International Comfort Products CCA924GKA100, HCA924GKA100, TCA924GKA100, CCA936GKA100, HCA936GKA100 User Manual

...
TECHNICAL SUPPORT MANUAL
Two Stage Split System Air Conditioner
(C,H,T)CA9
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
DANGER -- Immediate hazards which will result in severe personal injury or death.
WARNING -- Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION -- Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE -- Used to highlight suggestions which will result in enhanced installation, reliability, or opera­tion.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
WARNING
CAUTION
TABLE OF CONTENTS
Model Number Identification 2--3...................
R--410A Quick Reference Guide 4..................
Wiring Diagram Connection 5......................
Wiring Diagram Schematic 6......................
R--410A Charging Chart 7.........................
Flash Code 7....................................
Tech Labels (Expanded Data) 8--10.................
Cooling Multiplying Factors 1 1--37..................
Physical Data 38.................................
Accessories 39..................................
CCA9,HCA9,TCA9 Parts List 40--41................
Exploded Drawings 42-- 44.........................
MODELS
CCA924GKA100 HCA924GKA100 TCA924GKA100 CCA936GKA100 HCA936GKA100 TCA936GKA100 CCA948GKA100 HCA948GKA100 TCA948GKA100 CCA960GKA100 HCA960GKA100 TCA960GKA100
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons couldresult in equipment malfunction, prop­erty damage, personal injury and/or death.
The information contained in this manual is inten­ded for use by aqualified service technician famili­ar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
421 04 1801 00 February 2012
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)
Digit Position: 1 2 3 4 5, 6 7 8 9 10 11 12
Example Part Number:
HCT C A 9 24 G K A 1 0 0
H = Heil Mainline T = T empstar Mainline H = Arcoaire Mainline C = Comfortmaker Mainline C = Day & Night Mainline H = Airquest Mainline C = Keeprite Mainline C = Kenmore Mainline H = Kenmore Mainline T = Kenmore Mainline H = ICP Commercial Mainline
N = Tempstar Entry BRANDING N = Arcoaire Entry BRANDING N = Comfortmaker Entry BRANDING N = Day & Night Entry BRANDING N = Airquest Entry BRANDING N = Keeprite Entry BRANDING N = Kenmore Entry BRANDING N = Kenmore Entry BRANDING N = Kenmore Entry BRANDING
N = ICP Commercial Entry BRANDING
C = Communicating
CHARACTERISTIC
A = Air Conditioner H = Heat Pump 6 = 16 SEER
7 = 17 SEER 8 = 18 SEER
9 = 19 SEER 24 = 24,000 BTUH = 2 tons
36 = 36,000 BTUH = 3 tons 48 = 48,000 BTUH = 4 tons 60 = 60,000 BTUH = 5 tons
KEY
TYPE
NOMINAL EFFICIENCY
NOMINAL CAPACITY
G = Coil Guard Grille
K = 208/230--1--60
FEATURES
VOLTAGE
Sales Code
Engineering Revision
Extra Digit
Extra Digit
2 421 04 1801 00
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
ACCESSORIES PART NUMBER IDENTIFICATION GUIDE
Digit Position: 1 2 3 4 5 6, 7 8, 9 10, 11
Example Part Number:
N = Non-- Branded
A = Accessory PRODUCT GROUP
S = Split System (AC & HP) KIT USAGE
A = Original
B = 2nd Generation MAJOR SERIES
0 = Generic or Not Applicable
2=R--22
4 = R-- 410A REFRIGERANT
Product Identifier Number
Package Quantity
Type of Kit (Example: CH = Crankcase Heater)
N A S A 0 01 01 CH
421 04 1801 00 3
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
R--410A QUICK REFERENCE GUIDE
R--410A refrigerant operates at 50% -- 70% higher pressures than R--22. Be sure that servicing equipment and replacement components are designed to operate with R--410A.
R--410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R--410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose when charging into suction line with compressor operating.
Manifold sets should be 750 psig high--side and 200 psig low--side with 520 psig low--side retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
R--410A, as with other HFC refrigerants, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquid line filter--driers with rated working pressures less than 600 psig.
Do not install a suction line filter--drier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter--driers and service valves with wet cloth when brazing.
A liquid line filter--drier is required on every unit.
Do not use with an R--22 TXV.
If indoor unit is equipped with an R--22 TXV, it must be changed to an R--410A TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace all filter--driers. Evacuate
to 500 microns before recharging.
Do not vent R--410A into the atmosphere.
