International comfort products RGS036 Series, RGS048 Series, RGS060 Series, RGS072 Series Installation Instructions Manual

INSTALLATION INSTRUCTIONS
R--410A Single--Package Rooftop Gas Heating /
Electric Cooling
RGS036--072
NOTE: Read the entire instruction manual before starting the installation
SAFETY CONSIDERATIONS 2....................
Rated Indoor Airflow (cfm) 3.....................
INSTALLATION 6...............................
Jobsite Survey 6................................
Step 1 -- Plan for Unit Location 6..................
Roof Mount 7...............................
Step 2 -- Plan for Sequence of Unit Installation 7......
Curb--Mount Installation 7.....................
Pad--Mount Installation 7......................
Frame--Mount Installation 7....................
Step 3 -- Inspect Unit 7...........................
Step 4 -- Provide Unit Support 8...................
Roof Curb Mount 8..........................
Slab Mount (Horizontal Units Only) 8...........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 8..............
Step 5 -- Field Fabricate Ductwork 10...............
Step 6 -- Rig and Place Unit 10....................
Positioning on Curb 11.......................
Step 7 -- Convert to Horizontal & Connect Ductwork 11.
Step 8 -- Install Outside Air Hood 11...............
Economizer and Two Position Damper Hood
Package Removal and Setup — Factory Option 11.
Economizer Hood and Two--Position Hood 12.....
Step 9 -- Install Flue Hood 12.....................
Step 10 -- Install Gas Piping 12....................
Factory--Option Thru--Base Connections
(Gas Connections) 13.........................
Step 11 -- Install External Condensate Trap and Line 15..
Step 12 -- Make Electrical Connections 16...........
Field Power Supply 16........................
Units with Factory--Installed
Non--Fused Disconnect 16.....................
Units without Factory--Installed
Non--Fused Disconnect 17.....................
All Units 17................................
Convenience Outlets 18.......................
Factory--Option Thru--Base Connections
(Electrical Connections) 18....................
Units without Thru--Base Connections 18.........
Field Control Wiring 19.......................
Thermostat 19...............................
Unit without Thru--Base Connection Kit 19.......
Heat Anticipator Settings 19...................
EconoMi$er X (Factory--Installed Option) 19.......
Hot Gas Re--Heat Control Connections 20..........
Hot Gas Re--Heat -- Space RH Controller 20......
Smoke Detectors 22...........................
Step 13 -- Adjust Factory--Installed Options 25........
Step 14 -- Install Accessories 25...................
START--UP CHECKLIST 27.......................
Specifications are subject to change without notice.
509 01 3522 00 03/2015
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA 70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
. When you see this symbol on the
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
R--410A refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on R--410A refrigerant equipment.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
CAUTION
2 509 01 3522 00
Specifications are subject to change without notice.
Rated Indoor Airflow (cfm)
The table to the right lists the rated indoor airflow used for the AHRI efficiency rating for the units covered in this document.
Model Number Full Load Airflow (cfm)
RGS036 1275
RGS048 1400
RGS060 1800
RGS072 2200
MODEL NOMENCLATURE
MODEL SERIES RGS0 3 6HDAA0AAA
Position Number
R = Rooftop
12345678910111213
14
G = Gas/Electric
S = Standard ASHRAE 90.1-2010 Efficiency
036 = 3 Tons 048 = 4 Tons 060 = 5 Tons 072 = 6 Tons
K = 208/230−1−60 H = 208/230−3−60 L = 460−3−60 S = 575−3−60
D = Low Heat S = Low Heat, Stainless Steel Heat Exchanger E = Medium Heat R = Medium Heat, Stainless Steel Heat Exchanger F = High Heat T = High Heat, Stainless Steel Heat Exchanger L = Low Heat, Low NO M = Medium Heat, Low NO N = High Heat, Low NO
A = Belt Drive, Standard Static Motor B = Belt Drive, High Static Motor C = Belt Drive, Medium Static Motor X = Direct Drive, Standard Static (3, 4, and 5 ton models only)
A = None B = Economizer w/Baro−relief, OA Temp sensor E = Economizer w/Baro−relief + CO H = Economizer w/Baro−relief, enthalpy sensor L = Economizer w/Baro−relief + CO U = Temp Ultra Low Leak Economizer w/Baro−relief W = Enthalpy Ultra Low Leak Economizer w/Baro−relief P = 2−Position damper
x
x
x
Sensor, OA Temp sensor
2
Sensor, enthalpy sensor
2
Type
Efficiency
Nominal Cooling Capacity
Voltage
Heating Capacity
Motor Option (Indoor Fan)
Outdoor Air Options / Control
