International Comfort Products NAHB01001LP Installation Manual

INSTALLATION INSTRUCTIONS
NATURAL GAS to PROPANE GAS CONVERSION KIT
Condensing and Non−Condensing Gas Furnaces
(F/G)9MAC, (F/G)9MAE, (F/G)9MVT, (F/G)9MVE, (F/G)9MXT, (F/G)8MVL, (F/G)8MTL
NAHB01001LP
personnel must perform all other operations. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit, and
CERTIFIED
SAFETY CONSIDERATION
! WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion, or production of carbon monoxide could result causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this furnace with this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.
other safety precautions that may apply. Follow all safety codes. In the United States, follow all safety
codes including the current edition of the National Fuel Gas Code (NFGC) NFPA No. 54/ANSI Z223.1. In Canada, refer to the current edition of the National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC), CAN/CSAB149.1 and .2. Wear safety glasses and work gloves. Have a fire extinguisher available during start−up, adjustment steps, and service calls.
Recognize safety information. This is the safetyalert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION and NOTE. The words DANGER, WARNING, and CAUTION are used with the safety alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
!
LE FEU, L’EXPLOSION, CHOC ELECTRIQUE, ET MONOXYDE DE CARBONE EMPOISONNER
Cette trousse de conversion doit être installée par un servie d’entretien qualifié, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurezvous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, de blessure ou la mort. Le service d’entretien qualifié est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appereil converti n’a pas été vérfié selon les instructions du fabricant fornies avec la trousse.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. Trained service
AVERTISSEMENT
! WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow instructions could result in personal injury, death or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions, which could result in personal injury or death. Consult your distributor or branch for information or assistance. The qualified installer or agency must use only factory−authorized kits or accessories when servicing this product.
! WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Gas supply MUST be shut off before disconnecting electrical power and proceeding with conversion.
Specifications subject to change without notice.
443 06 1522 00 6/12/14
! WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and
CONDENSING FURNACES
MODEL NUMBERS BEGINNING WITH:
(F/G)9MAC (F/G)9MVT
(F/G)9MAE (F/G)9MVE
SECTION 1
(F/G)9MXT
install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
This instruction covers the installation of gas conversion kit Part No. NAHB01001LP to convert the following furnaces from natural gas usage to propane gas usage. See appropriate section for your furnace type.
Section 1—(F/G)9MAC, (F/G)9MAE, (F/G)9MVT, (F/G)9MVE, & (F/G)9MXT 35in. (889 mm ) 4-Way Multipoise, Hot Surface Ignition, Modulating VariableSpeed, Two−Stage VariableSpeed and TwoStage ECM Blower Motor Condensing Furnaces.
Section 2—(F/G)8MVL & (F/G)8MTL, 33.3in. (846 mm) High, InducedCombustion, HotSurface Ignition, Two-Stage,
INSTALLATION
1. Set room thermostat to lowest setting or “OFF”.
2. Remove outer doors.
3. Disconnect power at external disconnect, fuse or circuit
breaker.
4. Turn off gas at external shut-off or gas meter.
5. Remove outer doors and set aside.
6. Turn electric switch on gas valve to OFF.
Figure 1
Representative Furnace Drawing
HOT SURFACE IGNITER
GAS BURNER
MANUAL RESET ROLLOUT SWITCH
Variable-Speed, Non-Condensing Furnaces.
FLAME
DESCRIPTION AND USAGE
This kit is designed for use in the furnaces listed below. See Table 1 for kit contents. To accommodate many different furnace models, more parts are shipped in kit than will be needed to complete conversion. When installation is complete, discard extra parts.
Table 1 NAHB01001LP Contents
QUANTITY DESCRIPTION
1 VALVE CVRSN KIT - W/R F92-102100
SENSOR
MANUAL RESET ROLLOUT SWITCH
GAS VALVE
OPERATING INSTRUCTIONS NOT SHOWN (LOCATED ON MAIN FURNACE DOOR, SEE OPERATING INSTRUCTIONS INSIDE DOOR FIGURE).
