International Comfort Products N8MSL0451408, N8MSL0451412, N8MSL0701408, N8MSL0701412, N8MSL0701716 Installation Manual

...
INSTALLATION INSTRUCTIONS
80% Single Stage, PSC Motor
Category I, Gas Furnace
N8MSN, N8MSL
These instructions must be read and understood completely before attempting installation.
DANGER, WARNING, CAUTION, and NOTE Signal Words in Manuals
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manual that may apply to the product.
DANGER Immediate hazards which will result in severe person- al injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or property damage.
NOTE − Used to highlight suggestions which will result in en- hanced installation, reliability, or operation.
The signal word WARNING is used throughout this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures or product labels.
Safetyalert symbol
When you see this symbol on the unit and in instructions or manu­als, be alert to the potential for personal injury.
TABLE OF CONTENTS
DIMENSIONS 3...............................................
SAFETY CONSIDERATIONS 3..................................
INTRODUCTION 4............................................
CODES AND STANDARDS 5...................................
SAFETY 5................................................
GENERAL INSTALLATION 5................................
COMBUSTION AND VENTILATION AIR 5.....................
DUCT SYSTEMS 5........................................
ACOUSTICAL LINING AND FIBROUS GLASS DUCT 5.........
GAS PIPING AND GAS PIPE PRESSURE TESTING 5..........
ELECTRICAL CONNECTIONS 5............................
VENTING 5..............................................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 5...........
LOCATION 6.................................................
AIR FOR COMBUSTION AND VENTILATION 7....................
INSTALLATION 10..............................................
UPFLOW INSTALLATION 10.................................
DOWNFLOW INSTALLATION 11.............................
FILTER ARRANGEMENT 12.................................
AIR DUCTS 13.............................................
AIR DELIVERY − CFM 14....................................
ELECTRICAL CONNECTIONS 20............................
115 V WIRING 20..........................................
JBOX RELOCATION 20....................................
ELECTRICAL CONNECTION TO J−BOX 20....................
ELECTRICAL DATA 21......................................
24V WIRING 22...........................................
ACCESSORIES 22.........................................
VENTING 23..................................................
GENERAL VENTING REQUIREMENTS 23.....................
MASONRY CHIMNEY REQUIREMENTS 24....................
APPLIANCE APPLICATION REQUIREMENTS 26...............
ADDITIONAL VENTING REQUIREMENTS 26..................
SIDEWALL VENTING 27....................................
STARTUP, ADJUSTMENT, AND SAFETY CHECK 30...............
GENERAL 30..............................................
STARTUP PROCEDURES 30...............................
ADJUSTMENTS 31.........................................
SPEED SELECTION 32.....................................
CHECK SAFETY CONTROLS 33.............................
CHECKLIST 34............................................
ORIFICE SIZE AND MANIFOLD PRESSURE 35................
SERVICE AND MAINTENANCE PROCEDURES 39.................
CARE AND MAINTENANCE 39...................................
SEQUENCE OF OPERATION 43.................................
WIRING DIAGRAM 44..........................................
TROUBLESHOOTING GUIDE 45.................................
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org .
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death. The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with proper tools and test instruments. Installation must conform with local building codes and with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI Z223.1, and National standards of Canada CAN/CSAB149.1 and .2 Natural Gas and Propane Installation Codes.
INSTALLER: Affix these instructions on or adjacent to the furnace. CONSUMER: Retain these instructions for future reference.
Portions of the text and tables are reprinted from NFPA 54 /ANSI Z223.1−2009©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washing- ton, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.
Printed in U.S.A. 441 01 1402 00 Jan. 2011
Figure 1 - Dimensional Drawing
NOTES:
1. Two additional 7/8-in. (22 mm) diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle. b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle. c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
2
441 01 1402 00
Table 1—Dimensions In. (mm)
A B C D
OUTLET
FURNACE SIZE
N8MSN & N8MSL
0451408 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 104 (47) 0451412 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 107 (49) 0701408 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 111 (50) 0701412 143/16 (360) 129/16 (319) 95/16 (237) 1211/16 (322) 4 (102) 115 (52) 0701716 171/2 (445) 157/8 (403) 119/16 (294) 16 (406) 4 (102) 126 (57) 0901714 171/2 (445) 157/8 (403) 119/16 (294) 16 (406) 4 (102) 127 (58) 0902116 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 140 (64) 0902120 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 146 (66) 1101712 171/2 (445) 157/8 (403) 119/16 (294) 16 (406) 4 (102) 135 (61) 1102116 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 146 (66) 1102122 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102) 152 (69) 1352116 21 (533) 193/8 (492) 135/16 (338) 191/2 (495) 4 (102)* 149 (68) 1352422 241/2 (622) 227/8 (581) 151/16 (383) 23 (584) 4 (102)* 163 (74) 1552420 241/2 (622) 227/8 (581) 151/16 (383) 23 (584) 4 (102)* 170 (77)
*135 and 155 size furnaces require a 5 or 6-in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements.
