RISK OF ELECTRICAL SHOCK OR ELECTROCUTION. The electrical supply to this product
must be installed by a licensed or certifi ed electrician in accordance with the National Electrical
Code and applicable local codes and ordinances. Improper installation will create an electrical
hazard, which could result in death or serious injury to pool or spa users, installers, or others
due to electrical shock, and may also cause damage to property. Read and follow the specifi c
instructions inside this manual.
DANGER
RISQUE DE CHOC ÉLECTRIQUE OU ELECTROCUTION. Cet appareil doit être installé par un
électricien certifi é conformément au National Electrical Code et aux normes et règlementations
locales. Une installation incorrecte peut entraîner un risque de problème électrique ( choc
électrique ou électrocution) pouvant causer des blessures graves et même la mort des
installateurs et/ou utilisateurs de SPA et Piscines. Lire le manuel et se conformer aux directives.
PELIGRO
RIESGO DE DESCARGA ELÉCTRICA O ELECTROCUTAMIENTO. El suministro eléctrico de
este producto deberá ser instalado por un electricista autorizado o diplomado, de acuerdo al
Código Eléctrico Nacional y a los códigos y normativas que apliquen localmente. Una instalación
inadecuada podría originar riesgos eléctricos y ocasionar la muerte o lesiones graves a los
usuarios de de la piscina o spa, instaladores u otros, como consecuencia de una descarga
eléctrica, pudiendo así mismo ocasionar daños a la propiedad. Léa y siga las instrucciones
específi cas que se recogen en este manual.
H0569300B
Table of Contents
Page 1
Section 1. General Information ..................2
This manual provides installation and operation
instructions for the Jandy AE-Ti models of Heat Pumps.
Read these installation and operation instructions
completely before proceeding with the installation.
Consult Jandy with any questions regarding this
equipment. To obtain additional copies of this manual
contact us at 707-776-8200 ext. 237. The following is
the address information for Jandy:
2735 NW 63rd Court.
Fort Lauderdale, FL USA 33309
The AE-Ti heat pump gets electrical power from
an external source and provides a dual electronic
thermostat control system for pool/spa combinations or
preheat convenience.
This heat pump is specifically designed for heating
fresh water swimming pools and spas. Do not use it
as a general service heater. Consult your dealer for the
appropriate Jandy products for these applications.
NOTE “Fresh water swimming pools and spas” include
systems that utilize saltwater chlorine generator
units, such as the Jandy AquaPure Electronic
Chlorine Generator. Please ensure that the salt
content of the pool/spa does not exceed
4000 ppm and water fl ow rate is within
60-80 gpm (225-300 lpm)
ATTENTION
Installation and service must be performed by
a qualifi ed installer or service agency.
To the Installer: After installation, these
instructions must be given to
the homeowner or left on or
near the heat pump.
To the User: This manual contains
important information that
will help you in operating and
maintaining this heat pump.
Please retain it for future
reference.
1.2 Consumer Information and Safety
The AE-Ti series of heat pumps are designed
and manufactured to provide many years of safe
and reliable service when installed, operated and
maintained according to the information in this manual
and the installation codes referred to in later sections.
Throughout the manual, safety warnings and cautions
are identified by the ““ symbol. Be sure to read and
comply with all of the warnings and cautions.
1.2.1 Spa/Hot Tub Safety Rules
WARNING
The U.S. Consumer Product Safety Commission
warns that elevated water temperature can
be hazardous. Consult heater operation and
installation instructions for water temperature
guidelines before setting temperature.
AVERTISSEMENT
La Commission U.S. de Sécurité des Produits
pour les Consommateurs indique que des
températures de l’eau élevées peuvent être
dangereuses. Voir la notice d’installation
et de fonctionnement pour le réglage de la
température.
AVISO
La Comisión de Seguridad de Productos para
el Consumidor de los Estados Unidos, advierte
que una temperatura elevada del agua puede
ser peligrosa. Consulte las instrucciones de
instalación y funcionamiento del calentador
para seguir las directrices relacionadas con la
temperatura del agua antes de proceder a fi jar
la temperatura.
