiring Before
Modification
limit Switchlimit Switch
V
R
R
Wires to
Power Center
PCB
OFF
Bl
ON
RED
Figure 13. Pentair heater Wiring Before
Modification
VIO
BlK
Wires from
Power Center
BlK
RED
PCB
Figure 14. Pentair heater Wiring with Aqualink RS
3.4.5 GuidelinesforRaypakHeaters
For the 2-wire/1 function configuration, connect
the orange/black and black/orange wires to one
contact and the yellow/black wire to the other
contact (see Figure 15).
Pressure Switch
Figure 12. hayward heater Wiring with
Aqualink RS
3.4.4 GuidelinesforPentairHeaters
1. Remove the heater service door.
2. Separate the black wires (common) from
each other (see Figure 13).
3. Connect the wires from the Power Center
PCB to the two black wires on the heater
(see Figure 14).
To
Aqualink
RS System
P7
Terminal
Figure 15. Raypak heater Wiring with Aqualink RS
3.4.6 GuidelinesforaGasHeaterandaJandy
4 3 2 1 6 5 4 3 2 1
10 9 8 7 6 5 4 3 2 1
Battery
(9Volt)
®
JANDYAquaLink RS
FILTERPUMP OFF
AIR79°
06/26/04MON
6:00PM
EQUIPMENTON/OFF
ONETOUCH ON/OFF
MENU/ HELP
AE Series Heat Pump/Chiller Installation
Page 17
NOTE The following steps provide the procedure for
installing a Jandy AE Series Heat Pump.
1. Install a fixed resistor, with a value of 2.2K
Ohms, in the solar sensor terminals #3 and
#4 of the green, 10-pin terminal bar of the
AquaLink RS Power Center (see Figure
16).
2. To run the wires from the Heat Pump
control panel, remove the 5 screws that
attach the service/wiring cover panel to the
heat pump (see Figure 16).
NOTE One end of the wiring reserved for remote
control hook-up of the heat pump is connected
to terminals T5 and T6 on the control panel
printed circuit board (PCB), located on the back
of the control panel.
3. Run the wires from the Heat Pump control
panel through the wiring conduit located on
the outer right hand side of the Heat Pump.
4. Connect the Heat Pump to a standard
relay, then connect the relay to the solar
pump output on the PCB. Set the time to
11:59 PM; at 12:00 AM, the AquaLink
RS will auto-relabel Solar as Heat Pump.
Otherwise, the AquaLink RS will autorelabel Solar as Heat Pump within 24 hours.
5. The Solar Button will activate the heat
pump/chiller and the Pool and/or Spa
Heater Buttons will activate the gas heater.
In this manner the pool or spa can be heated
or chilled by the heat pump, the gas heater
or both.
NOTE To program the Heat Pump control panel, refer
to the Jandy AE Series Heat Pump Manual.
2.2K Ohms Resistor
Wireless OneTouch
Transceiver J-box
Note for All Button:
Green- Enabled
Red- On
Note for
OneTouch:
lED will not
come on for
heat Pump
Service/Wiring
Cover Panel
heat Pump/Chiller #1
To heat Pump #1
in Solar Sensor
Terminals for heat
Pump/Chiller
Gas heater Connections
Terminals 1 and 2
Standard high
Voltage Relay
low Voltage Wiring
to low Voltage Port
on heat Pump
Gas heater
To Pressure
Switch
Fireman's
Switch
From Fusible
link
heat Pump/Chiller #2
To heat Pump #2
Service/Wiring
Cover Panel
Port for low
Voltage Wires
Figure 16. heater and heat Pump/Chiller Wiring
Page 18
10 987654321
3.5 Temperature Sensors
1. Drill 3/8" hole in pipe between filter
pump and filter and install the Water Temperature Sensor per instructions
(make certain the o-ring is in place).
2. Install
Air Temperature Sensor outside the
Power Center can, not in direct sunlight and
away from motors and other heat sources.
3. Install Solar Temperature Sensor
(optional) adjacent to solar panels.
NOTE If a solar sensor (or a 2.2K Ohms resistor) is not
installed, the solar button can be labeled and
used as an extra auxiliary.
4. Run the wire to the Power Center, through
the low voltage raceway. Cut off excess
wire. Strip the wire jacket back 6", then
strip each wire ¼". Connect sensor wires to
the green, 10-pin terminal bar (see Figure
17).
2. Run the wire through the low voltage
raceway and plug the JVA connectors into
their proper sockets (see Section 6. Power Center Wiring Diagram). Verify that the
JVA on the suction plumbing is connected
to the Intake JVA Socket, and the discharge
plumbing is connected to the Return JVA
Socket.
NOTE Do not coil the JVA wires inside Power Center.
To shorten the wire, remove the JVA cover
and disconnect the wire. Shorten, strip, and
reconnect.
3. For alternate plumbing configurations the
JVA cam settings can be adjusted as needed.
See the Jandy Valve Actuator Installation
and Operation Manual, Cam Setting Chart
for proper settings.
3.7 Auxiliary Power Centers
Solar
Water
Temperature
Sensor
Freeze/Air
Temperature
Sensor
Green 10-Pin Terminal Bar
Figure 17. Temperature Sensor Wiring for a Pool/Spa
Combination
Temperature
Sensor
3.6JandyValveActuators
NOTE Mount the JVA's according to the Jandy Valve
Actuator Installation and Operation Manual.
JVA cable is type SJW-A marked water resistant
class 3 cable and does not require conduit.
Knockouts and Heyco fittings are provided in the
Low Voltage Raceway.
AquaLink RS All Button models support one (1)
Auxiliary Power Center.
AquaLink RS OneTouch models support a
maximum of three (3) Auxiliary Power Centers.
1. The auxiliary power centers may be wired
"in series", starting from the Primary Power
Center (solid line) or wired "in parallel"
from the Primary Power Center (dashed
line). See Figure 18.
Primary
Power
Center
or
Purelink
1. Route the JVA wire to the Power Center.
Figure 18. Wiring Multiple Power Centers
Page 19
4 3 2 1
2. Run four conductor, 22 AWG or larger
cable between the red, 4-pin terminal bars
in each Power Center.
NOTE
• All temperature sensors, heater connections
and the main filter pump must be wired to the
Primary Power Center.
• Never put more than two (2) wires into each
of the pins of the red, 4-pin terminal bar (use
a Jandy Multiplex Board).
• If more than one Auxiliary Power Center is
installed, set the jumpers as shown in Figure
19.
W1
W2
W1
W2
W1
W2
(No Jumpers on the Primary Power Center PCB)
Figure 19. Setting Jumpers for Multiple Auxiliary
Power Centers
Aux. PC #1
(AUX B1 to B8
for RS12, 16,
2/10, 2/14)
Aux. PC #2
(AUX C1 to
C8 for RS24,
2/22)
Aux. PC #3
(AUX D1 to D8 for
RS32, 2/30)
Mounting
Screw holes
Tab
Figure 20. All Button Control Panel - Back View
4-Conductor Cable
Access hole
3. Drill ¼" holes at the three (3) mounting
screw marks and insert the plastic anchors.
Drill a 1¼" (min.) to 2" (max.) hole for
cable access.
4. Mount the back of the control panel housing
to the wall and secure in place.
