personnel must perform all other operations. When working on
heating equipment, observe precautions in the literature, on
tags, and on labels attached to or shipped with the unit, and
CERTIFIED
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATION
!WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON
MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or
death.
This conversion kit shall be installed by a qualified service
agency in accordance with the manufacturer’s instructions
and all applicable codes and requirements of the authority
having jurisdiction. If the information in these instructions is
not followed exactly, a fire, explosion, or production of carbon
monoxide could result causing property damage, personal
injury, or loss of life. The qualified service agency is
responsible for the proper installation of this furnace with this
kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified
in the manufacturer’s instructions supplied with the kit.
other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the current edition of the National Fuel Gas
Code (NFGC) NFPA No. 54/ANSI Z223.1. In Canada, refer to
the current edition of the National Standard of Canada, Natural
Gas and Propane Installation Codes (NSCNGPIC),
CAN/CSA−B149.1 and .2. Wear safety glasses and work
gloves. Have a fire extinguisher available during start−up,
adjustment steps, and service calls.
Recognize safety information. This is the safety−alert symbol
. When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury. Understand the signal words DANGER, WARNING,
CAUTION and NOTE. The words DANGER, WARNING, and
CAUTION are used with the safety alert symbol. DANGER
identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
INTRODUCTION
!
LE FEU, L’EXPLOSION, CHOC ELECTRIQUE,
ET MONOXYDE DE CARBONE EMPOISONNER
Cette trousse de conversion doit être installée par un servie
d’entretien qualifié, selon les instructions du fabricant et selon
toutes les exigences et tous les codes pertinents de l’autorité
compétente. Assurezvous de bien suivre les instructions
dans cette notice pour réduire au minimum le risque
d’incendie, d’explosion ou la production de monoxyde de
carbone pouvant causer des dommages matériels, de
blessure ou la mort. Le service d’entretien qualifié est
responsable de l’installation de cette trousse. L’installation
n’est pas adéquate ni complète tant que le bon
fonctionnement de l’appereil converti n’a pas été vérfié selon
les instructions du fabricant fornies avec la trousse.
Installing and servicing heating equipment can be hazardous
due to gas and electrical components. Only trained and
qualified personnel should install, repair, or service heating
equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. Trained service
AVERTISSEMENT
!WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON
MONOXIDE POISONING HAZARD
Failure to follow instructions could result in personal injury,
death or property damage.
Improper installation, adjustment, alteration, service,
maintenance, or use can cause carbon monoxide poisoning,
explosion, fire, electrical shock, or other conditions, which
could result in personal injury or death. Consult your
distributor or branch for information or assistance. The
qualified installer or agency must use only factory−authorized
kits or accessories when servicing this product.
!WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK
HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Gas supply MUST be shut off before disconnecting electrical
power and proceeding with conversion.
Specifications subject to change without notice.
443 06 1522 00 6/12/14
!WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
CONDENSING FURNACES
MODEL NUMBERS BEGINNING WITH:
(F/G)9MAC(F/G)9MVT
(F/G)9MAE(F/G)9MVE
SECTION 1
(F/G)9MXT
install a lockout tag. There may be more than one disconnect
switch. Lock out and tag switch with a suitable warning label.
Verify proper operation after servicing.
This instruction covers the installation of gas conversion kit Part
No. NAHB01001LP to convert the following furnaces from
natural gas usage to propane gas usage. See appropriate
section for your furnace type.
Section 1—(F/G)9MAC, (F/G)9MAE, (F/G)9MVT, (F/G)9MVE,
& (F/G)9MXT 35−in. (889 mm ) 4-Way Multipoise, Hot Surface
Ignition, Modulating Variable−Speed, Two−Stage
Variable−Speed and Two−Stage ECM Blower Motor
Condensing Furnaces.
1. Set room thermostat to lowest setting or “OFF”.
2. Remove outer doors.
3. Disconnect power at external disconnect, fuse or circuit
breaker.
4. Turn off gas at external shut-off or gas meter.
5. Remove outer doors and set aside.
6. Turn electric switch on gas valve to OFF.
Figure 1
Representative Furnace Drawing
HOT SURFACE
IGNITER
GAS BURNER
MANUAL RESET
ROLLOUT SWITCH
Variable-Speed, Non-Condensing Furnaces.
