International comfort products PH55 Series, PYPA Series Installation Instructions Manual

DIRECT DRIVE BLOWER
PH55/PYPA SERIES
THREE PHASE
SINGLE PACKAGE HEAT
PUMPS
ELECTRIC HEAT
TABLE OF CONTENTS
1. SAFETY LABELING AND SIGNAL WORDS 2....................
2. UNIT DIMENSIONS 2......................................
3. SAFE INSTALLATION REQUIREMENTS 2.......................
4. LOCATING THE UNIT 2....................................
5. UNIT ELECTRICAL WIRING 4................................
6. ELECTRIC HEAT INSTALLATION GENERAL INFORMATION 6.......
7. AIR DISTRIBUTION SYSTEM 8..............................
8. START- UP PROCEDURES 8................................
9. SEQUENCE OF OPERATION 10.............................
Printed in U.S.A.
LP--1 10/15/01
427 01 1005 00
1. Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the product.
2. Dimensions
NOTE: DUCT COLLARS ATTACHED TO SUPPLY AND RETURN MUST BE REVERSED AT INSTALLATION. SEE INSTRUCTIONS ON PAGE 3.
ALL DIMENSIONS IN INCHES
COIL
ROUND FLANGE WILL ACCOMMODATE 14” DIA. RETURN DUCT
3
/
DIA HOLE**
8
ACCESS
261/
2
PRESSURE
PORTS
* ELECTRICAL ACCESS FOR LINE VOLTAGE POWER SUPPLY--ONE FOR UNIT, ONE FOR HEATER
**
FOR LOW VOLTAGE WIRING
3. Safe Installation Requirements
PANEL
26
51
CONDENSATE DRAIN
3
/
4
CONNECTION
10
3
11/
2
121/
2
4. Locating The Unit
The unit is designed for outdoor installation only. Place the unit on a platform at ground level. The unit may be installed on a concrete slab of 48² (1219mm) x 48² (1219mm) dimensions. Cement
Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA70--1990 or current edition.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Failure to carefully read and follow all instructions in this manual can result in unit malfunction, property damage, personal injury and/or death.
blocks on a 3’’ sand footing will also work. The slab or blocks SHOULD NOT be in contact with any part of the structure. Check local codes covering zoning, noise, platforms, etc..
If practical avoid locating next to fresh air intakes, vent or bed­room windows. Noise may carry into the openings and disturb people inside.
Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive noise, and may cause ice to build up on coil or fan.
Placement of the unit should be in a well drained area or the unit MUST be supported high enough so runoff will not enter the unit.
Do not locate unit where heat, lint or exhaust fumes will be dis­charged on unit (as from dryer vents.)
41
17
14
11/4DIA.*
1
1
/4DIA.*
3
/
4
8
ROUND SHAPED FLANGE WILL ACCOMMODATE 12” DIA. SUPPLY DUCT
9
1
1
/
2
· Seal supply and return air ducts.
· Check to see that filters are installed correctly and are the
proper type and size.
NOTE: It is the personal responsibility and obligation of the cus­tomer to contact a qualified installer to ensure that the installation is adequate and conforms to governing codes and ordinances.
CAUTION
Do NOT operate unit in a corrosive atmosphere containing chlorine, fluorine, or any other corrosive chemicals.
Clearances
Minimum clearances, as specified in FIGURE 1, MUST be main­tained from adjacent structures to provide adequate air circula­tion and room for service personnel.
While minimum clearances are acceptable for safety reasons, they may not allow adequate air circulation around the unit for proper operation. Whenever possible, it is desirable to allow addi­tional clearance, especially around the condenser inlet and dis ­charge openings.
Do NOT install the unit i n a recessed or confined area that will per­mit discharged air from the condenser to recirculate to the con­denser inlet.
2
427 01 1005 00
Minimum Clearances to Combustible Construction
SERVICE ACCESS CLEARANCES
Blower Access Panel Side 30² (762mm)...................
Electrical Access Panel Side 30² (762mm).................
OPERATIONAL CLEARANCES
Combustible Base
(Wood or Class A, B or C
roof covering material) 0²....................
Supply and Return Air Ducts 0²...........................
Duct Connection Side
Clearance between Overhang
and Top of Unit 48² (1219mm)...............
Clearance around Condenser Coil area to wall or shrubs 10’’.
Blower CompartmentFIGURE 2
0².......................................
FIGURE 1
Overhang
Evaporator
Access Panel
30’’
Recommended
48’’ Minimum Overhang Clearance
6’’
Installation
Minimum Clearances and Access Panels
around
10’’
condenser
coil area
.
.
.
.
.
.
30’’
Blower/Electrical Access Panel
Cover Plate
CAUTION
Blower Terminal Block
Installing Duct Collars
Duct collars are supplied with the unit and are attached to the sup­ply and return openings with the flanges to the inside and must be reversed before unit’s installation.
1. Remove the screws from the collars and reverse them so the flange is to the outside.
2. Make sure when pushing the collars into place that the ’’V’’ flange of the collars seats into the supply and return holes securely.
3. Re--install screw in each collar so it goes through both of the holes in the collar end. It does not matter how the ends of the collar overlap in order to accomplish this.
Duct Collar InstallationFIGURE 3
Collar Installed for Duct Connections
The unit must be installed with a slope no greater than1/8² per foot (10mm per meter). For side to side leveling, the con­densate drain side side MUST always be lower.
-- The unit MUST be situated in such a way as to provide safe
access for servicing.
-- The platform may be made of either concrete or pressure
treated wood and MUST be level and strong enough to support the unit’s weight.
-- Position platform separate from the building’s foundation.