CABINET WIDTH
IN (mm)
WIDTH
IN (mm)
SAFETY CONSIDERATIONS
!
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factoryauthorized and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical
WARNING
!
CAUTION
!
CAUTION
TOP AND
BOTTOM
FLUE COLLAR
IN (mm)
shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
Recognize safety information. This is the safetyalert symbol
. When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace.
2. Install this furnace only in a location and position as
3. Provide adequate combustion and ventilation air to the
4. Combustion products must be discharged outdoors.
5. Never test for gas leaks with an open flame. Use a
6. Always install furnace to operate within the furnace’s
BOTTOM
WIDTH
IN (mm)
Refer to the furnace rating plate.
specified in the “Location” section of these instructions.
furnace space as specified in “Air for Combustion and Ventilation” section.
Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instruc­tions.
commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section.
intended temperature−rise range with a duct system
VENT
CONNECTION
SIZE*
IN (mm)
SHIP WT
LB (KG)
441 01 1402 00
3
which has an external static pressure within the allow­able range, as specified in the “Start−Up, Adjustments, and Safety Check” section. See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas−fired furnace for installation in a residential gar- age must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION sec­tion of these instructions.
10. These Multipoise GasFired Furnaces are CSA (formerly A.G.A. and C.G.A.) designcertified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory−shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed accessory gas conver­sion kit is required to convert furnace for use with pro­pane gas.
11. See Figure 1 for required clearances to combustible construction.
12. Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in.
Figure 2 - Clearances to Combustibles
(914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manu­facturer’s coil model numbers END4X, ENW4X or when coil casing model number NAEA is used. See Figure 1 for clearance to combustible construction in­formation.
INTRODUCTION
N8MSN & N8MSL 4way multipoise Category I fan−assisted furnace is CSA design−certified. A Category I fan−assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory−shipped for use with natural gas. This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return−air temperature of 60F (16C) db or intermittent operation down to 55F (13C) db such as when used with a night setback thermostat. Returnair temperature must not exceed 80F (27C) db. Failure to follow these returnair temperature limits may affect reliability of heat exchangers, motors, and controls. (See Figure 3)
4
441 01 1402 00
Figure 3 - Return Air Temperature
80F/27C
60F/16C
A06745
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply
with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction. In the United States , follow all codes and standards for the following:
Step 1Safety
National Fuel Gas Code (NFGC) NFPA 542009/ANSI Z223.12009 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
Step 2General Installation
Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Associ­ation Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org).
Step 3Combustion and Ventilation Air
Section 9.3 of the NFGC, NFPA 54 / ANSI Z223.12009 Air for Combustion and Ventilation
Step 4Duct Systems
Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Con­tractors National Association (SMACNA), or Americ­an Society of Heating, Refrigeration, and Air Condi­tioning Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000 HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5Acoustical Lining and Fibrous Glass Duct
Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6Gas Piping and Gas Pipe Pressure Testing
NFGC; NFPA 54 / ANSI Z223.1−2009 chapters 5, 6, 7 and 8 and National Plumbing Codes
Step 7Electrical Connections
National Electrical Code (NEC) ANSI/NFPA 702008
Step 8Venting
NFGC NFPA 54 / ANSI Z223.1−2009; chapters 12 and 13
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in furnace component damage.
Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple discon­nects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satis­factorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do noth­ing to recharge your body with static electricity (for ex­ample; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, un­painted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (un­grounded) furnaces.
6. Before removing a new control from its container, dis­charge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur­nace. Put all used and new controls into containers be­fore touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
441 01 1402 00
5
LOCATION
!