FLAME
DESCRIPTION AND USAGE
This kit is designed for use in the furnaces listed below. See
Table 1 for kit contents. To accommodate many different
furnace models, more parts are shipped in kit than will be
needed to complete conversion. When installation is complete,
discard extra parts.
Table 1NAHB01001LP Contents
QUANTITYDESCRIPTION
1VALVE CVRSN KIT - W/R F92-102100
SENSOR
MANUAL RESET
ROLLOUT SWITCH
GAS VALVE
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
BLOWER DOOR
SAFETY SWITCH
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
INDUCER MOTOR
ASSEMBLY
2VALVE CVRSN KIT - W/R SPRING 92-0659
7ORIFICE - #55
7ORIFICE - #56
FURNACE
CONTROL
BOARD
BLOWER AND
MOTOR
7ORIFICE - 1.25mm
7ORIFICE - 1.30mm
7SCREW - SPOILER (CONDENSING)
7SCREW - SPOILER (NON−CONDENSING)
1CONNECTOR - BRASS 1/8” NPT X2”
1CONNECTOR,SPLC - 3/16”
1CONNECTOR-1/4QC ME BOTH ENDS
1ELBOW, STREET - 150# 1/8” NPT
1ELBOW, STREET - BRASS 1/8” NPT
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
MANIFOLD/ORIFICE/BURNER
REMOVAL
CAPACITOR/
POWER CHOKE
L11F045
1NIPPLE - HEX (BRASS)
1SWITCH, PRESSURE
1TEE - MALE BRANCH (BRASS)
1TEE, STREET - MALE BRANCH (BRASS)
1BIT, DRILL 7/64” CONDENSING
1BIT, DRILL 5/64” NON−CONDENSING
2WIRE ASSY - ORANGE
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage or
improper operation.
Label all wires prior to disconnection when servicing controls.
!CAUTION
1LABEL 339268-201
1LABEL 339268-202
!
PRUDENCE
1LABEL 339268-203
1LABEL 339268-204
1LABEL 339268-205
1LABEL 339268-206
1LABEL 339268-209 (FRENCH)
1LABEL 339268-211 (FRENCH)
1LABEL 339268-214 (FRENCH)
1INSTRUCTIONS
D’EQUIPEMENT D’OPERATION
Toute erreur de câblage peut être une source de danger et
de panne.
Lors des opérations d’entretien des commandes, étiqueter
tous les fils avant de les déconnecter.
NOTE: Use a back-up wrench on the gas valve to prevent the
valve from rotating on the manifold or damaging the mounting
to the burner box.
2443 06 1522 00
Specifications subject to change without notice.
1. Disconnect the gas pipe from gas valve and remove pipe
from the furnace casing.
2. Disconnect the connector harness from gas valve.
Disconnect wires from Hot Surface Igniter (HSI) and
Flame Sensor.
3. Support the manifold and remove the four (4) screws that
secure the manifold assembly to the burner box and set
aside.
4. Note the location of the green/yellow wire ground wire for
re-assembly later. (See Figure 2)
5. Slide one−piece burner assembly out of slots on sides of
burner box. (See Figure 3)
6. Remove the flame sensor from the burner assembly.
7. Remove the orifices from the manifold and discard.
Figure 2
Connect Green/Yellow
ground wire here
Gas valve is parallel to manifold
C
L
within + or - 3˚
Gas valve must be installed on
manifold with minimum engagement of
6 threads. Cross threading is not
acceptable.
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPREARANCE.
Gas Valve with Orifices
Orifice
Manifold
Gas Valve
Indicated surfaces
˚+ or -2˚
to be 90
Figure 3Burner Assembly
BURNER SUPT. ASSY
BURNER ASSY
IGNITER
BRACKET, IGNITER
A11486
ORIFICE SELECTION/DERATE
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
DO NOT re−drill burner orifices. Improper drilling may result
in burrs, out−of−round holes, etc. Obtain new orifices if orifice
size must be changed. (See Figure 4)
Figure 4Burner Orifice
BURNER
ORIFICE
BURNER
ORIFICE
A96249
Refer to conversion kit rating plate 339268−201 or 339268−206
to determine main burner orifice size. (See Figure 6)
Furnace gas input rate on furnace rating plate is for installations
at altitudes up to 2000 ft.
In the U.S.A.; the input rating for altitudes above 2000 ft. must
be reduced by 2 percent for each 1000 ft. above sea level.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 ft. to 4500 ft. above sea level.