5. Pull the 4-conductor, 22 AWG or larger
cable through the access hole and tie a loose
knot to prevent the cable from slipping back
through the access hole. Strip cable jacket
6", and each individual wire ¼".
6. Remove the red, 4-pin terminal bar from the
control panel PCB. Connect the 4 conductor
cable to the red, 4-pin terminal bar (see
Figure 21). Reconnect the red, 4-pin
terminal bar back to the Control Panel PCB.
3.8 All Button Control Panel Installation
3.8.1 SingleIndoorControlPanel
1. With the aid of the homeowner, find the
best location for the Control Panel.
2. Open the Indoor Control Panel Assembly by
pressing in on the tab located on the lower
end of the back of the control panel (see
Figure 20). Place the back of the control
panel against the wall. Level the back of
the control panel and mark the three (3)
mounting screw holes and the cable access
hole.
Green
Yellow
Black
Red
Red 4-Pin Connector
Figure 21. All Button Control Panel PCB
7. Hang the Control Panel front over the two
tabs at the top of the control panel back.
Swing the bottom of the Control Panel front
down and snap into place.
Page 20
W2
W1
First Controller
Third Controller
W2
W1
Second Controller
W2
W1
Fourth Controller
W2
W1
Yellow
Green
Black
Red
W2
W1
Multiple Control Panels
RS
TM
RS
TM
RS
TM
RS
TM
3.8.2 MultipleAquaLinkRSAllButton
Control Panel Installation
The AquaLink RS allows each system to support
a maximum of 4 indoor control panels (see Figure
22). The control panels may be wired "in series"
starting from the first control panel (solid lines), or
wired "in parallel" from the AquaLink RS Power
Center (dotted lines), or any combination of the
two. In other words, any number of Indoor control
panels and/or Power Centers can be connected
by means of the red, 4-pin terminal bar in any
combination of "series" or "parallel" wiring.
NOTE Minimum wire size should be 22 AWG. If more
than one control panel is installed, or the length
of run is more than 300 feet, larger wire should
be used.
Jumper
location
Back of
All Button PCB
Figure 23. Jumper Settings for Multiple All Button
Control Panels
3.9 OneTouch Control Panel Installation
3.9.1 Surface Mount OneTouch Installation
1. With the aid of the homeowner, find the
best location for the Control Panel.
22 AWG
Minimum
Figure 22. Installing Multiple All Button Control
Panels
3.8.3. AquaLinkRSControlPanelJumper
Settings:
Move these jumpers only when installing more
than one control panel on a system (see
Figure 23). The jumpers are used to give each
control panel a unique system address. When
replacing an existing control panel, change the
jumper settings to match those on the one being
replaced.
NOTE If an AquaLink RS Personal Computer Interface
is installed, the AquaLink RS system will
recognize the interface as the fourth All Button
control panel.
2. Place Surface Mount Box in the location
chosen for the Control Panel. Mark the
holes for drilling. Drill 3/16" holes for the
sheet rock anchors and a 1¼" hole for the
4-conductor cable.
3. Run the 4-conductor cable from the Power
Center to the location of the Control Panel
(see Figure 24).
Surface
Mount Box
OneTouch PCB
Faceplate
Figure 24. OneTouch Surface Mount Installation
4. Pull the 4-conductor cable through the
Sheetrock
hole in the wall and the hole in the Surface
Mount Box. Mount the box to the wall
using the screws provided.
Page 21
W2
W1
4 3 2 1
5. Wire the 4-conductor cable to the red, 4-pin
terminal bar (see Figure 25). Push the 4-pin
terminal bar onto the back of the OneTouch
PCB. Place the PCB with LCD and buttons
back into the box. Insert the screws and
hand tighten. Do not overtighten. Snap the
Faceplate into place.
Green
Yellow
Black
Red
Figure 25. OneTouch PCB - Back View
3.9.2 FlushMountOneTouchInstallation
1. With the aid of the homeowner, find the
best location for the Control Panel.
2. Place the Flush Mount box in the location
chosen for the Control Panel. Level the box
and trace around the outside of the box with
a pencil. Cut the hole being careful not to
oversize.
3. Route the 4-conductor cable from the Power
Center to the Indoor Control Panel.
Slide cleat into the slot opening,
thread screw through the boss
and into cleat.
Sheet Rock
Boss
OneTouch PCB
Flush Mount
Faceplate
Figure 26. OneTouch Flush Mount Installation
(1/2" or
5/8" with a
4" square
cutout)
housing
5. Depending on what size sheet rock (5/8" or
1/2"), determine which side of the cleat is to
be facing you (see Figure 27).
4. Pull the 4-conductor cable through the hole
in the wall and the hole in the flush mount
box. Push the flush mount box into the hole
in the wall with the correct orientation (see
Figure 26).
Figure 27. Cleat Orientation
This side
faces towards
you for 5/8"
sheetrock.
This side
faces towards
you for 1/2"
sheetrock.
6. Insert a screw through the screw boss (see
Figure 26). Put a cleat into the top "U"
shaped hole. Hand tighten the screw and
repeat the process for the bottom cleat.
7. Wire the 4-conductor cable to the red, 4-pin
terminal bar. Push the 4-pin terminal bar
onto the back of the OneTouch PCB. Place
the OneTouch PCB back into the Flush
Mount Housing. Insert the screws with
rubber washers and hand tighten. Do not overtighten. Snap the faceplate into place.
Page 22
W2
W1
4 3 2 1
W2
W1
First Controller
Third Controller
W2
W1
Second Controller
W2
W1
Fourth Controller
W2
W1
3.9.3 MultipleAquaLinkRSOneTouch
Control Panel Installation
The AquaLink RS allows each system to support
a maximum of 4 indoor control panels (see Figure
28). The control panels may be wired "in series"
starting from the first control panel (solid lines), or
wired "in parallel" from the AquaLink RS Power
Center (dotted lines), or any combination of the
two. In other words, any number of Indoor Control
Panels and/or Power Centers can be connected
by means of the red, 4-pin terminal bar in any
combination of "series" or "parallel" wiring.
NOTE Minimum wire size should be 22 AWG. If more
than one control panel is installed, or the length
of run is more than 300 feet, larger wire should
be used.
Jumper
location
Back of
OneTouch
PCB
Figure 29. Jumper Settings for Multiple OneTouch
Control Panels
3.10 Wireless OneTouch Control Panel
Installation
22 AWG
Minimum
Figure 28. Installing Multiple OneTouch Control
Panels
3.9.4 AquaLinkRSOneTouchControlPanel
Jumper Settings
Move these jumpers only when installing more
than one control panel on a system (see Figure 29).
The jumpers are used to give each control panel a
unique system address. When replacing an existing
control panel, change the jumper settings to match
those on the one being replaced.
NOTE If an AquaLink RS Personal Computer Interface
is installed, the AquaLink RS system will
recognize the interface as the fourth OneTouch
control panel.
Installation Considerations. The transceivers
will transmit through walls and around corners.
Steel framing, aluminum siding, wrought iron,
cyclone fences, leaded glass, microwave ovens,
and other 2.4 GHz frequency items may inhibit/
prevent communication between the Wireless
AquaLink RS Control Panel and the Power Center.
The transceivers do not require line of sight to
communicate. To optimize communication, locate
transceivers to minimize interference. The Battery
Wireless AquaLink RS system requires OneTouch
Indoor PCB revision "E" or later and firmware
revision "B11" or later in order to work properly.
