International Comfort Products RHS Installation Manual

INSTALLATION INSTRUCTIONS
R410A Single Package Rooftop Heat Pumps
RHS181 243
These instructions must be read and understood completely before attempting installation
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliablility, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2..................
INSTALLATION 6..............................
Step 1 Plan for Unit Location 6.................
Step 2 Plan for Sequence of Unit Installation 7...
Step 3 Inspect Unit 7.........................
Step 4 Provide Unit Support 7..................
Step 5 Field Fabricate Ductwork 10..............
Step 6 Rig and Place Unit 10...................
Step 7 Duct Connection 10.....................
Step 8 Install Outside Air Hood 11...............
Step 9 Install External condensate Trap &
Piping 12...............................
Step 10 Make Electrical Connections 13..........
Step 11 Adjust FactoryInstalled Options 19......
Step 12 Install Accessories 19..................
Unit Wire/Fuse or HACR Breaker Sizing Data 21....
Typical Wiring Diagrams 24......................
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments.
Installation must conform with local building codes and with the national Electrical Code NFPA70 current edition or Canadian Electrical Code part 1 CSA C.22.1.
516 01 2601 01 01−04−11
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
R410A refrigerant systems operate at higher pressures than standard R−22 systems. Do not use R−22 service equipment or components on R−410A refrigerant equipment.
Recognize safety information. This is the safety−alert symbol . When you see this symbol in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in serious injury or death. WARNING signifies a hazard which could result in serious injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
!
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Ware safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning units.
CAUTION
2
516 01 2601 01
FIGURE 1 RHS Base Unit Dimensions: 15 Ton
Connection Sizes
A 1-3/8” [35] DIA Field Power Supply Hole B 3” [76] Field Power Supply Knockout C 3-5/8” [92] Field Power Supply Knockout D 7/8” [22] Field Control Wiring Hole E 3/4” 14 NPT Condensate Drain
516 01 2601 01
3
Fig. 1 − Unit Dimensional Drawing − 15 Ton
Unit Size
RHS 15 Ton 2156 980 581 264 442 201 489 222 643 292 45-1/4 [1149] 55-1/2 [1405] 16-1/2 [419]
Base Unit Weight
LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z
Corner WeightACorner WeightBCorner Weight
C
Corner Weight
D
Center of Gravity
4
516 01 2601 01
FIGURE 2 RHS Base Unit Dimensions: 20 Ton
Connection Sizes
A 1-3/8” [35] DIA Field Power Supply Hole B 3” [76] Field Power Supply Knockout C 3-5/8” [92] Field Power Supply Knockout D 7/8” [22] Field Control Wiring Hole E 3/4” 14 NPT Condensate Drain
516 01 2601 01
5
Fig. 2 − Unit Dimensional Drawing − 20 Ton
Unit Size
RHS 20 Ton 2200 998 633 288 609 277 607 276 631 287 43 [1092] 69-1/2 [1765] 16-1/2 [419]
Base Unit Weight
LBS. KG. LBS. KG. LBS. KG. LBS. KG. LBS. KG. X Y Z
Corner WeightACorner WeightBCorner Weight
C
Corner Weight
D
Center of Gravity
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installation requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 3.
6
FIGURE 3
Service Clearance Dimansional Drawing
36" (914)
42" (1067)
18" (457)
NOTE:Consider also the effect of adjacent units.
516 01 2601 01
42" (1067)
Unit may be installed directly on wood flooring or on Class A, B, or C roof−covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 9 — Install External Trap for Condensate Drain – for required trap dimensions.
Roof mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curbmounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curbmounted installation —
Install roof curb Install fieldfabricated ductwork inside curb Install accessory thru−base service connection package, if
used, (affects curb and unit) Rig and place unit Remove top skid Install condensate line trap and piping Make electrical connections Install other accessories
Padmounted installation —
Prepare pad and unit supports Rig and place unit Remove duct covers and top skid Install fieldfabricated ductwork at unit duct openings Install condensate line trap and piping Make electrical connections Install other accessories
Framemounted installation —
Framemounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 4 (15 ton units) and Fig. 5 (20 ton units). Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE:The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 4 and Fig. 5. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 6. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the
unit. The accessory thru−the−base power and gas connection package must be installed before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan remove knockouts in basepan located in control box area, see Fig. 7 for location. Attach the service connections to the basepans.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE:Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (In Lieu of Curb or Slab Mount) —
A non−combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 4in. x 4in. (102 mm x 102 mm) pads on each side. Locate pads so that they support the rails. Make sure to avoid the fork openings.
Table 1—Operating Weights
UNITS LB (KG)
Component 15 Ton 20 Ton Base Unit 2035 [923] 2200 [998] Economizer 245 [111] 245 [111] Curb 14in/356 mm 243 [111] 273 [124] 24in/610 mm 315 [143] 350 [159]
516 01 2601 01
7
FIGURE 4
RoofCurb Accessory A Unit Size
CRRFCURB045A00 1' 2 “ [356] CRRFCURB046A00 2' 0” [610]
Roof Curb Details RHS
15 Ton
8
516 01 2601 01
Loading...
+ 17 hidden pages