International comfort products DLF4A6, DLF4A9, DLC4A6, DLC4A9, DLC4A18 Service Manual

...
SERVICE MANUAL
R410A Ductless Split System
Air Conditioner and Heat Pump
MODELS: DLC4(A/H)6−Outdoor, DLF4(A/H)6−Indoor
SIZES: 9K, 12K, 18K, and 24K
INTRODUCTION
This Service Manual provides the necessary information to service, repair, and maintain the DLF4(A,H), DLC4(A/H)
TABLE OF CONTENTS PAGE
SAFETY CONSIDERATIONS 1........................
MODEL / SERIAL NUMBER NOMENCLATURE 2........
STANDARD FEATURES AND ACCESSORIES 3.........
PHYSICAL DATA 4−7.................................
AHRI CAPACITY RATINGS 8..........................
AIRTHROW DATA 8..................................
SOUND RATINGS 9..................................
DIMENSIONS INDOOR 10...........................
DIMENSIONS OUTDOOR 11........................
CLEARANCES 13....................................
SYSTEM OPERATING ENVELOPE 14.................
ELECTRICAL DATA 17...............................
CONNECTION DIAGRAMS 18.........................
WIRING DIAGRAMS 19...............................
REFRIGERATION SYSTEM DIAGRAM 23...............
SYSTEM EVACUATION AND CHARGING 25............
REMOTE CONTROL AND FUNCTIONS 26−27...........
FUNCTION AND CONTROLS 28−31....................
TROUBLESHOOTING 3259..........................
APPENDIX TABLES 60−62...........................
UNIT REMOVAL PROCEDURES 63....................
Indoor 9k − 12k 115v 64.................................
Outdoor 9k 12k 115v 75...............................
Indoor 12k 18k 230v 79................................
Outdoor 12k 230v 85...................................
Outdoor 18k 230v 90...................................
Indoor 24k 230v 96.....................................
Outdoor 24k 230v 102..................................
service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety−alert
!
!
symbol instructions or manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
When you see this symbol on the unit and in
!
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer,
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start−up.
CAUTION
421 08 9205 00 2/21/14
MODEL NOMENCLATURE
MODEL SERIES Position Number 1 2 3 4 5 6 7 8 9 10 11
DLC = Outdoor DLF = Indoor Outdoor/Indoor
4A6 = AC 4H6 = HP
09 = 9k BTU 12 = 12k BTU 18 = 18k BTU 24 = 24k BTU
J = 115−1−60 K = 208/230−1−60
1A Factory Designation
D L C 4 A 6 0 9 J 1 A
Type
Size
Voltage
2 421 01 9204 01
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation
Mounting Brackets S
Low Voltage Controls S Comfort Features Microprocessor Controls S
Wireless Remote Control S Rapid Cooling/Heating S Automatic Air Sweep S Cold Blow Prevention S Continuous Fan * S Auto Restart Feature S Memory Function S Auto Changeover on Heat Pumps S Dry Function S
Energy Saving Features
Inverter Driven Compressor S Sleep Mode S 24 Hour Stop/Start Timer S
Safety And Reliability
Indoor Unit Freeze Protection S 3 Minute Compressor Time Delay S High Compressor Discharge Temperature S Low Voltage Protection S Compressor Overload Protection S Compressor Over current Protection S IPM Module Protection S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostic LED’s On Outdoor Board S Error Messages Displayed Front Panel S
Application Flexibility
Condensate Pump A
Standard Warranty
7 Year Compressor Limited Warranty** S 5 Year Parts Limited Warranty** S
Legend S Standard A Accessory O Optional F Field Fabricated
* Cooling Only ** For owner occupied residential applications.
For Commercial applications, warranty is 1 year parts and 5 years compressor.
INDOOR UNITS
On high wall fan coils, the condensate pump accessory is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
The pump has a lift capability of 12 ft (3.6 m) on the discharge side if the pump is mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump is remote mounted.
16 ft Transparent Suction/Discharge Tubing 1 Condensate Pump Assembly 1 Low voltage Power Cord 1 Transparent Detection Unit Vent Tubing 1 Power Cable 1 Wire Ties 6 Wall Mount Bracket 1 Adhesive 1 Detection Unit Mounting Bracket 1 -in Rubber Elbow 1 Detection Unit 1
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
Figure 1 - Condensate Pump Accessory
Table 1—Accessory Condensate Pump Kit Contents
Item Qty.
