International comfort products DLFCAB, DLFCHB, DLCCAR, DLCCHR, DLCDAR Installation Instructions Manual

...
DLFCAB / DLCCAR / DLFCHB / DLCCHR DLFDAB / DLCDAR / DLFDHB / DLCDHR
INSTALLATION INSTRUCTIONS
High Wall Ductless Split System − Sizes 09 to 36
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
GENERAL 2.............................................
SYSTEM REQUIREMENTS 2...............................
Piping 2.............................................
PIPING AND REFRIGERANT TABLES DLFCAB / DLCCAR /
DLFCHB / DLCCHR 3.....................................
PIPING AND REFRIGERANT TABLES DLFDAB / DLCDAR /
DLFDHB / DLCDHR 4....................................
DIMENSIONS−INDOOR 6.................................
DIMENSIONS−OUTDOOR 7...............................
CLEARANCES−INDOOR 8................................
CLEARANCES−OUTDOOR 8..............................
INSTALLATION GUIDE 9..................................
Install Mounting Plate 9.................................
Drill Hole in Wall for Interconnecting Piping, Drain
and Wiring 9.........................................
OUTDOOR UNIT INSTALLATION 9.........................
Piping Connections to Outdoor Unit 9.....................
INSTALL ALL POWER, INTERCONNECTING WIRING AND
PIPING TO INDOOR UNIT 11..............................
SYSTEM VACUUM AND CHARGE 11.......................
START−UP 13............................................
WIRING DIAGRAMS 14...................................
TROUBLESHOOTING 15..................................
The following parts are included in your indoor unit. Please contact your dealer if any parts are damaged or missing.
Table 1—Parts List
Mounting Plate 1 Mounting Hardware 7 Remote Control 1 Remote Control Holder 1 Battery (1.5V) 2
Parts Qty
Specifications subject to change without notice.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air−conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start−up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code (NEC) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
!
Recognize safety information. This is the safety−alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start−up.
WARNING
CAUTION
GENERAL
These instructions cover the installation, start−up and servicing of outdoor and indoor units ductless systems.
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 4 for minimum required distances between unit and walls or ceilings.
Piping IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor
units is 10 ft. (3 m).
S The following maximum lengths are allowed.
2 421 019420 02
Specifications subject to change without notice.
PIPING AND REFRIGERANT TABLES DLFCAB / DLCCAR / DLFCHB / DLCCHR
T able 2—Piping Information DLFCAB / DLCCAR / DLFCHB / DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Min. Piping
Length
Standard
Piping Length
Max. Outdoor-
Indoor Height
Difference
Max. Piping
Length w/ No
Additional
Refrigerant
Charge
Max. Piping
Length
Gas Pipe (size
- connection type)
Liquid Pipe
(size -
connection
type)
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Cooling
Only
Heat
Pump
ft 10 10 10 10 10 10 10 10
m 3 3 3 3 3 3 3 3
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 32.8 32.8 32.8 32.8 32.8 32.8 32.8 32.8
m 10 10 10 10 10 10 10 10
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 49.2 65.6 49.2 65.6 82 82 98.4 98.4
m 15 20 15 20 25 25 30 30
in 3/8 1/2 3/8 1/2 5/8 5/8 5/8 5/8
in 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
T able 3— Refrigerant Information DLFCAB / DLCCAR / DLFCHB / DLCCHR
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between Standard – Max Piping
Length)
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between Standard – Max Piping
Length)
-- R410A R410A R410A R410A R410A R410A R410A R410A
Oz 42.3 47.6 45.9 47.6 56.4 81.1 84.66 84.7 Kg 1.2 1.35 1.3 1.35 1.6 2.3 2.4 2.4
Oz/ft 0.161 0.161 0.161 0.161 0.161 0.161 0.161 0.16
g/m 15 15 15 15 15 15 15 15
-- R410A R410A R410A R410A R410A R410A R410A R410A
Oz 42.3 47.6 45.9 47.6 56.4 77.6 84.66 91.7
kg 1.2 1.35 1.3 1.35 1.6 2.2 2.4 2.6
Oz/ft 0.215 0.215 0.215 0.215 0.161 0.538 0.538 0.54
g/m 20 20 20 20 15 50 50 50
421 019420 02 3
Specifications subject to change without notice.
