IPSO DR30 Owner's Manual

Page 1
- USA
OWNER'S MANUAL
Shown with manual
double timer
control system
Technical specifications
Installation instructions
Operating instructions
Maintenance
DR30
IPSO - USA
3101 South Haven Highway 77, Suite A
Panama City, FL, 32405
Phone: (850)271-8486
THIS MANUAL MUST BE GIVEN TO THE EQUIPMENT OWNER
MAN DR2030 (ECN5652) 9/99 D0566
Page 2
IMPORTANT NOTICES—PLEASE READ
For optimum efficiency and safety, we recommend that you read the manual before operating the equipment. Store this manual in a file or binder and keep for future reference.
WARNING: Purchaser must post the following notice in a prominent location:
WARNING: For your safety, the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage, personal injury or death.
- Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Clear the room, building or area of all occupants.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: In the event the user smells gas odor, instructions on what to do must be posted in a
prominent location. This information can be obtained from the local gas supplier.
WARNING: Wear safety shoes to prevent injuries.
WARNING: Purchaser must post the following notice in a prominent location:
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: A clothes dryer produces combustible lint and should be exhausted outside the
building. The dryer and the area around the dryer should be kept free of lint.
WARNING: Be safe, before servicing machine, the main power should be shut off.
Page 2
Page 3
ATTENTION: L’ACHETEUR DOIT PLACER L’AVERTISSEMENT SUIVANT DANS UN ENDROIT CLAIR ET VISIBLE:
AVERTISSEMENT. Assurez-vous de bien
suivre les instructions donnees dans cette notice pour reduire au minimum le risque d’incendie ou d’explosion ou pour eviter tuot dommage materiel, toute blessure ou la mort.
__ Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre apparell.
__ QUE FAIRE SI VOUS SENTEZ UNE
ODEUR DE GAZ:
• Ne pas tenter d’allumer d’apparell.
• Ne touchez a aucun interrupteur. Ne pas
vous servir des telephones se trouvant dans le batiment ou vous vous trouvez.
• Evacuez la piece, le batiment ou la zone.
• Appelez immediatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incendies.
__ l’installation et l’entretien doivent etre assures
par un installateur ou un service d’entretien qualifie ou par le fournisseur de gaz.
ATTENTION: L’ACHETEUR DOIT PLACER L’AVERTISSEMENT SUIVANT DANS UN ENDROIT CLAIR ET VISIBLE:
POUR VOTRE SECURITE
Ne pas entreposer ni utiliser d’ essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
Page 3
Page 4
WARNING: To avoid fire hazard, do not dry articles containing foam rubber or similar texture materials.
Do not put into this dryer flammable items such as baby bed mattresses, throw rugs, undergarments (brassieres, etc.) and other items which use rubber as padding or backing. Rubber easily oxidizes causing excessive heat and possible fire. These items should be air dried.
WARNING: Synthetic solvent fumes from drycleaning machines create acids when drawn through the dryer. These fumes cause rusting of painted parts, pitting of bright or plated parts, and completely removes the zinc from galvanized parts, such as the tumbler basket. If drycleaning machines are in the same area as the tumbler, the tumbler's make-up air must come from a source free of solvent fumes.
WARNING: Do not operate without guards in place.
WARNING: Check the lint trap often and clean as needed but at least a minimum of once per day.
WARNING: Alterations to equipment may not be carried out without consulting with the factory and only by a qualified engineer or technician. Only Manufacturer’s parts may be used.
WARNING: Remove clothes from dryer as soon as it stops. This keeps wrinkles from setting in and
reduces the possibility of spontaneous combustion.
WARNING: Be Safe - shut main electrical power and gas supply off externally before attempting service.
WARNING: Never use drycleaning solvents, gasoline, kerosene, or other flammable liquids in the dryer.
FIRE AND EXPLOSION WILL OCCUR. NEVER PUT FABRICS TREATED WITH THESE LIQUIDS INTO THE DRYER. NEVER USE THESE LIQUIDS NEAR THE DRYER..
WARNING: Do not place items exposed to cooking oils in your dryer. Items contaminated with cooking oils may contribute to a chemical reaction that could cause a load to catch fire.
WARNING: Never let children play near or operate the dryer. Serious injury could occur if a child should crawl inside and the dryer is turned on.
WARNING: Never tumble fiberglass materials in the dryer unless the labels say they are machine dryable. Glass fibers break and can remain in the dryer. These fibers cause skin irritation if they become mixed with other fabrics.
WARNING: Before operating gas ignition system - purge air from natural gas or propane gas lines per manufacturer’s instructions.
WARNING: To reduce the risk of electric shock, disconnect this appliance from the power supply before attempting any user maintenance other than cleaning the lint trap. Turning the controls to the OFF position does not disconnect this appliance from the power supply.
Page 4
Page 5
IPSO DRYER WARRANTY
IPSO warrants all new equipment (and the original parts thereof) to be free from defects in material or workmanship for a period of two (2) years from the date of sale thereof to an original purchaser for use, except as hereinafter provided. With respect to non-durable parts normally requiring replacement in less than two (2) years due to normal wear and tear, and with respect to all new repair or replacement parts for IPSO equipment for which the two (2) year warranty period has expired, or for all new repair or replacement parts for equipment other than IPSO equipment, the warranty period is limited to ninety (90) days from date of sale. The warranty period on each new replacement part furnished by IPSO in fulfillment of the warranty on new equipment or parts shall be for the unexpired portion of the original warranty period on the part replaced.
With respect to electric motors, coin meters and other accessories furnished with the new equipment, but not manufactured by IPSO, the warranty is limited to that provided by the respective manufacturer.
IPSO’s total liability arising out of the manufacture and sale of new equipment and parts, whether under the warranty or caused by IPSO’s negligence or otherwise, shall be limited to IPSO-USA repairing or replacing, at its option, any defective equipment or part returned f.o.b. IPSO’s factory, transportation prepaid, within the applicable warranty period and found by IPSO to have been defective, and in no event shall IPSO be liable for damages of any kind, whether for any injury to persons or property or for any special or consequential damages. The liability of IPSO does not include furnishing (or paying for) any labor such as that required to service, remove or install; to diagnose troubles; to adjust, remove or replace defective equipment or a part; nor does it include any responsibility for transportation expense which is involved therein.
The warranty of IPSO is contingent upon installation and use of its equipment under normal operating conditions. The warranty is void on equipment or parts; that have been subjected to misuse, accident, or negligent damage; operated under loads, pressures, speeds, electrical connections, plumbing, or conditions other than those specified by IPSO; operated or repaired with other than genuine IPSO replacement parts; damaged by fire, flood, vandalism, or such other causes beyond the control of IPSO; altered or repaired in any way that effects the reliability or detracts from its performance, or; which have had the identification plate, or serial number, altered, defaced, or removed.