0A = No Options AT = Non−powered 115v C.O. 4B = Non−Fused Disconnect BR = Supply Air Smoke Detector AA = Easy Access Hinged Panels Factory Installed Options
A = Aluminum / Copper Cond & Evap Coil B = Precoat Alum/Copper Cond with Alum / Copper Evap (3 phase only) C = E−Coated Alum/Copper Cond with Alum / Copper Evap (3 phase only) D = E−Coated Alum / Copper Cond & Evap (3 phase only) E = Copper/Copper Cond & Alum/Copper Evap (3 phase only) F = Copper/Copper Cond & Evap (3 phase only) Condenser / Evaporator Coil Configuration
A = Standard Single Speed Indoor Fan Motor. For W7212 Controls B = Standard Single Speed Indoor Fan Motor. For W7220 Controls Motor Type Option
NOTE: Factory installed options are NOT available on single phase models. This includes economizers and 2 position dampers.
1
Combinations of FIOPS are available.
509 01 3522 00 3
1
C150163
Specifications are subject to change without notice.
Fig. 1 -- Unit Dimensional Drawing
C150164
4 509 01 3522 00
Specifications are subject to change without notice.
Fig. 1 -- Unit Dimensional Drawing (cont.)
C150165
509 01 3522 00 5
Specifications are subject to change without notice.
C
D
B
A
LOCATION DIMENSION CONDITION
48---in (1219 mm)
A
B
C
D
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application
18---in (457 mm) 18---in (457) mm 12---in (305 mm)
42---in (1067 mm) 36---in (914 mm) Special
36---in (914 mm) 18---in (457 mm)
48---in (1219 mm) 42---in (1067 mm) 36---in (914 mm Special
planning overhead obstruction or for vertical clearances.
Unit disconnect is mounted on panel No disconnect, convenience outlet option Recommended service clearance Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Check sources of flue products within 10 --- ft of unit fresh air intake hood
Side condensate drain is used Minimum clearance
No flue discharge accessory installed, surface is combustible material Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass) Check for adjacent units or building fresh air intakes within 10--- ft of this unit’s flue outlet
Fig. 2 -- Service Clearance Dimensional Drawing
C08337
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units.
6 509 01 3522 00
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is used.
Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA----54----84----1. In Canada, installation must be in accordance with the CAN1----B149 installation codes for gas burning appliances.
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Specifications are subject to change without notice.
Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.
Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted Installation —
Install curb Install field--fabricated ductwork inside curb Install accessory thru--base service connection package
(affects curb and unit) (refer to accessory installation instructions for details)
Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 11 for details)
Rig and place unit Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted Installation —
Prepare pad and unit supports Check and tighten the bottom condensate drain
connection plug Rig and place unit Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted Installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Table 1 – Operating Weights
RGS
Base Unit 483 (219) 537 (244) 569 (258) 652 (296)
Economizer
Vertical 50 (23) 50 (23) 50 (23) 50 (23)
Horizontal 80 (36) 80 (36) 80 (36) 80 (36)
Hot Gas Re ---Heat System N/A N/A N/A 41 (15)
Cu Fins 25 (11) 43 (20) 56 (25) 73 (33)
Unpowered Outlet 32 (15) 32 (15) 32 (15) 32 (15)
Curb
14---in/356 mm 110 (50) 110 (50) 110 (50) 110 (50)
24---in/610 mm 145 (66) 145 (66) 145 (66) 145 (66)
036 048 060 072
UNITS LB (KG)
509 01 3522 00 7
Specifications are subject to change without notice.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 4. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 4. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 3. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
Fig. 3 -- Unit Leveling Tolerances
B-C
1.0” (25)
A-C
1.0” (25)
C06110
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit. The accessory thru--the--base power and gas connection package must be installed before the unit is set on the roof curb. If field--installed thru--the--roof
curb gas connections are desired, use factory--supplied
1
/2--in. pipe coupling and gas plate assembly to mount the thru--the--roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the basepan, attach the accessory thru--the--base service connections to the basepan in accordance with the accessory installation instructions.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (InLieuofCurborSlabMount)—
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.