ELECTRICAL JUNCTION BOX (IF REQUIRED, LOCATION MAY VARY)
BLOWER DOOR SAFETY SWITCH
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
INDUCER MOTOR ASSEMBLY
2 VALVE CVRSN KIT - W/R SPRING 92-0659
7 ORIFICE - #55
7 ORIFICE - #56
FURNACE CONTROL BOARD
BLOWER AND MOTOR
7 ORIFICE - 1.25mm
7 ORIFICE - 1.30mm
7 SCREW - SPOILER (CONDENSING)
7 SCREW - SPOILER (NONCONDENSING)
1 CONNECTOR - BRASS 1/8” NPT X2”
1 CONNECTOR,SPLC - 3/16”
1 CONNECTOR-1/4QC ME BOTH ENDS
1 ELBOW, STREET - 150# 1/8” NPT
1 ELBOW, STREET - BRASS 1/8” NPT
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
MANIFOLD/ORIFICE/BURNER REMOVAL
CAPACITOR/ POWER CHOKE
L11F045
1 NIPPLE - HEX (BRASS)
1 SWITCH, PRESSURE
1 TEE - MALE BRANCH (BRASS)
1 TEE, STREET - MALE BRANCH (BRASS)
1 BIT, DRILL 7/64” CONDENSING
1 BIT, DRILL 5/64” NONCONDENSING
2 WIRE ASSY - ORANGE
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage or improper operation.
Label all wires prior to disconnection when servicing controls.
! CAUTION
1 LABEL 339268-201
1 LABEL 339268-202
!
PRUDENCE
1 LABEL 339268-203
1 LABEL 339268-204
1 LABEL 339268-205
1 LABEL 339268-206
1 LABEL 339268-209 (FRENCH)
1 LABEL 339268-211 (FRENCH)
1 LABEL 339268-214 (FRENCH)
1 INSTRUCTIONS
D’EQUIPEMENT D’OPERATION
Toute erreur de câblage peut être une source de danger et de panne.
Lors des opérations d’entretien des commandes, étiqueter tous les fils avant de les déconnecter.
NOTE: Use a back-up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box.
2 443 06 1522 00
Specifications subject to change without notice.
1. Disconnect the gas pipe from gas valve and remove pipe from the furnace casing.
2. Disconnect the connector harness from gas valve. Disconnect wires from Hot Surface Igniter (HSI) and Flame Sensor.
3. Support the manifold and remove the four (4) screws that secure the manifold assembly to the burner box and set aside.
4. Note the location of the green/yellow wire ground wire for re-assembly later. (See Figure 2)
5. Slide onepiece burner assembly out of slots on sides of burner box. (See Figure 3)
6. Remove the flame sensor from the burner assembly.
7. Remove the orifices from the manifold and discard.
Figure 2
Connect Green/Yellow ground wire here
Gas valve is parallel to manifold
C
L
within + or - 3˚
Gas valve must be installed on manifold with minimum engagement of 6 threads. Cross threading is not acceptable.
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPREARANCE.
Gas Valve with Orifices
Orifice
Manifold
Gas Valve
Indicated surfaces
˚+ or -2˚
to be 90
Figure 3 Burner Assembly
BURNER SUPT. ASSY
BURNER ASSY
IGNITER
BRACKET, IGNITER
A11486
ORIFICE SELECTION/DERATE
! CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
DO NOT redrill burner orifices. Improper drilling may result in burrs, out−of−round holes, etc. Obtain new orifices if orifice size must be changed. (See Figure 4)
Figure 4 Burner Orifice
BURNER ORIFICE
BURNER ORIFICE
A96249
Refer to conversion kit rating plate 339268201 or 339268206 to determine main burner orifice size. (See Figure 6)
Furnace gas input rate on furnace rating plate is for installations at altitudes up to 2000 ft.
In the U.S.A.; the input rating for altitudes above 2000 ft. must be reduced by 2 percent for each 1000 ft. above sea level.
In Canada, the input rating must be derated by 5 percent for altitudes of 2000 ft. to 4500 ft. above sea level.
The Conversion Kit Rating Plate accounts for high altitude derate.
INSTALL ORIFICES
1. Install main burner orifices. Do not use Teflon tape. Fingertighten orifices at least one full turn to prevent crossthreading, then tighten with wrench.