The Conversion Kit Rating Plate accounts for high altitude
derate.
INSTALL ORIFICES
1. Install main burner orifices. Do not use Teflon tape.
Finger−tighten orifices at least one full turn to prevent
cross−threading, then tighten with wrench.
2. There are enough orifices in each kit for largest furnace.
Discard extra orifices.
NOTE: DO NOT reinstall the manifold at this time.
INSTALL MIXER SCREWS
NOTE: There are two sets of mixer screws. One set is for
Condensing gas furnaces, the other set is for Non-condensing
gas furnaces. Use only the parts in the bag marked
“REQUIRED FOR THE CONVERSION OF CONDENSING
GAS FURNACES TO PROPANE GAS”
See Figure 5 to verify you have the correct set of mixer screws.
Figure 5
Gas Conversion Kit
FLAME ROLLOUT
SWITCH
FLAME SENSOR
(BELOW BURNER)
443 06 1522 003
Specifications subject to change without notice.
A11403
A11294
1. Locate the dimple on each burner venturi tube. If you
cannot locate the dimple, refer to Figure 7 for location of
the mixer screw.
2. Drill a 7/64−in. (2.8 mm) hole (supplied in kit) in each
dimple.
3. Install a mixer screw in each drilled hole drilling as
straight as possible. The screw head should be flush with
the top of the burner venturi.
Figure 7Mixer Screw Location
REINSTALL BURNER ASSEMBLY
To reinstall burner assembly:
1. Attach flame sensor to burner assembly.
2. Insert one−piece burner in slot on sides of burner box
and slide burner back in place.
1.9”
(48.76 mm)
Drill out with
7/64” drill bit
3. Reattach HSI wires to HSI.
4. Verify igniter to burner alignment. See Figure 8 and
Figure 9.
Figure 8Igniter Position − Back View
1.8”
(46.96 mm)
1-1/4-in.
(31.8)
2-1/2-in.
A11460
4443 06 1522 00
Specifications subject to change without notice.
(64.4)
A11405
Figure 9Igniter Position − Side View
2 − in.
(50 mm)
3/8 − in.
(9.6 mm)
3/16− in.
(4.6 mm)
(F/G)9MAC & (F/G)9MAE − Modulating
Gas Valve
Refer to Figure 10 and Figure 11.
Figure 10
Propane Jumper
3/32− in., +1/32 -3/64-in.
(2.5 mm
, +0.8 -1.5)
A12392
CONVERT GAS VALVES
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
The gas valve must be converted and pre−adjusted before
operating on propane gas. If not converted and pre−adjusted,
sooting and corrosion will occur leading to early heat
exchanger failure.
!WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK
HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Gas supply MUST be shut off before disconnecting electrical
power and proceeding with conversion.
!WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag. There may be more than one disconnect
switch. Lock out and tag switch with a suitable warning label.
Verify proper operation after servicing.
A11373
Figure 11Installing Propane Jumper
A11375
NOTE: The Propane jumper for the modulating gas valve is
very small. Needle-nose pliers are required to insert the jumper
into the valve. If the jumper is not installed, the valve will not
operate properly on propane.
1. Locate the round “NAT GAS” sticker on the top of the
gas valve.
2. Peel the sticker off and discard.
3. Note the small square opening in the top of the gas
valve.
4. Note the two jumper pins inside the modulating gas
valve.
5. Remove the small black plastic propane jumper from the
envelope.
6. Use needle-nosed pliers to hold the jumper by the tab on
the end.
7. Insert the jumper on the pins inside the gas valve.
8. Cover the opening in the gas valve with the label marked
“LP GAS”
443 06 1522 005
Specifications subject to change without notice.
Figure 12
Inlet
Pressure Tap
(F/G)9MAC & (F/G)9MAE − Redundant
Automatic Control Valve (Modulating)
ON/OFF Switch
GAS FLOW
MODULATING
Turn screw 1 click per
second to adjust rate.
Clockwise to increase
rate, counter clockwise
to decrease rate.
Min/Max Heat Adust
(Under Cap)
INSTALL LOW GAS PRESSURE
SWITCH
NOTE: Install the Low Gas Pressure Switch before installing
the manifold on the burner assembly.
There are two ways to mount the Low Gas Pressure Switch.