NOTE All new Wireless AquaLink RS indoor and
outdoor transceiver boards (PCB Assembly
7983 Rev B) use a C03 (or later) circuit chip
and are not compatible with the earlier
revision of the PCB that use a C02 (or earlier)
chip.
3.10.1 OutdoorTransceiverJ-boxInstallation
1. Turn off all power to the Power Center.
2. Mount the Outdoor Transceiver J-box at
least 6' above the ground and at least 8'
from an air blower (see Figure 30).
3. Open the door to the Power Center and
remove the dead panel.
Page 23
O
N
1
2
3
4
5
6
7
8
Air
J-box
Transceiver
Ground
level
6'
3 Yellow
4 Green
1 Red
2 Black
Minimum 8'
low Voltage Raceway
Red 4-Pin
Terminal Bar
Blower
Power
Center
Figure 30. Outdoor Transceiver J-box Installation
for Wireless OneTouch Control Panel
4. Feed the four conductor wire into the Power
Center through the low voltage raceway.
5. Cut off the excess wire. Strip the jacket
back 6" and strip the individual wires
approximately ¼". Connect the four
conductor wire to the red terminal bar on
the Power Center PCB.
6. Install the dead panel to the Power Center
and restore all power.
3.10.2 IndoorControlPanelInstallation
1. Connect the transformer to the back of the
control panel (see Figure 31).
2. Plug the transformer into a wall socket.
3. Charge for 24 hours before removing
the Power Supply/Charger (the system is
operational while charging).
When not in use, turn
the ON/OFF Switch to
the off position.
Power Supply/
Charger Cord
Figure 31. Wireless OneTouch Control Panel
Installation
3.10.3 ChangingtheTransmissionCode
If your AquaLink RS system is turning items on
or off at undesignated times, another AquaLink
RS Wireless Control Panel may be in close
proximity using the same or similar code. To
prevent unwanted operation, the code for your
AquaLink RS Wireless system can be personalized.
Except for DIP switch #8, both the Power Center
Transceiver and the Control Panel Transceiver
must be set to the same code. The Indoor Control
Panel Transceiver DIP switch #8 must be OFF and
the Power Center Transceiver DIP switch #8 must
be ON.
1. At the Indoor Control Panel, remove the
screws to expose the transceiver PCB.
2. Locate the small set of DIP switches on the
Control Panel PCB (see Figure 32). Except
for DIP switch #8, turn on one or more
DIP switches. Important- Before installing
the Control Panel cover, press the reset
button (SW1). Note which switches you
have turned on then reinstall the cover and
screws.
If any DIP Switch is moved, you
Always OFF
must press SW1 to establish
communication (may need to press
more than one time).
SW1
Indoor Control
Panel Transceiver
PCB
Figure 32. DIP Switch Settings at Wireless Indoor
Control Panel
Page 24
O
N
1
2
3
4
5
6
7
8
MENU
CANCEL
BACK
FORWARD
ENTER
3. At the Outdoor Transceiver J-box, remove
the cover to expose the Transceiver PCB
(see Figure 33). Set the DIP switches
(except #8) to the same settings as the
Control Panel Transceiver PCB that is in
the house. Important- Before installing the
J-box cover, press the reset button (SW1).
Close the cover and test the system.
Always ON
Power Center
Transceiver
PCB
If any DIP Switch is moved, you
must press SW1 to establish
communication.
SW1
Section 4. System Startup
4.1 All Button Programming
4.1.1 Basic Programming
To set a particular piece of equipment to turn on
and off at predetermined times, press the MENU
button (see Figure 34), scroll to the PROGRAM
MENU, press ENTER, and then press the button
for the equipment that you want to program. The
Control Panel Display will ask you to enter the day.
Use the arrow keys to select, and press ENTER.
The display will now prompt you for the starting
time and ending time. Repeat this process for each
piece of equipment that you wish to program. You
may enter as many programs as needed for each
piece of equipment.
Arrow Keys
Figure 33. DIP Switch Settings at Power Center
J-Box
Figure 34. Aqualink RS All Button Control Panel
Buttons
4.1.2 Set the Time
MENU > SET TIME > YEAR > MONTH > DAY > HOUR > MINUTE
To set the time, press the MENU button. Use the
arrow keys to scroll to the SET TIME menu and
press ENTER. Now scroll to the correct year,
month, and day and press ENTER. Scroll to the
correct hour and minute and press ENTER.
NOTE Depending on the version of the AquaLink RS,
the following items can be found either in the
Main Menu or in a Sub Menu under SETUP.
4.1.3 Set the Temperature
Pool/Spa Combination
1.
MENU > SET TEMP > POOL or SPA > SET TEMP VALUE
Press the MENU button, scroll to the SET TEMP
menu, and press ENTER. Use the arrow keys to
select POOL or SPA and press ENTER. Once you
have selected which heater to set the temperature
for, use the arrow keys to select the desired
temperature, and press ENTER to complete.
Page 25
2. Pool/Spa Only
MENU > SET TEMP >SET TEMP1 or SET TEMP2 > SET TEMP
VALUE
Press the MENU button, scroll to the SET TEMP
menu, and press ENTER. Use the arrow keys to
select SET TEMP1 and press ENTER (TEMP1
must be higher than TEMP2). Use the arrow
keys to select the desired temperature, and press
ENTER to complete. Press the MENU button,
scroll to the SET TEMP menu, and press ENTER.
Use the arrow keys to select SET TEMP2 and
press ENTER (TEMP1 must be higher than
TEMP2). Use the arrow keys to select the desired
temperature, and press ENTER to complete.
3a.
Maintain Temperature
NOTE Maintain Temperature Hours must be set when
Maintain Temperature is set, see Step 3b.
MENU > SET TEMP > SET MAINTAIN TEMP
Under the SET TEMP menu, scroll to MAINTAIN
and press ENTER. Use an arrow button to select
POOL, SPA or OFF. MAINTAIN will run the pump
for the chosen body of water to keep the water at
the desired temperature. If this function is on, as
long as the heater/chiller is enabled for that body
of water, the system will automatically turn on the
pump every couple of hours for just enough time
to test the water temperature. If the temperature
meets the set point, the pump will return to off. If
the measured temperature is different than the set
temperature, the pump will stay on and the heater/
chiller will operate long enough to bring the water
to the set temperature.
3b.
Maintain Temperature Hours
MENU > SET TEMP > SET MAINTAIN TEMP > SET HOURS
NOTE If DIP switch 1,2 or 3 are on, auxiliaries 1, 2
and 3 are labeled CLEANER, LOW SPEED
and SPILLOVER respectively and cannot be
relabeled.
4.1.5 SetFreezeProtection
MENU > SYSTEM SETUP > FRZ PROTECT > SELECT
EQUIPMENT
The AquaLink RS Freeze Protection senses when the
air temperature falls below 38° F (3°C) and will auto-
To add freeze protection to other equipment press the
MENU button. Scroll to SYSTEM SETUP and press
ENTER, then scroll to FRZ PROTECT and press ENTER. Press the button for the equipment you want to
protect.
4.1.6 Assign JVAs
MENU > SYSTEM SETUP > ASSIGN JVA > SELECT JVA
The assign JVA menu lets you assign Jandy Valve
Actuators (JVA) to any auxiliary button. This
means that whenever you press that auxiliary
button, a valve turns. On pool/spa combination
models, there are two JVAs that can be assigned to
auxiliary buttons: the Cleaner JVA and the Solar
JVA (unless the solar function is installed).