2. There are enough orifices in each kit for largest furnace. Discard extra orifices.
NOTE: DO NOT reinstall the manifold at this time.
INSTALL MIXER SCREWS
NOTE: There are two sets of mixer screws. One set is for
Condensing gas furnaces, the other set is for Non-condensing gas furnaces. Use only the parts in the bag marked
“REQUIRED FOR THE CONVERSION OF CONDENSING GAS FURNACES TO PROPANE GAS”
See Figure 5 to verify you have the correct set of mixer screws.
Figure 5
Gas Conversion Kit
FLAME ROLLOUT SWITCH
FLAME SENSOR (BELOW BURNER)
443 06 1522 00 3
Specifications subject to change without notice.
A11403
A11294
1. Locate the dimple on each burner venturi tube. If you cannot locate the dimple, refer to Figure 7 for location of the mixer screw.
2. Drill a 7/64in. (2.8 mm) hole (supplied in kit) in each dimple.
Figure 6
Conversion Kit Rating Plate (F/G)9MAC & (F/G)9MAE
Conversion Kit Rating Plate (F/G)9MVT, (F/G)9MVE & (F/G)9MXT
3. Install a mixer screw in each drilled hole drilling as straight as possible. The screw head should be flush with the top of the burner venturi.
Figure 7 Mixer Screw Location
REINSTALL BURNER ASSEMBLY
To reinstall burner assembly:
1. Attach flame sensor to burner assembly.
2. Insert onepiece burner in slot on sides of burner box and slide burner back in place.
1.9”
(48.76 mm)
Drill out with 7/64” drill bit
3. Reattach HSI wires to HSI.
4. Verify igniter to burner alignment. See Figure 8 and
Figure 9.
Figure 8 Igniter Position Back View
1.8”
(46.96 mm)
1-1/4-in.
(31.8)
2-1/2-in.
A11460
4 443 06 1522 00
Specifications subject to change without notice.
(64.4)
A11405
Figure 9 Igniter Position Side View
2 in. (50 mm)
3/8 in. (9.6 mm)
3/16in. (4.6 mm)
(F/G)9MAC & (F/G)9MAE Modulating Gas Valve
Refer to Figure 10 and Figure 11.
Figure 10
Propane Jumper
3/32in., +1/32 -3/64-in. (2.5 mm
, +0.8 -1.5)
A12392
CONVERT GAS VALVES
! CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage.
The gas valve must be converted and preadjusted before operating on propane gas. If not converted and pre−adjusted, sooting and corrosion will occur leading to early heat exchanger failure.
! WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Gas supply MUST be shut off before disconnecting electrical power and proceeding with conversion.
! WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label. Verify proper operation after servicing.
A11373
Figure 11 Installing Propane Jumper
A11375
NOTE: The Propane jumper for the modulating gas valve is very small. Needle-nose pliers are required to insert the jumper into the valve. If the jumper is not installed, the valve will not operate properly on propane.
1. Locate the round “NAT GAS” sticker on the top of the gas valve.
2. Peel the sticker off and discard.
3. Note the small square opening in the top of the gas valve.
4. Note the two jumper pins inside the modulating gas valve.
5. Remove the small black plastic propane jumper from the envelope.
6. Use needle-nosed pliers to hold the jumper by the tab on the end.
7. Insert the jumper on the pins inside the gas valve.
8. Cover the opening in the gas valve with the label marked
“LP GAS”
443 06 1522 00 5
Specifications subject to change without notice.
Figure 12
Inlet Pressure Tap
(F/G)9MAC & (F/G)9MAE Redundant Automatic Control Valve (Modulating)
ON/OFF Switch
GAS FLOW
MODULATING
Turn screw 1 click per second to adjust rate. Clockwise to increase rate, counter clockwise to decrease rate.
Min/Max Heat Adust (Under Cap)
INSTALL LOW GAS PRESSURE SWITCH
NOTE: Install the Low Gas Pressure Switch before installing
the manifold on the burner assembly. There are two ways to mount the Low Gas Pressure Switch.
