is not followed exactly, a fire or explosion may result causing
property damage, personal injury or death.
-- Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a near by phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
-- Installation and service must be performed by a qualified
installer, service agency, or the gas supplier.
100320962_2000575058 Rev A
CXi™ Pool Heater
Installation & Operation Manual
Models: 500, 650, 750
⚠
WARNING:
This manual supplies information for the
installation, operation, and servicing of the
appliance. It is strongly recommended that this
manual and the Jandy® CXi™ Pool Heater Service
Manual be reviewed completely before proceeding
with an installation. Perform steps in the order
given. Failure to comply could result in severe
personal injury, death, or substantial property
damage.
Revision Notes .................................................. Back Cover
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels
or to important information concerning the life of the product.
⚠
DANGER
⚠
WARNING
⚠
CAUTION
CAUTION
NOTICE
2
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate
injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not
avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not
related to personal injury or property damage.
Please read before proceeding
Special instructions
Jandy®, CXi™ Pool Heater Installation & Operation Manual
NOTICE
⚠
WARNING
⚠
WARNING
This is a gas appliance and should be installed
by a licensed electrician and/or certified gas
supplier. Service must be performed by a
qualified service installer, service agency or
the gas supplier.
If the information in these instructions is
not followed exactly, a fire or explosion may
result causing property damage, personal
injury, or death.
This appliance MUST NOT be installed in
any location where gasoline or flammable
vapors are likely to be present, unless the
installation is such to eliminate the probable
ignition of gasoline or flammable vapors.
Improper installation, adjustment,
alteration, service or maintenance can
cause injury or property damage. Refer
to this manual for assistance or additional
information, consult a qualified installer,
service agency or the gas supplier.
Checking equipment –
Upon receiving equipment, check for signs of shipping damage.
Pay particular attention to parts accompanying the appliances
which may show signs of being hit or otherwise being
mishandled. Verify total number of pieces shown on packing
slip with those actually received. In case there is damage or a
shortage, immediately notify the carrier.
Do not use this appliance if any part has been under water.
The possible damage to a flooded appliance can be extensive
and present numerous safety hazards. Any appliance that
has been under water must be replaced.
NOTICE
REMOVAL OF COMBUSTION CHAMBER LINING OR
BASE PANELS:
¢ Avoid breathing dust and contact with skin and eyes.
• Use NIOSH certified dust respirator (N95). This type of
respirator is based on the OSHA requirements for
cristobalite at the time this document was written. Other
types of respirators may be needed depending on the
job site conditions. Current NIOSH recommendations
can be found on the NIOSH website at
http://www.cdc.gov/niosh/homepage.html .
NIOSH approved respirators, manufacturers, and phone
numbers are also listed on this website.
The ceramic fiber material used in this
appliance is an irritant; when handling or
replacing the ceramic materials it is advisable
that the installer follow these safety guides.
¢Apply enough water to the combustion chamber
lining to prevent airborne dust.
¢ Remove the combustion chamber lining from the
appliance and place it in a plastic bag for disposal.
• NIOSH stated First Aid:
Eye: Irrigate immediately.
Breathing: Fresh air.
⚠
WARNING
The combustion chamber insulation in this
appliance contains ceramic fiber material.
Ceramic fibers can be converted to cristobalite
in very high temperature applications.
The International Agency for Research on
Cancer (IARC) has concluded, “Crystalline
silica in the form of quartz or cristobalite
from occupational sources is carcinogenic
to humans (Group 1).” Normal operating
temperatures in this appliance are below the
level to convert ceramic fibers to cristobalite.
Abnormal operating conditions would have
to be created to convert the ceramic fibers in
this appliance to cristobalite.
The ceramic fiber material used in this
appliance is an irritant; when handling
or replacing the ceramic materials it is
advisable that the installer follow these safety
guidelines.
Warranty –
Factory warranty (shipped with unit) does not apply to units
improperly installed or improperly operated.
Experience has shown that improper installation or system
design, rather than faulty equipment, is the cause of most
operating problems.
1. Excessive water hardness causing a lime/scale build-up in
the copper tube is not the fault of the equipment and is
not covered under the manufacturer’s warranty (see
Water Treatment and Water Chemistry).
2. Excessive pitting and erosion on the inside of the copper
tube may be caused by too much water velocity through
the tubes and is not covered by the manufacturer’s
warranty (see Pool heater Flow Rates for flow requirements).
• Wear long-sleeved, loose fitting clothing, gloves, and eye
protection.
33
Please read before proceeding
Safety information
Jandy®, CXi™ Pool Heater Installation & Operation Manual
⚠
Owner warning –
The information contained in this manual is intended for use
by qualified professional installers, service technicians, or gas
suppliers.
NOTICE
A gas appliance that draws combustion air from the equipment
room where it is installed must have a supply of fresh air
circulating around it during burner operation for proper gas
combustion and proper venting.
⚠
WARNING
Consult and follow all local Building and
Fire Regulations and other Safety Codes that
apply to this installation. Consult local gas
utility company to authorize and inspect all
gas and flue connections.
Should overheating occur or the gas supply
fail to shut off, do not turn off or disconnect
the electrical supply to the pump. Instead,
shut off the gas supply at a location external
to the appliance.
Prevention of freezing –
Heat exchangers and headers damaged by freezing are not
covered by warranty.
See Section 6, Operating Information - Freeze Protection for
more information.
Codes
The equipment shall be installed in accordance with those
installation regulations in force in the local area where the
installation is to be made. These shall be carefully followed in all
cases. Authorities having jurisdiction shall be consulted before
installations are made. In the absence of such requirements, the
installation shall conform to the latest edition of the National Fuel
Gas Code, ANSI Z223.1 and/or CAN/CGA-B149 Installation
Code. All pool heater heat exchanger construction conforms to
the latest edition of the ASME Boiler and Pressure Vessel Code,
Section IV.
⚠
WARNING
1. Pool heaters are heat producing appliances. To avoid
damage or injury, do not store materials against the pool
heater or the vent-air intake system. Use proper care to
avoid unnecessary contact (especially children) with the
pool heater and vent-air intake components.