NOTE If a solar sensor is installed, the Solar JVA will
automatically be assigned and will be marked
as USED.
On pool only/spa only models, there are four JVAs
available. The AquaLink RS installer must set up
these JVAs for this feature to operate correctly.
Assigning JVAs lets the owner control certain
features like diverting water to a waterfall or bank
of spa jets.
Sets the desired time when this function will
activate (default setting is 12AM to 12AM; 24
hours a day). Under SET TEMP scroll to HOURS
and press ENTER. Use the arrow keys to change
the HOURS the system will maintain the set
temperature.
4.1.4 LabelAuxiliaryFunctions
MENU > SYSTEM SETUP > LABEL AUX > CHOOSE LABEL
Press the MENU button, scroll to SYSTEM
SETUP and press ENTER. Scroll to the LABEL
AUX menu and press ENTER. Press the button (on
the control panel) to be labeled (example: AUX1).
Scroll to the desired label and press ENTER.
Repeat for all functions.
To assign JVA values, press the MENU button. Use
the arrow keys to scroll to SYSTEM SETUP, press
ENTER. Use the arrow keys to scroll to ASSIGN
JVA menu and press ENTER. The AquaLink RS
display will read CLEANER JVA. If both JVAs are
being used, you will not be able to use this menu.
Use the arrow keys to choose among the JVAs
listed. When the JVA you want to assign to an
auxiliary is displayed, press ENTER.
The AquaLink RS display will read SELECT
AUX TO ASSIGN JVA TO. Press the button of the
auxiliary you want to activate the JVA.
Page 26
JANDYAquaLink RS
FILTERPUMP OFF
AIR 79°
06/26/04 MON
6:00 PM
EQUIPMENT ON/OFF
ONETOUCH ON/OFF
MENU / HELP
4.2AllButtonResetandDisplayMessages
4.2.1 Reviewing
MENU > REVIEW > SELECT ITEM TO REVIEW
To review equipment, press the MENU button, then
use the FORWARD arrow key to scroll to the REVIEW
menu. Press ENTER, use the arrow keys to scroll to the
item you wish to review, and press ENTER again.
4.2.2 Canceling Items
CANCEL > SELECT ITEM TO CANCEL
If you make a mistake in programming or you want
to change, for example, the ON/OFF times for a spe-
equipment. For example, to canceladimmer, press
the CANCEL button; use the arrow keys to advance
to DIMMERS and press ENTER. The AquaLink RS
display will prompt you to select an Aux. Press the
button of the auxiliary for which you want to cancel the
dimmer.
CANCEL button. Use the arrow keys to scroll to JVA
ASSIGNS and press ENTER. The AquaLink RS display
will read CLEANER JVA. Use the arrow keys to toggle
between JVAs to cancel. When the JVA assignment
that you want to cancel is displayed, press ENTER.
The AquaLink RS display will read PRESS ENTER
TO CANCEL JVA ASSIGNMENT, OR CANCEL TO
ABORT. Press ENTER to cancel the JVA assignment, or
press CANCEL to abort.
4.3 OneTouch Programming
4.3.1. Basic Programming
To set a particular piece of equipment to turn
on and off at predetermined times, highlight
MENU/HELP and press SELECT (see Figure 35).
Highlight PROGRAM and press SELECT. Use the
UP or DOWN buttons to highlight the equipment
(for example, Filter Pump) then press SELECT.
Follow the on-screen prompts. Use the UP or
DOWN buttons to pick each number, starting with
ON hours, press SELECT to enter and move on
to the next item to change, including picking what
day(s) the program will run. If you make a mistake,
use the BACK button to return to a number. If the
program is already entered, highlight CHANGE
PROGRAM and step through to the entry that
should be corrected.
NOTE The following items can be found either in the
MENU/HELP or in a Sub Menu under SYSTEM
SETUP.
4.3.2 Set the Time Menu
MENU/HELP > SET TIME
To set the time, highlight the MENU/HELP and
press SELECT. Highlight SET TIME and press
SELECT. Use the UP or DOWN button to set the
values. Press SELECT to continue.
4.2.3 ResettingtheSystem
MENU > SYSTEM SETUP > CLEAR MEMORY
To remove all labeling, programming, assignments, and
temperature settings, press the MENU button, use the
arrow keys to scroll to SYSTEM SETUP and press ENTER. Scroll to CLEAR MEMORY and press ENTER.
Page Up
UP
Button
BACK
Page Down
SElECT Button
Figure 35. OneTouch Control Panel Buttons
Green- heater enabled or
Red- heater on and firing
heater lED
up to temperature
DOWN
Button
4.3.3 Set the Temperature
1.Pool/Spa Combination
MENU/HELP > SET TEMP > POOL or SPA > SET TEMP VALUE
Highlight MENU/HELP and press SELECT.
Highlight SET TEMP and press SELECT. Use the
UP or DOWN button to highlight either POOL or
SPA and press SELECT. Use the UP or DOWN
button to increase or decrease the temperature and
press SELECT. Use the BACK button to return to
the main screen.
2. Pool/Spa Only
MENU/HELP > SET TEMP > TEMP1 > SET TEMP1 VALUE >
TEMP2 > SET TEMP2 VALUE
Highlight MENU/HELP and press SELECT.
Highlight SET TEMP and press SELECT (TEMP1
must be higher than TEMP2). Press SELECT on
TEMP1. Use the UP or DOWN button to increase
or decrease the temperature and press SELECT.
Page 27
Highlight TEMP2 and press SELECT (TEMP1
must be higher than TEMP2). Use the UP or
DOWN button to increase or decrease the
temperature and press SELECT. Use the BACK
button to return to the main screen.
3. Maintain Temperature
MENU/HELP > SET TEMP >MAINTAIN
In the SET TEMP menu, highlighting MAINTAIN
and pressing SELECT will turn on (or off) the
MAINTAIN function. MAINTAIN will run the
pump for the chosen body of water to keep the
water at the desired temperature. If this function
is on, as long as the heater/chiller is enabled for
that body of water, the system will automatically
turn on the pump every couple of hours for just
enough time to test the water temperature. If
the temperature meets the set point, the pump
will return to off. If the measured temperature is
different than the set temperature, the pump will
stay on and the heater/chiller will operate long
enough to bring the water to the set temperature.
4. Maintain Temperature Hours
MENU/HELP > SET TEMP >HOURS
NOTE The Auxiliary labels AIR BLOWER and FILL
LINE have an automatic 30 minute runtime.
To change this setting, refer to the DEVICE
RUNTIME feature.
If DIP switch 1,2 or 3 are on, auxiliaries 1, 2
and 3 are labeled CLEANER, LOW SPEED
and SPILLOVER respectively and cannot be
relabeled.
4.3.5 SetFreezeProtection
MENU/HELP > SYSTEM SETUP > FREEZE PROTECT > SET
TEMP VALUE > SELECT FREEZE PROTECT DEVICE
Highlight MENU/HELP and press SELECT.
Highlight SYSTEM SETUP and press SELECT.
Highlight FREEZE PROTECT and press SELECT.