WARNING
CARBON MONOXIDE POISONING AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death, and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
Figure 4 - Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
GENERAL
This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Figure 4.
This furnace must:
be installed so the electrical components are protec­ted from water.
not be installed directly on any combustible material other than wood flooring for upflow applications. Downflow installations require use of a factoryap­proved floor base, coil model numbers END4X, ENW4X or coil casing model number NAEA when installed on combustible materials or wood flooring. (Refer to SAFETY CONSIDERATIONS).
be located as close to the chimney or vent and at­tached to an air distribution system. Refer to Air Ducts section.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
be provided ample space for servicing and cleaning. Always comply with minimum fire protection clear­ances shown on the furnace clearance to combust­ible label.
The following types of furnace installations may re­quire OUTDOOR AIR for combustion due to chemic­al exposures:
Commercial buildings Buildings with indoor pools Laundry rooms Hobby or craft rooms, and Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Water softening chemicals Deicing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All fuelburning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the returnair duct to prevent pulling air from the burner area and from draft safeguard opening.
6
441 01 1402 00
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 in. (457 mm) above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFPA 54/ANSI Z223.12009 . (See Figure 5)
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in furnace component damage.
This gas furnace may be used for heating buildings under construction provided that:
The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
The furnace is controlled by a thermostat. It may not be hot wired to provide heat continuously to the structure without thermostatic control.
Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
The temperature of the return air to the furnace is maintained between 55F (13C) and 80F (27C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
WARNING
!
CAUTION
Figure 5 - Installation in a Garage
18IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect returnair ducts to the back of the furnace. (See Figure 6)
Figure 6 - Prohibit Installation on Back
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the fullheat or full−cool position.
WARNING
A02054
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
Section 9.3 of the NFPA 54 / ANSI Z223.12009, Air for Combustion and Ventilation, and applicable pro­visions of the local building codes.
441 01 1402 00
7
2. Figure 7 illustrates how to provide TWO OUTDOOR
!
CAUTION
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make−up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of makeup air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cu/ft. per 1,000 Btuh input rating for all gas appliances installed in the space.
Spaces having less than 50 cu/ft. per 1,000 Btuh require the OUTDOOR COMBUSTION AIR METHOD.
Spaces having at least 50 cu/ft. per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combus­tion, ventilation, and dilution of flue gases using per­manent horizontal or vertical duct(s) or opening(s) dir­ectly communicating with the outdoors or spaces that freely communicate with the outdoors.
Table 2—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors
TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING
FURNACE
INPUT
(BTUH)
44,000 22 (14194) 6 (152) 14.7 (9484) 5 (127) 11 (7096) 4 (102) 66,000 33 (21290) 7 (178) 22.0 (14193) 6 (152) 16.5 (10645) 5 (127)
88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152) 110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152) 132,000 66 (42580) 10 (254) 44 .0 (28387) 8 (203) 33 (21290) 7 (178)
154,000 77 (49677) 10 (254) 51.3 (33096) 9 (229) 38.5 (24839) 8 (203)
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
Free Area of
Opening and Duct
Sq. In. (Sq. mm)
Round Duct
Dia.
In. (mm)
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
Free Area of
Opening and Duct
Sq. In. (Sq. mm)
OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12 in. (300
mm) of the ceiling and the second opening MUST
commence within 12 in. (300 mm) of the floor. b. Size openings and ducts per Figure 7 and Table 2. c. TWO HORIZONTAL DUCTS require 1 sq./in. of free
area per 2,000 Btuh (1,100 mm
input for all gas appliances in the space per
Figure 7 and Table 2. d. TWO OPENINGS OR VERTICAL DUCTS require 1
sq./in. of free area per 4,000 Btuh (550 mm2/kW)
for combined input of all gas appliances in the
space per Figure 7 and Table 2.
3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734
mm2/kW) for combined input of all gas appliances in the space per Table 2 and
b. Not less than the sum of the areas of all vent con-
nectors in the space.
The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air NFPA & AGA Standard and KnownAirInfiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or KnownAirInfiltration Method is used.
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.
Round Duct
Dia.
In. (mm)
WARNING
TWO OPENINGS OR VERTICAL
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of
Opening and Duct
Sq. In. (Sq. mm)
2
/kW) of combined
DUCTS
Round Duct
Dia.