To minimize the possibility of serious
personal injury, fire or damage to your
unit, never violate the following safety
rules.
2. Never cover your pool heater, lean anything against it, store
trash or debris near it, stand on it, or in any way block the
flow of fresh air to your pool heater.
3. UNDER NO CIRCUMSTANCES must flammable materials
such as gasoline or paint thinner be used or stored in the
vicinity of this pool heater, vent-air intake system or any
location from which fumes could reach the pool heater or
vent-air intake system.
4. This pool heater is only for use with the type of gas indicated
on the rating plate.
5. If you smell gas, shut off the gas supply:
• Do not try to light any appliance;
• Do not touch any electrical switch; do not use any
telephone in your building;
• Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions;
• If you cannot reach your gas supplier, call the fire
department.
6. This appliance is a high efficiency pool heater which has
been designed to operate scale-free and trouble free for
many years. Particular attention should be directed to the
following items:
• Correct piping to the pool filter system with specified pipe
materials and size;
• Electrical interconnection of the pool heater controls,
bypass pump and filter pump to ensure continuous
circulation;
• Proper venting;
• Water chemistry.
7. Follow all clearances from combustibles contained in this
manual.
8. Appliance surfaces become hot during operation. Be careful
not to touch hot surfaces. Keep all adults, children, and
animals away from an operating pool heater. Severe burns
can occur.
9. This pool heater must have an adequate supply of fresh air
during operation for proper gas combustion and venting.
10. Make sure all exhaust venting is properly installed and
maintained. Improper venting of this pool heater could lead
to increased levels of carbon monoxide.
11. Do not use this pool heater if any part has been under water.
Immediately call a qualified service technician to replace the
pool heater. The possible damage to a flooded pool heater
can be extensive and present numerous safety hazards. Any
appliance that has been under water must be replaced.
12. Do not alter this pool heater in any way. Any change to this
pool heater or its controls can be dangerous.
4
Jandy®, CXi™ Pool Heater Installation & Operation Manual
The Jandy® CXi™ - How it works...
1. Heat exchanger
The heat exchanger allows system water to flow through specially
designed tubes for maximum heat transfer. The glass lined
headers and copper fined tubing are encased in a jacket that
contains the combustion process.
2. Heat exchanger access cover
The heat exchanger access cover is a galvanized steel door which
allows access for service, maintenance, and removal of the
heat exchanger from inside the combustion chamber.
3. Blower
The blower pulls in and injects air into the individual burners
along with gas from the gas manifold where the mix is burned inside
the combustion chamber.
4. Gas valve
The referenced gas valves have a dual purpose; changing the gas
supply pressure to manifold pressure, and the reference side of
the gas valve is designed to allow chamber pressure to change the
volume of gas through the valve. This is not a design to
compensate for gas supply pressure issues.
5. Outlet/limit temperature sensor
This 4-wire limit rated sensor monitors the outlet temperature
to ensure safe operation. The appliance will adjust its firing rate
to maintain water temperatures below the maximum allowable
outlet temperature.
6. Inlet temperature sensor
This 2-wire sensor monitors the inlet temperature. The appliance
will adjust the position of the 3-way valve to maintain the inlet
water temperature above the minimum allowable inlet
temperature.
7. Electronic display
The electronic display consists of 6 buttons and a two-line
16-character liquid crystal display used to monitor the
operation of the heater as well as enter and view the
programming of the main control board.
8. Burner
The burner is a ported stainless steel construction which uses a gas
air mix to operate at a fixed input. Banks of burners turn on
or off to vary the firing rate.
9. Pool supply/limit sensor (not shown)
This 4-wire limit rated sensor monitors the temperature of
the water being supplied to the pool to ensure safe operation.
The appliance will shut down if the maximum allowable pool
supply temperature is exceeded.
10. Pool return sensor (not shown)
This 2-wire sensor is the controlling sensor and it monitors the
temperature of the pool water. The appliance will stage to
maintain pool temperature set point and turn off when set point
is met.
11. Gas supply pipe
The gas supply pipe on this appliance is 1 1/4 or 2" (depending on
model) diameter NPT. Please reference the National Fuel Gas
Code charts for connection details.
12. Control Module
The Control Module is the main control for the
appliance. This module contains the programming that
operates the blower, gas valve, and pumps in addition to other
programmable features.
13. Air intake
Fresh air for combustion is drawn through a filter provided at the
air intake, located at either the rear or right side of the appliance.
14. Line voltage terminal strip
The line voltage terminal strip provides a location to connect
all of the line voltage (120 VAC) contact points to the unit.
15. Low voltage connection board
The low voltage connection board provides a location to connect
all of the low voltage devices to the appliance. This is where most
of the external safety controls are connected.
16. Front doors - upper and lower
The front doors provide access to the gas train as well as the
blower, burners and other key components for service and
maintenance.
17. Hot surface igniter (HSI)
The hot surface igniter is a device that is used to ignite the
air/gas mixture as well as monitor the performance of the flame
during operation. This device acts as a flame sense electrode.
18. Flame inspection window (sight glass)
The flame inspection windows, located on either side of the
appliance, allow for visual inspection of the burners and flame
during operation.
19. Manual reset high limit sensor
This device monitors the outlet water temperature to ensure
safe operation. If the temperature exceeds its setting (field
adjustable), it will break the control circuit, shutting the
appliance down. Manual reset is performed through the display.
20. Relief valve
The relief valve is a safety device that ensures the maximum
pressure of the appliance is not exceeded. Pool heaters operate
on temperature and pressure and are shipped standard as 150 PSI
and 210°F (98.9°C).
21. Power switch
The power switch is used to engage and disengage power to the
appliance on the 120 VAC circuit.
22. Air pressure switch
The air pressure switch is a safety device which ensures proper
blower operation. The air pressure switch is wired in series with
the low voltage control circuit in such a way that if the fan does not
engage or shuts down prematurely the device will break the
control circuit and the unit will shut down.