Use the UP or DOWN button to change the
temperature. Once the temperature is set press
the SELECT button to move to the next screen
to assign freeze protection to a selected piece of
equipment. Highlight a device and press SELECT.
"X" means the device has been assigned.
NOTE The filter pump is always assigned to freeze
protection.
4.3.6 Assign JVAs
Sets the desired time when this function will
activate (default setting is 12AM to 12AM;
24 hours a day). Highlight HOURS and press
SELECT. Use the UP or DOWN buttons to change
the HOURS the system will maintain the set
temperature.
4.3.4 LabelAuxiliaryFunctions
MENU/HELP > SYSTEM SETUP > LABEL AUX > AUX 1-X >
CHOOSE LABEL TYPE > CHOOSE LABEL
Highlight MENU/HELP and press SELECT.
Highlight SYSTEM SETUP and press SELECT.
Highlight LABEL AUX and press SELECT.
Highlight the AUX you want to label and
press SELECT. Highlight GENERAL, LIGHT,
WATERFALL or CUSTOM LABEL and press
SELECT. Choose a name within these categories
by using the UP or DOWN button or the PAGE UP
or PAGE DOWN button, press SELECT when you
find the correct name. Choose CUSTOM to type in
your own names.
MENU/HELP > SYSTEM SETUP > ASSIGN JVAs > SELECT JVA
Highlight MENU/HELP and press SELECT. Highlight
SYSTEM SETUP and press SELECT. Highlight ASSIGN JVA and press SELECT. Highlight the JVA you
wish to assign and press SELECT.
NOTE If a solar sensor is installed, the Solar JVA will
automatically be assigned and will be marked
as USED.
4.4OneTouchResetandDisplayMessages
4.4.1 RestartingtheSystem
MENU/HELP > SYSTEM SETUP > CLEAR MEMORY >
CONTINUE > FINAL WARNING > CONTINUE
To remove all labeling, programming, assignments
and temperature settings, highlight MENU/HELP and
press SELECT. Highlight SYSTEM SETUP and press
SELECT. Highlight CLEAR MEMORY and press
SELECT. Highlight CONTINUE and press SELECT.
Use the UP or DOWN button to highlight YES or NO
and press SELECT. There will be about a 15 second
delay before you see the FINISHED screen. Highlight
CONTINUE and press SELECT to return to the
SYSTEM SETUP.
Default Temperature (Pool/Spa Combination)Default Pool Temp = 80° F
Default Spa Temp = 102° F
Default Temperature (Pool/Spa Only)Default TEMP1 = 80° F
Default TEMP2 = 60° F
Default Spa Side Switch SettingsButton 1 = Spa (Filter Pump for pool/spa only models)
Button 2 = Spa Heater (Temp1 for pool/spa only models)
Button 3 = AUX1
Button 4 = AUX2
Default Freeze Protection SettingsFILTER PUMP: freeze protection ON. ALL OTHER EQUIPMENT,
freeze protection OFF.
NOTE If you select SPA to be freeze protected, water circulation will switch between pool and spa every 30
minutes during freezing conditions once freeze mode is active.
4.5.1 Power Center Service Switch
AUTOMode(automatic)
1. The control panel has complete control of all
functions.
2. All programmed settings will operate.
3. All safety delays and equipment protection
interlocks are operational.
SERVICEMode
1. The power center has complete control of all
functions.
2. Service mode must be turned on/off at the
power center.
3. No programmed settings will work.
CAUTION
In service mode, the safety interlocks for
equipment protection are overridden.
4.5.2 ChangingtheChlorineProduction
Settings at the Equipment
The AquaPure and AquaLink RS now have twoway communication. The AquaLink RS Power
Center will read settings or modifications made
from the AquaPure Service Panel. This feature
is available with AquaPure front PCB firmware
version 11230A05 or later. Your firmware revision
number can be found on the back of the front
AquaPure PCB.
ChangingChlorineProductionPercentageRate
1 At the AquaLink RS Power Center:
A. The AquaLink RS Control System must be
set to Service Mode before you can change the
chlorine production levels from the AquaPure
Service Panel. Press the Mode Select button to
move the AquaLink RS from Auto Mode into
Service Mode. The indicator light located next
to the Service will turn ON.
TIMEOUTMode
1. The power center has complete control for
three (3) hours.
2. After three (3) hours the system will return to
AUTO mode.
3. Programmed on/off times will be overridden
during the three (3) hours.
4. After the three (3) hour "time out", the system
will resume any programmed items that were
overridden.
B. Press the Valve Select button to choose
either Pool Mode to change pool chlorine
production, or Spa Mode to change spa
chlorine production.
C. Press the Filter Pump Button to turn on the
pump and apply power to the AquaPure system.
Mode Select
Button
Filter Pump
Button
Valve Select
Button
1. Broadcast or Spread Salt into Shallow End of Pool. Do Not Add Salt through
Skimmers, Main Drain or Surge Tank.
2. Set Unit to "00" % for 24 Hours. The AquaPure must read "00" for 24 hours
after the salt has been added and circulated in the pool.
Boost - 24 Hour 100% Chlorine Production Cycle - Refer to Manual
- - - - To Enter Boost Mode Press and Hold "Temperature" Button for 10 Seconds
Pool Temperature - Temperature of Pool Water at Flow Sensor
CELL ON - Making Chlorine
CELL RESTING - Off Portion of Chlorine Production Cycle
FLOW - Water Flow Present
CELL REVERSING - Automatic Cleaning Cycle in Progress
ADD SALT - Salinity Should be 3.0 - 3.5 Grams / Liter
SERVICE - Refer to Manual -
- - - - To Silence Audible Service Alarm Press and Hold "Salinity" Button for 5 Seconds
DIRECTIONS FOR ADDING SALT
Power On
CELL ON
CELL RESTING
FLOW
CELL REVERSING
ADD SALT
SERVICE
CHLORINE
PRODUCTION RATE
C
D
A
B
??
SalinityPool
Temperature
- Boost -
Press to increase or decrease
% Chlorine Production
2. At the AquaPure Service Panel:
A. Press the UP/DOWN arrow buttons on the
AquaPure Service Panel to increase or decrease
chlorine production rate for either the pool or
spa.
When the desired value for chlorine production
is set from the AquaPure Service Panel, return
to the AquaLink RS Power Center.
3. At the AquaLink RS Power Center:
A. Press the Mode Select button to put the
AquaLink RS in Time Out mode.
Page 29
4.5.4 Power Interruption
In the event there is a power interruption, and the
AquaLink RS system is in Service or Time Out
mode, the system will default to Auto. In previous
firmware versions, the system would default to last
mode of operation.
ATTENTION
Special Note to Startup Person: The
AquaLink RS allows two (2) options for
operating the pool equipment on the first day of
operation:
Option #1 - Once all programming of
equipment is completed, the AquaLink RS will
automatically review all programs and turn on
any equipment which is programmed to be on.
Option #2 - To operate the filter pump or
cleaner continually for the first day, leave the
power center service button in AUTO mode. At
the indoor control panel, press the filter pump
or cleaner buttons for the equipment you want
to run. The equipment that is activated will run
continuously, ignoring the first programmed
off time, and will turn off at the programmed
off time for the next day (only if a program has
been entered).
B. Press the Mode Select button again to place
it back into Auto mode.