All 14 3/16-in Casings or Vent Passes Between Inducer
Assembly and Burner Assembly
If the vent pipe passes between the inducer and burner
assembly, or the furnace is a 14 3/16-in. wide casing, install the
switch as follows (See Figure 14):
LGPS for 14−3/16 Casing or When Vent
Figure 14
Passes Between Inducer and Burner
Assembly
1/2” NPT Outlet
Manifold
Pressure Tap
A10496
(F/G)9MVT, (F/G)9MVE & (F/G)9MXT −
Two Stage Gas Valve
Refer to Figure 13.
1. Be sure gas and electrical supplies to furnace are off.
2. Remove caps that conceal adjustment screws for high
heat and low heat gas−valve regulators. (See
Figure 13)
3. Remove the high heat and low heat regulator adjustment
screws.
4. Remove the high heat and low heat regulator springs
(silver).
5. Install the high heat and low heat propane gas regulator
springs (white).
6. Install the high heat and low heat regulator adjustment
screws.
7. Turn high heat stage adjusting screw clockwise (in) 13.5
full turns. This will increase the manifold pressure closer
to the propane set point.
8. Turn low heat stage adjusting screw clockwise (in) 9.5
full turns. This will increase the manifold pressure closer
to the propane low heat set point.
9. Do not install regulator seal caps at this time.
Figure 13
1/2” NPT Inlet
(F/G)9MVT, (F/G)9MVE & (F/G)9MXT −
Two −Stage Gas Valve
TWO-STAGE
ON/OFF Switch
Regulator Seal Cap
Regulator Adjustment
Regulator Seal Cap under Cap
Black Iron Street 90 Pointing
Low Gas Pressure Switch
Brass Street Tee
Inlet Pressure Tap with
Brass Street 90
Brass Hex Nipple
A11367
1. Remove the 1/8-in. (3 mm) NPT pipe plug from the gas
valve inlet pressure tap.
NOTE: Use pipe dope approved for use with Propane Gas.
NOTE: Tighten all fittings and the Low Gas Pressure Switch
with a small wrench. Do not over-tighten, check for gas leaks
after gas supply has been turned on.
!WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury
and/or death.
NEVER test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections. A fire or
explosion may result causing property damage, personal
injury or loss of life.
!
AVERTISSEMENT
RISQUE D’EXPLOSION ET D’INCENDIE
Le fait de ne pas suivre cet avertissement pourrait entraîner
1/8” NPT Inlet
Pressure Tap
des dommages corporels et / ou la mort.
Ne jamais examiner pour les fuites de gaz avec une flamme
vive. Utilisez plutôt un savon fait specifiquement pour la
1/2” NPT Outlet
détection des fuites de gaz pour verifier tous les connections.
Un incendie ou une explosion peut entrainer des dommages
matériels, des blessures ou la mort.
1/8” NPT Manifold
Pressure Tap
A11152
6443 06 1522 00
Specifications subject to change without notice.
2. Apply pipe dope sparingly to the male threads of the
1/8−in. (3 mm) Black iron street elbow. Install the street
elbow into the gas valve inlet pressure tap. Point the
open end of the street elbow toward you.
3. Apply pipe dope sparingly to the male threads of the
1/8−in. (3 mm) brass street tee. Install the male end of
the street tee as shown in Figure 14. One opening on
the street tee should face you. The other opening should
be parallel with the inlet of the gas valve.
4. Apply pipe dope sparingly to the male threads of the
1/8−in. (3 mm) brass hex nipple. Install the hex nipple
into the open end of the brass street tee. See Figure 14.
The hex nipple should be parallel with the boss on the
gas valve.
5. Install the open end of the brass street elbow on the end
of the hex nipple. Tighten the street elbow so the male
threads of the elbow point away from you.
6. Apply pipe dope sparingly to the male threads of the
1/8−in. brass street elbow. Install the Low Gas Pressure
Switch on the male threads of the 1/8−in. (3 mm) street
elbow. Tighten switch at hex fitting at base of switch. Do
not use switch body to tighten switch. Do not over-tighten
switch.
7. The remaining opening on the brass street tee is the new
gas valve inlet pressure tap. Install manometer fitting to
the open end of the brass street tee. Or if installation is to
be completed later, apply pipe dope to inlet pressure
plug from gas valve and install in open end of brass
street tee.
8. Check all fittings for leaks after gas supply has been
turned on.