Do not use capillary tube indoor coils.
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
International Comfort Products, LLC
Lewisburg, TN 37091 USA
4 421 04 1801 00
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
Model Sizes: 24, 36, 48, 60
421 04 1801 00 5
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
Model Sizes: 24, 36, 48, 60
6 421 04 1801 00
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
R--410A CHARGING CHART
Rating Plate (required) Subcooling Temperature ° F(° C)
Measured Liquid
Pressure (psig)
251 78 26 76 24 74 23 72 22 70 21 68 20 259 80 27 78 26 76 24 74 23 72 22 70 21 266 82 28 80 27 78 26 76 24 74 23 72 22 274 84 29 82 28 80 27 78 26 76 24 74 23 283 86 30 84 29 82 28 80 27 78 26 76 24 291 88 31 86 30 84 29 82 28 80 27 78 26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 42 106 41 104 40 102 39 100 38 98 37 395 110 43 108 42 106 41 104 40 102 39 100 38 406 112 44 11 0 43 108 42 106 41 104 40 102 39 416 114 46 11 2 44 11 0 43 108 42 106 41 104 40 427 116 47 11 4 46 11 2 44 110 43 108 42 106 41 439 118 48 11 6 47 11 4 46 112 44 11 0 43 108 42 450 120 49 118 48 11 6 47 11 4 46 11 2 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 11 4 46
° F (° C) ° F (° C) ° F (° C) ° F (° C) F (° C) F (° C)
6 3 8 4 10 6 12 7 14 8 16 9
R-- 410A Required Liquid Line Temperature ° F(° C)
FLASH CODE
On, No Flash
1, Pause
2, Pause
Continuous Flash
16
25
31
32
45
46
47
Short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the status code.
This control board contains a five minute short cycle protector. A five minute delay will occur between compressor off/on cycles. To bypass delay, short forced defrost pins for 1 second then release. The crankcase heater is energized during off cycle below 65ºF.
FAULT DEFINITION
Standby
Low Stage
High Stage
Emergency Mode
System Communications Failure
Invalid Model Plug
High Pressure Switch Trip
Low Pressure Switch Trip
Control Fault
Brown out (230V)
No 230v with Call to Run
UNIT OPERATION
FLASH CODE
53
55
56
71
72
73
74
81
82
83
84
FAULT DEFINITION
Outdoor Air Temp Sensor
Coil Temp Sensor Temp Sensor Range Error
Low Stage Thermal Cutout
High Stage Thermal Cutout
Contactor Shorted
Contactor Open (No 230v to Comp)
Low Stage Thermal Lockout (4 HRS)
High Stage Thermal Lockout (4 HRS)
Low Pressure Lockout (4 HRS)
High Pressure Lockout (4 HRS)
421 04 1801 00 7
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 ° Fdb
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
^ System amps are total of indoor and outdoor amps.
‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the
formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula
below.
(Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.).05