8 509 01 3522 00
Specifications are subject to change without notice.
1-3/4"
[44.4]
(004-007)
B
ACCESSORY CONVENIENCE
OUTLET WIRING CONNECTOR
FITTING
1/2" [12.7] NPT 1/2" [12.7] NPT
CONTROL WIRING
FITTING
3/4" [19] NPT
POWER WIRING
1/2" [12.7] NPTCRRFCURB002A01
THRU THE CURB
CRBTMPWR003A01 THRU THE BOTTOM
CRBTMPWR001A01 3/4" [19] NPT
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
1-3/4"
[44.5]
11 3/4"[298.5] WIDE
INSULATED DECK PANELS
1.00"
[25.4]
"A"
SEE NOTE #2
2-3/8"
[61]
1' 4-13/16"
[427] INSIDE
8 9/16"[217.5] WIDE
INSULATED DECK PANEL
GAS SERVICE PLATE
THRU THE CURB
1-3/4"
[44.4]
E-E
SCALE 0.250
SECTION
DRILL HOLE
2" [50.8] @
ASSEMBLY (IF
REQUIRED)
(SEE NOTE #8)
RETURN AIR
1-3/4"
[44.5]
SUPPLY AIR
[1711.3]
5' 7-3/8"
"A"
NAIL (FIELD SUPPLIED)
TYPICAL (4) SIDES
UNIT
[944.6]
3'-1 3/16"
SEE VIEW "B"
ROOFING FELT
COUNTER FLASHING
(FIELD SUPPLIED)
7/16"
[11]
CURB ASY, ROOF
THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN
IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT
BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART,
WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
1041738
TOLERANCES ON:
AUTHORIZATION NUMBER TITLE
DIMENSIONS ARE IN INCHES
----
UNLESS OTHERWISE SPECIFIED
1 DEC 2 DEC 3 DEC ANG
PRODUCTION
CERTIFIED DRAWING
---
MATERIAL
DRAWING RELEASE LEVEL:
THIRD ANGLE
PROJECTION
ROOFING MATERIAL
(FIELD SUPPLIED)
CANT STRIP
(FIELD SUPPLIED)
(FIELD SUPPLIED)
RIGID INSULATION
SHEET 5 OF 5
48TC400427
SIZE DRAWING NUMBER REV
D
-
-
-
DRAFTER CHECKER
ENGINEERING MANUFACTURING
-
MMC 06/17/11 - -
-
T-005, Y-002
WEIGHT:
- PURCH - N/A MMC
ENGINEERING REQUIREMENTS
SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION
ECN NO.APP'DCHK'DBYDATEREVISION RECORDREV
1067898--MMC04/22/13
(FIELD SUPPLIED)
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
7. DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
A
14"
ROOF CURB
ACCESSORY #
CRRFCURB001A01
[356]
24"
[610]
11.96"
5.42"
[303.8]
[137.7]
21.74" [552.2]
VIEW "B"
CORNER DETAIL
70.87" [1800.2]
32.19" [817.6]
E
E
RETURN AIR
4.96" [126.0]
OPENING
1/3/4"[44.5]
15.19" [385.8]
21.84"
3.00"
[554.7]
[76.2]
16.03" [407.2]
SUPPLY AIR
OPENING
14.00" [355.6]
Fig. 4 -- Roof Curb Details
DUCT
GASKET
(FIELD SUPPLIED)
(SUPPLIED WITH CURB)
13.78" [350.0]
3.00"
[76.2]
40.69" [1033.5]
20.41" [518.3]
1.75" [44.5]
OVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GA
MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS
WITH CURB
A
SUPPLY AIR RETURN AIR
1/4"
[7.0]
[115.5]
4 9/16"
C13310
509 01 3522 00 9
Specifications are subject to change without notice.
Loading...
+ 19 hidden pages