NOTE: ThE POWER CENTER MUST BE IN POOl
MODE TO ChANGE ThE AqUAPURE POOl
SETTING; IT MUST BE IN SPA MODE TO
ChANGE ThE AqUAPURE SPA SETTING. USE
ThE VAlVE SElECT BUTTON TO SWITCh
BETWEEN ThE TWO MODES. SYSTEM MUST
BE CYClED ThROUGh SERVICE, TIME OUT
ThEN BACK TO AUTO TO ACCEPT ThE POOl
SETTINGS VS. SPA SETTING.
4.5.3 Battery Backup
A nine-volt battery is located at the power center.
The battery keeps the clock running during a
power outage so the time and date will be correct
when power is restored. Programming will not be
lost even if the battery is dead. Do not install the
battery in the power center until the system is ready
to operate. Battery will drain if power is left off.
Review DIAGNOSTICS in the SYSTEM SETUP
section of the menu. The DIAGNOSTICS will
indicate when the battery needs replacement.
Page 30
REVIEW
PROGRAM
SELECT
EQUIPMENT
ON ALL DAYS
SET TEMP
POOL TEMP
SPA TEMP
SET TIME
SET YEAR, DAY
HOUR & MINUTE
LOCKOUTS
SYSTEM
SPASWITCH
SPALINK
DEVICE
PGM GROUP
GROUP A
GROUP B
DISPLAY LIGHT
PROGRAMS
TEMP SET
SPA SWITCH
SPA LINK
FRZ PROTECT
AUX LABELS
DIMMERS
JVA ASSIGNS
LOCKOUTS
ALL OFF TIME
SET POOL*
MAINTAIN TEMP
SYSTEM SETUP
ALL OFF TIME
ASSIGN JVA
TEMP CAL
DEGREES F/C
AIR TEMP
FRZ PROTECT
SPA LINK**
SPA SWITCH**
MAIN LABEL MENU
SEE SECTION 8 FOR
AN EXPANDED LIST
SET DIMMERS**
SELECT EQUIPMENT
ALL OFF
LABEL AUX
AQUAPURE
†
DAYLIGHT SAVINGS
DIAGNOSTICS
IN FLOOR CLN
SOLAR HEAT PRIORITY
PUMP LOCKOUT
SET TIME FOR BOOST
FEATURE ON
FEATURE OFF
3 SWITCHES
2 SWITCHES
1 SWITCH
3
LINKS
2
LINKS
1 SPA LINK
TEMP SETTINGS
ASSIGN ITEMS
DIAGNOSTIC READOUT
CLEAR MEMORY
WARNING! CLEARS ALL MEMORY
CHOOSE JVA
TEMP UP
TEMP DOWN
CELSIUS
FAHRENHEIT
SELECT EQUIPMENT
OFF
ON
SOLAR HEAT PRIORITY
IN FLOOR CLN
COLOR LIGHTS
SET AQUAPURE
†
COLOR LIGHTS
AQUAPURE MODE
†
POOL
SPILLOVER
SPA
SPA
BOOST
†
START
PAUSE
STOP
†
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
CHOOSE LIGHT
CHOOSE BUTTON
CHOOSE BUTTON
ON WEEKENDS
ON WEEKDAYS
ON SPECIFIC DAY
SET SPA*
4.6AllButtonMenuFlowChart
†
Items Seen Only With Optional Equipment
* Items Seen Only In Revision "M"
** Not Available on Export Models
4.7OneTouchMenuFlowChart
ONETOUCH ON/OFF
SPA MODE
CLEAN MODE
ONETOUCH 3
ON
OFF
MENU/HELP
PROGRAM
SET TEMP
POOL HEAT
SPA HEAT
SET TIME
SET MONTH, DAY,
YEAR & TIME
DISPLAY LIGHT
ON
OFF
2 MIN. DELAY
LOCKOUTS
SYSTEM
SPA SWITCH
SPA LINK
DEVICES
LOCK
UNLK
SELECT DEVICESELECT DEVICE
LOCK
UNLK
PROGRAM
GROUP
GROUP A
GROUP B
SYSTEM
SETUP
LABEL AUX
TEMP CALIBRATE
IN FLOOR CLEAN
SOLAR HEAT PRIORITY
†
ASSIGN JVAs
DIMMERS**
SPA SWITCH**
SPA LINK**
PRODUCT INFO
CLEAR MEMORY
ONETOUCH
ONETOUCH 1
ONETOUCH 2
ONETOUCH 3
SELECT NAME
CUSTOM NAME
SET DEVICES
ON
OFF
GENERAL LABELS
LIGHT LABELS
WTRFALL LABELS
(TYPE PERSONALIZED
DESCRIPTION)
INTAKE
RETURN
CLEANER
SOLAR
1
2
3
1
2
3
OK
GO BACK
ENABLED
DISABLED
ENABLED
DISABLED
SET TEMP
FREEZE PROTECTION
AIR TEMP
DEGREES F/C
ENABLED
DISABLED
FAHRENHEIT
CELCIUS
SET TEMP
DAYLIGHT SAVINGS
ENABLED
DISABLED
PUMP LOCKOUT
ENABLED
DISABLED
DUSK SETUP
DUSK CTRL
DURATION
TIME ADJUST
YOUR LOCATION
YOUR TIME ZONE
SET DEVICES
SELECT LOCATION
PACIFIC
MOUNTAIN
CENTRAL
EASTERN
SELECT EQUIPMENT
BOOST
†
SET AQUAPURE
†
SET POOL*
AQUAPURE
†
SET TIME
MAINTAIN
HOURS
HELP
KEYS
SERVICE
DIAGNOSTICS
OFF
SPA
POOL
START
GO BACK
ON
OFF
SET TIME
ALL OFF TIME
FEATURE
OFF TIME
OFF
ON
SET TIME
EQUIPMENT
ON/OFF
SELECT
EQUIPMENT
ON
OFF
ALL OFF
ADD PROGRAM
DELETE
CHANGE
CHILL
†
MODEL
SENSORS
REMOTES
ERRORS
MODE
††
POOL
SPILLOVER
COLOR LIGHTS
JANDY LIGHT
SAM/SAL LIGHT
ASSIGN TO AUX
DEVICE RUNTIME
SELECT
EQUIPMENT
0:30 TO 2:00 HOURS
OFF
HEAT PUMP
†
HEAT MODE
CHILL MODE
SELECT
EQUIPMENT
SELECT
DEVICE
SELECT
DEVICE
SELECT
DEVICE
SELECT
LABEL
CUSTOM LABELS
SET SPA*
Page 31
†
* Items Seen Only In Revision "M"
** Not Available on Export Models
Items Seen Only With Optional Equipment
††
Mode Only Displayed When DIP Switch #3 is Set to ON
Page 32
Section 5. Troubleshooting
5.1AllButtonandOneTouchQuick
TroubleshootingGuide
SymptomProblemPossible Solution
Power Center override switches
operate when in Service or
Time Out Mode, but the control
panel is completely dead (no
lights on, no display).
All LEDs are on at the control
panel and the part # and
revision letter of the control
panel software are displayed.
The override switches at the
power center operate as they
should.
All LEDs are on at the control
panel and the part # and
revision letter are displayed, but
override switches at the power
center do not operate at all.
Some buttons do not operate
from the control panel, nor
from the power center override
switches.