No defective equipment or part may be returned to IPSO for repair or replacement without prior written authorization from IPSO. Charges for unauthorized repairs will not be accepted or paid by IPSO.
IPSO MAKES NO OTHER EXPRESSED OR IMPLIED WARRANTY, STATUTORY OR OTHERWISE, CONCERNING THE EQUIPMENT OR PARTS INCLUDING, WITHOUT LIMITATION, A WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, OR A WARRANTY OF MERCHANTABILITY. THE WARRANTIES GIVEN ABOVE ARE EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. IPSO NEITHER ASSUMES, NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT, ANY OTHER WARRANTY OR LIABILITY IN C ON NE C TI ON WITH THE MANUFACTURE, USE OR SALE OF ITS EQUIPMENT OR PARTS.
For warranty service, contact the distributor from whom the IPSO equipment or part was purchased. If the distributor cannot be reached, contact IPSO.
IDENTIFICATION NAMEPLATE
The identification nameplate is located on the rear wall of the dryer. It contains the dryer serial number, product number, model number, electrical specifications and other important data that may be needed when servicing and ordering parts, wiring diagrams, etc. Do not remove this nameplate.
Page 5
Page 6
Contents
Safety Instructions .............................................................................. 2-4
Cissell Dryer Warranty ....................................................................... 5
Table of Contents ................................................................................ 6
Symbols ............................................................................................... 7
Unpacking / General Installation ....................................................... 8-9
Technical Data and Dimensions......................................................... 10-11
Electric Connections ........................................................................... 12
Gas Connections ................................................................................. 13
Gas Piping Installation ....................................................................... 14-15
Gas service Installation Instructions ................................................ 16
Gas Pipe Size Chart ............................................................................ 17
Dryer Installation with Multiple Exhaust ...........................................18-19
Dryer Make-Up Air Requirements ...................................................... 20
Dryer Installation with Separate Exhaust ......................................... 21
Exhaust and Venting ........................................................................... 22
Rules for Safe Operation of Dryer ..................................................... 23
Direct-Spark Ignition Operation......................................................... 24-25
General Maintenance ..........................................................................26-27
Operating Instruction for Double Timer ........................................... 28
PARTS .................................................................................................. 29-43
Front View ................................29
Front Panel Assembly .............31
Wire Box Assembly .................33
Lint Door Assembly ................ 35
Rear View .................................37
Basket Bearings/Sheave Assy 39
Idler Assembly .........................41
Gas Heating Unit Assembly ...43
Control Door Assembly ..........30
Thermostat Assembly ............. 32
Door Assembly ........................34
Basket & Spider Assembly .....36
Air Switch Assembly............... 38
Motor & Fan Assembly ........... 40
Rear Control Panel Assembly 42
Page 6
Page 7
SYMBOLS
The following symbols are used in this manual and/or on the machine.
Symbol
Description
NOTE!
Hot! Do Not Touch Heiß! Nicht Beruhren Haute temperature! Ne pas toucher Caliente! no tocar
dangerous voltage tension dangereuse Gefährliche elektrische Spannung tension peligrosa
On Marche Ein Conectado
Off Arrêt Aus Desconectado
Symbol
Rotation in two directions Rotation dans les deux sens Drehbewigung in zwei Richtungen Movimiento rotativo en los dos sentidos
Direction of rotation Sens de mouvement continu De rotation Drehbewegung in Pfeilrichtung movimiento Giratorio o rotatorio en el sentido de la flecha
End of Cycle
Caution Attention Achtung Atencion; precaucion
Start Demarrage Start Arranque de un movimiento
Emission of heat in general Emission de chaleur en general Warmeabgabe allgemein Emisión de calor
Cooling Refroidissement Kühlen Enfriamiento
Page 7
Page 8
Unpacking/General Installation (All Dryers)
UNPACKING
GENERAL INSTALLATION (ALL DRYERS)
Upon arrival of the equipment, any damage in shipment should be reported to the carrier immediately.
Upon locating permanent location of a unit, care should be taken in movement and placement of equipment.
See outline clearance diagrams for correct dimensions. Remove all packing material such as: tape, manuals, skid,
etc Leveling: Use spirit level on top of dryer. Adjust leveling
bolts on dryer (see adjustable leveling bolts in maintenance section).
Check voltage and amperes on rating plate before installing the dryer.
The construction of the dryers permit installation side-by-side to save space or to provide a wall arrangement. Position dryer for the least amount of exhaust piping and elbows, and allow free access to the rear of dryer for future servicing of belts, pulleys and motors. The installation clearance from all combustable material is 0" ceiling clearance for the first 4" (102 mm)from the front of the dryer. After the first 4" (102 mm), the ceiling clearance required is 6" (153 mm). The rear clearance required is 0", and the side clearance is 1" (26 mm).
Before operating dryer, open basket door and remove blocking between front panel and basket. Read the instruction tags, owner’s manual, warnings, etc.
IMPORTANT Opening the clothes loading door deactivates the door switch to shut off the motors, fan, gas, steam, or electric element. To restart the dryer, close the door and press in the push to start button.
IMPORTANT This dryer is designed for a capacity maximum load. Overloading it will result in long drying times and damp spots on some clothes.
IMPORTANT Maximum operating efficiency is dependent upon proper air circulation. The lint screen must be kept clean daily to ensure proper air circulation throughout the dryer.
IMPORTANT Provide adequate clearance for air opening into the combustion chamber.
Page 8
Page 9
Unpacking/General Installation (All Dryers)
GENERAL INFORMATION
DRYER “COOL-DOWN” CYCLE
The dryer is so designed that when an operator opens the dryer door, the basket and exhaust fan stop. You can expect fast drying from a laundry dryer. Hot, dry air is properly and effectively moved through the basket and exhausted through a lint trap to the atmosphere. The dryer comes equipped with an inclined self­cleaning lint screen. In this system, lint accumulates on the underside of the screen until a blanket of lint will fall from the screen to the bottom of the dryer cabinet, and should be removed daily or as required, to prevent an over-accumulation.
IMPORTANT Provide adequate clearance for air openings into the combustion chamber.
Permanent press, durable press and other modern day fabrics require the care that your dryers now provide. At the end of the drying cycle, a timed “Cool-Down” control automatically takes over and continues the rotation of the fan and basket without heat until the garment load reaches a safe cool temperature. This function is performed at the end of each drying cycle.