Sensible Capacity at Indoor db LOWER than 80 ° F=(MBhxS/T) --
Sensible Capacity at Indoor db HIGHER than 80 ° F=(MBhxS/T) +
( 80 -- Indoor db ) x 835 x In­door CFM
(
( Indoor db -- 80 ) x 835 x In-
(
door CFM
1000
1000
) )
8 421 04 1801 00
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
421 04 1801 00 9
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
10 421 04 1801 00
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
POWER FURNACE MODEL
LOW
SPEED
CAPACITY
POWER
HIGH
SPEED
CAPACITY
MODEL
COOLING INDOOR
(C,H,T)CA9 24
POWER FURNACE MODEL
COOLING Multiplying Factors for other Indoor Combinations 33
LOW
SPEED
CAPACITY
POWER
HIGH
SPEED
CAPACITY
MODEL
*FCM4X48**** 1.00 1.00 1.00 1.00 EN(A,D)4X24*17** 0.95 1.02 0.95 1.06 *9MA*0801714A**
EA*4X24*14A* 0.97 1.02 0.96 1.04 *8MV*0701412** EN(A,D)4X24*17** 0.93 1.06 0.9 1.01 *9MV*0401410A**
EA*4X24*14A* 0.94 1.02 0.92 0.98 *8MX*0451408** EN(A,D)4X24*17** 0.94 1.02 0.92 0.99 *9MV*0601714A**
EA*4X24*14A* 0.94 1.06 0.91 1.02 *9MV*0401410A** EN(A,D)4X24*17** 0.94 1.01 0.92 0.98 *9MV*0801716A**
EA*4X24*14A* 0.94 1.12 0.92 1.17 EN(A,D)4X24*17** 0.94 1.10 0.9 1.00 *9MX*0401410A**
EA*4X24*17A* 0.97 1.02 0.97 1.04 *8MV*0701412** EN(A,D)4X24*17** 0.97 1.08 0.95 1.02 *9MX*0601714A**
EA*4X24*17A* 0.97 1.02 0.97 1.02 *8MV*0901716** EN(A,D)4X24*17** 0.95 1.00 0.92 0.95 MV08B15**B*
EA*4X24*17A* 0.95 1.02 0.92 0.98 *8MX*0451408** EN(A,D)4X24*17** 0.97 1.08 0.91 0.96 OLV098A12A
EA*4X24*17A* 0.95 1.04 0.95 1.06 *9MA*0601714A** EN(A,D)4X24*17** 0.95 1.04 0.91 0.96 OMV098J12A
EA*4X24*17A* 0.95 1.02 0.95 1.04 *9MA*0801714A** EN(A,D)4X24*17** 0.97 1.06 0.97 1.03 OMV112K14A
EA*4X24*17A* 0.94 1.06 0.91 1.02 *9MV*0401410A** EN(A,D)4X24*17** 0.94 1.12 0.92 1.16
EA*4X24*17A* 0.94 1.01 0.93 0.99 *9MV*0601714A** EN(A,D)4X30*14** 0.98 1.03 0.97 1.05 *8MV*0701412**
EA*4X24*17A* 0.94 1.02 0.93 0.98 *9MV*0801716A** EN(A,D)4X30*14** 0.95 1.02 0.92 0.98 *8MX*0451408**
EA*4X24*17A* 0.94 1.10 0.9 0.99 *9MX*0401410A** EN(A,D)4X30*14** 0.94 1.06 0.91 1.02 *9MV*0401410A**
EA*4X24*17A* 0.97 1.06 0.95 1.01 *9MX*0601714A** EN(A,D)4X30*14** 0.95 1.11 0.9 0.99 *9MX*0401410A**
EA*4X24*17A* 0.95 0.99 0.92 0.94 MV08B15**B* EN(A,D)4X30*14** 0.95 1.13 0.92 1.17
EA*4X24*17A* 0.97 1.06 0.9 0.95 OLV098A12A EN(A,D)4X30*17** 0.98 1.03 0.97 1.03 *8MV*0701412**
EA*4X24*17A* 0.95 1.02 0.91 0.95 OMV098J12A EN(A,D)4X30*17** 0.98 1.01 0.97 1.01 *8MV*0901716**
EA*4X24*17A* 0.98 1.05 0.97 1.01 OMV112K14A EN(A,D)4X30*17** 0.96 1.03 0.93 0.98 *8MX*0451408**
EA*4X24*17A* 0.94 1.12 0.92 1.17 EN(A,D)4X30*17** 0.96 1.03 0.95 1.05 *9MA*0601714A**
EA*4X30*14A* 0.98 1.03 0.97 1.04 *8MV*0701412** EN(A,D)4X30*17** 0.96 1.03 0.96 1.04 *9MA*0801714A**