All 14 3/16-in Casings or Vent Passes Between Inducer Assembly and Burner Assembly
If the vent pipe passes between the inducer and burner assembly, or the furnace is a 14 3/16-in. wide casing, install the switch as follows (See Figure 14):
LGPS for 143/16 Casing or When Vent
Figure 14
Passes Between Inducer and Burner Assembly
1/2” NPT Outlet
Manifold Pressure Tap
A10496
(F/G)9MVT, (F/G)9MVE & (F/G)9MXT Two Stage Gas Valve
Refer to Figure 13.
1. Be sure gas and electrical supplies to furnace are off.
2. Remove caps that conceal adjustment screws for high heat and low heat gasvalve regulators. (See Figure 13)
3. Remove the high heat and low heat regulator adjustment screws.
4. Remove the high heat and low heat regulator springs (silver).
5. Install the high heat and low heat propane gas regulator springs (white).
6. Install the high heat and low heat regulator adjustment screws.
7. Turn high heat stage adjusting screw clockwise (in) 13.5 full turns. This will increase the manifold pressure closer to the propane set point.
8. Turn low heat stage adjusting screw clockwise (in) 9.5 full turns. This will increase the manifold pressure closer to the propane low heat set point.
9. Do not install regulator seal caps at this time.
Figure 13
1/2” NPT Inlet
(F/G)9MVT, (F/G)9MVE & (F/G)9MXT Two Stage Gas Valve
TWO-STAGE
ON/OFF Switch
Regulator Seal Cap
Regulator Adjustment Regulator Seal Cap under Cap
Black Iron Street 90 Pointing
Low Gas Pressure Switch
Brass Street Tee
Inlet Pressure Tap with
Brass Street 90
Brass Hex Nipple
A11367
1. Remove the 1/8-in. (3 mm) NPT pipe plug from the gas valve inlet pressure tap.
NOTE: Use pipe dope approved for use with Propane Gas. NOTE: Tighten all fittings and the Low Gas Pressure Switch
with a small wrench. Do not over-tighten, check for gas leaks after gas supply has been turned on.
! WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury and/or death.
NEVER test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
!
AVERTISSEMENT
RISQUE D’EXPLOSION ET D’INCENDIE
Le fait de ne pas suivre cet avertissement pourrait entraîner
1/8” NPT Inlet Pressure Tap
des dommages corporels et / ou la mort. Ne jamais examiner pour les fuites de gaz avec une flamme
vive. Utilisez plutôt un savon fait specifiquement pour la
1/2” NPT Outlet
détection des fuites de gaz pour verifier tous les connections. Un incendie ou une explosion peut entrainer des dommages matériels, des blessures ou la mort.
1/8” NPT Manifold Pressure Tap
A11152
6 443 06 1522 00
Specifications subject to change without notice.
2. Apply pipe dope sparingly to the male threads of the 1/8in. (3 mm) Black iron street elbow. Install the street elbow into the gas valve inlet pressure tap. Point the open end of the street elbow toward you.
3. Apply pipe dope sparingly to the male threads of the 1/8in. (3 mm) brass street tee. Install the male end of the street tee as shown in Figure 14. One opening on the street tee should face you. The other opening should be parallel with the inlet of the gas valve.
4. Apply pipe dope sparingly to the male threads of the 1/8in. (3 mm) brass hex nipple. Install the hex nipple into the open end of the brass street tee. See Figure 14. The hex nipple should be parallel with the boss on the gas valve.
5. Install the open end of the brass street elbow on the end of the hex nipple. Tighten the street elbow so the male threads of the elbow point away from you.
6. Apply pipe dope sparingly to the male threads of the 1/8in. brass street elbow. Install the Low Gas Pressure Switch on the male threads of the 1/8in. (3 mm) street elbow. Tighten switch at hex fitting at base of switch. Do not use switch body to tighten switch. Do not over-tighten switch.
7. The remaining opening on the brass street tee is the new gas valve inlet pressure tap. Install manometer fitting to the open end of the brass street tee. Or if installation is to be completed later, apply pipe dope to inlet pressure plug from gas valve and install in open end of brass street tee.