REPLACEMENT PARTS
Replacement parts for this dryer are available from your distributor or by contracting the factory at the address or phone number printed on the cover page of this manual.
Page 9
Page 10
30 lb. Dryer Dimensions - Standard Gas, Steam and Electric Heated
snoitacificepSerusaeM.S.U
yticapaC
)neniLyrD(
.sbl03gk6.31
cirteM
erusaeM
teksaB
retemaiDsehcni03mm048 htpeDsehcni emuloVtf9.11
92mm518
3
retil533
tenibaC
thgieHsehcni27mm8281 htdiWsehcni33mm838 htpeDsehcni61/5-34mm0011
gninepOrooD
retemaiDsehcni8/5-22m
m575
thgiehgnidaoLsehcni2/1-13mm008
erutarepmeT
0
muminiM001 mumixaM581
F83oC
0
F580C
rotoM
gnisrever-noN.P.H2/1Wk73.0
murD-gnisreveR.P.H2/1Wk73.0
naF.P.H3/1Wk52.0
tsuahxE
3
etaRwolFmfc526m3601
h/
retemaiDsehcni8mm302
sreyrDcirtcelE-.nnoCcirtcelE
gnisreveR-noNgnisreveR
V802HP3-06A76A86
V042/022HP3-06/05A06/
55A06/55
V514/083HP3-05A73/43A63/33
V084HP3-06A03A13
sreyrDsaG,maetS-.nnoCcirtcelE
/511HP1-06/05A4.9A8.4
V042-802
gnisreveR-noNgnisreveR
V514/083HP3-06/05A2.1A1.1
V084HP3-06/05A9.0A9.0
rewoP
cirtcelEWk5.22Wk5.22
saGh/utB000,011h/lack0
27,72
maetSP.H.B5.4h/lack000,83
noitcennocmaetS
telnI"4/302ND
teltuO"2/151ND
noitcennoCsaG
noitcennoCsaG"2/151ND
sserPsaG"21-"5bm03-21
eru
gnippihS
snoisnemiD
)DxWxH(
84X63X87
sehcni
419X1891
mm9121X
thgieW
teN.sbl705gk032
ssorG.sbl2
45gk642
Page 10
Page 11
DR30 Dryer Dimensions - Gas
(Illustration)
Page 11
Page 12
Electric connection
Dryers must be electrically grounded by a separate #14 or larger green wire from the grounding terminal within the Service Connection Box, to a cold water pipe. In all cases, the grounding method must comply with local electrical code requirements; or in the absence of local codes, with the National Electrical
Code, ANSI/NFPA 70 or the Canadian Electrical Code, CA C22.1.
See wiring diagram furnished with dryer. Do not change wiring without consulting the factory, as you may void the factory warranty. DO NOT CONNECT THE DRYER TO ANY VOLTAGE OR CURRENT OTHER THAN THAT SPECIFIED ON THE DRYER RATING PLATE. (Wiring diagram
is located on rear wall of dryer.)
All panels must be in position before operation of dryer.
The connection needs to be made in the wiring box at the back. Remove the coverplate (G) in order to reach the connection clamps.
The connection cable needs to be brought in through the opening (H) in the side of
the wiring box.
L1
L2
L3
N
115 and 208-240 V - 1 ph 208-240 and 480 V - 3 ph
380-415V - 3 ph
It is necessary to ground the dryer for your personal safety and to ensure a good operation.
115 and 208-240 V - 1 ph
The mains wires (Ll) and (L2) should be connected to the 2 left clamps and the yellow/green grounding wire (PE) should be connected to the grounding clamp.
208-240 and 480 V - 3 ph
The 3 mains wires (L1), (L2) and (L3) should be connected to the 3 left clamps and the yellow/green grounding wire (PE) should be connected to the grounding clamp.
380-415V - 3 ph
The 3 mains wires (L1), (L2) and (L3) should be connected to the 3 left clamps, the blue neutral (N) should be connected to the right clamp and the yellow/green grounding wire (PE) should be connected to the grounding clamp.
«Attention. Lors des opérations d’entretien des commandes, ètiqueter tous les fils avant de les dèconnecter. Toute erreur de câblage peut être une source de danger et de panne»
Page 12
Page 13
Gas connection
The gas supply pipe should be connected to the gas tap (I), which is on the right next to the wiring box on the back.
It is important to have the connections done by a qualified technician, in order to ensure that the installation is in accordance with the prevailing standards and instructions.
The dryer should be connected to the type of gas indicated on the serial plate. The use of too small gas pipes can result in insufficient gas supply, which can lead
to slow heat-up and poor drying quality.
I
When the dryer is used in combination with a weighing platform, the gas supply pipe has to be made of flexible material to allow the weighing system to keep moving freely.
Test all connections for possible leaks by means of a soap solution, but
never with a flame.
It is important to work with the right gas pressure (see technical remarks) in order to obtain a good ignition, heating and consequently a good operation in general.
After the gas supply has been connected, the gas tap in the dryer should be turned on
(clockwise).
Electrical Controls Service
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Page 13
Page 14
Gas Piping Installation
GAS PIPING INSTALLATION
1. The installation must conform with local codes, or in the
absence of local codes with the National Fuel Gas Code,
ANSI Z223.1 or the CAN/CGA-B149, Installation Codes.
2. Check Identification Nameplate for type of gas for dryer.
3. Check the altitude of dryer.
4. Check with utilities company for proper gas pressure and gas supply line.
5. Natural Gas Only—Check the gas pressure inlet supply to dryer, 11 inches water column (27.4 mbar) maximum. Manifold Pressure—3.5 inches water column (8.8 mbar) pressure.
6. L.P. Gas Only—Manifold pressure—13 inches water column (32.4 mbar) maximum.
CAUTION: Low gas pressure and intermittent gas will cause gas ignition problems and inadequate drying of laundry.
Page 14
Page 15
Gas Piping Installation (Illustrations)
The dryer and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (.04 bar).
The dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (.04 bar).
Page 15
Page 16
Gas Service Installation Instructions
GAS SERVICE INSTALLATION INSTRUCTIONS
The size of the gas service pipe is dependant upon many variables, such as tees, lengths, etc. Specific pipe size should be obtained from the gas supplier. Refer to the “Gas Pipe Size” chart in this manual for general gas pipe size information.
CAUTION: Gas loop piping must be installed as illustrated to maintain equal gas pressure for all dryers connected to a single gas service
Other gas-using appliances should be connected upstream from the loop.
GAS PRESSURE REGULATOR FOR LIQUIFIED PETROLEUM GASES
WARNING: LIQUIFIED PETROLEUM GASES ONLY !