WARNING
The following “Safety Rules for Hot Tubs,”
recommended by the U.S. Consumer Product
Safety Commission, should be observed when
using the spa.
AVERTISSEMENT
Les Règlements suivants pour Cuves
Thermales, tel que recommandés par la
Commission U.S. de Sécurité des Produits pour
les Consommateurs, devraient être respectés
lors de l’utilisation du spa.
AVISO
Al utilizar el spa, deberán observarse, las
siguientes “Reglas de Seguridad para Baños
Calientes” recomendadas por la Comisión de
Seguridad de Productos para el Consumidor de
los Estados Unidos.
Page 3
1. Spa or hot tub water temperature should never
exceed 104°F (40°C). One hundred degrees
Fahrenheit (100°F [38°C]) is considered safe for a
healthy adult. Special caution is recommended for
young children.
2. The drinking of alcoholic beverages before or
during spa or hot tub use can cause drowsiness
which could lead to unconsciousness, and
subsequently result in drowning.
3. Pregnant women take note! Soaking in water
above 102°F (38.5°C) can cause fetal damage
during the fi rst three months of pregnancy (which
could result in the birth of a brain-damaged or
deformed child). If pregnant women are going
to use a spa or hot tub, they should make sure
the water temperature is below 100°F (38°C)
maximum.
4. The water temperature should always be checked
with an accurate thermometer before entering a
spa or hot tub. Temperature controls may vary by
as much as 1F° (1C°).
5. Persons with a medical history of heart disease,
diabetes, circulatory or blood pressure problems
should consult their physician before using a hot
tub or spa.
6. Persons taking any medication which induces
drowsiness (e.g., tranquilizers, antihistamines, or
anticoagulants) should not use spas or hot tubs.
7. Prolonged immersion in hot water can induce
hyperthermia.
Hyperthermia occurs when the internal body
temperature reaches a level several degrees above the
normal body temperature of 98.6°F (37°C). Symptoms
include dizziness, fainting, drowsiness, lethargy, and an
increase in the internal body temperature. The effects of
hyperthermia include:
1.2.2 Swimming Pool Energy Saving Tips
It is important to note that a heat pump will not
heat a pool as fast as a large gas or electric pool heater.
If the pool water is allowed to cool significantly, it may
take several days to return to the desired swimming
temperature. For weekend use, it is more economical
to maintain the pool water temperature at or near your
desired swimming temperature. If you do not plan to
use your pool for a prolonged period, then you might
choose to turn the heat pump completely off or decrease
the temperature setting of the control several degrees to
minimize energy consumption.
Jandy offers the following recommendations to
help conserve energy and minimize the cost of operating
your heat pump without sacrificing comfort.
1. The American Red Cross recommends a maximum
water temperature of 78°F (25°C). Use an accurate
pool thermometer. A difference of 4°F (2°C) ,
between 78°F and 82°F (26°C and 28°C), will
signifi cantly increase energy consumption.
2. Carefully monitor the water temperature of your
pool in the summertime. You can reduce heat
pump usage due to warmer air temperatures.
3. During the winter or when on vacation for longer
than a week, turn off the heat pump.
4. Find the proper setting on the heat pump
temperature control and use the Keypad Lock
function or lock the smoke-colored cover on
the heat pump controller to discourage further
adjustments.
5. Set the pump time clock to start the pump no
earlier than 6:00 AM during the pool heating
season. This is the time when nightly heat loss
balances.
6. Where possible, shelter the pool from prevailing
winds with well-trimmed hedges or other
landscaping, cabanas, or fencing.
• Lack of awareness of impending hazard
• Failure to perceive heat
• Failure to recognize need to leave spa
• Physical inability to leave spa
• Fetal damage in pregnant women
• Unconsciousness resulting in a danger of
drowning
7. Always use a pool cover when practical. Besides
providing a valuable safety feature, a pool cover
will reduce heat loss, conserve chemicals, and
reduce the load on fi lter systems.
1.3 Warranty
The AE-Ti heat pump is sold with a limited factory
warranty. Details are specified on the back cover of this
manual.