EA*4X30*14A* 0.95 1.02 0.92 0.98 *8MX*0451408** EN(A,D)4X30*17** 0.94 1.07 0.91 1.01 *9MV*0401410A**
COOLING INDOOR
EA*4X30*14A* 0.94 1.06 0.91 1.02 *9MV*0401410A** EN(A,D)4X30*17** 0.95 1.02 0.93 0.99 *9MV*0601714A**
421 04 1801 00 11
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
FURNACE MODELPOWER
LOW
SPEED
CAPACITY
POWER
COOLING Multiplying Factors for other Indoor Combinations (continued)33
HIGH
LOW
SPEED
MODEL
COOLING INDOOR
FURNACE MODELPOWER
SPEED
CAPACITY
CAPACITY
POWER
HIGH
SPEED
CAPACITY
MODEL
EA*4X30*14A* 0.95 1.11 0.9 0.99 *9MX*0401410A** EN(A,D)4X30*17** 0.95 1.00 0.94 0.99 *9MV*0801716A**
EA*4X30*14A* 0.95 1.13 0.92 1.17 EN(A,D)4X30*17** 0.95 1.11 0.90 0.99 *9MX*0401410A**
EA*4X30*17A* 0.98 1.03 0.97 1.03 *8MV*0701412** EN(A,D)4X30*17** 0.98 1.08 0.95 1.02 *9MX*0601714A**
EA*4X30*17A* 0.98 1.01 0.97 1.01 *8MV*0901716** EN(A,D)4X30*17** 0.96 1.00 0.92 0.94 MV08B15**B*
EA*4X30*17A* 0.96 1.03 0.93 0.98 *8MX*0451408** EN(A,D)4X30*17** 0.98 1.05 0.91 0.95 OLV098A12A
EA*4X30*17A* 0.96 1.03 0.95 1.05 *9MA*0601714A** EN(A,D)4X30*17** 0.96 1.03 0.91 0.95 OMV098J12A
EA*4X30*17A* 0.96 1.01 0.95 1.03 *9MA*0801714A** EN(A,D)4X30*17** 0.98 1.04 0.97 1,00 OMV112K14A
EA*4X30*17A* 0.94 1.07 0.91 1.02 *9MV*0401410A** EN(A,D)4X30*17** 0.95 1.13 0.92 1.17
EA*4X30*17A* 0.95 1.02 0.93 0.99 *9MV*0601714A** EN(A,D)4X31*17** 0.99 1.03 0.99 1.03 *8MV*0701412**
EA*4X30*17A* 0.95 1.00 0.94 0.99 *9MV*0801716A** EN(A,D)4X31*17** 1.00 1.01 1.00 1.02 *8MV*0901716**
EA*4X30*17A* 0.95 1.11 0.9 0.99 *9MX*0401410A** EN(A,D)4X31*17** 0.98 1.03 0.95 0.98 *8MX*0451408**
EA*4X30*17A* 0.98 1.08 0.95 1.02 *9MX*0601714A** EN(A,D)4X31*17** 0.98 1.04 0.98 1.05 *9MA*0601714A**
EA*4X30*17A* 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D)4X31*17** 0.98 1.02 0.98 1.03 *9MA*0801714A**
EA*4X30*17A* 0.98 1.05 0.9 0.94 OLV098A12A EN(A,D)4X31*17** 0.97 1.06 0.93 1.02 *9MV*0401410A**
EA*4X30*17A* 0.96 1.03 0.91 0.95 OMV098J12A EN(A,D)4X31*17** 0.97 1.02 0.95 0.99 *9MV*0601714A**
EA*4X30*17A* 0.98 1.04 0.97 1.00 OMV112K14A EN(A,D)4X31*17** 0.98 1.01 0.96 1.00 *9MV*0801716A**
EA*4X30*17A* 0.95 1.13 0.92 1.17 EN(A,D)4X31*17** 0.98 1.11 0.92 0.99 *9MX*0401410A**
EA*4X36*14A* 0.98 1.03 0.97 1.04 *8MV*0701412** EN(A,D)4X31*17** 1.01 1.08 0.97 1.02 *9MX*0601714A**
EA*4X36*14A* 0.96 1.03 0.93 0.98 *8MX*0451408** EN(A,D)4X31*17** 0.98 0.99 0.94 0.94 MV08B15**B*
EA*4X36*14A* 0.94 1.07 0.91 1.01 *9MV*0401410A** EN(A,D)4X31*17** 1.00 1.05 0.92 0.94 OLV098A12A
EA*4X36*14A* 0.96 1.12 0.9 0.99 *9MX*0401410A** EN(A,D)4X31*17** 0.98 1.03 0.93 0.95 OMV098J12A
EA*4X36*14A* 0.95 1.13 0.92 1.16 EN(A,D)4X31*17** 1.01 1.04 0.99 1.00 OMV112K14A
EA*4X36*17A* 0.98 1.01 0.97 1.03 *8MV*0701412** EN(A,D)4X31*17** 0.98 1.14 0.94 1.16
COOLING INDOOR