A gas pressure regulator for liquified petroleum gases is not furnished on gas heated clothes dryers. This regulator is normally furnished by the installer. In accordance with American Gas Association (AGA) standards, a gas pressure regulator, when installed indoors, must be equipped with a vent limiter or a vent line must be installed from the gas pressure regulator vent to the outdoors.
Page 16
Page 17
Gas Pipe Size Chart
TOTAL BTU/HR
(for LP Gas correct
total BTU/HR below by
multiplying by .6)
60,000
80,000 100,000 120,000 140,000 160,000 180,000 200,000 300,000 400,000 500,000 600,000 700,000 800,000 900,000
1,000,000 1,100,000 1,200,000 1,300,000 1,400,000 1,500,000 1,600,000 1,700,000 1,800,000 1,900,000 2,000,000 2,200,000 2,400,000 2,600,000 2,800,000 3,000,000 3,200,000 3,400,000 3,600,000 3,800,000 4,000,000
TOTAL
KCAL
HOUR
15000 20000 25200 30200 35200 40300 45300 50400
75600 100800 126000 151200 176400 202000 230000 250000 270000 300000 330000 350000 380000 400000 430000 450000 480000 504000 550000 605000 650000 705000 750000 806000 850000 907000 960000
1000000
GAS PIPE SIZE FOR 1000 BTU (250 KCAL) NATURAL GAS
In figuring total length of pipe, make allowance for tees and elbows.
(25 ft.) 7,62 m
3/4 3/4 3/4 3/4 3/4 3/4
1 1
1 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2
2
2
2
2
2
2
2
2
2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3
3
3
3
3
(50 ft.)
15,24 m
1 1/4 1 1/4 1 1/2 1 1/2
2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3 1/2 3 1/2 3 1/2 3 1/2
AT 7” W.C. (17.5MM) PRESSURE
(75 ft.)
22,86 m
3/4 3/4 3/4
1 1 1 1 1
2 2 2 2 2 2
3 3 3 3 3 3
3/4 3/4
1 1 1 1
1 1 1/4 1 1/4 1 1/2 1 1/2
2
2
2
2
2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3
3
3
3
3
3
3 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2
(100 ft.) 30,48 m
3/4
1 1 1
1 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2
2
2
2
2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3
3
3
3
3
3
3 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2
4
4
(125 ft.)
38,1 m
3/4
1 1 1
1 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2
2
2
2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3
3
3
3
3
3
3 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2
4
4
4
4
(150 ft.) 45,72 m
1 1/4 1 1/4 1 1/4 1 1/2 1 1/2
2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2
3 1/2 3 1/2 3 1/2 3 1/2 3 1/2
3/4
1 1 1
2 2 2
3 3 3 3 3 3 3
4 4 4 4 4 4
Page 17
Page 18
No. of Dryers Duct Diameter
(in inches) (in cm)
Dryer Installation With Multiple Exhaust
For exhaust duct less than 14 feet (5 m) and 2 elbows equivalent and less than 0.3 inches (8 mm) static pressure.
DRYER EXHAUSTS
Area of section “A-A” must be equal to the sum of dryer exhaust pipes entering multiple exhaust pipe. (See chart below.)
DR30
1 2 3 4 5 6 7 8 9 101112131415161718192021222324 8 1214161820222324262728293031323334353637383940
20 30 25 41 46 51 56 58 61 66 68 71 73 76 78 81 84 86 89 91 94 97 99 100
Power Supply
to Fan
Relay Coils
Start and Stop
Switches on
Dryers
_ _ _ _
Page 18
_ _ _ _
_ _ _ _
Exhaust
Booster Fan
_ _ _ _
_ _ _ _
_ _ _ _
Page 19
Dryer Installation with Multiple Exhaust
DRYER INSTALLATION WITH MULTIPLE EXHAUST
For exhaust duct more than 14 feet (5 m) and 2 elbows equivalent and more than 0.3 inches (8 mm) static pressure.
1. Make-up air from outside the building may enter enclosure from top or
side walls. (See Dryer Make-Up Air Requirements Chart)
2. Use constant diameter duct with area equal to the sum of dryer duct areas.
EXAMPLE: Six 8 inch (204 mm) diameter ducts = one 19.6 inch (498 mm) diameter duct in area. Use 20 inch (508 mm) diameter duct or diameter to match tube-axial fan.
3. Enclosure (plenum) with service door. This separates the dryer air from room comfort air. If dryers use room air instead of outside air, the heat loss can be another 25 Btu/hr (6.3 kcal/hr) for each cubic foot per minute (cfm) used.
4. The installation clearance from all combustible material is 0" ceiling clearance for the first 4" (102 mm) from the front of the dryer. After the first 4" (102 mm), the ceiling clearance required is 6" (153 mm). the rear clearance required is 0", and the side clearance is 1" (26 mm).
5. Heat loss into laundry room from dryer fronts only is about 60 Btu/hr per square foot (15 kcal/hr per 0.1m²).
6. Flange mounted, belt driven tube-axial fan. Fan must run when one or more dryers are running. See suggested Automatic Electrical Control Wiring Diagram on previous page. Must meet local electrical codes. Fan air flow (cfm or m³/min.) is equal to the sum of dryer air flows, but static pressure (SP) is dependent on length of pipe and number of elbows.
7. Barometric Bypass Damper—Adjust to closed flutter position with all dryers and exhaust fan running. Must be located within enclosure.
CAUTION: Never install hot water heaters or other gas appliances in the same room as dryers. Never install cooling exhaust fans in the same room as dryers.
CAUTION: Never exhaust dryers with other types of equipment.
Page 19
Page 20
Suggested Minimum Dryer Make-up Air Requirements
Dryer Dryer Pocket Maximum Air Flow Duct Size For Required Make-up Model Capacity Rate per Pocket Service Connection Air Area per Pocket
lb kg cfm m3/h inch mm sq. in. cm2
C 30 30 13.6 700 1190 8 203 135 871 C 30 E/S 30 13.6 400 680 6 153 77 497 C 30 ST 30 13.6 450 765 6 153 87 561 C 50 50 22.7 800 1360 8 20 3 154 994 C 50 E/S 50 22.7 450 765 6 153 87 561 C 75 75 34 1000 1700 8 203 192 1239 C 75 E/S 75 34 536 911 6 153 103 665 C 75 ST 75 34 1000 1700 12 305 192 1239 HD80 80 36.3 1465 2490 10 254 282 1819 C 110 1 10 50 2200 3740 12 305 422 2723 C 110 E/S 110 50 850 1445 8 203 163 1052 C 125 1 2 5 56.7 2000 3400 12 305 384 2477 C 150 150 68 2250 3825 12 305 432 2787 HD175 175 79.4 2780 4726 12 305 534 3445 HD190 190 86.2 3000 5100 12 305 576 3716 WMC/HD20 20 9.1 450 765 6 1 53 87 561 WMC/HD30 30 13.6 625 1063 8 203 120 774 WMC/HD50 50 22.7 700 1190 8 2 03 135 871 WMC/HD75 75 34 750 1275 8 203 144 929
Notes:
1) The Model C 30 ST has 2 pockets per dryer , each pocket has the above listed characteristics; each pocket is exhausted separately with a 6" (153mm) duct.