23. Flow switch
The flow switch is a safety device that ensures flow through the
heat exchanger during operation. This appliance is low mass and
should never be operated without flow. The flow switch makes
contact when flow is detected and allows the unit to operate. If
flow is discontinued during operation for any reason the flow
switch will break the control circuit and the unit will shut down.
24. Drain port(s)
Location from which the heat exchanger can be drained. The
drain ports are located underneath the front header.
25. Manual shutoff valve (not shown)
Manual valve used to isolate the unit from the gas supply.
5
Jandy®, CXi™ Pool Heater Installation & Operation Manual
The Jandy® CXi™ - How it works...
Models CXi500, CXi650, CXi750 Front View
Models CXi500, CXi650, CXi750 Rear View
Models CXi500, CXi650, CXi750 Right Side (inside unit)
6
Models CXi500, CXi650, CXi750 Left Side (inside unit)
Ratings
Jandy®, CXi™ Pool Heater Installation & Operation Manual
Specifications
Air / Vent
Sizes
(Note 1)
NOTICE
Model Number
CXi5001.72"1-1/4"6"
CXi6502.02"1-1/4"8"
CXi7502.12"1-1/4"8"
Appliance Water
Content Gallons
Water ConnectionsGas Connections
Maximum allowed working pressure is located on the rating plate.
Notes:
1. Jandy® CXi™ pool heaters require special gas venting. Use only the vent materials and methods specified in the Jandy® CXi™
Pool Heater Installation and Operation Manual.
2. The Jandy® CXi™ is orificed for operation up to 2000 feet altitude, and including up to 4,500 feet, with no field adjustments.
The appliance will de-rate by 4% for each 1000 feet above sea level up to 4,500 feet. Consult the factory for installations above
4,500 feet elevation.
7
Jandy®, CXi™ Pool Heater Installation & Operation Manual
1 Determine unit location
Location of unit
This unit meets the safe lighting performance criteria with the
gas manifold and control assembly provided, as specified in
the ANSI standards for gas-fired units and ANSI Z21.13/CSA
4.9 - latest edition.
1. Maintain all clearances from combustible construction
when locating appliance. See Clearances from Combustible
Construction, this page.
2. Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the unit.
The pan must not restrict combustion airflow. Under no
circumstances is the manufacturer to be held responsible
for water damage in connection with this unit, or any of its
components.
3. The appliance must be installed so that the ignition
system components are protected from water (dripping,
spraying, rain, etc.,) during appliance operation and service
(circulator replacement, control replacement, etc.,).
4. Appliances located in a residential garage and in adjacent
spaces that open to the garage and are not part of the living
space of a dwelling unit must be installed so that all burners
and burner ignition devices have a minimum clearance of
not less than 18" (46 cm) above the floor. The appliance
must be located or protected so that it is not subject to
physical damage by a moving vehicle.
5. DO NOT install this appliance in any location where
gasoline or flammable vapors are likely to be present.
6. The appliance must be installed on a level floor.
7. Combustible floor installation:
a. Models CXi500, CXi650 and CXi750 require an
approved floor kit for installation on combustible
flooring (reference Table 1A).
8. DO NOT install this appliance directly on carpeting or
other combustible material.
9. Maintain required clearances from combustible surfaces,
reference the Indoor Clearances from Combustible Construction Section, this page.
10. For outdoor models, you must install an optional vent
cap. Instructions for mounting the vent cap are included
in the venting section of this manual. Do not install
outdoor models directly on the ground. You must install
the outdoor unit on a concrete, brick, block, or other
non-combustible pad. Outdoor models have additional
special location and clearance requirements. See Outdoor
Installation Venting, page 32. A wind proof cabinet
protects the unit from weather.
Indoor clearances from combustible
construction
Maintain minimum specified clearances for adequate
operation. Allow sufficient space for servicing pipe
connections, pump and other auxiliary equipment, as well
as the unit. See rating plate for specific service clearance
requirements.
Right Side 3" (7.5 cm)
Rear 3" (7.5 cm) (3" min. from any surface)*
Left Side 6" (15 cm) (24" (0.61 m) suggested for
service)
Front Alcove* (30" (0.76 m) suggested for service)
Top 3" (7.5 cm)
Flue 1" (25.4 mm)
Hot Water Pipes 1" (25.4 mm)
*An Alcove is a closet without a door. Thirty-six inches (36")
to rear required for outdoor installation.
Note: No additional clearance is needed on the right side of the
unit for the observation port. An observation port is located on
both the right and left side of the unit.
Figure 1-1_Indoorclearances from combustible construction
NOTICE
Clearances from combustible construction
are noted on the appliance rating plate.
TABLE - 1A
COMBUSTIBLE FLOOR KITS
ModelKit Number
CXi500 100136977
CXi650100136978
CXi750100136979
Freeze protection
Installations are not recommended in areas where the danger of
freezing exists. You must provide proper freeze protection for
outdoor installations, units installed in unheated mechanical
rooms or where temperatures may drop to the freezing point or
lower. If freeze protection is not provided for the system, a low
ambient temperature alarm is recommended for the mechanical
room. Damage to the unit by freezing is non-warrantable.
8
1 Determine unit location
Anytime the inlet temperature drops below 45°F, the
control turns on the pump contact. If the inlet temperature is
below 37°F, and the unit is in the ON Mode, the rst stage will
re.
Location
Locate indoor pool heaters in a room having a temperature
safely above freezing [32°F (0°C)].
Jandy®, CXi™ Pool Heater Installation & Operation Manual
⚠
CAUTION
A mechanical room operating under a negative
draft pressure may experience a down draft in
the flue of a pool heater when it is not firing.
The cold outside air pulled down the flue
may freeze a heat exchanger. This condition
must be corrected to provide adequate freeze
protection.
Hydronic systems anti-freeze
Freeze protection for a pool heater using an indirect coil can
be provided by using hydronic system antifreeze. Follow the
appliance manufacturers instructions. Do not use undiluted or
automotive type antifreeze (see page 42).
Outdoor pool heater installation
A snow screen should be installed to prevent snow and ice
accumulation around the unit or its venting system.