EA*4X36*17A* 0.98 1.01 0.97 1,00 *8MV*0901716** EN(A,D)4X36*21** 0.98 1.01 0.97 1.01 *8MV*0901716**
12 42104180100
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
FURNACE MODELPOWER
LOW
SPEED
CAPACITY
POWER
COOLING Multiplying Factors for other Indoor Combinations (continued)33
HIGH
LOW
SPEED
MODEL
COOLING INDOOR
FURNACE MODELPOWER
SPEED
CAPACITY
CAPACITY
POWER
HIGH
SPEED
CAPACITY
MODEL
EA*4X36*17A* 0.96 1.01 0.93 0.98 *8MX*0451408** EN(A,D)4X36*21** 0.98 1.01 0.97 1.02 *8MV*1102120**
EA*4X36*17A* 0.96 1.03 0.96 1.05 *9MA*0601714A** EN(A,D)4X36*21** 0.96 1.03 0.95 1.05 *9MA*0601714A**
EA*4X36*17A* 0.97 1.02 0.96 1.03 *9MA*0801714A** EN(A,D)4X36*21** 0.96 1.03 0.96 1.05 *9MA*0602120A**
EA*4X36*17A* 0.94 1.06 0.92 1.02 *9MV*0401410A** EN(A,D)4X36*21** 0.96 1.01 0.96 1.04 *9MA*0801714A**
EA*4X36*17A* 0.95 1.02 0.94 0.99 *9MV*0601714A** EN(A,D)4X36*21** 0.97 1.02 0.96 1.02 *9MA*0802120A**
EA*4X36*17A* 0.96 1.01 0.95 0.99 *9MV*0801716A** EN(A,D)4X36*21** 0.97 1.02 0.96 1.02 *9MA*1002122A**
EA*4X36*17A* 0.96 1.12 0.91 0.99 *9MX*0401410A** EN(A,D)4X36*21** 0.95 1.02 0.93 0.99 *9MV*0601714A**
EA*4X36*17A* 0.98 1.08 0.95 1.01 *9MX*0601714A** EN(A,D)4X36*21** 0.95 1.00 0.94 0.99 *9MV*0801716A**
EA*4X36*17A* 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D)4X36*21** 0.98 1.08 0.95 1.02 *9MX*0601714A**
EA*4X36*17A* 0.98 1.06 0.91 0.95 OLV098A12A EN(A,D)4X36*21** 0.96 1,00 0.92 0.95 MV12F19**B*
EA*4X36*17A* 0.96 1.03 0.92 0.95 OMV098J12A EN(A,D)4X36*21** 0.98 1.05 0.91 0.95 OLV098A12A
EA*4X36*17A* 0.98 1.02 0.97 0.99 OMV112K14A EN(A,D)4X36*21** 0.96 1.03 0.91 0.95 OMV098J12A
EA*4X36*17A* 0.95 1.13 0.92 1.16 EN(A,D)4X36*21** 0.98 1.04 0.97 1.00 OMV112K14A
EA*4X36*21A* 0.98 1.01 0.98 1.01 *8MV*0901716** EN(A,D)4X36*21** 0.95 1.13 0.92 1.17
EA*4X36*21A* 0.98 1.01 0.98 1.01 *8MV*1102120** EN(A,D)4X37*17** 1.01 1.02 1.01 1.03 *8MV*0701412**
EA*4X36*21A* 0.97 1.04 0.96 1.04 *9MA*0601714A** EN(A,D)4X37*17** 1.01 1.02 1.01 1.01 *8MV*0901716**
EA*4X36*21A* 0.97 1.02 0.96 1.03 *9MA*0602120A** EN(A,D)4X37*17** 0.99 1.03 0.95 0.98 *8MX*0451408**
EA*4X36*21A* 0.97 1.02 0.96 1.02 *9MA*0801714A** EN(A,D)4X37*17** 0.99 1.03 0.99 1.05 *9MA*0601714A**
EA*4X36*21A* 0.97 1.00 0.96 1.01 *9MA*0802120A** EN(A,D)4X37*17** 0.99 1.03 0.99 1.03 *9MA*0801714A**
EA*4X36*21A* 0.97 1.00 0.96 1.00 *9MA*1002122A** EN(A,D)4X37*17** 0.98 1.07 0.95 1.02 *9MV*0401410A**
EA*4X36*21A* 0.96 1.01 0.95 1.00 *9MV*0601714A** EN(A,D)4X37*17** 0.98 1.02 0.96 1.00 *9MV*0601714A**
EA*4X36*21A* 0.97 1.02 0.95 1.00 *9MV*0801716A** EN(A,D)4X37*17** 0.99 1.03 0.97 0.99 *9MV*0801716A**
EA*4X36*21A* 0.96 1.00 0.92 0.95 MV12F19**B* EN(A,D)4X37*17** 0.98 1.10 0.93 0.99 *9MX*0401410A**
COOLING INDOOR