2) The Model C 75 ST has 2 pockets per dryer , each pocket has the above listed characteristics; both pockets have one 8" (203mm) exhaust manifolded into one 12" (305mm) exhaust duct for exhaust connection.
3) For the C 30 ST and the C 75 ST Models, the Required Make-up Air Area shown in the table should be doubled since it is shown per pocket,only .
4) E/S indicates an Energy Saving Model.
Page 20
Page 21
Dryer Installation With Separate Exhaust (Preferred)
DRYER INSTALLATION WITH SEPARATE EXHAUST (PREFERRED)
For ductwork less than 14 feet (5 m) and 2 elbows equivalent and less than 0.3 inches (8 mm) static pressure:
NEVER exhaust the dryer into a chimney. NEVER install wire mesh screen over the exhaust or make-up air
area. NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-up air from outside the building may enter the enclosure from
the top or side walls. (See Dryer Make-Up Air Requirements Chart)
2. Enclosure (plenum) with service door. This separates the dryer air from the room comfort air. If dryers use room air instead of outside air, additional heat loss can be another 25 Btu/hr (6.3 kcal/hr) for each cubic foot per minute (cfm) (.03m³/min.) used.
3. The installation clearance from all combustible material is 0" ceiling clearance for the first 4" (102 mm) from the front of the dryer. After the first 4" (102 mm), the ceiling clearance required is 6" (153 mm). The rear clearance required is 0", and the side clearance is 1" (26 mm).
4. Heat loss into laundry room from dryer front panels is about 60 Btu/hr per square foot (15 kcal/hr per 0.1m²).
Page 21
Page 22
Exhaust and Venting
DRYER AIR FLOW INSTALLATION
EXHAUST DUCT
MAKE-UP AIR
Nothing is more important than air flow for the proper operation of a clothes dryer. A dryer is a pump which draws make-up air from the out-of-doors, through the heater, through the clothes and then forces the air through the exhaust duct back to the out-of-doors. Just as in a fluid water pump, there must be a fluid air flow to the inlet of the dryer, if there is to be the proper fluid air flow out of the exhaust duct. In summary, there must be the proper size out-of-doors inlet air opening and an exhaust duct, size and length of which allows flow through the dryer with no more than 0.3 inches water column (.8 mbar) static pressure in the exhaust duct. In some instances, special fans are required to supply make-up air, and/or booster exhaust fans are required.
FOR BEST DRYING:
1. Exhaust duct maximum length 14 feet (5 m) of straight duct and maximum of two 90° bends.
2. Use 45° and 30° elbows wherever possible.
3. Exhaust each dryer separately.
4. Do not install wire mesh or other restrictions in the exhaust duct.
5. Use clean-outs in the exhaust duct and clean periodically when needed.
6. Never exceed 0.3 inches (.8 mbar) water column static pressure in the exhaust duct.
7. Inside surface of the duct must be smooth.
8. Recommend pop rivets for duct assembly.
FOR BEST DRYING:
1. Make-up air from outside the building may enter the enclosure from the top or side walls. The area of the opening must be a minimum of 210 square inches (135484 mm²) for each dryer. This will deliver the proper amount of make-up air at an air velocity of approximately 500 fpm (152 m/min) through the opening.
2. Use barometric shutters in the inlet air opening to control air when dryers are not running.
OTHER RECOMMENDATIONS
TROUBLESHOOTING
OTHER RECOMMENDATIONS
To assure compliance, consult local building code requirements.
TROUBLESHOOTING
Hot dryer surfaces, scorched clothes, slow drying, lint accumulations, or air switch malfunction are indicators of exhaust duct and/or make­up air problems.
Page 22
Page 23
Rules for Safe Operation of Dryer
RULES FOR SAFE OPERATION OF DRYER
1. Be sure your dryer is installed properly in accordance with the recommended instructions.
2. CAUTION Be safe—shut main electrical power supply and gas supply off externally before attempting service.
3. CAUTION Never use drycleaning solvents: gasoline, kerosene, or other flammable liquids in the dryer. Fire and explosion will occur.
Never put fabrics treated with these liquids into the dryer. Never use these liquids near the dryer. Always keep the lint screen clean. Never use heat to dry items that contain plastic, foam or
sponge rubber, or rags coated with oils, waxes or paints. The heat may damage the material or create a fire hazard. Rubber easily oxidizes, causing excessive heat and possible fire. Never dry the above items in the dryer.
4. Never let children play near or operate the dryer. Serious injury will occur if a child should crawl inside and the dryer is turned on.
5. Never use dryer door opening and top as a step stool.
6. Read and follow manufacturer’s instructions on packages of laundry and cleaning aids. Heed any warnings or precautions.
7. Never tumble fiberglass materials in the dryer unless the labels say they are machine dryable. Glass fibers break and can remain in the dryer and could cause skin irritation if they become mixed into other fabrics.
8. Reference Wiring diagrams are located on the rear cover of the dryer cabinet.
9. The dryer must not be installed or stored in an area where it will be exposed to water and/or weather.
ENERGY-SAVING TIPS
1. Install dryer so that you can use short, straight venting. Turned elbows and long vent tubing tend to increase drying time. Longer drying time means the use of more energy and higher operating costs.
2. Operate dryer using full-size loads. Very large loads use extra energy. Very small loads waste energy.
3. Dry light-weight fabrics separately from heavy fabrics. You will use less energy and get more even drying results by drying fabrics of similar weight together.
4. Clean the lint screen area daily. A clean lint screen helps give faster, more economical drying.
5. Do not open the dryer door while drying. You let warm air escape from the dryer into the room.
6. Unload the dryer as soon as it stops. This saves having to re­start your dryer to remove wrinkles.
Page 23
Page 24
Direct-Spark Ignition Operation
DIRECT SPARK IGNITION OPERATION
NOTE: All dryers manufactured are equipped with the DSI (Direct Spark Ignition) modules. These are designed to increase dryer efficiency and to reduce dryer operating costs. The main burner is directly ignited from a spark electrode. A burning flame provides an electrical path for a small amount of sensing current to allow gas valve operation. If the main burner flame extin­guishes for any reason (aside from the thermostatic control) sensing current will shut down the gas valve and the spark ignition circuit.