In. (mm)
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings
66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts
8
441 01 1402 00
Table 3—Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
ACH
0.60
0.50
0.40
0.30
0.20
0.10
30 40 50 44 66 88 110 132 154
1,050
(29.7)
1,260
(35.6)
1,575
(44.5)
2,100
(59.4)
3,150
(89.1)
6,300
(178.3)
1,400 (39.6)
1,680 (47.5)
2,100 (59.4)
2,800 (79.2)
4,200
(118.9)
8,400
(237.8)
1,750 (49.5)
2,100 (59.4)
2,625 (74.3)
3,500 (99.1)
5,250
(148.6)
10,500 (297.3)
1,100 (31.1)
1,320 (37.3)
1,650 (46.7)
2,200 (62.2)
3,300 (93.4)
6,600
(186.8)
Space Volume Ft
1,650 (46.7)
1,980 (56.0)
2,475 (70.0)
3,300 (93.4)
4,950
(140.1)
9,900
(280.3)
FAN‐ASSISTED TOTAL
(1,000'S BTUH GAS INPUT RATE)
3
3
(M
) 2,200
(62.2)
2,640 (74.7)
3,300 (93.4)
4,400
(124.5)
6,600
(186.8)
13,200 (373.7)
2,750
(77.8)
3,300
(93.4)
4,125
(116.8)
5,500
(155.7)
8,250
(233.6)
16,500 (467.2)
3,300 (93.4)
3,960
(112.1)
4,950
(140.1)
6,600
(186.8)
9,900
(280.3)
19,800 (560.6)
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted
Figure 7 - Air for Combustion, Ventilation, and Dilution
for Outdoors
1 SQ IN.
E
12 ″ MAX
(305mm)
PER 4000 BTUH*
F
1 SQ IN .
BTUH*
1 SQ IN .
BTUH*
G
1 SQ IN. PER 4000 BTUH*
12
(305mm)
MAX
PER 4000
OUTDOORS
PER
4000
12
(305mm)
MAX
A03174
DUCTS
TO
O UTDOORS
(305mm)
12 ″ MAX
1 SQ IN. PER 2000 BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN. PER 2000 BTUH*
(305mm)
12 ″ MAX
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3-in. (76 mm).
NOTE: Use any of the following combinations of openings:
A & B C & D D & E F & G
B
AIR DUCTS
C IRCULA TING
A
OF COMB USTION AIR
CLEARANCE IN FRONT
D
VENT THR OUGH R OOF
(76mm)
AT LEAST 3 IN .
OPENINGS SHALL BE
C
DUCT
TO
OUTDOORS
The Standard Method:
1. The space has no less volume than 50 cu/ft. per 1,000 Btuh of the maximum input ratings for all gas appli­ances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
1. Less than 0.40 ACH and
Figure 8 - Air for Combustion, Ventilation, and Dilution
from Indoors
CIRCULATING AIR
DUCTS
INTERIOR
HEATED
SPACE
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. (64516 sq. mm)with minimum dimensions of 3 in. (76 mm) † Minimum of 3 in. (76 mm) when type‐B1 vent is used.
VENT THROUGH ROOF
12" MAX
1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL
UNCONFINED SPACE
(152mm)
6" MIN (FRONT)
1 SQ IN. PER 1000 BTUH* IN DOOR
OPENINGS SHALL BE AT LEAST 3 IN.
OR WALL
CLEARANCE IN FRONT OF COMBUSTION AIR
12" MA X
(305mm)
Ü
Table 3 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.12009/NFPA 54−2009, 9.3.2.2:
1. For other than fanassisted appliances, such as a draft hoodequipped water heater:
Volume
Other
=
21ft ACH
3
I
other
1000 Btu/hr
2. Equal to or greater than 0.10 ACH Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 3 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the
2. For fanassisted appliances such as this furnace:
Volume
Fan
=
15ft ACH
3
I
fan
1000 Btu/hr
space.
441 01 1402 00
3,850
(109.0)
4,620
(130.8)
5,775
(163.5)
7,700
(218.0)
11,550 (327.0)
23,100 (654.1)
(305mm)
A03175
A04002
A04003
9
If:
I
other = combined input of all other than fanassisted
appliances in Btuh/hr
I
fan = combined input of all fan−assisted appliances in
Btuh/hr ACH = air changes per hour (ACH shall not exceed
0.60.) The following requirements apply to the Standard
Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each open-
ing shall have free area of at least 1 in. (2,000 mm
2
/kW) of the total input rating of all gas
appliances in the space, but not less than 100 in.
