International Comfort Products CSA6, HSA6, TSA6 Installation Manual

INSTALLATION INSTRUCTIONS
R410A Split System Air Conditioner
CSA6, HSA6, TSA6
These instructions must be read and understood completely before attempting installation.
IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to
applicable regional efficiency standards issued by the Department of Energy.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Safety Considerations 2...........................
Installation Requirements 2........................
Installation 2.....................................
Startup Procedure 7.............................
General Sequence of Operation 8..................
Control Functions & Sequence of Operation 8........
Troubleshooting 9................................
Status Codes 10.................................
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in per­sonal injury and/or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 discon­nect switch. Lock out and tag switch with a suit­able warning label.
!
CUT HAZARD
Failure to follow this caution may result in per­sonal injury
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
WARNING
CAUTION
421 01 5104 03 02/11/15
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safetyalert symbol
!
!
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INSTALLATION RECOMMENDATIONS
Figure 1
OUTDOOR WALL INDOOR WALL
HANGER STRAP
(AROUND VAPOR
1 (25.4 mm)MIN.
Connecting Tube Installation
Avoid contact between tubing and structureNOTE:
CAULK
INSULATION
THROUGH THE WALL
TUBE ONLY)
SUSPENSION
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
Outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of fieldsupplied or factory accessory tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section of this instruction.
IMPORTANT: Maximum liquidline size is 3/8in. OD for all residential applications including long line.
IMPORTANT: Always install the factorysupplied liquid−line filter drier. Obtain replacement filter driers from your distributor or branch.
INSTALLATION
NOTE: In some cases noise in the living area has been
traced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable siliconbased caulk. (See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4 mm) wide and conform to shape of tubing insulation. (See Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
R410A refrigerant systems operate at higher pressures than standard R22 systems. Do not use R22 service equipment or components on R−410A refrigerant equipment.
Specifications for this unit in residential new construction market require the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation.
Check Equipment and Job Site
Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.
2 421 01 5104 03
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
For hurricane tie downs contact your local distributor for details and PE (Professional Certification), if required by local authorities.
On rooftop applications, mount on level platform or frame. Place unit above a loadbearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles. Consult the LowAmbient pressure switch installation instructions for wind baffle construction.
NOTE: Unit must be level to within ±2_ (±3/8 in./ft..) per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30 in. (762 mm) clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
Figure 2
3/8-in. (9.53 mm) Dia. Tiedown Knockouts in Basepan(2) Places
UNIT BASE PAN
Dimension
31–1/2 X 31–1/2 9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
35 X 35 9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface.
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
Tie Down Knockouts
View From Top
A B C
Make Piping Connections
!
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Use all service ports and open all flowcontrol devices, including solenoid valves.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm) may be buried without further special consideration. Do not bury lines more than 36 in. (914.4 mm).
Outdoor units may be connected to indoor section using accessory tubing package or fieldsupplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 80 ft/24.38 m, substantial capacity and performance losses can occur. Following the recommendations in the Long Line Applications Guideline for SplitSystem Air Conditioners and Heat Pumps will reduce these losses. Refer to Table 1 for accessory requirements. Refer to Table 2 for field tubing diameters.
There are no buriedline applications greater than 36 in. (914.4 mm).
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Outdoor Unit Connected to Factory Approved
WARNING
CAUTION
Indoor Unit
Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F (12.78_C) without low ambient cooling enabled, and the maximum outdoor operating ambient in cooling mode is 125°F (51.67_C).
Table 1 − Accessory Usage
REQUIRED FOR LOWAMBIENT
COOLING APPLICATIONS
Accessory Crankcase Heater Yes Yes Compressor Start Assist Capacitor and Relay Yes Yes Evaporator Freeze Thermostat Yes No Liquid Line Solenoid Valve No See Long Line Applications Guideline Lowambient Pressure Switch Yes No Support Feet Recommended No Thermal Expansion Valve (TXV) Hard Shutoff Winter Start Control Yes No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Long Line Applications Guideline.
421 01 5104 03 3
Specifications subject to change without notice.
(Below 555F / 12.85C)
Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of fieldsupplied or factoryaccessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.
REQUIRED FOR LONG LINE
APPLICATIONS* (Over 80 ft. / 24.38 m)
Yes Yes
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
RATED VAPOR
LIQUID
Connection and Tube
UNIT SIZE
18, 24, 30, 3/8 3/4 3/4
36, 42, 48 3/8 7/8 7/8
60 3/8 7/8 11/8
* Units are rated with 25 ft. (7.6 m) of lineset. See Specification sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Long Line Applications Guideline.
Diameter
Install Liquid Line Filter Drier Indoor
Connection
Diameter
Evacuate Refrigerant Tubing and Indoor Coil
up to 80 ft. (24.38 m)*
Rated Tube
Diameter
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Installation of filter drier in liquid line is required. Filter drier must be wrapped in a heatsinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid tube. Flow arrow must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
Figure 3
CAUTION
Liquid Line Filter Drier
Refrigerant Tubing Connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2.) Connect and braze the 3/8” coupling (provided with the filter drier) to the liquid service valve and connect and braze the liquid tubing to the other end of this coupling. Use refrigerant grade tubing.
Sweat Connection
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a heat−sinking material such as a wet cloth.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. An alternate triple evacuation method may be used. See triple evacuation method in Service Manual.
IMPORTANT: Always break a vacuum with dry nitrogen.
CAUTION
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 4)
Figure 4
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
Deep Vacuum Graph
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
MINUTES
A95424
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Make Electrical Connections
!
WARNING
Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
4 421 01 5104 03
Specifications subject to change without notice.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not supply power to unit with compressor terminal box cover removed.
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate. Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 44014 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
WARNING
Connect Ground and Power Wires
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24−v/40−va minimum.
NOTE: Use of available 24−v accessories may exceed the minimum 40va power requirement. Determine total transformer load and increase the transformer capacity or split the load with an accessory transformer as required.
Final Wiring Check
IMPORTANT: Check factory wiring and field wire
connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required for lowambient cooling or if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Long Line Applications Guideline Residential Split−System Air Conditioners and Heat Pumps Using R−410A Refrigerant.
Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Check OAT Thermistor and OCT Thermistor Attachments
Outdoor Air Temperature (OAT) Thermistor is factory installed by inserting the nibs on either sides of the thermistor body through a keyhole in the bottom shelf of the control box and locking it in place by turning it 90 degrees, such that the spherical end of a nib faces the front of the control box.
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig. 5.
Figure 5
DISCONNECT PER N. E. C. AND/OR LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
Line Power Connections
CONTACTOR
GROUND LUG
Check to make sure the OAT is locked in place. See Fig. 6.
Figure 6
OAT Thermistor must be locked in place
with spherical nib end facing towards
the front of the control box
Outdoor Air Thermistor (OAT) Attachment
DX+ DX- C R
Connect Control Wiring
Route 24−v control wires through control wiring grommet and connect leads to control wiring. (See Fig. 10 & Fig. 11)
Use No. 18 AWG colorcoded, insulated (35_C minimum) wire. If thermostat is located more than 100 ft. (30.48 m) from unit, as measured along the control voltage wires, use No. 16 AWG colorcoded, insulated wire to avoid excessive voltage drop.
421 01 5104 03 5
Specifications subject to change without notice.
The Outdoor Coil Temperature (OCT) Thermistor is factory installed on the liquid tube between the coil assembly and the liquid service valve. See Fig. 7.
Check to make sure the thermistor is securely attached on the liquid tube with the clip as shown in Fig. 7.
Loading...
+ 9 hidden pages