1. Once flame is established, the spark shuts off, and the main burner flame is then electronically monitored by means of a sensing spark probe which is located over the burner. The gas valve remains energized (open).
2. If no flame is detected within the first 11 seconds the DSI will go into a safety “lock-out”. The gas valve is de-energized.
3. Recovery from a safety lockout requires one of the following:
A. Opening the main door thus interrupting power to the DSI module and allowing dryer diagnostic trouble shooting.
B. Disconnecting the entire dryer from a power source using a circuit breaker as a switch.
4. By closing the main door the ignition circuit will be restored for another trial of the ignition circuit.
5. Once the thermostatic control has been satisfied by reaching a pre-set temperature or the drying timer has been timed out, the ignition circuit will be de-energized thus extinguishing the flames.
6. The dryer will continue to run in a cool-down mode without heat. This process will cool the load to the touch and help to eliminate wrinkling.
7. The cool - down time is pre-set on some models and manually set on other dryer models. The cool-down cycle prevents fabric wrinkles by allowing clothes to reach room ambient temperature while still in a continuous levitation state until clothes are ready to be folded or pressed.
Page 24
Page 25
DIRECT SPARK
IGNITION OPERATION
FLOW CHART
The DSI module is powered by a 24 volt AC supplied by a step-down transformer in series with eight safety interlocks:
A. Timer Switching Device (1) B. Main Door and Lint Door Switches (2) C. Sail Switch (1) D. Under Basket and Burner Housing Thermal Safety Switches (2) E. Variable Thermostat (1) F. Push to Start Switch (1)
THERMOSTAT CALLS
FOR HEAT
YES
IGNITION CYCLE
BEGINS, GAS VALVE
ON
MAIN BURNER FLAME
DETECTED
YES
SPARK IGNITION OFF
FLAME MONITOR ON
GAS VALVE ON
FLAME IS LOST DUE TO POWER OUTAGE,
DOOR OPEN
NO
CONTROL LOCK-OUT
RESET POWER
REQUIRES A MANUAL
RESET (Opening/closing
door, power switch ON/
OFF)
NO
FLAME IS ON UNTIL
THERMOSTAT OR
TIMER IS SATISFIED
Page 25
Page 26
General Maintenance
GENERAL MAINTENANCE
1. Clean lint trap daily. Remove lint before or after each day of
operation. A clean lint trap will increase the efficiency of the dryer and the moisture-laden air will be exhausted outside more quickly.
2. Keep basket and sweep sheets clean. Clean as
often as needed. The basket and sweep sheets are accessible by removing the front panel of the dryer.
3. Gas burners, steam coils, electric coils. Check and
clean often.
4. Pulleys and belts. Keep clean, as oil and dirt will
shorten the life of a belt. Check periodically for alignment. Pulley shafts must be parallel and the grooves must be aligned. Check belt tension periodically. Adjust tension by movement of Idler Bracket. Lubricate basket shaft bearings once every two months, using six grams of high temperature grease. Do not over-
grease.
5. Electric motor. Keep motor clean and dry. Motors
are packed with sufficient grease for 10 years normal service. After that, bearings and housing should be cleaned and repacked one-third full with Chevron Grease No. SR1-2. See label on motor for further information.
If motor overheats, check voltage and wiring. Low voltage, inadequate wiring and loose connections are the main cause of motor failures.
6. Adjustable leveling bolts. One at each corner
permits accurate alignment of dryer. To adjust: Block one corner of dryer up off the floor, loosen hex nut. With wrench, turn bolt clockwise to raise dryer, opposite to lower. Rear bolts are inside the rear cover of the dryer, and front bolts are inside lint trap compartment.
Page 26
Page 27
General Maintenance
GENERAL MAINTENANCE (continued)
7. Periodically clean and examine exhaust system.
8. Keep dryer area clean and free of gasoline, combustible materials and other flammable liquids or vapors.
9. Do not obstruct the flow of combustion (make-up) air and ventilating air.
10. Check gas pressure periodically.
Page 27
Page 28
OPERATING INSTRUCTION - DOUBLE TIMER
OPERATING INSTRUCTIONS
- DOUBLE TIMER MODELS
1. After loading the dryer with water washed clothes, close the loading door.
2. Turn the 60 minute drying (heat) timer to the desired time.
3. Turn the 60 minute cooling (air) to the desired time.
4. Select the temperature desired: Low, Medium, or High.
HIGH HEAT
175° F (80° C)exhaust temperature, heavy fabrics and hard to dry, such as cottons, towels, denim, etc..
PERMANENT PRESS (medium)
155° F (69° C) exhaust temperature, synthetic blends, including a mixed wash load.
LOW HEAT
135° F (58° C) exhaust temperature, delicate, sheer fabrics.
5. Press the “push to start” button to start the drying cycle. The heat or drying light will stay on until the drying cycle is completed
6. At the end of the drying cycle, the cool down cycle will automatically count down until all time runs out. The cool down light will stay on until the end of the cycle.
7. Drying cycle will not start unless a few minutes of the cool-down cycle are set on the cool-down timer.
8. Open the door to shut the dryer off at any time during the cycles.
Page 28
Page 29
FRONT VIEW
Ref. Part No. Description No.
1 CSA50036WH Jacket gas/electric (white) 1 CSA-50051WH Jacket steam (white) 2 TU7733 Screw self drilling 8-18 X 1/2” 3 CA-11987-0 Top panel 4 CA-11546-0 Cover plate (non-coin models) 5 TU7733 Screw self drilling 8-18 X 1/2” 6 CSA-01435-0 Coin chute w/a 7 EA-00650-0 Microswitch door 8 CA-11991-0 Right sweepsheet 9 CA-11991-0 Left sweepsheet (gas & elec) 9 CA-13087-0 Left sweepsheet (steam)
Page 29
Ref. Part No. Description No.
10 CB36 Screw -hex 1/4-20 X 1/2” 11 TU2846 Lockwasher 1/4” medium 12 TU2847 Washer 1/4” 13 CA-10567-0 Lint frame 13 CA-13033-0 LintScreen 14 TU3211 Leveling bolt 15 TU7733 Screw self drilling 8-18 X 1/2” 16 CSA-01528-0 Support filter 17 CSA-01388-0 Insulation side WMC complete
-used on gas models only-
18 CA-13094-0 Insulation cover-steam-left
side-not shown
Page 30
CONTROL DOOR ASSEMBLY
CSA-01582WH Complete control door assy. - Simple microprocessor CSA-01407WH Complete control door assy. - Double Timer
Note: Door rod assy. is not part of above complete assy.