Combustion and ventilation air
Provisions for combustion and ventilation air must be in
accordance with Air for Combustion and Ventilation, of the
latest edition of the National Fuel Gas Code, ANSI Z223.1, in
Canada, the latest edition of CAN/CGA-B149 Installation Code
for Gas Burning Appliances and Equipment, or applicable
provisions of the local building codes.
Provide properly-sized openings to the equipment room to
assure adequate combustion air and proper ventilation when
the unit is installed with conventional venting or sidewall
venting.
Combustion air options
⚠
CAUTION
This unit has four combustion air options.
1. Outside Combustion Air, No Ducts
You can direct outside combustion air to this unit using either
one or two permanent openings.
Under no circumstances should
the equipment room ever be under
a negative pressure. Particular care
should be taken where exhaust fans, attic
fans, clothes dryers, compressors, air
handling units, etc., may take away air
from the unit.
Figure 1-2_Outside Combustion Air - Single Opening
Two Openings
The combustion air opening must have a minimum free area of
one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You
must locate this opening within 12" (30 cm) of the bottom of the
enclosure (see FIG. 1-3).
The ventilation air opening must have a minimum free area of
one square inch per 4000 Btu/hr input (5.5 cm2 per kW). You
must locate this opening within 12" (30 cm) of the top of the
enclosure.
Figure 1-3_Outside Combustion Air - Two Openings
2. Outside Combustion Air, Using Ducts
You can direct outside combustion air to this unit using two air
ducts to deliver the air to the mechanical room (see FIG. 1-5).
Each of the two openings must have a minimum free area of one
square inch per 2000 Btu input (11cm2 per kW).
3. Combustion Air from Interior Space
You can direct combustion air to this unit using air from an
adjoining interior space. You must provide two openings from
the mechanical room to the adjoining room (see FIG. 1-4).
Each of the two openings must have a net free area of one square
inch per 1000 Btu input (22cm2 per kW), but not less than 100
square inches (645cm2).
One Opening
The opening must have a minimum free area of one square
inch per 3000 Btu input (7 cm2 per kW). You must locate this
opening within 12" (30 cm) of the top of the enclosure (see FIG.
1-2).
Figure 1-4_Combustion Air from Interior Space
9
1 Determine unit location
Jandy®, CXi™ Pool Heater Installation & Operation Manual
All dimensions are based on net free area in square inches.
Metal louvers or screens reduce the free area of a combustion air
opening a minimum of approximately 25%. Check with louver
manufacturers for exact net free area of louvers. Where two
openings are provided, one must be within 12" (30 cm) of the
ceiling and one must be within 12" (30 cm) of the floor of the
equipment room. Each opening must have a minimum net free
area as specified in TABLE 1B, this page. Single openings shall
be installed within 12" (30 cm) of the ceiling.
Figure 1-5_Outside Combustion Air Through Ducts
4. Outside Combustion Air - Using Direct Venting
With this option, you can connect combustion air vent piping
directly to the unit. See the information under Direct Venting
starting on page 25 for specific information regarding this
option.
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
*Outside Air from
Model
Number
CXi500
CXi650
CXi750
2 Openings Directly from
Outdoors
Top
Opening, in
125
(806 cm2)
163
(1052 cm2)
188
(1213 cm2)
Bottom
2
Opening, in
(806 cm2)
(1052 cm2)
(1213 cm2)
125
163
188
*Outside Air from
1 Opening Directly
from Outdoors, in
2
167
(1077 cm2)
217
(1400 cm2)
250
(1613 cm2)
2
⚠
CAUTION
The combustion air supply must be
completely free of any flammable vapors
that may ignite or chemical fumes which
may be corrosive to the appliance. Common
corrosive chemical fumes which must be
avoided are fluorocarbons and other
halogenated compounds, most commonly
present as refrigerants or solvents, such as
Freon, trichlorethylene, perchlorethylene,
chlorine, etc. These chemicals, when
burned, form acids which quickly attack
the heat exchanger finned tubes, headers,
flue collectors, and the vent system. The
result is improper combustion and a nonwarrantable, premature unit failure.
Inside Air from
2 Ducts Delivered from
Outdoors
Top
Opening, in
2
Opening, in
Bottom
250
(1613 cm2)
(1613 cm2)
325
(2097 cm2)
(2097 cm2)
375
(2420 cm2)
(2420 cm2)
250
325
375
Inside Air from
2 Ducts Delivered from
Interior Space
Top
2
Opening, in
500
(3226 cm2)
650
(4194 cm2)
750
(4839 cm2)
2
Opening, in
(3226 cm2)
(4194 cm2)
(4839 cm2)
Bottom
2
500
650
750
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a
duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The
above requirements are for the pool heater only; additional gas fired appliances in the equipment room will require an increase in
the net free area to supply adequate combustion air for all appliances.
10
Jandy®, CXi™ Pool Heater Installation & Operation Manual
1 Determine unit location (continued)
Exhaust fans
Any fan or equipment which exhausts air from the mechanical
room may deplete the combustion air supply and/or cause a
down draft in the venting system. Spillage of flue products from
the venting system into an occupied living space can cause a
very hazardous condition that must be immediately corrected.
If a fan is used to supply combustion air to the mechanical
room, the installer must make sure that it does not cause drafts
which could lead to nuisance operational problems with the
pool heater.
Vertical DirectAire™, Horizontal DirectAire™, and Direct Vent
venting systems have specific requirements for combustion air
ducts from the outside which are directly connected to the unit.
See the requirements for combustion air duct in the venting
section.
NOTICE
Use of filters having MERV (Minimum
Efficiency Reporting Value) ratings higher
than 4 is not recommended. Higher efficiency
low-micron filters can limit combustion
air leading to either nuisance problems or
potential component damage if used over
prolonged periods of time. Filters having
a MERV rating of 5 to 6 may be used
on a limited basis during the construction
phase of a project provided they are replaced
once filter loading becomes apparent. After
the construction phase is completed, it is
recommended that the filter be changed to a
4 or lower MERV disposable type filter.