Page 4
Make all warranty claims to an authorized Jandy
dealer or directly to the factory. Claims must include the
heat pump serial number and model (this information
can be found on the rating plate), installation date, and
name of the installer. Shipping costs are not included in
the warranty coverage.
The warranty does not cover damage caused by
improper assembly, installation, operation, winterizing,
field modification, or failure to earth bond and
properly ground the unit. Any changes to the heat
pump, evaporator, heat exchanger, wiring, or improper
installation may void the warranty.
1.4 Codes and Standards
The AE-Ti heat pump is listed by ETL as
complying with the latest edition of the “UL Standard
for Safety for Heating and Cooling Equipment”, UL
1995 and CSA C22.2 No. 236.
All Jandy heat pumps must be installed in
accordance with the local building and installation
codes as per the utility or authority having jurisdiction.
All local codes take precedence over national codes. In
the absence of local codes, refer to the latest edition of
the National Electric Code (NEC) in the United States
and the Canadian Electric Code (CEC) in Canada for
installation.
1.5 Technical Assistance
Consult Jandy Technical Support Department or
your local Jandy dealer with any questions or problems
involving the specifications, installation, and operation
of your Jandy equipment. An experienced technical
support staff is ready to assist you in assuring the proper
performance and application of Jandy products. For
technical support call the Jandy Heat Pumps Technical
Service Department at (954) 970-4800
1.6 Materials Needed For Installation
1.6.1 Materials for All Installations
The following items are needed and are to be
supplied by the installer for all heat pump installations:
1. Plumbing connections (2”).
NOTE Flex conduit is recommended for connecting
the electrical supply wires to the heat pump so
that the front panel may be removed easily for
servicing.
4. Electric cutout switch that will interrupt all power
to the unit. This switch must be within line of sight
of the heat pump.
5. Watertight conduit to run the electrical supply line.
1.6.2 Recommended Materials for
Installations
Jandy recommends installing isolation valves
on the inlet and outlet water connections for ease of
serviceability.
3. Suitable electrical supply line. See rating plate on
unit for electrical specifi cations. A junction box is
not needed at the heat pump; connections are made
inside of the heat pump electrical compartment.
Conduit may be attached directly to the heat pump
jacket.
See Figure 1 for a diagram showing the heat
pump’s dimensions and for dimensions to critical
connections.
Section 2. Installation Instructions
2.1 General Information
Install the Jandy heat pumps in accordance
with the procedures in this manual, local codes and
ordinances, and in accordance with the latest edition of
the appropriate national code. (See Section 1.4, “Codes
and Standards”.)
Correct installation is required to assure safe
operation. The requirements for Jandy heat pumps
include the following:
1. Field assembly (if required).
2. Appropriate site location and clearances.
3. Suffi cient air ventilation.
4. Proper electrical wiring.
2.2.1 Introduction
NOTE Indoor installations require special
considerations for condensate drainage and
venting the cold air produced by the heat
pump. Contact the Jandy Heat Pump Technical
Service Department at (954) 970-4800.
CAUTION
When pool equipment is located below the pool
surface, a leak from any component can cause
large scale water loss or fl ooding. Jandy Pool
Products, Inc. cannot be responsible for such
water loss or fl ooding or resulting damage.
ATTENTION
Lorsque l’équipement d’une piscine est situé
sous la surface de l’eau, une fuite provenant de
n’importe quel élément peut causer une perte
d’eau importante ou une inondation. Jandy Pool
Products, Inc. n’est pas responsable des pertes
d’eau, des inondations ou des avaries causées
par une installation ou un entretien inadéquat.
5. Adequate water fl ow.
This manual provides the information needed to
meet these requirements. Review all application and
installation procedures completely before continuing the
installation.
PRECAUCIÓN
Cuando el equipo de la piscina esté situado
por debajo de la superfi cie de la piscina, la
fuga de cualquiera de los componentes, podría
ocasionar la pérdida de grandes cantidades de
agua o inundación. Jandy Pool Products, Inc. no
se responsabilizará de dichas pérdidas de agua
o inundaciones, ni de los daños que puedan
derivarse de las mismas.