EA*4X36*21A* 0.98 1.06 0.91 0.95 OLV098A12A EN(A,D)4X37*17** 1.02 1.07 0.99 1.02 *9MX*0601714A**
421 04 1801 00 13
TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)CA9
FURNACE MODELPOWER
LOW
SPEED
CAPACITY
POWER
COOLING Multiplying Factors for other Indoor Combinations (continued)33
HIGH
LOW
SPEED
MODEL
COOLING INDOOR
FURNACE MODELPOWER
SPEED
CAPACITY
CAPACITY
POWER
HIGH
SPEED
CAPACITY
MODEL
COOLING INDOOR
EA*4X36*21A* 0.96 1.01 0.92 0.95 OMV098J12A EN(A,D)4X37*17** 0.98 0.98 0.95 0.94 MV08B15**B*
EA*4X36*21A* 0.99 1.03 0.97 0.98 OMV112K14A EN(A,D)4X37*17** 1.01 1.04 0.93 0.94 OLV098A12A
EA*4X36*21A* 0.95 1.13 0.92 1.16 EN(A,D)4X37*17** 0.98 1.02 0.94 0.95 OMV098J12A
ED*4X24F** 0.95 0.99 0.92 0.94 MV08B15**B* EN(A,D)4X37*17** 0.98 1.15 0.95 1.16
ED*4X24B** 0.95 1.00 0.92 0.95 MV08B15**B* EN(A,D)4X37*17** 1.02 1.03 1.01 1.00 OMV112K14A
ED*4X24F** 0.95 0.99 0.92 0.96 MV12F19**B* EN(A,D,W)4X36*17** 0.98 1.03 0.97 1.03 *8MV*0701412**
ED*4X30F** 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D,W)4X36*17** 0.96 1.03 0.93 0.98 *8MX*0451408**
ED*4X30B** 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D,W)4X36*17** 0.98 1.01 0.97 1.01 *8MV*0901716**
ED*4X30F** 0.96 1.00 0.92 0.96 MV12F19**B* EN(A,D,W)4X36*17** 0.96 1.03 0.95 1.05 *9MA*0601714A**
ED*4X36B** 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D,W)4X36*17** 0.96 1.03 0.96 1.04 *9MA*0801714A**
ED*4X36F** 0.98 1.01 0.97 1.00 *8MV*0901716** EN(A,D,W)4X36*17** 0.94 1.07 0.91 1.01 *9MV*0401410A**
ED*4X36F** 0.98 1.01 0.97 1.01 *8MV*1102120** EN(A,D,W)4X36*17** 0.95 1.02 0.93 0.99 *9MV*0601714A**
ED*4X36F** 0.96 1.03 0.96 1.05 *9MA*0601714A** EN(A,D,W)4X36*17** 0.95 1.00 0.94 0.99 *9MV*0801716A**
ED*4X36F** 0.97 1.02 0.96 1.03 *9MA*0801714A** EN(A,D,W)4X36*17** 0.95 1.11 0.9 0.99 *9MX*0401410A**
ED*4X36F** 0.95 1.02 0.94 0.99 *9MV*0601714A** EN(A,D,W)4X36*17** 0.98 1.08 0.95 1.02 *9MX*0601714A**
ED*4X36F** 0.96 1.01 0.95 0.99 *9MV*0801716A** EN(A,D,W)4X36*17** 0.96 1.00 0.92 0.94 MV08B15**B*
ED*4X36F** 0.98 1.08 0.95 1.01 *9MX*0601714A** EN(A,D,W)4X36*17** 0.98 1.05 0.91 0.95 OLV098A12A
ED*4X36F** 0.96 1.00 0.92 0.94 MV08B15**B* EN(A,D,W)4X36*17** 0.96 1.03 0.91 0.95 OMV098J12A
ED*4X36F** 0.96 1.00 0.92 0.95 MV12F19**B* EN(A,D,W)4X36*17** 0.98 1.04 0.97 1.00 OMV112K14A
ED*4X36F** 0.98 1.06 0.91 0.95 OLV098A12A EN(A,D,W)4X36*17** 0.95 1.13 0.92 1.17
ED*4X36F** 0.96 1.03 0.92 0.95 OMV098J12A ENH4X24*17** 0.97 1.04 0.97 1.06 *8MV*0701412**
ED*4X36F** 0.98 1.02 0.97 0.99 OMV112K14A ENH4X24*17** 0.97 1.02 0.97 1.04 *8MV*0901716**
ED*4X36J** 0.96 1.00 0.92 0.95 MV12F19**B* ENH4X24*17** 0.97 1.02 0.97 1.04 *8MV*1352422**
ED*4X36F** 0.95 1.13 0.92 1.16 ENH4X24*17** 0.97 1.04 0.97 1.06 *8MV*1102120**
14 42104180100