!
WARNING
A07892
3 421 08 9205 00
PHYSICAL DATA − DLC4A6
Outdoor Unit DLC4A6 09 12 12 18 24
System Voltage 115-1-60 208/230-1-60
Control Voltage Low Voltage Pulse DC
Rated Cooling Capacity (Btuh) 9,000 11,800 12,000 18,000 22,000
Cooling. Capacity Range Min - Max (Btuh)
Operating Weight lb. (kg) 75 (34) 63.8 (30) 112.2 (51)
Refrigerant Type R-410A
Metering Device @ Outdoor Unit Cap. Tube EXV
Charge lb. (kg) 2.3 (1.05) 2.8 (1.27) 2.2 (1.0) 2.8 (1.27) 3.4 (1.55)
Compressor
Type Twin Rotary Inverter Driven
Model KNB092FHBMC QXA-B096ZC190 SNB130FGYMC C-6RZ146H1A
Outdoor Fan
CFM 1060 942 1880 1880
RPM 850 880 690 690
Diameter (in) 15.7 14.6 20.5 20.5
Watts 30 21 60
Outdoor Coil
Face Area (sq.) 4.4 3.7 5.9 6.1
No. Rows 2
Fins per inch 16 18
Refrigerant Lines
Connection Type Flare
Liquid (Mix Phase) in OD 1/4"
Vapor Line in OD 3/8" 1/2"
Maximum Length ft. 50 65 50 82
Max Lift (Fan Coil Above) ft. 33
Max Drop (Fan Coil Below) ft. 33
External Finish White
3,500-11,000 3,300-12,500 3,300-12,500 4,500-21,000 6,400-24,000
421 08 9205 00 4
PHYSICAL DATA CONTINUED DLF4A6
Indoor Unit DLF4A6 09 12 12 18 24 System Voltage 115 V 208/230-1-60 Control Voltage Low Voltage Pulse DC Electrical Connections Indoor Unit Powered From Outdoor Unit Rated Cooling Capacity (Btuh) 9,000 11,800 12,000 18,000 22,000 Operating Weight lb. (kg) 18.7 (8.5) 19.8 (9.0) 26.5 (12.0) 33.1 (15.0) Refrigerant Type R-410A Metering Device @ Outdoor Unit Cap. Tube EXV Moisture Removal Rate (pints/hr.) 1.7 2.9 2.9 3.8 4.5 Indoor Fan RPM/CFM (Turbo) - Cooling 1300/330 1350/341 1350/341 1400/471 1350/588
RPM/CFM (High) - Cooling 1100/277 1150/288 1150/288 1150/400 1150/471 RPM/CFM (Medium) - Cooling 900/224 950/235 950/235 1000/330 1000/412 RPM/CFM (Low) - Cooling 700/188 750/200 750/200 850/271 850/353 Motor Watts 15 20 35 Blower Quantity … Size (DxL) in 1 3.62 x 23.4 1 3.9 x 25.6 1 3.9 x 30.1
Indoor Coil
Face Area (sq.) 1.93 2.2 2.8 No. Of Rows 2 Fins Per Inch 18 17
Filters
Quantity 2 2 2 2 Controls Integrated Microprocessor Wireless Remote Standard Modes Cool/Heat/Dry/Auto Fan Mode High/Medium/Low/Auto Emergency Mode Yes Defrost Method Demand Defrost Diagnostics Yes Air Sweep Yes Soft Start Yes Rapid Cooling/Heating Ye s Cold Blow Prevention Yes Sleep Mode Yes 24 Hour Timer Yes Auto Restart Yes Freeze Protection On Indoor Unit Yes
Refrigerant Lines
Connection Type Flare Liquid (Mix Phase) in OD 1/4" Vapor Line in OD 3/8" 1/2" Maximum Length ft. 50 65 50 82 Max Lift (Fan Coil Above) ft. 33 Max Drop (Fan Coil Below) ft. 33
Condensate Drain
Size in ID = 1/2" OD = 5/8" External Finish White
5 421 08 9205 00
PHYSICAL DATA CONTINUED DLC4H6
Outdoor Unit DLC4H6 09 12 12 18 24
System Voltage 115-1-60 208/230-1-60