-- Install in a well--drained area, with the top surface of the platform above grade level and above the average winter snow levels to prevent coil blockage.
-- Platform MUST be high enough to allow for proper conden­sate drainage.
Collar as shipped with unit
3
427 01 1005 00
Condensate Drain
The condensate drain outlet is a3/4² (19.1mm) threaded female PVC connection located at the bottom of the unit to the left of the evaporator access panel .
The circulating blower and the condenser fan create a negative pressure on the condensate drain line that will prevent the con­densate from draining properly without a trap. Tocombatthis neg­ative pressure, a field supplied condensate trap that will allow a standing column of water of at least 2² (50.8mm) MUST be installed. The outlet of the trap must be at least 1’’ below the unit drain connection. Install the trap as near to the unit as possible
forproperdrainage.
3
/4² (19.1mm) drain line MUST be installed if required by local
A codes or if location of unit requires it. Run the drain line to an open drain or other suitable disposal point.
FIGURE 4
3
/4² (19.1mm) Threaded Female PVC Fitting
33/4² (82.5mm)
Condensate Drain Information *
1² (25.4mm)
2² (50.8mm)
* Condensate trap MUST be installed.
3
/4² (19.1mm)
Drain Line
Ground Connections
A ground lug is installed on the control plate (or electric heat mounting plate) for the ground connection. Use a copper conduc­tor of the appropriate size from the unit to a grounded connection in the electrical service panel ortoaproperlydriven andelectrical­ly grounded ground rod. See warning on this page.
Line Voltage Wiring
Do NOT complete line voltage connections until unit is perma­nently grounded. All line voltage connections and the ground con­nection MUST be made with copper wire.
Connections for line voltage are made on the unit electrical con­trol plate (see NO TAG). For access, remove the Blower/Electri­cal access panel.
Refer to applicable wiring diagram in this Manual. Complete the line service connections to the contactor ‘L1, L2, L3’ terminals on the electrical control plate. Check all screw terminals to ensure they are tight.
NOTE: If an Electric Heat Accessory is installed, refer to the Elec­tric Heat Accessory section of this manual to determine line volt­age connections. The Electric Heat Accessory mounts inside the unit in the heater box. Field supplied line voltage wires for the Electric Heat Accessory (separate from the field supplied line voltage wires to the unit) connect to the appropriate circuit break­er (if used) in the Electric Heat Accessory.
Converting 230V Units to 208V
To convert 230V units to 208V:
1. Turn electric power OFF .
5. Unit Electrical Wiring
Electrical shock hazard.
Disconnect power at fuse box or service panel before making any electrical connections.
Unit MUST be grounded to electrical service panel.
Failure to follow this warning can result in property damage, personal injury, and/or death.
NOTE: All electrical work MUST conform with the requirements of
local codes and ordinances and in the United States with National Electrical Code ANSl/NFPA 70--1990 (or current edition). Provide line voltage power supply from a separate fused circuit with a dis­connect switch (when required) located within sight of the unit. Supply voltage, amperage, fuse and disconnect switch sizes MUST conform with local codes and ordinances.
Wiring MUST be protected from possible mechanical damage and MUST NOT interfere with removal of access panels, filters, etc.
All exposed line voltage connections MUST be made through liq­uid tight conduit to prevent water from entering the unit through the electrical access..
2. Remove the blower/electrical access panel.
3. Locate the 24V control transformer.
4. Remove wire from the terminal labeled “240V” on the 24V control transformer and reconnect it to the 208V terminal of the 24V control transformer.
5. Replace the blower / electrical access panel.
Low Voltage Wiring
For access, removetheelectricalblower/electricalaccesspanel.
Refer to the connection wiring diagram for the applicable model and to the instructions included with the thermostat.
Route low voltage wires through the port located on the rear panel and up to the control box.
NOTE: If an Electric Heat Accessory is installed, see the Electric Heat Accessory Installation Section of this manual for low voltage connections.
Thermostat Connections
The location of the thermostat has an important effect on the op­eration of the unit. See the thermostat instructions for proper con­nection. See NO TAG for Low Voltage Wire Harness Connections
4
427 01 1005 00
Field Installed Equipment
Wiring to be done in the field between the unit and other devices, or between separatedeviceswhicharefield installed and located, MUST NOT exceed the temperature limitations for type T wire and MUST be installed according to the manufacturer’s instruc ­tions for the devices.
Final Electrical Check
Make a final wiring check to be s ure system is correctly wired. In­spect field installed wiring and the routing to ensure that rubbing or chafing due to vibration will not occur.
NOTE: Wiring MUST be installed so it is protected from possible mechanical damage.
FIGURE 5
NOTES: * Common maybe ‘‘B’’ or ‘‘X’’ on some T --stats.
[C]*[G] [R] [Y] [W]
[Blue] [Green] [Red] [Yellow] [White] [Orange]
Com (when used)
Electronic Thermostat Low Voltage Wiring Harness Connection Diagram
Typical Thermostat Subbase
** ‘‘W’’ may be ’’W2’’ on some T--stats.
**
(when used)
W2
Fan 24V
Unit Low Voltage Wiring Harness.
Hot
Com­pressor
Elect. Heat Acces.
When outdoor thermostat is used, route this.
[O]
Reversing valve (energized in cooling)
FIGURE 6
Typical Connections at Unit
FIGURE 7
Low Volt Wire Entrance
Control Box Configuration
Transformer
Defrost Board
Blower Sequencer
Ground lug
Contactor
Condensor Fan Capacitor
Component Wire Opening
Control Box
Line Volt Wire Entrance
5
427 01 1005 00
Loading...
+ 9 hidden pages