Casings Wider Than 14 3/16-in./Vent Does Not Pass Between
Inducer and Burner Assembly
1. If the vent pipe does not pass between the inducer and
burner assembly, or the furnace is wider than a 14
3/16-in. wide casing, install the switch as follows (See
Figure 15):
2. Remove the 1/8-in. (3 mm) NPT pipe plug from the gas
valve inlet pressure tap.
NOTE: Use pipe dope approved for use with Propane Gas.
NOTE: Tighten all fittings and the Low Gas Pressure Switch
with a small wrench. Do not overtighten, check for gas leaks
after gas supply has been turned on.
3. Apply pipe dope sparingly to the male threads of the
1/8−in. (3 mm) brass street elbow. Install the street
elbow into the gas valve inlet pressure tap. One end of
the opening of the street elbow should be parallel with
the inlet boss on the gas valve.
4. Apply pipe dope sparingly to the male threads of the
1/8−in. (3 mm) x 2−in. (50.8 mm) brass nipple. Install the
brass nipple into the open end of the brass street elbow.
5. Install the open end of the brass street elbow on the end
of the brass nipple. Tighten the street elbow so the male
threads of the elbow point away from you.
6. Apply pipe dope sparingly to the male threads of the
1/8−in. brass street elbow. Install the Low Gas Pressure
Switch on the male threads of the 1/8−in. (3 mm) brass
street elbow finger tight. Tighten switch at hex fitting at
base of switch. Do not use switch body to tighten switch.
Do not overtighten switch.
7. The remaining opening on the brass street tee is the new
gas valve inlet pressure tap. Install manometer fitting to
the open end of the brass street tee. Or if installation is to
be completed later, apply pipe dope to inlet pressureplug from gas valve and install in open end of brass
street tee.
8. Check all fittings for leaks after gas supply has been
turned on.
INSTALL LOW GAS PRESSURE
SWITCH WIRES
1. Locate the orange wire in the kit with an insulated
straight female spade terminal and an insulated straight
male terminal on the other end.
2. Connect the female terminal to a terminal on the Low
Gas Pressure Switch.
3. Locate the orange wire in kit with an insulated straight
female spade terminal and an insulated female flag
terminal on the other end.
4. Connect both straight female terminals of the orange
wires to the terminals on the Low Gas Pressure Switch.
LGPS for Casing Wider Than 14−3/16
Figure 15
For larger casing when Vent Pipe does not pass across casing. All Sizes
switch contacts must point toward the Cell Panel. Black Iron Street 90 can be
used at Valve Inlet instead of Brass Street 90.
Inlet Pressure Tap with Plug
Low Gas Pressure Switch
and Vent Does Not Pass Between
Inducer and Burner Assembly
Brass Street Tee
Brass Street
Brass Nipple
A11366
INSTALL MANIFOLD
1. Align the orifices in the manifold assembly with the
support rings on the end of the burner.
2. Insert the orifices in the support rings of the burners.
Manifold mounting tabs should fit flush against the burner
box
NOTE: If manifold does not fit flush against the burner box, the
burners are not fully seated forward. Remove the manifold and
check burner positioning in the burner box assembly.
3. Attach the green/yellow wire and ground terminal to one
of the manifold mounting screws.
4. Install the remaining manifold mounting screws.
5. Connect the wires to the flame sensor and hot surface
igniter.
6. Connect the connector harness to gas valve
NOTE: Use only propane−resistant pipe dope. Do not use
Teflon tape.
7. Insert the gas pipe through the grommet in the casing.
Apply a tin layer of pipe dope to the threads of the pipe
and thread the pipe into the gas valve.
NOTE: Use a back-up wrench on the gas valve to prevent the
valve from rotating on the manifold or damaging the mounting
to the burner box.
8. With a back-up wrench on the inlet boss of the gas valve,
finish tightening the gas pipe to the gas valve.
9. Turn gas on at electric switch on gas valve.
MODIFY PRESSURE SWITCH WIRING
!CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage or
improper operation.
Label all wires prior to disconnection when servicing controls.
!PRUDENCE
D’EQUIPEMENT D’OPERATION
Toute erreur de câblage peut être une source de danger et
de panne.
Lors des opérations d’entretien des commandes, étiqueter
tous les fils avant de les déconnecter.
443 06 1522 007
Specifications subject to change without notice.
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.