Control Voltage Low Voltage Pulse DC
Rated Cooling Capacity (Btuh) 9,000 11,800 12,000 18,000 22,000
Cooling. Capacity Range Min - Max (Btuh)
Rated Heating Capacity (Btuh) 9,800 13,000 12,000 19,200 24,200
Heating. Capacity Range Min - Max (Btuh)
Operating Weight lb (kg) 75 (34) 63.8 (30) 112.2 (51)
Refrigerant Type R-410A
Metering Device @ OD Unit Cap. Tube EXV
Charge lb (kg) 2.2 (1.0) 2.9 (1.3) 3.4 (1.55)
Compressor
Type Twin Rotary Inverter Driven
Model KNB092FHBMC QXA-B096ZC190 SNB130FGYMC C-6RZ146H1A
Outdoor Fan
CFM 1060 942 1880 1880
RPM 850 880 690 690
Diameter (in) 15.7 14.6 20.5 20.5
Watts watts 30 21 60
Outdoor Coil
Face Area (sq. ft) 4.4 3.7 5.9 6.1
No. Rows 2
Fins per inch 16 18
Refrigerant Lines
Connection Type Flare
Liquid (Mix Phase) in OD 1/4"
Vapor Line in OD 3/8" 1/2"
Maximum Length ft 65 50 82
Max Lift (Fan Coil Above) ft 33
Max Drop (Fan Coil Below) ft 33
External Finish White
3,500 - 11,000 3,300 - 12,500 3,300 - 12,500 4,500 - 21,000 6,400 - 24,000
2,500 - 11,000 3,400 - 13,500 3,400 - 13,500 4,000 - 23,000 4,100 - 24,200
421 08 9205 00 6
PHYSICAL DATA CONTINUED DLF4H6
Indoor Unit DLF4H6 09 12 12 18 24 System Voltage 115 V 208/230-1-60 Control Voltage Low Voltage Pulse DC Electrical Connections Indoor Unit Powered From Outdoor Unit Rated Cooling Capacity (Btuh) 9,000 11,800 12,000 18,000 22,000 Rated Heating Capacity (Btuh) 9,800 13,000 12,000 19,200 24,200 Operating Weight lb (kg) 18.7 (8.5) 19.8 (9.0) 26.5 (12.0) 33.1 (15.0) Refrigerant Type R-410A Metering Device @ Outdoor Unit Cap. Tube EXV @ Outdoor Unit Moisture Removal Rate(pints/hr) 1.7 2.9 3.8 4.2 Indoor Fan RPM/CFM (Turbo) - Cooling 1300/330 1350/341 1350/341 1400/471 1350/588
RPM/CFM (High) - Cooling 1100/277 1150/288 1150/288 1150/400 1150/471 RPM/CFM (Medium) - Cooling 900/224 950/235 950/235 1000/330 1000/412 RPM/CFM (Low) - Cooling 700/188 750/200 750/200 850/271 850/353 RPM/CFM (Turbo) - Heating 1300/330 1350/341 1350/341 1450/471 1350/588 RPM/CFM (High) - Heating 1150/277 1200/288 1200/288 1250/400 1150/471 RPM/CFM (Medium) - Heating 980/224 1000/235 1000/235 1100/330 1000/412 RPM/CFM (Low) - Heating 820/188 850/200 850/200 950/271 900/353 Motor Watts 15 20 35 Blower Quantity … Size (DxL) in 1 3.62 x 23.4 1 3.9 x 25.6 1 3.9 x 30.1
Indoor Coil
Face Area (sq.ft) 1.93 2.2 4.2 No. Of Rows 2 Fins Per Inch 18 17
Filters
Quantity 2 2 2 2 Controls Integrated Microprocessor Wireless Remote Standard Modes Cool/Heat/Dry/Auto Fan Mode High/Medium/Low/Auto Emergency Mode Yes Defrost Method Demand Defrost Diagnostics Yes Air Sweep Yes Soft Start Yes Rapid Cooling/Heating Yes Cold Blow Prevention Yes Sleep Mode Yes 24 Hour Timer Yes Auto Restart Yes Freeze Protection On Indoor Unit Yes