Ref. Part No. Description
No.
1 CSA-01578WH Control door assy. - Simple microprocessor
1 CSA-01408WH Control door assy. - Double timer 2 CA-00856-0 Trim - Control door 3 LA-11941-0 Cam lock-Control door 4 LA-00121-0 Lock - Control door 5 LA-00119-0 Key - Control door 6 CA-13098-0 Gasket 7 CA-10085-0 Support rod 8 SB-00951-0 Screw -Phillips #8 X 7/16 flat hd. 9 SB-00971-0 Tinnerman push- on fastener 10 TU7733 Screw self drilling 8-18*1/2"
Page 30
Page 31
FRONT PANEL ASSEMBL Y
11
Ref. Part No. Description No.
1 SB-00915-0 Screw self drilling #10-16 X 5/8 2 CSA-01564WH Front panel, welded assy.-Coin 2 CSA-01563WH Front panel, welded assy-OPL 3 TU5158 Latch & catch asm.
5 CA-00675-1 Insulation 6 SB-00924-0 Screw 4-40*3/8 taptite 7 SB-00938-0 Washer 4 external tooth 8 CA-00699-0 Bezel - Coin box 9 ESA-00862-0 Reed switch assy. 10 SB-00975-0 Screw 6-32*1/4 phillips 11 EA-00827-0 Mounting plate - Reed switch
Page 31
Page 32
THERMOSTAT ASSEMBLY ­DOUBLE TIMER
Ref. Part No. Description No.
1 EA-00607-0 Thermostat knob 2 CA-13213-0 Thermostat bracket 3 EA-00606-0 Thermostat 4 CA-13215-0 Thermostat bracket adapter 5 TU3624 Screw 6 - 32 X 1/4” 6 TU7733 Screw - self drilling 8 - 18 X 12” 7 EA-00434-0 Clip - 3/8” spring 8 EA-00608 - 0 Grommet / rubber 9 CA-13214-0 Plate 10 EA-00594-0 Thermostat - HI-Limit 11 SB-00828-0 Screw 8-32 X 1/2” 12 TU3266 Nut-brass 8-32
NOTE: Items 1 thru 6 mounted in front wire box. Items 7 thru 12 are mounted under the basket
Page 32
Page 33
WIRE BOX ASSEMBLY ­DOUBLE TIMER
67
2
2
3
2
5
1
1
2
4
Ref. Part No. Description No.
CSA-01608WH Wire box door assy complete
1 TUT316 Light LED 24V 2 EA-11614-0 Timer-manual 24V - 60 min. complete 3 EA-00619-0 Switch - start 4 CA-13170-0 Overlay- dual timer non-rev 5 CSA-01607WH Wire box door . 6 SB-00865-0 Screw-self drilling #6-20 X 12” 7 EA-00210-0 Terminal block 8 ESA-00967-0 Wire harness (not shown) 9 SB-00868-0 Bushing 7/8”
Page 33
Page 34
DOOR ASSEMBLY
Ref. Part No. Description No.
MSD-00859WH Complete door assy (consists of items 1 thru 9 only)
1 MD-00362-0 Door Glass - clear 2 MD-00354-0 Gasket - door glass - straight 3 TU5158 Latch & catch pin asm.
5 MD-00337-0 Magnet - reed switch 6 MD-00338-0 Gasket - door rim
7 TU2874 Basket door handle 8 MSD-00857WH Basket door 9 TU3215 Screw #10 - 32 X 3/8” 10 SB-00852-0 Washer 1/4” external starluck 11 SB-00921-0 Screw 1/4”-20 round head 12 MD-00348-0 Hinge spacer
Page 34
Page 35
LINT DOOR ASSEMBLY
For OPL models only.
Ref. Part No. Description No.
CSA-01386WH Complete Asm - WMC30 OPL
CSA-01465WH Complete Asm - WMC30 Coin 1 CSA-01387WH Lint door w/latch holes(white) OPL 1 CSA-01098WH Lint door w/lock holes(white) Coin 2 CA-00833-0 Kickplate 3 SB-00949-0 Fastener plastic kickplate 4 CA-11930-0 Insulation lower frontpanel WMC30 5 SB-00915-0 Screw self drilling #10-16 X 5/8 6 TU2853 Gasket
7 CA-00646-0 Handle lint door 8 CA-00841-0 Label (not part of assy.) 9 CA-00655-0 Trim-rubrail-specify 33” long 10 LA-11359-0 Cam lock 11 LA-00121-0 Lock 12 LA-00119-0 Key 13 LA-00124-0 Latch - trigger
Page 35
Page 36
BASKET & SPIDER ASSEMBL Y
Ref. Part No. Description No.
CSA-01539-0 Basket & Spider Asm.WMC30 - S.S.
CSA-01637-0 Basket & Spider Asm.WMC30 - Galv. 1 CSA-01538-0 Stainless steel basket assy. 1 CSA-01636-0 Galvanized basket assy. 2 CSA-01434-0 Spider assy. 3 TU5439 Screw-cap 5/16-18 X 3/4" 4 TU2814 Lock washer 5/16" 5 SB-00843-0 Washer fender 3/8” X 1 1/2” 6 SB-00906-0 Nut 5/16” - 18 stover 7 TU2814 Lock washer 5/16” 9 TU7006 Shim 10 CA-13208 Basket rib support 11 DA-00445-0 Tie rod (4 req’d) 12 SB-00965-0 Screw-button cap 5/16 - 18
Page 36
Page 37
REAR VIEW
Ref. Part No. Description No.
1 CA-11987-0 Top panel 2 TU7733 Screw self drilling 8-18*1/2" 3 CA-11936-0 Cover plate
4 CA-11975-0 Backpanel 5 TU7733 Screw self drilling 8-18*1/2"
Page 37
Page 38
AIR SWITCH ASSEMBLY
Ref. Part No. Description No.
CSA-01334-0 Sail switch assy. complete
1 CA-11854-0 Bracket sailswitch 2 SB-00955-0 Screw phillips #4 X 3/4" 3 TU7733 Screw self drilling 8-18*1/2" 4 CSA-01669-0 Sailswitch plate and rod assy. 5 SB-00954-0 Clip-twin-Tinnerman
6 EA-00618-0 Microswitch
Page 38
Page 39
BASKET BEARINGS, SUPPORT, AND SHEAVE
Ref. Part No. Description No.