Combustion air filter
This unit has a standard air filter located at the combustion air
inlet. This filter helps ensure clean air is used for the combustion
process. Check this filter every month and replace when it
becomes dirty. The filter size on Models CXi500, CXi650 and
CXi750 is 12" x 12" x 1" (30.5 cm x 30.5 cm x 2.5 cm). You can
find these commercially available filters at any home center or
HVAC supply store.
For convenience and flexibility, you can direct the combustion
air inlet from either the back or right side of the unit. To arrange
the combustion air inlet for side entry, follow the steps below:
1. Remove the metal panel from the unit’s side wall (see
FIG. 1-6).
2. Remove screws from the air filter/bracket assembly.
3. Move the filter/bracket assembly from the rear of unit to the
side opening (see FIG. 1-7).
4. Attach filter/bracket assembly to the unit’s side using the
pre-drilled screw holes.
5. Attach the metal panel to the rear combustion air opening
to seal it off.
Figure 1-6_Metal Panel Covering Side Combustion
Air Inlet
NOTICE
CAUTION
During construction the air filter should be checked more frequently to ensure it does not become clogged with
combustion dirt and debris.
Sustained operation of an appliance with a clogged filter may result in nuisance operational problems, bad
combustion, and non-warrantable component failures.
Figure 1-7_Moving Air Filter / Bracket Assembly from
Rear of Unit to Side
11
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting
BEFORE YOU BEGIN
Identify your appliance’s vent system:
This manual covers venting requirements for CAT I models and CAT IV vent materials. Be sure to correctly identify the type of
vent system your appliance requires before proceeding.
Venting options:
CXi 0500
CXi 0650
CXi 0750
⚠
DANGER
Failure to use correct venting materials can result in loss of life from flue gas spillage into working or living
space.
ABC
E
F
= Direct Vent Options
CAT IV
= Outdoor Vent Option
D
= B-Vent Material
CAT I
Venting Category Definitions: (Reference National Fuel Gas Code ANSI Z223.1)
CAT I: Negative pressure non-condensing
An appliance that operates with a non-positive vent static pressure with a vent gas temperature that avoids excessive condensate
production in the vent.
CAT IV: Positive pressure condensing
An appliance that operates with a positive vent static pressure with a vent gas temperature that may cause excessive condensate
production in the vent.
CAT IV Flue pipe materials
The following manufacturers supply flue materials suitable for these models when installed as CAT IV. All materials are made
with AL29-4C stainless steel.
Heat-Fab Inc., Saf-T CI Vent with AL29-4C stainless steel
Protech Systems Inc., Fas N Seal Vent with AL29-4C stainless steel
Metal-Fab Inc., Corr/Guard Vent with AL29-4C stainless steel
Or other listed Category IV vent systems suitable for a condensing, positive pressure, gas fired appliance.
A Category IV flue MUST have all vent joints and seams sealed gastight and have provisions for a drain to properly collect and
dispose of condensate that may occur in the venting system.
12
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting (continued)
Vent system options: (Note: Installations shown below are representative, actual installations may vary from those shown.)
This option uses a vertical rooftop flue termination
with air supplied from the equipment room - see
A
CONVENTIONAL NEGATIVE
DRAFT VENTING
B
VERTICAL DIRECTAIRE VENTING
page 15.
This option uses a vertical conventional vent for
flue products with air supplied by a pipe from the
sidewall or rooftop - see page 18.
This option uses a powered vent assembly to
exhaust the flue products out a sidewall with air
D
HORIZONTAL DIRECTAIRE
VENTING
E
supplied by a pipe from the sidewall - see page 24.
This option uses a sealed AL29-4C flue and a
separate combustion air pipe to the outdoors.
This system terminates both the flue and
combustion air inlet in the same pressure zone
- see page 25.
C
SIDEWALL VENTING
This option uses a powered vent assembly to
exhaust the flue products out a sidewall vent
termination with air supplied from the equipment
room - see page 21.
This option uses the installation of a special air
inlet / vent cap on top of the unit - see page 32.
F
OUTDOOR VENTING
13
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting
General information
You must supply adequate combustion and ventilation air to this unit. You must provide minimum clearances for the vent
terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition
of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas
Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys
must be in accordance with “Venting of Equipment” of the above-mentioned standards.
NOTICE
Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness.
Also check for corrosion or deterioration. If you find any problems, correct them at once.
Venting support
Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot
(21mm/m) on all horizontal runs from the unit to the vertical flue run or to the vent terminal on sidewall venting installations.
Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the
venting system must not rest on the unit. Provide adequate support of the venting system. Follow all local and applicable codes.
Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.
Barometric damper location
Any venting system option that requires a barometric damper must adhere to the following directions for optimum performance.
The preferred location for the barometric damper is in a tee or collar installed in the vertical pipe rising from the unit’s flue outlet.
The barometric damper MUST NOT be installed in a bull head tee installed on the unit’s flue outlet. The tee or collar containing
the barometric damper should be approximately three feet vertically above the connection to the unit’s flue outlet. This location
ensures that any positive velocity pressure from the unit’s internal combustion fan is dissipated and the flue products are rising
due to buoyancy generated from the temperature of the flue products. Adjust the weights on the damper to ensure that draft is
maintained within the specified range.
TABLE - 2A
FLUE AND AIR INLET PIPE SIZES
MODELFLUE SIZEAIR INLET SIZE
CXi5006"6"
CXi6508"8"
CXi7508"8"
*Minimum diameter for air inlet pipe. Installer may increase diameter one pipe size for ease of installation, if needed.
14
2 Venting (continued)
Conventional negative draft venting - see page 13.
A
NOTICE
This option uses Type-B double-wall flue outlet piping. The blower brings in combustion air. The buoyancy of the
heated flue products cause them to rise up through the flue pipe. The flue outlet terminates at the rooftop.
Negative draft
The negative draft in a conventional vent installation must be within the range of 0.02 to 0.08 inches w.c. to ensure
proper operation. Make all draft readings while the unit is in stable operation (approximately 2 to 5 minutes).