Page 6
Table 1. Heat Pump Clearances
Side of Heat
pump
Minimum Clearances for
Operation
InchesCentimetersInchesCentimeters
Front
Rear
Left
Right
Top
6152460
6151230
6151230
6151230
6015060150
Recommended Clearances for
Serviceability
NOTE Clearances listed in
Table 1 are manufacturer’s
tested values. These are
given as minimum values.
Where local and national
codes apply, and values are
different than those listed in
Table 1, use the greater value
to ensure safe and proper
operation.
Avoid placing the heat pump in locations where
it can cause damage by water or condensate leakage. If
this is not possible, provide a suitable drain pan to catch
and divert any leakage.
All criteria given in the following sections reflect
minimum clearances. However, each installation must
also be evaluated, taking into account the prevailing
local conditions such as proximity and height of walls,
and proximity to public access areas.
2.2.2 Clearances
The heat pump must be placed to provide
clearances on all sides for maintenance and inspection.
See Table 1.
24” (61cm) access in front of the heat pump
provides adequate room for serviceability.
If the heat pump is to be installed in a garage
or under a vertical overhang, the unit must have a
minimum of 5 feet clearance from the top of the heat
pump.
In the U.S., the heat pump must be installed at least
5 feet (1.52 meters) from the inside wall of the pool or
spa unless the heat pump is separated from the pool or spa
by a 5 foot high solid fence or other permanent barrier.
Aux Etats-Unis, ce chauffe-piscine doit être
installé á au moins 5 pieds (1.5 m) de la paroi interne
de la piscine à moins d’être isolé de la piscine par une
clôture, un mur ou autre barrière permanente.
En Estados Unidos, esta bomba de calor deberá
instalarse a una distancia de al menos 5 pies (1.5
metros) de la pared interior de la piscina; a menos que la
bomba de calentar esté separada de la piscina mediante
una valla sólida de 5 pies (1.5 metros) de altura u otra
barrera permanente.
In Canadian installations, the minimum distance to
be maintained from the inside wall of the pool or spa is
3 meters (approx. 10 feet).
Pour les installations canadiennes, la distance
minimale à maintenir du mur intérieur de la piscine ou
du spa est de 3 mètres (approximativement 10 pieds).
2.2.3 Equipment Pad
Place the heat pump on a flat slightly pitched
surface, such as a concrete or fabricated slab (pad). This
allows proper drainage of condensation and rain water
from the base of the unit. If possible, the pad should be
placed at the same level or slightly higher than the filter
system equipment pad.
NOTE Ensure that the pad is pitched not more than ¼
inch per foot toward the compressor end (front)
of the heat pump. Pitch slab from back to front
¼ inch per foot maximum and level from side to
side.
2.2.4 Condensation and Drainage
Condensation will occur from the evaporator coil
while the unit is running and drain at a steady rate,
usually three to five gallons per hour, depending upon
ambient air temperature and humidity. The more humid
the ambient conditions, the more condensation will be
produced. The bottom of the unit acts as a tray to catch
rainwater and condensation. Keep the drain hole located
on the right side of the base of the unit clear of debris.
If the heat pump is installed indoor a means of
condensate disposal must be provided. The drain hole
in the base of the heat pump is tapped to fit an optional
3/4” diameter barbed adapter, Jandy p/n R3004100 (see
Section 9, “Replacement Parts”). If using the barbed
adapter, connect a length of 3/4” tubing (5’ is included
in Jandy p/n R3004100) to the adapter, then route it
into a drain or outside the building to dispose of the
condensate. It is important to remember that no part of
the tubing or hose may be above the level of the drain
hole in the base of the heat pump.
2.2.5 Lawn Sprinklers
Keep lawn sprinkler heads from spraying on the
heat pump to prevent corrosion and damage. Use a
deflector if needed.
2.2.6 Roof Run-off
Make sure the heat pump is not located where
large amounts of water may run-off from a roof into
the unit. Sharp sloping roofs without gutters will allow
massive amounts of rain water, mixed with debris from
the roof to be forced through the unit. A gutter or down
spout may be needed to protect the heat pump.