Refrigerant Lines
Connection Type Flare Liquid (Mix Phase) in OD 1/4" Vapor Line in OD 3/8" 1/2" Maximum Length ft 65 50 82 Max Lift (Fan Coil Above) ft 33 Max Drop (Fan Coil Below) ft 33
Condensate Drain
Size in ID = 1/2" OD = 5/8" External Finish White
7 421 08 9205 00
AHRI* CAPACITY RATINGS
Model Numbers Cooling High Heating 47°F Low Heating 17°F
Outdoor Unit Indoor Unit
Capacity
(Btuh)
EER SEER
Capacity
(Btuh)
HSPF Capacity (Btuh)
DLC4A609J1A DLF4A609J1A 9,000 12.0 16.0 - - ­DLC4A612J1A DLF4A612J1A 11,800 9.4 16.0 - - ­DLC4A612K1A DLF4A612K1A 12,000 9.8 16.0 - - ­DLC4A618K1A DLF4A618K1A 18,000 11.1 16.0 - - ­DLC4A624K1A DLF4A624K1A 22,000 10.0 16.0 - - ­DLC4H609J1A DLF4H609J1A 9,000 12.0 16.0 9,800 8.6 5,400
DLC4H612J1A DLF4H612J1A 11,800 9.4 16.0 13,000 8.6 8,500 DLC4H612K1A DLF4H612K1A 12,000 9.8 16.0 12,000 8.5 6,800 DLC4H618K1A DLF4H618K1A 18,000 11.1 16.0 19,200 8.0 12,000 DLC4H624K1A DLF4H624K1A 22,000 10.0 16.0 24,200 8.5 18,600
*Air Conditioning, Heating & Refrigeration Institute
- = N/A
Legend HSPF - Heating Seasonal Performance Factor SEER - Seasonal Energy Efficiency Ratio NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80F (26.67C) db, 67F (19.44C) wb air entering indoor unit and 95F (35C) db air entering outdoor unit. High Temperature Heating Standard: 70F (21.11C) db air entering indoor unit and 47F (8.33C) db, 43F (6.11C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for air flows at all available fan speeds.
AIR THROW DATA
Approximate Air Throw ft. (m)
Unit Size
9 K 18 (5.5) 21 (6.4) 23 (7.0) 28 (8.5) 12 K 20 (6.1) 23 (7.0) 25 (7.6) 30 (9.1) 18 K 22 (6.7) 27 (8.2) 33 (10.1) 39 (11.9) 24 K 25 (7.6) 29 (8.8) 34 (10.4) 42 (12.8)
Low Medium High Turbo
421 08 9205 00 8
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
DLC4A609J1A 63 53
DLC4A612J1A 65 55
DLC4A612K1A 62 52
DLC4A618K1A 66 56
DLC4A624K1A 63 53
DLC4H609J1A 63 53
DLC4H612J1A 65 55
DLC4H612K1A 62 52
DLC4H618K1A 66 56
DLC4H624K1A 66 56
Indoor Units
Low Medium High Turbo
Model Number
DLF4A609J1A 42 32 45 35 47 37 50 40
DLF4A612J1A 42 32 45 35 47 37 50 40
DLF4A612K1A 38 28 43 33 49 39 54 44
DLF4A618K1A 44 34 48 38 53 43 58 48
DLF4A624K1A 44 34 49 39 53 43 59 49
DLF4H609J1A (cool/heat) 42/42 32/32 45/45 35/35 47/47 37/37 50/50 40/40
DLF4H612J1A (cool/heat) 42/42 32/32 45/45 35/35 47/47 37/37 50/50 40/40
DLF4H612K1A (cool/heat) 38/38 28/28 43/43 33/33 49/49 39/39 54/54 44/44
DLF4H618K1A (cool/heat) 44/44 34/34 48/48 38/38 53/53 43/43 58/58 48/48
DLF4H624K1A (cool/heat) 44/44 34/34 49/49 39/39 53/53 43/43 59/59 49/49
NOTES:
1. Sound power ratings are per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
Sound Power
dBA
Sound
Pressure
dBA