Connect the flue vent directly to the flue outlet opening on the top of the unit. No additional draft diverter or
barometric damper is needed on single unit installations with a dedicated stack and a negative draft within the
specified range of 0.02 to 0.08 inches w.c. If the draft in a dedicated stack for a single unit installation exceeds the
maximum specified draft, you must install a barometric damper to control draft. Multiple unit installations with
combined venting or common venting with other Category I negative draft appliances require each pool heater to
have a barometric damper installed to regulate draft within the proper range.
Do not connect vent connectors serving appliances vented by natural draft (negative draft) to any portion of a
mechanical draft system operating under positive pressure. Connecting to a positive pressure stack may cause flue
products to be discharged into the living space causing serious health injury.
Before installing a venting system, follow requirements found in the General Venting section.
Jandy®, CXi™ Pool Heater Installation & Operation Manual
Flue outlet piping
With this venting option, you must use Type-B double-wall vent materials. Vent materials must be listed by a
nationally-recognized test agency for use as vent materials. Make the connections from the unit vent to the outside
stack as direct as possible with no reduction in diameter. Use the National Fuel Gas Code venting tables for
double-wall vent to properly size all vent connectors and stacks. Follow the vent manufacturer’s instructions when
installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
Provide adequate clearance to combustibles for the vent connector and firestop.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls, ceilings,
and floors. Locate the unit as close as possible to a chimney or gas vent.
Avoid long horizontal runs of the vent pipe, 90° elbows, reductions and restrictions.
No additional draft diverter or barometric damper is required on single unit installations with a dedicated stack and
a negative draft maintained between 0.02 to 0.08 inches w.c.
Common Venting Systems
You can combine the flue with the vent from any other negative draft, Category I appliance. Using common venting
for multiple negative draft appliances requires you to install a barometric damper with each unit. This will regulate
draft within the proper range. You must size the common vent and connectors from multiple units per the venting
tables for Type-B double-wall vents in the latest edition of the National Fuel Gas Code, ANSI Z223.1 and/or CAN/
CGA-B149 Installation Code.
Common venting systems may be too large when an existing unit is removed.
At the time of removal of an existing appliance, the following steps shall be followed with each appliance remaining
connected to the common venting system placed in operation, while other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch. Make sure there is no blockage or
restriction, leakage, corrosion and other unsafe conditions.
3. If possible, close all building doors and windows. Close all doors between the space in which the appliances
remaining connected to the common venting system are located and other building spaces.
15
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting
4. Turn on clothes dryers and any other appliances not connected to the common venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
5. Close fireplace dampers.
6. Place in operation the unit being inspected. Follow the lighting instructions. Adjust thermostat so unit will operate continuously.
7. Test for spillage at the draft hood/relief opening after 5 minutes of main burner operation. Use the flame of a match or candle,
or smoke from a cigarette, cigar or pipe.
8. After making sure that each appliance remaining connected to the common venting system properly vents when tested as
above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions
of use.
9. Correct any improper operation of the common venting system so that the installation conforms to the latest edition of the
National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B149 Installation Code for Gas Burning
Appliances and Equipment. When resizing any portion of the common venting system, resize to approach the minimum size
as determined using the appropriate tables of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the
latest edition of CAN/CGA-B149 Installation Code for Gas Burning Appliances and Equipment.
Masonry chimney installations
A masonry chimney must be properly sized for the installation of a high efficiency gas-fired appliance. Venting of a high efficiency
appliance into a cold or oversized masonry chimney can result in operational and safety problems. Exterior masonry chimneys,
with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the
flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to generate
proper draft. This will result in condensing of flue products, damage to the masonry flue/tile, insufficient draft and possible spillage
of flue products into an occupied living space. Carefully inspect all chimney systems before installation.
⚠
WARNING
NOTICE
Inspection of a masonry chimney
A masonry chimney must be carefully inspected to determine its suitability for the venting of flue products. A clay-tile-lined
chimney must be structurally sound, straight and free of misaligned tile, gaps between liner sections, missing sections of liner or any
signs of condensate drainage at the breaching or clean out. If there is any doubt about the condition of a masonry chimney, it must
be relined with a properly-sized and approved chimney liner system. An unlined masonry chimney must not be used to vent flue
products from this high-efficiency unit. An unlined chimney must be relined with an approved chimney liner system when a new
appliance is being attached to it. Metallic liner systems (Type-B double-wall or flexible or rigid metallic liners) are recommended.
Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.
Do not vent this unit into a masonry chimney without a sealed stainless steel liner system. Any breaks, leaks,
or damage to the masonry flue/tile will allow the flue products to leak from the chimney and into occupied
living spaces. This could cause serious injury or death due to carbon monoxide poisoning and other harmful
flue products.
Check with local code officials to determine code requirements or the advisability of using a masonry chimney
with a sealed corrosion-resistant liner system.
Vertical vent termination clearances and location
The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61 m) above the highest point of the roof
within a 10 foot (3.05 m) radius of the termination.
The vertical termination must be a minimum of 3 feet (0.91 m) above the point of exit.
A vertical termination less than 10 feet (3.05 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher than the parapet
wall.
Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.
16
2 Venting (continued)
Jandy®, CXi™ Pool Heater Installation & Operation Manual
Figure 2-1_Vent Termination from Peaked Roof - 10 ft.
or Less From Ridge
NOTICE
Figure 2-3_Vent Termination from Flat Roof - 10 ft.
or Less From Parapet Wall
Vent terminations are not shown in FIG.’s 2-1 thru 2-4. Make sure all vertical vents are installed with vent
terminations recommended by the vent manufacturer.
Figure 2-2_Vent Termination from Peaked Roof - 10 ft.
or More From Ridge
Figure 2-4_Vent Termination from Flat Roof - 10 ft. or
More From Parapet Wall
17
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting
Vertical DirectAire ™ venting - see page 13.
NOTICE
B
The Vertical DirectAire™ vent system is the same as the Conventional Negative Draft vent system, except it pulls
combustion air from the outdoors through a separate air inlet pipe. Follow all requirements in the Conventional
Negative Draft Venting section on page 15.