2
/1,000 Btuh
2
(0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Figure 8)
c. Combining space on different floor levels. The
volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in. (4,400 mm
2
/kW) of total input rating of all gas appli-
2
/1,000 Btuh
ances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1−in.
2
/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for com­bustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight con­struction, additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section.
Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a
continuous, sealed vapor barrier. Openings are gas­keted or sealed and
b. Doors and openable windows are weatherstripped
and
c. Other openings are caulked or sealed. These in-
clude joints around window and door frames, between sole plates and floors, between wall−ceil- ing joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Com- bustion Air Method below and,
2. Outdoor openings shall be located as required in the Outdoor Combustion Air Method mentioned previ­ously and,
3. Outdoor openings shall be sized as follows: a. Calculate the Ratio of all Indoor Space volume di-
vided by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus
the Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size
required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minimum dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bot­tom filler panel. (See Figure 9.)
Figure 9 - Removing Bottom Closure Panel
BOTTOM CLOSURE PANEL
BOTTOM FILLER PANEL
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when only side return air is used.
NOTE: Side return−air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side returnair openings in DOWNFLOW configuration.
In upflow position with side return inlet(s), leveling legs may be used. (See Figure 10) Install field−supplied, 5/16 x 1−1/2 in. (8 x 38 mm) (max) corrosionresistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1. in Bottom Return Air Inlet section.
10
441 01 1402 00
Figure 10 - Leveling Legs
5/
16
(8mm)
(8mm)
5/
16
Figure 11 - Floor and Plenum Opening Dimensions
1 3 / 4 ″
(44mm)
3
/ 4 ″
1
(44mm)
(8mm)
5
/
16
(8mm)
5/
16
1
(44mm)
3/
4 ″
3/
1
4 ″
A89014
(44mm)
Leveling Legs (If Desired)
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Figure 10)
2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (In­stall flat washer if desired.)
4. Adjust outside nut to provide desired height, and tight­en inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved
for use on combustible flooring when any one of the following 3 accessories are used:
Downflow combustible floor subbase Coil model number END4X or ENW4X Coil casing model number NAEA
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Figure 11.
3. Construct plenum to dimensions specified in Table 4 and Figure 11.
4. If downflow subbase is used, install as shown in Figure 12. If coil model numbers END4X, ENW4X or coil casing model number NAEA is used, install as shown in Figure 13.
A
B D
C
A96283
NOTE: It is recommended that the perforated supply−air duct flanges be completely folded over or removed from furnace when installing the furnace on a factorysupplied cased coil or coil box. To remove the supplyair duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Figure 14)
Figure 12 - Furnace, Plenum, and Subbase Installed on
a Combustible Floor
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
441 01 1402 00
11
Figure 13 - Furnace, Plenum, and Coil or Coil Casing
Installed on a Combustible Floor
FURNACE
APPROVED
COIL ASSEMBLY
OR
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
A08556
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bot­tom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
HORIZONTAL INSTALLATION
!
WARNING
FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return−air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawl space on either the lefthand (LH) or righthand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a noncombustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Figure 15 and Figure 16) Secure angle iron to bottom of furnace as shown. Heavy−gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from
each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4in. (19 mm) screws into the side and 2 #8 x 3/4−in. (19 mm) screws in the bottom of the furnace casing for each strap. (See Figure 15 and Figure 16)
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Figure 2 and Figure 17) For furnaces with 1−in. (25 mm) clearance requirement on side, set furnace on non combustible blocks, bricks or angle iron. For crawl space installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
RollOut Protection
Provide a minimum 17−3/4 in. x 22 in. (451 x 559 mm) piece of sheet metal for flame rollout protection in front of burner area for furnaces closer than 12 inches (305 mm) above the combustible deck or suspended furnaces closer than 12 inches (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. (25 mm) with the door removed.
The bottom closure panel on furnaces of widths 171/2 in. (445 mm) and larger may be used for flame roll−out protection when bottom of furnace is used for return air connection. See Figure 17 for proper orientation of roll−out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bot­tom filler panel. (See Figure 9)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom returnair opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet.
Not all horizontal furnaces are approved for side return air connections. (See Figure 20)
FILTER ARRANGEMENT
!