Page 7
W
2.2.7 Installation of Anchor Clamps
In Florida, building codes require that the heat
pump be anchored to the equipment pad or platform
to withstand high wind pressures created during
hurricanes.
This heat pump was provided with anchor clamps
designed to hold the unit to the equipment pad in high
wind conditions. Installation of the anchor clamps is
recommended in all installations and are required in
Florida (reference Florida Building Code, Mechanical
Section 301.13).
To install the anchor clamps:
1. Be sure that the heat pump is in its permanent
location on the equipment pad.
2. Remove the anchor clamps from the installation
and instruction package.
NOTE: Bolts and bolt anchors are not included with
the heat pump. Jandy recommends that a
1/4” x 1½” long stainless steel Tapcon® type
concrete screw is used to mount the clamp
to the equipment pad. The Tapcon type
concrete screw meets Florida building code
requirements.
3. Place the clamps at the base of the heat pump in
the locations indicated in Figure 2.
Attach anchor
brackets to base
of heat pump
where indicated
by the arrows.
EVAPORATOR
COIL GUARD
EVAPORATOR
COIL
HEAT PUMP
PLASTIC BASE
CONCRETE
EQUIPMENT PAD
1/4" x 1-1/2"
STAINLESS STEEL
TAPCON® TYPE
CONCRETE SCRE
AND WASHER
(Installer Provided)
HEAT PUMP
ANCHOR
BRACKET
3/16" DRILLED
HOLE
3" minimum
Figure 3. Anchor Clamp Installation
5. Mark the position of the hole in each clamp on the
equipment pad.
6. Drill a hole in the cement using a masonry drill
bit, with a diameter as determined by the concrete
anchor, at each of the marks on the equipment pad.
The hole should be approximately 1-1/2” deep.
7. Insert a bolt anchor into each of the holes. Be sure
the anchors are set completely into the holes.
8. Position the anchor clamps so that the holes in the
clamps are over the bolt anchors. Be sure that the
clamp hooks are over the lip of the heat pump base
(see Figure 3).
Figure 2. Anchor Clamp Positions
NOTE: To Install the brackets on the front of the heat
pump, the front cover must be loosened enough
in order to place the bracket over then lip of
the base. Be sure to re-tighten the front jacket
panel to the heat pump.
4. Fit the hook of each clamp over the lip on the
base panel of the heat pump. The hook should
fi t between the lip of the base panel and the
evaporator coil guard (see Figure 3).
9. Insert an anchor bolt through each clamp into the
anchor and tighten to secure the clamp and heat
pump to the equipment pad.
Section 3. Water Connections
3.1 Plumbing Layout
Figure 4 illustrates the standard plumbing layout
with a single heat pump unit. Following the diagram
from right to left, the plumbing sequence is as follows:
Pool > Pool Pump > Filter > Heat Pump > Check
Valve > Chemical Loop > Chlorinator > Pool
NOTE For normal installations, do not install a shutoff
valve or any kind of variable restriction in the
water piping between the heat pump outlet and
the pool/spa.
Page 8
CHEMICAL LOOP
OR OPTIONAL CHLORINE
GENERATION SYSTEM
(JANDY AQUAPURE SHOWN)
Sensors
CHEMICAL FEEDER
e
r
u
P
a
u
q
A
TO POOL OR SPA
CHECK VALVE
Figure 4. Standard Plumbing Layout
The heat pump must be protected from backsiphoning of water. If there is any chance of backsiphoning, provide a check valve between the pool
and the filter pump inlet. Arrangement of pool system
components other than as illustrated in the preceding
and following diagrams can affect the operation of the
heat pump’s water pressure switch. Location of the heat
pump above or below the pool water surface can also
affect operation of the switch. In general, the pressure
switch can be adjusted to accommodate this effect if the
heat pump water connections are no more than five feet
below the pool water surface or no more than 11 feet
above it. See instructions for pressure switch adjustment
(Section 5.7) in the heat pump start-up section of this
manual for more information. If the heat pump is
installed outside of this range, an external flow switch
may need to be installed in the plumbing upstream of
the heat pump. Call the Jandy Heat Pump Technical
Service department at (954) 970-4800 for details.