The Vertical DirectAire™ vent system requires you to install two pipes directly to the unit; one vertical pipe with
a rooftop termination for the flue products and one pipe for combustion air. For this venting option, you must
purchase the DV box adapter from the appliance manufacturer. The DV box attaches to the air inlet of the unit. The
pipe for combustion air attaches to the DV box (see FIG. 2-11 on page 27). Reference page 27 for a list of approved
air intake materials.
Combustion air inlet piping
Before installing a venting system, follow requirements found in the General Venting section.
⚠
WARNING
The sidewall or vertical rooftop DirectAire™ combustion air supply system has specific material and installation requirements. The
air inlet pipe connects directly to the unit to supply combustion air. In most installations, the combustion air inlet pipe will be a
dedicated system with one air inlet pipe per unit. You can combine multiple air inlets if the guidelines in Combined Air Inlet Points,
page 19 are followed. The air inlet pipe will be connected to a combustion air inlet cap as specified in this section.
For normal installations, this system uses a single-wall pipe to supply combustion air from outdoors directly to the unit.
In cold climates, use a Type-B double-wall vent pipe or an insulated single-wall pipe for combustion air. This will help prevent
moisture in the cool incoming air from condensing and leaking from the inlet pipe.
Locate and install the combustion air inlet cap correctly. Failure to do so can allow the discharge of flue products
to be drawn into the combustion process. This can result in incomplete combustion and potentially hazardous
levels of carbon monoxide in the flue products. This will cause operational problems and the spillage of flue
products. Spillage of flue products can cause personal injury or death due to carbon monoxide poisoning.
Length of air inlet pipe
The installed length of air inlet pipe from the unit to the outside air inlet cap must not exceed 50 equivalent feet (15.2 m). Subtract
5 feet (1.5 m) of equivalent length for each 90° elbow. Subtract 2.5 feet (0.7 m) of equivalent length for each 45° elbow.
Do not exceed the limits for the combustion air inlet piping lengths.
Sidewall air inlet
The sidewall air inlet cap is supplied in the Sidewall Air Inlet Kit. Order the kit from the appliance manufacturer. This sidewall
cap supplies combustion air for a single unit only. See Table 2B, page 20, for kit numbers.
Locate the unit as close as possible to the sidewall where you will install the combustion air supply system.
Figure 2-5_Sidewall Combustion Air Inlet
18
Figure 2-6_Air Inlet Cap for Sidewall Termination
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting (continued)
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance
requirements in the latest edition of the National Fuel Gas Code and/or CAN/CGA-B149 Installation Code and instructions in the
Installation and Operation Manual.
Clearances
You must install the combustion air inlet cap at least one foot (0.30 m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91 m) below the point of flue gas termination if
it is located within 10 feet (3.05 m) of the flue outlet. Make sure to properly install the air inlet cap assembly on the air inlet pipe.
Do not install the combustion air inlet cap closer than 10 feet (3.05 m) from an inside corner of an L-shaped structure.
Vertical Rooftop Air Inlet
Use the vertical air inlet terminations available from the appliance manufacturer, recommended and/or supplied by the vent
manufacturer, or use two 90° elbows as described on page 28.
You must locate the air inlet termination elbow at least 12"
(30 cm) above the roof or above normal snow levels.
If the air inlet cap is within a 10-foot (3.05 m) radius of the flue
outlet, the point of termination for the combustion air inlet
cap must be at least 3 feet (0.91 m) below the point of flue gas
termination (vent cap).
Do not install the combustion air inlet cap closer than 10 feet
(3.05 m) from an inside corner of an L-shaped structure.
Combined air inlet points
The air inlet pipes from multiple pool heaters can be combined
to a single common connection if the common air inlet pipe has
a cross sectional area equal to or larger than the total area of all
air inlet pipes connected to the common air inlet pipe.
Example: Two 10" air inlet pipes (78.5 in2 area each) have a total
Figure 2-7_Rooftop Combustion Air Inlet
The air inlet point for multiple pool heater air inlets must be provided with an exterior opening which has a free area equal to
or greater than the total area of all air inlet pipes connected to the common air inlet. This exterior opening for combustion air
must connect directly to the outdoors. The total length of the combined air inlet pipe must not exceed a maximum of 50 (15.2 m)
equivalent feet. Subtract 5 feet (1.5 m) for each 90° elbow in the air inlet pipe. You must deduct the restriction in area provided by
any screens, grills or louvers installed in the common air inlet point. These are common on the sidewall air inlet openings. Screens,
grills or louvers installed in the common air inlet can reduce the free area of the opening from 25% to 75% based on the materials
used.
You can terminate the combustion air pipe either horizontally with a sidewall air inlet or vertically with a rooftop air inlet. The
installed length of air inlet pipe from the unit to the outside air inlet cap must not exceed 50 equivalent feet (15.2 m).
area of 157 in2 and will require a 15" (176.7 in2 area) common
air inlet pipe.
19
2 Venting
Jandy®, CXi™ Pool Heater Installation & Operation Manual
⚠
Figure 2-8_Vertical DirectAire™ Installation
w/Rooftop Combustion Air Inlet
WARNING
For single unit installations with sidewall air inlet you must order the sidewall
air inlet kit from the appliance manufacturer. The part number for each SVK kit
is listed by unit size in Table 2B.
For single unit installations with rooftop air inlet (see FIG. 2-8), you must order
the rooftop air inlet kit from the appliance manufacturer. The part number for
each VDK kit is listed by unit size in Table 2B. Purchase the flue pipe, rooftop
flue termination, and air inlet pipe locally.
There is no vent kit for combined air supply systems for multiple units. Make
sure the air inlet cap is properly sized. You must purchase this cap locally.
Venting of flue products
For venting flue products vertically to the outdoors, follow all requirements in
the installation instructions for conventional venting in this manual.
Follow all clearance requirements in Vertical Vent Termination Clearances and
Location on page 16.
Only use a sidewall air inlet cap supplied by the appliance
manufacturer or a rooftop air inlet cap supplied by either the vent
or appliance manufacturer. Using any other air inlet cap for single
unit installations or using a common air inlet cap for multiple
units with insufficient free area and/or protections from wind and
weather may result in operational problems and the spillage of
flue products. Spillage of flue products can cause personal injury
or death due to carbon monoxide poisoning.