PIPING AND REFRIGERANT TABLES DLFDAB / DLCDAR / DLFDHB / DLCDHR
T able 4— Piping Information DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K* 36K*
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Min. Piping
Length
Standard
Piping Length
Max.
Outdoor-
Indoor Height
Difference
Max. Piping
Length w/ No
Additional
Refrigerant
Charge
Max. Piping
Length
Gas Pipe
(size -
connection
type)
Liquid Pipe
(size -
connection
type)
Cooling
Only
Heat
Pump
ft 10 10 10 10 10 10 10 10
m 3 3 3 3 3 3 3 3
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 32.8 32.8 32.8 32.8 32.8 32.8 32.8 32.8
m 10 10 10 10 10 10 10 10
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 65.6 65.6 49.2 49.2 82 82 98.4 98.4
m 20 20 15 15 25 25 30 30
in 3/8 3/8 3/8 3/8 1/2 5/8 5/8 5/8
in 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
T able 5—Refrigerant Information DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K*
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Refrigerant
Type
Charge Amount
Additional
Refrigerant
Charge
(between
Standard – Max
Piping Length)
Refrigerant
Type
Charge Amount
Additional
Refrigerant
Charge
(between
Standard – Max
Piping Length)
-- R410A R410A R410A R410A R410A R410A
oz 26.5 31.8 24.7 30 35.3 56.45 kg 0.75 0.9 0.7 0.85 1 1.6
oz/ft 0.161 0.161 0.161 0.161 0.161 0.161
g/m 15 15 15 15 15 15
-- R410A R410A R410A R410A R410A R410A R410A R410A
oz 24.7 31.8 24.7 30 49.4 65.27 84.7 92 kg 0.7 0.9 0.7 0.85 1.4 1.85 2.4 3
oz/ft 0.215 0.215 0.215 0.215 0.215 0.538 0.54 1
g/m 20 20 20 20 20 50 50 50
NOTE: * Sizes 30 and 36 not available as Cooling Only.
4 421 019420 02
Specifications subject to change without notice.
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use the Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect the fuse or breakers respectively.
Per the caution note, only Stranded copper conductors with a 600 volt rating and double insulated copper wire must be used.
NOTE: The use of BX cable is not recommended.
Recommended Connection Method for Power and Communication
Wiring − Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit.
Two wires are high voltage AC power, one is the communication wiring and the other is a ground wire.
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference)
PowerWiring:
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to the indoor unit consists of three
(3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
T o minimize a voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
Communication Wiring:
A separate shielded stranded copper conductor only, with a minimum 600 volt rating and double insulated copper wire, must be used as the communication wire from the outdoor unit to the indoor unit.
Please use a separate shielded 16GA stranded control wire.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes. S Use copper conductors only with a 600 volt rating and
double insulated copper wire.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Comply with local codes while running wire from indoor
unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause a terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected.
S No wire should touch refrigerant tubing, the compressor
or any moving parts.
S Disconnecting means must be provided and must be
located within sight and readily accessible from the air conditioner.
S Connecting the cable with conduit shall be routed
through a hole in the conduit panel.
CAUTION
CAUTION
Table 6—Electrical Data
DLFCAB - DLCCAR / DLFCHB - DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
MCA A 12 17 9 9 16 20 20 24
MOCP A 20 25 15 15 25 30 30 40
Table 7—Electrical Data
DLFDAB - DLCDAR / DLFDHB - DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
MCA A 17 20 9 9 16 15/16 20 24
MOCP A 25 30 15 15 25 25 30 40
421 019420 02 5
Specifications subject to change without notice.
Loading...
+ 11 hidden pages