Power supply problem.Check connection of the outside two wires (red
& green) of the four conductor cable. If wired
correctly, check the voltage between these two
wires. Voltage for an All Button system should
be 7+ VDC and for a OneTouch system, 8+ VDC
(use the higher voltage for a mixed system).
Control panel is not
communicating with the power
center PCB.
1. Damaged or improperly
installed PPD.
2. Damaged power center
PCB.
Wrong PPD chip installed at
the power center PCB.
Check the two center wires (black & yellow)
of the four conductor cable. Also check the
installation of the PPD on the power center PCB.
If the PPD is not seated correctly the system will
not communicate.
1. Check alignment of the PPD.
2. If PPD is installed correctly, replace the
power center PCB.
Check part number and revision letter by
pressing the reset button at the control panel.
The second part number and revision letter
displayed is for the PPD indicating which model.
System locked up.Microprocessor locked.Turn off power to the system. Disconnect battery
and turn on power. Reconnect the battery and
reset time and date.
Programs do not run at the
correct time.
One button on the Four
Function Remote or SpaLink
RS does not operate.
Pool cleaner booster pump
turns on without the filter pump
being on, and can run with the
spa on.
Cannot assign cleaner JVA.DIP switches not set correctly.DIP switch #1 must be off, and DIP switch #7
AquaLink does not display
correct time and date.
Check programming first. If
the Four Function Remote or
SpaLink RS is programmed
correctly, the button may be
shorted.
System is not recognizing DIP
switch #1 is on. Note: before
turning on any DIP switches,
first turn off all equipment.
At the control panel set correct time and date.
In Diagnostics check battery level. If LOW
BATTERY is displayed, replace battery to ensure
correct time and date are maintained.
Replace the Four Function Remote or SpaLink
RS. Use MENU, REVIEW, SPA SWITCH (or
SPA LINK) to check programming.
Turn off all equipment buttons, then turn off
power to the system, finally turn off, then on, DIP
switch #1. Turn on power and test system.
must be on to assign the cleaner JVA to an
auxiliary (Revision F or older).
SymptomProblemPossible Solution
Page 33
Model is one of the AquaLink
RS Dual Equipment, message
scrolls "ADJUSTABLE FREEZE
SENSOR NOT INSTALLED".
System comes on at times that
are not programmed.
System comes on at times that
are not programmed.
Heater will not fire. Heater LED
will not light in "Service Mode".
Normal operation when a Dual
Equipment AquaLink RS is
controlling a solar system and
an adjustable freeze sensor is
not installed.
Phantom programs.At the control panel press MENU, then scroll
Water temperature sensor not
installed or defective.
The Wireless AquaLink RS will stop
communicating anytime interference (such
as from a microwave oven or other 2.4 GHz
devices) prevents a valid signal transmission.
When communication is lost the control panel
will lock on "Model Number" until a good link
is again achieved, usually within a few seconds.
If communication is not reestablished within
a few seconds or this happens often, use the
troubleshooting information in the following table
for suggestions.
Either install the adjustable freeze sensor, or
wait 24 hours and this message will go away.
to REVIEW. Make note of all programs (the
Four Function Remote setting, labels, and
temperature settings) then turn off all DIP
switches and go to the control panel. CLEAR
MEMORY, reprogram and try system again.
Check water temperature sensor.
NOTE On the Battery Wireless, the display screen will
go into "Sleep Mode" after 60 seconds. That
is, if a button has not been pressed within 60
seconds, the screen will go blank. Press any
button on the control panel to turn the display
on again.
SymptomProblemPossible Solution
RS System operation is slow or
display is erratic.
LCD screen display stays on
"Firmware B11" (or later).
Older firmware installed.Replace socketed chip in OneTouch printed
No communication between
indoor Control Panel and
Power Center J-box.
circuit board with Firmware B11 or newer.
1. Confirm DIP switch settings on both the
Indoor Control Panel Transceiver and Power
Center Transceiver are as follows:
• DIPs 1-7 are set identical
• DIP 8 is ON at Power Center J-box PCB
• DIP 8 is OFF at Control Panel Transceiver
PCB
2. At the Power Center J-box Transceiver board,
press the SW1 setup button and confirm
that the green LED flashes approximately 10
times.
Page 34
Symptom (continued)ProblemPossible Solution
LCD screen display stays on
"Firmware B11" (or later).
No communication between
indoor Control Panel and
Power Center J-box.
3. Repeat Step 2 for the Indoor Desktop Control
Panel.
4. Recheck the Indoor Desktop Control Panel
for proper performance.
5. If there is no communication yet, check
LED’s at the Power Center J-box Transceiver
PCB.
• Red LED must be lit to indicate power. If
red LED is not lit check 4-conductor wire
connection to the red, 4-pin terminal bar at
the Power Center.
• Amber middle LED must blink continually. If
not blinking, transceiver needs to be replaced
with part #8114 or #8241 depending on the
manufacture date. If amber LED is blinking
at Power Center J-box Transceiver, go to the
Indoor Control Panel.
6. If still no communication, check LED’s at the
Indoor Control Panel Transceiver PCB.
• At the Indoor Control Panel Transceiver PCB,
confirm that the red LED is on indicating
power. If red LED is not lit, confirm unit is
plugged into wall socket and 4-conductor
wires are connected to the red, 4-pin terminal
bar on the Indoor Control Panel PCB.
• If green LED is lit, indicates correct data is
being received from the Power Center. If
green LED is not lit, there is an obstruction of
the RF signal caused by metal barriers.
• Test Indoor Control Panel in close proximity
to Power Center. If the unit tests okay, the
placement of one or both transceivers needs
to be moved for proper communication.
• If green LED is lit, verify that the middle
amber LED is blinking continuously which
indicates data transmission from the Indoor
Control Panel to the Power Center.
• Go to the Power Center and verify that the
green LED is lit, indicating correct data being
received from the Indoor Control Panel.
• This completes verification of the data
transmission loop from the Power Center to
the Indoor Control Panel and back.
7. Wireless Control Panel does not revert
to sleep mode after 30 seconds, install
OneTouch PCB Firmware B11 or newer.
Section6.PowerCenterWiringDiagram
Aux. 4 Relay
Aux. 7 Relay
Aux. 5 RelayAux. 6 Relay
Filter Pump Relay
Aux. 3 Relay
Aux. 1 Relay
Line One
Low Voltage Raceway (do not run high voltage wire in this compartment)
Line Two
Load One
Load Two
Aux. 2 Relay
Grounding Bar
Wire Nut to
120VAC Power
System Power
Intake
JVA
Cleaner
JVA
Solar
Pump
Return
JVA
Solar
JVA
Elect.
Heater
Red
Black
Green
White
Yellow
Green
Black
Red
Brown
To Remote
(brown terminal bar)
To Sensors, etc.
(green terminal bar)
To Controller
(red terminal bar)
4 3 2 1 6 5 4 3 2 1
Blue
Red
Black
Red
Black
F. Pump
Aux. 2 Aux. 3Aux. 6Aux. 5Aux. 4
Relay Sockets
(24 VDC output)
JVA Sockets
(24 VAC output)
# OFF
1 Aux 1
2 1 SPD Pump
3 Aux 3
4 Cool Down
5 Normal
6 Spare Aux
(Pool Mode)
7 See Manual
8 Heater 3 min.
Off
Battery
(9Volt)
Dip Switch Settings
Factory Setting
ON
Cleaner
2 SPD Pump
Spa Spillover
Disabled
See Manual
Spare Aux
(Spa Mode)
See Manual
If you installed a booster pump for a pool cleaner,
the relay coil for the booster pump must be plugged
into the AUX 1 relay socket. If a non-booster
pump cleaner is installed, plug the JVA into the
cleaner JVA socket. Turn ON DIP Switch #1.