CARBON MONOXIDE AND POISONING HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage. Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces.
A field−supplied accessory external filter rack is required. This furnace requires 1 in. (25 mm) external filter rack. Refer to the instructions supplied with external filter rack for
assembly and installation options.
WARNING
12
441 01 1402 00
FURNACE
CASING
WIDTH
14–3/16
(360)
17–1/2
(445)
21
(533)
241/2
(622)
Table 4—Opening Dimensions − In. (mm)
APPLICATION
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible Flooring
(subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
Upflow Applications on Combustible or Noncombustible Flooring
(subbase not required)
Downflow Applications on Noncombustible Flooring
(subbase not required)
Downflow Applications on Combustible flooring
(subbase required)
Downflow Applications on Combustible Flooring with Coil END4X,
ENW4X or Coil Casing NAEA (subbase not required)
PLENUM OPENING FLOOR OPENING
A B C D
1211/16
(322)
129/16
(319)
11−13/16
(284)
125/16
(319)
16
(406)
157/8
(403)
151/8
(384)
151/2
(394)
191/2
(495)
193/8
(492)
185/8
(473)
19
(483)
23
(584)
227/8
(581)
221/8
(562)
221/2
(572)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
215/8
(549)
19
(483)
19
(483)
19
(483)
211/8
(537)
19
(483)
19
(483)
19
(483)
135/16
(338)
133/16
(335)
137/16
(341)
135/16
(338)
165/8
(422)
161/2
(419)
163/4
(425)
161/2
(419)
201/8
(511)
20
(508)
201/4
(514)
20
(508)
235/8
(600)
231/2
(597)
233/4
(603)
231/2
(597)
221/4
195/8
205/8
221/4
195/8
205/8
221/4
195/8
205/8
221/4
195/8
205/8
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
(565)
(498)
(600)
20
(508)
AIR DUCTS General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 5 − AIR DELIVERY−CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply and returnduct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment NOTE: Metal duct systems that do not have a 90 degree
elbow and 10 ft. (3 M) of main duct to the first branch take−off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
441 01 1402 00
13
Table 5—Air Delivery CFM (with Filter)*
FURNACE
SIZE
0451408A
0451412A
0701408A
0701412A
0701716A
0901714B
0902116A
0902120A
1101712A
1102116A
1102122A
1352116A
1352422A
1552420A
* A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized accessory
filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.
-- Indicates unstable operating conditions.
RETURNAIR
INLET
Bottom
or
Side(s) Bottom
or
Side(s) Bottom
or
Side(s) Bottom
or
Side(s) Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom
or
Side(s)
Bottom Only
Both Sides
or
1 Side & Bottom
1 Side Only
Bottom
or
Side(s) Bottom
or
Side(s)
Bottom Only
Bottom, Sides
or 1 Side &
Bottom
1 Side Only
Bottom
or
Side(s)
Bottom Only
Bottom, Sides
or Side &
Bottom
1 Side Only
Bottom Only
Both Sides
or
1 Side & Bottom
1 Side Only
SPEED
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedHigh
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
High
MedLow
Low
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1085
920 820
1440 1360 1250
1030
835 725
1425 1320 1200
1805 1630 1460
1650 1515 1385 1205 2060 1790 1505
2405 2225 2020
2530 2285 1995
2475 2260 1950
1625 1510 1360
2035 1745 1530
2530 2230 1920
2235 1920
2540 2125
2090 1790 1545
2485 2195 1880
“2180
1880
2135 1880
2465 2115 1800
2155 1800
2140 1800
−−
−−
−−
−−
−−
−−
1035
875 775
1375 1300 1210
1010
815 700
1375 1280 1175
1740 1585 1420
1600 1485 1360 1180 1985 1765 1505
2310 2155 1955
2450 2215 1945
2395 2190 1910
1575 1470 1335
1965 1710 1515
2470 2205 1900
−−
220
1900 2495
2120 1795
2010 1755 1525
2400 2150 1850
−−
2145 1850
−−
2085 1850
2430 2105 1790
−−
2135 1790
−−
2095 1790
EXTERNAL STATIC PRESSURE (in. w.c.)