A barometric damper is not required in the flue on Vertical DirectAire™
installations if the draft is within the negative 0.02 to 0.08 inches w.c. required
for proper operation. If the draft exceeds this range, install a barometric damper.
*The SVK kits include a DV box adapter and sidewall air inlet cap. The VDK kits include a DV box adapter and a rooftop air inlet cap.
20
2 Venting (continued)
Sidewall venting - see page 13.
Jandy®, CXi™ Pool Heater Installation & Operation Manual
C
NOTICE
This option uses a powered vent assembly which pulls the flue products out of the stack. This fan generates a negative
draft at the unit. Combustion air is drawn from the equipment room (see Combustion and Ventilation Air on 10).
Sidewall with fan
The sidewall fan can be mounted on the inside/outside (depending upon model) with a sidewall vent hood installed
on the exterior wall. The sidewall fan and accessories are included in a venting kit provided by the appliance
manufacturer. The barometric damper must be installed on the flue and adjusted to supply a negative draft within
the range of 0.02 to 0.08 inches w.c. while unit is operating. See Table 2C on page 23 for kit numbers.
Flue outlet piping
With this venting option, you must use Type-B double-wall (or equivalent) vent materials. Vent materials must be
listed by a nationally-recognized test agency for use as vent materials. Make the connections from the unit vent to
the sidewall fan/cap as direct as possible with no reduction in diameter. Follow the vent manufacturer’s instructions
when installing Type-B vents and accessories, such as firestop spacers, vent connectors, thimbles, caps, etc.
When planning the venting system, avoid possible contact with plumbing or electrical wiring inside walls.
The maximum installed length of sidewall vent pipe with an induced draft fan must not exceed 100 feet (30.5 m).
Subtract 5 feet (1.5 m) for each 90° elbow. Subtract 2.5 feet (0.7 m) for each 45° elbow.
Sidewall venting termination
The sidewall vent cap must be installed on an exterior sidewall. The sidewall fan/powered sidewall vent cap and
accessories are included in a venting kit which is furnished by the appliance manufacturer in accordance with CSA
requirements. This venting kit includes the powered sidewall fan/cap, proving switch and all necessary relays to
interlock with the heaters control system.
Before installing a venting system, follow all requirements found in the General Venting
section.
The sidewall fan/powered vent cap must be interlocked with the units control system to start the fan on a call for
heat and prove fan operation before the pool heater fires. Plug-in and terminal strip connections are provided on
the unit for easy connection of the factory supplied vent kit and control package for the sidewall vent fan. See the
installation instructions provided with the vent kit.
Sidewall vent termination clearances and location
Locate the bottom of the vent terminal at least 12 inches (30 cm) above grade and above normal snow levels. Locate
the bottom of the vent terminal at least 7 feet (2.13 m) above grade when located adjacent to public walkways. Do
not terminate directly above a public walkway.
Do not terminate the venting system in a window well, stairwell, alcove, courtyard, or other recessed area. Do not
terminate the venting system below grade.
Locate vent termination at least 3 feet (0.91 m) from an inside corner of an L-shaped structure.
Provide a minimum clearance of 4 feet (1.2 m) horizontally from electric meters, gas meters, regulators, and relief
equipment. Never locate vent cap above or below electric meters, gas meters, regulators, and relief equipment unless
a 4 foot (1.2 m) horizontal clearance is maintained.
21
Jandy®, CXi™ Pool Heater Installation & Operation Manual
2 Venting
Terminate the venting system at least 3 feet (0.9 m) above any forced air inlet within 10 feet (3.05 m).
Terminate the venting system at least 4 feet (1.2 m) below, 4 feet (1.2 m) beside, or 1 foot (30cm) above any door, window, or
gravity air inlet into any building.
Locate vent termination at least 8 feet (2.4 m) horizontally from any combustion air intake located above the sidewall termination
cap.
⚠
CAUTION
Sidewall venting without fan
For Models CXi500, CXi650, and CXi750 which are approved for sidewall venting without an external power vent fan, you must
install specific vent kits and venting materials (reference Table 2C on page 23 for kit numbers).
The following is a detailed explanation of Sidewall Venting Without an External Power Vent Fan installation requirements.
Flue outlet piping
Venting Guidelines
Units which are shut down or will not operate may experience freezing due to convective air flow in the flue
pipe, through the air inlet, or from negative pressure in the equipment room. In cold climates, operate the
pump continuously to help prevent freezing of pool heater water. Provide proper freeze protection. See Freeze
Protection, page 47.
If using this venting option, a sealed AL29-4C venting system for flue products is required on all models of this appliance. This
venting system operates with a positive pressure in the vent. The internal combustion air blower generates this positive pressure
which operates the combustion process and also exhausts the flue products from the building.
This vent system has specific vent material and installation requirements. Only use listed sealed AL29-4C vent system materials.
Follow all installation requirements. See Table 2A for proper pipe size for your unit. A list of sealed AL29-4C flue pipe
manufacturers is located on page 14.
Seal all vent joints and seams gas-tight.
Drain tee installation
A drain tee must be installed in the vent pipe to collect and dispose of any condensate that may occur in the vent system. The drain
tee must be installed as the first fitting after the horizontal ell on the top of the unit (see FIG. 2-9). Plastic drain tubing, sized per
the vent manufacturer’s instructions, shall be provided as a drain line from the tee. The drain tubing must have a trap provided by
a 3" (7.6 cm) diameter circular trap loop in the drain tubing. Prime the trap loop by pouring a small quantity of water into the drain
hose before assembly to the vent. Secure the trap loop in position with nylon wire ties. Use caution not to collapse or restrict the
condensate drain line with the nylon wire ties. The condensate drain must be routed to a suitable drain for disposal of condensate
that may occur in the direct vent system. Refer to the condensate drain installation instructions as supplied by the manufacturer
of the vent material.
Figure 2-9_Sidewall Vent
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.