•Mainlterpumpturnsonwhenevercleaner
turns on.
•Cleanerwillnotturnonuntillterpump
has been on for three (3) minutes (to ensure
priming of system).
• Cleaner turns off when water circulation is
to spa.
• Cleaner turns off when spa spillover feature
is activated.
• Cleaner turns off for three (3) minutes when
solar is activated (to ensure air is purged
from the system).
• AquaLink RS Control Panel display reads
"CLEANER" rather than "AUX 1".
DIP #2 ON- AUX 2 Controls Low Speed of Filter
Pump
Turn this switch ON if you want to control both
speeds of a two-speed filter pump. With this switch
on, the filter pump button on the AquaLink RS
Control Panel will control high speed and the AUX
2 button will control low speed.
IMPORTANT You must also install a Jandy Two-
Speed Relay.
DIP #4 ON- Heater Cool Down Disabled
Turn this switch ON to disable the heater cool
down safety feature on the AquaLink RS.
CAUTION
Turn this DIP Switch ON only if you are using
an electric heater or a heat pump that does
not retain residual heat. If you are turning this
switch ON for service purposes, be sure to turn
it back off.
DIP #5 ON- Factory Use Only
This switch is used for calibration by Jandy
certified technicians only (will momentarily
display the solar temperature and if installed, actual
FlowLink water pressure). Please leave this switch
in the OFF position.
DIP #6 ON
Change Spare AUX to activate when Filter
Pump is on and system is in spa mode (pool/spa
combination units only). Spare AUX socket is on
the back side of the Power Center PCB.
DIP #7 ON- Not Used
Dip #8 ON- Heat Pump Instead of Gas Heater
Turn this switch ON if you have installed a heat
pump instead of a gas heater. After thermostat
setting has been reached, heater will remain OFF
for 5 minutes.
DIP #3 ON- AUX 3 Controls Spa Spillover
(Operates with Pool/Spa Combination)
Turn this switch ON, and when the AUX 3 button
on the AquaLink RS Control Panel (or Spa Side
Switch) is pressed, the Return Valve Actuator will
rotate to spa circulation. Because the Intake Valve
Actuator does not rotate, the spa will fill with water
and overflow into the pool.
NOTE Leave AUX 3 relay socket empty.
Factory setting is with all DIP
1
OFF ON
3
4
5
6
7
8
2
switches off.
7.2DIPSwitchSettingsforPool and Spa Combination
DIP Switch #OFFON
Page 37
1AUX1= any equipmentAUX1= Pool Cleaner
2AUX2= any equipmentAUX2= Low Speed for a two-speed filter
pump.
Filter pump circuit becomes High Speed.
3AUX3= any equipmentAUX3= Spa Spillover effect- Combination
controls only.
4Heater cool down operates.Heater cool down disabled.
5Normal operationFactory adjustment- when this switch is on,
temperature delays are eliminated and solar
temperature is displayed.
Do not leave this switch in the ON
position.
6Spare Aux activates with Filter Pump when
Spa OFF.
No change on Revision "HH" or older PPD.
With Revision "I" or newer, Spare AUX
operation is reversed.
7SpareNo change on Combination or Only
Controls.
8After thermostat setting has been reached,
heater will remain OFF for 3 minutes.
After thermostat setting has been reached,
heater will remain OFF for 5 minutes.
Page 38
7.3DIPSwitchSettingsforPool or Spa Only
DIP Switch #OFFON
1AUX1= any equipmentAUX1= Pool Cleaner
2AUX2= any equipmentAUX2= Low Speed for a two-speed filter
pump.
Filter pump circuit becomes High Speed.
3AUX3= any equipmentNo change
4Heater cool down operates.Heater cool down disabled.
5Normal operationFactory adjustment- when this switch is on,
temperature delays are eliminated and solar
temperature is displayed.
Do not leave this switch in the ON
position.
6SpareNo change
7SpareNo change
8After thermostat setting has been reached,
Thank you for purchasing Jandy® pool and spa products. Jandy Pool Products, Inc. warrants all parts to be free
from manufacturing defects in materials and workmanship for a period of one year from the date of retail
purchase, with the following exceptions:
•
AquaLink® RS units installed with Jandy Surge Protection Kits will be covered for two years.
•
NeverLube® valves are warranted for the life of pool and/or spa on which they were originally installed.
•
AquaPureTM Electronic Chlorine Generator Electrolytic Cells carry a 5 year limited warranty on a prorated basis.
This warranty is limited to the first retail purchaser, is not transferable, and does not apply to products that have
been moved from their original installation sites. The liability of Jandy Pool Products, Inc. shall not exceed the
repair or replacement of defective parts and does not include any costs for labor to remove and reinstall the
defective part, transportation to or from the factory, and any other materials required to make the repair. This
warranty does not cover failures or malfunctions resulting from the following:
1. Failure to properly install, operate or maintain the product(s) in accordance with our published Installation,
Operation and Maintenance Manuals provided with the product(s).
2. The workmanship of any installer of the product(s).
3. Not maintaining a proper chemical balance in your pool and/or spa [pH level between 7.2 and 7.8, Total
Alkalinity (TA) between 80 to 120 ppm, Total Dissolved Solids (TDS) less than 2000 not including salt ppm].
4. Abuse, alteration, accident, fire, flood, lightning, rodents, insects, negligence or acts of God.
5. Scaling, freezing, or other conditions causing inadequate water circulation.
6. Operating the product(s) at water flow rates outside the published minimum and maximum specifications.
7. Use of non-factory authorized parts or accessories in conjunction with the product(s).
8. Chemical contamination of combustion air or improper use of sanitizing chemicals, such as introducing
sanitizing chemicals upstream of the heater and cleaner hose or through the skimmer.
9. Overheating; incorrect wire runs; improper electrical supply; collateral damage caused by failure of O-Rings,
DE grids, or cartridge elements; or damage caused by running the pump with insufficient quantities of water.
LIMITATION OF LIABILITY:
This is the only warranty given by Jandy Pool Products, Inc. No one is authorized to make any other warranties
on behalf of Jandy Pool Products, Inc. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF FITNESS
FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. JANDY POOL PRODUCTS, INC. EXPRESSLY
DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL, INCIDENTAL, INDIRECT OR
PUNITIVE DAMAGES FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY. This warranty gives
you specific legal rights. You may also have other rights which vary by state or province.
WARRANTY CLAIMS:
For prompt warranty consideration, contact your dealer and provide the following information: proof of purchase,
model number, serial number and date of installation. The installer will contact the factory for instructions
regarding the claim and to determine the location of the nearest designated service center. If the dealer is not
available, you can locate a service center in your area by visiting www.jandy.com or by calling our technical
support department at (707) 776-8200 extension 260. All returned parts must have a Returned Material
Authorization number to be evaluated under the terms of this warranty.
6000 Condor Drive • Moorpark, CA USA 93021 • 707.776.8200 • Fax 707.763.7785