975 830 730
1305 1240 1160
980 790 675
1320 1240 1145
1670 1530 1385
1535 1440 1320 1160 1915 1715 1480
2220 2080 1880
2365 2150 1900
2300 2110 1855
1515 1415 1295
1880 1650 1470
2400 2165 1880
2415 2155 1880
2430 2105 1790
1930 1705 1500
2310 2090 1820
2385 2060 1820
2245 2035 1820
2375 2075 1770
2375 2095 1770
2260 2040 1770
915 770 680
1240 1175 1100
945 760 645
1265 1205 1105
1600 1470 1325
1465 1380 1260 1120 1820 1645 1440
2130 1995 1805
2270 2075 1840
2200 2035 1795
1445 1355 1250
1790 1560 1400
2320 2110 1845
2350 2100 1845
2355 2060 1765
1835 1640 1450
2215 2000 1780
2305 2010 1780
2155 1975 1780
2305 2030 1735
2285 2040 1735
2180 1975 1735
845 710 620
1160 1115
1040
900 720 600
1200 1140 1050
1530 1405 1280
1385 1300 1195 1065 1720 1560 1375
2025 1895 1730
2165 1985 1770
2090 1940 1730
1355 1285 1180
1680 1450 1310
2220 2035 1795
2250 2040 1795
2265 2010 1720
1710 1550 1380
2110 1920 1715
2195 1945 1715
2055 1895 1715
2230 1980 1695
2200 1975 1695
2085 1890 1695
770 640 555
1070 1040
965 845
675 555
1125 1075
990
1445 1330 1220
1285 1220 1120 1005 1610 1470 1300
1920 1785 1630
2065 1890 1685
1985 1845 1650
1260 1185 1100
1495 1340 1215
2115 1950 1730
2145 1955 1730
2175 1940 1650
1590 1465 1315
2000 1825 1635
2085 1865 1635
1940 1795 1635
2110 1910 1640
2105 1895 1640
1975 1810 1640
675 555 470
975 950 885
775 610 475
1035
995 920
1360 1255 1155
1175 1115 1025
925 1490 1345 1190 1790 1675 1535
1940 1780 1600
1865 1735 1555
1165 1070
985 1365
1205 1095
2000 1855 1650
2015 1850 1650
2065 1840 1585
1470 1360 1215
1880 1720 1540
1960 1765 1540
1825 1685 1540
2000 1830 1570
1995 1790 1570
1865 1705 1570
565 440 360
870 850 790
680 490 390
940 905 840
1280 1170 1080
1055
990 915
810 1340 1195 1045 1660 1565 1420
1805 1660 1480
1730 1620 1445
990
890
810 1215
1090
990 1865
1740 1555
1875 1740 1555
1935 1730 1500
1335 1210 1005
1725 1565 1415
1825 1660 1415
1695 1565 1415
1865 1725 1465
1870 1685 1465
1740 1595 1465
390 250 190
730 725 670
490 375 300
830 790 725
1180 1080
995 895
830 710
630 1135 1010
890 1530
1420 1275
1670 1525 1350
1585 1475 1310
785
725
−−
1075
955
830 1730
1615 1460
1715 1595 1460
1785 1615 1390
1025
945
855 1535
1405 1290
1670 1515 1290
1555 1445 1290
1725 1590 1345
1730 1550 1345
1605 1480 1345
195
−−
−−
560 575 520
335 265
−−
655 620 555
1075
990 910
645 600 565 510 925 820 740
1350 1260 1135
1505 1360 1180
1425 1325 1150
−−
−−
−−
875 750 670
1590 1485 1340
1560 1470 1340
1650 1485 1280
835 785 670
1355 1255 1160
1465 1325 1160
1385 1265 1160
1545 1425 1225
1570 1400 1225
1455 1325 1225
14
441 01 1402 00
Figure 14 - Duct Flanges
UPFLOW DOWNFLOW HORIZONTAL
90°
120°
MIN
YES
YES
NO
120°
MIN
YES
YES
NO
Figure 15 - Horizontal Unit Suspension
1
/ 4
" (6mm) THREADED ROD
4 REQ.
120° MIN
90°
YES
YES
NO
A02020
OUTER DOOR A S SEMBLY
8" (203mm) FOR DOOR REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD
MIN
SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH
3
/4" (19mm) SCREWS
3 #8 x TYPICAL FOR 2 SUPPORTS
1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED
A10130
441 01 1402 00
15
Loading...
+ 32 hidden pages