8. Check all fittings for leaks after gas supply has been turned on.
Casings Wider Than 14 3/16-in./Vent Does Not Pass Between Inducer and Burner Assembly
1. If the vent pipe does not pass between the inducer and burner assembly, or the furnace is wider than a 14 3/16-in. wide casing, install the switch as follows (See Figure 15):
2. Remove the 1/8-in. (3 mm) NPT pipe plug from the gas valve inlet pressure tap.
NOTE: Use pipe dope approved for use with Propane Gas. NOTE: Tighten all fittings and the Low Gas Pressure Switch
with a small wrench. Do not overtighten, check for gas leaks after gas supply has been turned on.
3. Apply pipe dope sparingly to the male threads of the 1/8in. (3 mm) brass street elbow. Install the street
elbow into the gas valve inlet pressure tap. One end of the opening of the street elbow should be parallel with the inlet boss on the gas valve.
4. Apply pipe dope sparingly to the male threads of the 1/8in. (3 mm) x 2in. (50.8 mm) brass nipple. Install the
brass nipple into the open end of the brass street elbow.
5. Install the open end of the brass street elbow on the end of the brass nipple. Tighten the street elbow so the male threads of the elbow point away from you.
6. Apply pipe dope sparingly to the male threads of the 1/8in. brass street elbow. Install the Low Gas Pressure
Switch on the male threads of the 1/8in. (3 mm) brass street elbow finger tight. Tighten switch at hex fitting at base of switch. Do not use switch body to tighten switch. Do not overtighten switch.
7. The remaining opening on the brass street tee is the new gas valve inlet pressure tap. Install manometer fitting to the open end of the brass street tee. Or if installation is to be completed later, apply pipe dope to inlet pressure plug from gas valve and install in open end of brass street tee.
8. Check all fittings for leaks after gas supply has been turned on.
INSTALL LOW GAS PRESSURE SWITCH WIRES
1. Locate the orange wire in the kit with an insulated straight female spade terminal and an insulated straight male terminal on the other end.
2. Connect the female terminal to a terminal on the Low Gas Pressure Switch.
3. Locate the orange wire in kit with an insulated straight female spade terminal and an insulated female flag terminal on the other end.
4. Connect both straight female terminals of the orange wires to the terminals on the Low Gas Pressure Switch.
LGPS for Casing Wider Than 14−3/16
Figure 15
For larger casing when Vent Pipe does not pass across casing. All Sizes switch contacts must point toward the Cell Panel. Black Iron Street 90 can be used at Valve Inlet instead of Brass Street 90.
Inlet Pressure Tap with Plug
Low Gas Pressure Switch
and Vent Does Not Pass Between Inducer and Burner Assembly
Brass Street Tee
Brass Street
Brass Nipple
A11366
INSTALL MANIFOLD
1. Align the orifices in the manifold assembly with the support rings on the end of the burner.
2. Insert the orifices in the support rings of the burners. Manifold mounting tabs should fit flush against the burner box
NOTE: If manifold does not fit flush against the burner box, the burners are not fully seated forward. Remove the manifold and check burner positioning in the burner box assembly.
3. Attach the green/yellow wire and ground terminal to one of the manifold mounting screws.
4. Install the remaining manifold mounting screws.
5. Connect the wires to the flame sensor and hot surface igniter.
6. Connect the connector harness to gas valve
NOTE: Use only propane−resistant pipe dope. Do not use Teflon tape.
7. Insert the gas pipe through the grommet in the casing. Apply a tin layer of pipe dope to the threads of the pipe and thread the pipe into the gas valve.
NOTE: Use a back-up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box.
8. With a back-up wrench on the inlet boss of the gas valve, finish tightening the gas pipe to the gas valve.
9. Turn gas on at electric switch on gas valve.
MODIFY PRESSURE SWITCH WIRING
! CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage or improper operation.
Label all wires prior to disconnection when servicing controls.
! PRUDENCE
D’EQUIPEMENT D’OPERATION
Toute erreur de câblage peut être une source de danger et de panne. Lors des opérations d’entretien des commandes, étiqueter tous les fils avant de les déconnecter.
443 06 1522 00 7
Specifications subject to change without notice.
Loading...
+ 15 hidden pages