Be advised that when pool equipment is located
below the pool surface a leak can result in large scale
water loss or flooding. Jandy cannot be responsible for
such water loss or flooding or the damage caused by
either occurrence.
3.2 Water Connections at Heat Pump
Shipping plugs have been installed in the water
inlet and outlet ports of the heat pump at the factory.
Before installing any plumbing, remove the shipping
plugs. Filtered water is plumbed to the inlet, located on
the right side of the heat pump front panel. Heated water
flows through the outlet, located on the left side of the
heat pump front. Two inch unions are provided.
POOL HEATER
FILTER
POOL PUMP
FROM POOL OR SPA
MANUAL BYPASS VALVE
Plastic piping (PVC Schedule 40) should be
connected to the heat pump. The unions, provided with
the unit, accept 2” PVC pipe.
CAUTION
Make sure that fl ow requirements and pool
water turn over rates can be maintained with
the installation of additional heat pumps and
plumbing restrictions.
ATTENTION
Assurez-vous que la circulation d’eau requise
soit maintenue même si des pompes d’appoints
ou des éléments de plomberie, causant des
restrictions, sont ajoutés.
PRECAUCIÓN
Asegúrese de que los requerimientos de fl ujo
e índices de volumen de agua de la piscina
puedan mantenerse, con la instalación de
bombas de calentar adicionales y restricciones
de fontanería.
3.3 Check Valve Installation
The heat pump must be protected from backsiphoning of water. If there is any chance of backsiphoning, provide a check valve between the pool and
the filter pump inlet.
When an automatic chemical feeder is installed
in the plumbing, it must be installed downstream of the
heat pump. A check valve must be installed between
the heat pump and the chemical feeder to prevent backsiphoning of chemically saturated water into the heat
pump where it will damage the components.
Page 9
3.4 Automatic Flow Control Valve
The inlet/outlet header of the AE-Ti heat pump
comes equipped with an internal automatic flow control
valve. The automatic flow control valve maintains
the proper flow through the heat pump at rates up to
approximately 125 gpm (475 lpm). If the filter system
flow rate is higher than approximately 125 gpm (475
lpm), install a manual bypass valve (see Figure 4).
NOTE Be advised that if your circulation pump is
over 2 HP or if the total fl ow exceeds 125
gpm, you will have to add an external bypass
valve. Excess water fl ow will damage the heat
exchanger.
3.5 Multiple Unit Installation
3.5.1 Heat Pump and Heater Combination
In certain regions of the country it may be more
economical to run a heat pump during the warmer
months and a gas heater during the cooler months. In
some situations it may be desirable to run the heat pump
in the “Chiller” mode during the hottest portion of the
year and a heater during the cooler months. The Jandy
heat pump may be plumbed with a gas or electric heater
or any combination of heat sources including solar.
All heat sources must be plumbed in parallel to work
correctly and efficiently.
Figure 5 illustrates a recommended plumbing
layout for a heat pump / heater / solar combination
heating system for a pool / spa combination. Your
system may not contain all of these components, but the
basic plumbing will apply by eliminating the component
in the illustration that is not a part of your system.
3.5.2 Multiple Heat Pump Connections
All plumbing on multiple heat pump installations
must be done in parallel (see Figures 6 through 9). An
equal flow of water to each heat pump is important for
optimum operation.
NOTE It may be necessary to adjust water pressure
switch if a unit is installed below the water level.
See Section 5.7 for details on when and how to
adjust the pressure switch.
NOTE Each heat pump allows a maximum fl ow rate of
125 gpm and requires a minimum of 30 gpm.
POOL
INTAKE
SPA
INTAKE
POOL
RETURN
SPA
RETURN
SPA
DRAIN
CHECK
VALVE
POOL
DRAIN
SPA
MAKE-UP
FILTER
HEATER
FILTER
PUMP
CHECK
VALVE
HEAT PUMP
FROM SOLAR
TO SOLAR
Figure 5. Plumbing For Heating System Combinations
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.