1 DA-11911-0 Pulley - basket 2 Part of pulley 3 TU5887 Key 4 C249 Hex nut 5/16-18" 5 SB-00876-0 Stud - 5/16 - 18” 6 DSA-00728-0 Bearing box assy. 7 TU4787 Hex nut 3/8-16" 8 VSB134 Lock Washer 3/8" 9 IB140 Washer 3/8" 10 IB140 Washer 3/8" 11 IB139 Screw 3/8-16*1-1/4" 12 C249 Hex nut 5/16-18"
13 SB-00935-0 Screw cap 5/16 - 18 X 3 14 DA-00421-0 Bearing flange 1 3/8”
Ref. Part No. Description No.
15 IB140 Washer 3/8" 16 IB139 Screw 3/8-16*1-1/4" 17 IB139 Screw 3/8-16*1-1/4" 18 IB140 Washer 3/8" 19 IB140 Washer 3/8" 2 0 VSB134 Lock Washer 3/8" 21 TU4787 Hex nut 3/8-16" 2 2 VSB134 Lock Washer 3/8" 23 TU4787 Hex nut 3/8-16" 24 DA-00421-0 Bearing - flange 1 3/8” 2 5 Part of bearing
Page 39
Page 40
MOTOR & FAN ASSEMBLY- NON-REVERSING
Ref. Part No. Description No.
1 DA-00428-0 Fan motor 1/2 HP 115/208/230/60/50/1 2 TU2814 Lock washer 5/16”
3 TU5439 Screw-cap 5/16-18 X 3/4" 4 DSA-00801-0 Motor mount w/a - non-rev. 5 SB-00842-0 Nut, grip, Tinnerman
6 SB-00836-0 Screw, phillips, pancake head 7 DSA-00773-0 Fan (12")
8 SB-00813-0 Nut 1/2-20" - Left hand thread 9 SB-00847-0 Washer -1" O.D. X .505 I.D. 10 IB140 Washer cut 3/8" 1 1 VSB134 Washer lock 3/8" 12 TU4787 Hex nut 3/8-16" 13 DA-00460-0 Seal, acoustical 14 SB-00847-0 Washer -1" O.D. X .505 I.D. 15 DA-00509-0 Sheave, 60 cycle, 1/2” bore 15 DA-00508-0 Sheave, 50 cycle, 1/2” bore 16 TU2473 Gasket - curved (2 req’d) 17 TU2474 Gasket - straight (2 req’d)
Page 40
Page 41
IDLER ASSEMBLY
Ref. Part No. Description No.
1 DA--00531-0 Idler pulley 9” 2 DA-00523-0 Basket belt - non-reversing - AX66 2 DA-00523-0 Basket belt -reversing - AX66 3 FB124 Screw 5/16-18*1" 4 VSB130 Washer 5/16"
5 CA-12059-0 Idler adjusting plate 6 DA-00518-0 Bearing 7 DA-00517-0 Housing - idler bearing 8 TU2814 Lock washer 5/16" 9 C249 Hex Nut 5/16-18" 10 DA-00518-0 Bearing
Page 41
Ref. Part No. Description No.
11 C249 Hex Nut 5/16-18" 12 TU2814 Lock Washer 5/16" 1 3 VSB130 Washer 5/16" 14 SB-00935-0 Screw 5/16”-18 X 3” 1 5 VSB130 Washer 5/16" 1 6 VSB130 Washer 5/16" 17 TU5439 Screw 5/16-18*1" 18 DA-11711-0 Idler shaft
1 9 TUD0187 Key 3/16 square 2-1/2" 20 DA-00530-0 V-belt pulley 2-1/2”
21 DA-00525-0 Belt - motor to idler pulley AX51
Non-reversing
21 TU10888 Belt - motor to idler pulley AX64
Reversing
Page 42
REAR CONTROL PANEL ASSEMBLY - NON-REVERSING DOUBLE TIMER MODELS-GAS ONLY
Ref. Part No. Description No.
ESA-00966-0 Wire box assy, rear, gas - 115V - 2 timer ESA-00974-0 Wire box assy, rear, gas - 208/240V - 2 timer
1 CA-11935-0 Rear wiring box 2 SB-00868-0 Bushing, insulating 7/8” 3 SB-00867-0 Bushing, insulating 1/2” 4 TU7733 Screw self drilling 8-18 X 1/2" 5 GA-00765-0 Ignitor ram III DSI 6 EA-00651-0 Varistor/relay/motor 7 GA-00803-0 High voltage lead/ram 8 TU2490 Plug button 9 EA-00680-0 Knock-out plug 10 EA-11618-0 Motor relay- 3 pole -30amp - 24V
Ref. Part No. Description No.
11 EA-00467-0 Terminal block 12 TU7733 Screw self drilling 8-18 X 1/2" 13 TU7738 Ground lug 14 TU7733 Screw self drilling 8-18 X 1/2" 15 SB-00865-0 Screw self drilling 6 - 20 X 1/2 16 EA-00210-0 Terminal block 17 EA-00646-0 Transformer 24V
18 TU7733 Screw self drilling 8-18 X 1/2"
Page 42
Page 43
GAS HEATING UNIT
Ref. Part No. Description No.
GSA-00784-0 Comp. assy. - Nat. gas GSA-00775-0 Comp. assy. - LP gas
1 GSA-00255-0 Housing gas burner 2 TU11613-0 Lock washer 10 external tooth
3 SB-00831-0 Screw 10-32*3/8" 4 GA-00756-0 Gas burner 5 LB20 Nipple - 1/2” X 3” 6 CA-11878-0 Bracket -pipe 7 GA-00770-0 Gas valve 24V 1/2"(Nat.gas) 8 TU7733 Screw self drilling 8-18 X 1/2" 9 FG274 Gas pipe 1/2 X 30” 10 TU5439 Screw cap 5/16-18X3/4" 1 1 VSB130 Washer 5/16" 12 390501053 Elbow 1/2" 13 OP308 Nipple 1/2” X 4”
Page 43
Ref. Part No. Description No.
14 OP314 Union (gas pipe) 15 GSA-00508-0 Manifold assy. 16 TU7733 Screw self drilling 8-18X1/2" 17 TU7733 Screw self drilling 8-18X1/2" 18 EA-00245-0 Thermostat HI LIMIT -330 19 TU7733 Screw self drilling 8-18 X 1/2" 20 CA11028-0 Bracket thermostat 21 GA-00761-0 Gas orifce (specify size) 22 TU3266 Hex nut-brass 8-32" 2 3 AT368 Lock washer #8 24 M262 Screw mach.truss head 8/32X3/8" 25 GA-11003-0 Gas ignition electrode 26 GA-10457-0 Bracket 27 TU7733 Screw self drilling 8-18 X 1/2"
0
Loading...