Sound Power
dBA
Sound
Pressure
dBA
Sound Power
dBA
Sound
Pressure
dBA
Sound Power
dBA
Sound
Pressure
dBA
9 421 08 9205 00
DIMENSIONS INDOOR
Unit Size
9 K 30.3 (770) 11.1 (283) 7.9 (201) 18.7 (8.5) 12 K 30.3 (770) 11.1 (283) 7.9 (201) 19.8 (9.0) 18 K 34.0 (865) 12.0 (305) 8.5 (215) 26.4 (12) 24 K 39.7 (1008) 12.6 (319) 8.7 (221) 33.1 (15.0)
DIMENSIONS OUTDOOR
W
In. (mm)
WD
H
A12377
H
In. (mm)
D
In. (mm)
Net Operating Weight
Lbs. (Kg)
Figure 2 - Indoor Unit Dimensions
30.0 (762)
10.1 (257)
Unit: IN. (mm)
33.4 (848)
11.7 (267)
21.3 (540)
Figure 3 - 9K and 12K 115V (Net Operating Weight: 75 lbs. / 34 kg)
21.3 (540)
12.6 (320)
A12531
421 08 9205 00 10
DIMENSIONS OUTDOOR
10.8 (274)
25.9 (658)
21.7 (551)
Unit: IN. (mm)
28.0 (711)
18.5 (470)
11.8 (300)
Figure 4 - 12K 230V (Net Operating Weight: 63.8 lbs. / 30 kg)
12.5 (318)
Unit: IN. (mm)
A12532
11 421 08 9205 00
13.4 (340)
35.0 (890)
27.6 (700)
Unit: IN. (mm)
37.9 (963)
22.0 (560)
14.3 (364)
Figure 5 - 18K and 24K (Net Operating Weight: 112.2 lbs. / 51 kg)
15.6 (396)
A12533
421 08 9205 00 12
CLEARANCES
Indoor Unit
Distance to Ceiling
6 in (152 mm)
Distance to Wall
6 in (152 mm)
Distance in Front of Unit
118 in (2997 mm)
The clearance dimensions are necessary for a correct installation
Distance to Floor
66 in (1676 mm)
and are the minimum permissible distances to adjacent structures.
Outdoor Unit
Distance to Wall
6 in (152 mm)
NOTE: Refrigerant lines may be routed in any of the (4) directions, right, right rear, left, or left rear. See instructions for details
Distance to Back Wall 12 in (305 mm)
Air Discharge Side
79 in (2007 mm)
Figure 6 - Indoor and Outdoor Unit Clearances
13 421 08 9205 00
Above Unit
20 in (508 mm)
Air Inlet Side
12 in (305 mm)
Distance to Wall
20 in (508 mm)
valve cover
A12385
SYSTEM OPERATING ENVELOPE
64.4ºF
75ºF
5ºF
113ºF
Heating
5ºF
75ºF
5ºF
86ºF
109ºF
Supply Voltage 115-1-60 AC 208/230-1-60 AC
Model 9k 12k 12k 18k 24k
Indoor Operating Range (A/C and HP) °F (°C)
Cooling Ambient Operating Range (A/C) °F (°C)
Cooling Ambient Operating Range (HP) °F (°C)
Heating Ambient Operating Range (HP) °F (°C)
64 - 113 (18 - 45)
64 - 113 (18 - 45)
5 - 75
(-15 - 24)
64 - 113
(18 - 45)
64 - 113
(18 - 45)
5 - 75
(-15 - 24)
See Figure 7 8 9 10 & 11
120
110
100
90
86ºF
80
Heating
Continuous
Indoor Temperature (°F)
70
Operation
61 - 86 (16 - 30)
5 - 109
(-15 - 43)
5 - 109
(-15 - 43)
5 - 75
(-15 - 24)
Cooling
Continuous
Operation
5 - 118
(-15 - 48)
5 - 118
(-15 - 48)
19 - 75
(-7 - 24)
86ºF
5 - 118
(-15 - 48)
5 - 115
(-15 - 46)
19 - 75
(-7 - 24)
61ºF
60
50
40
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (°F)
61ºF
Figure 7 - 9k / 12k 115V System Operating Envelope
120
110
100
90
86ºF
Indoor Temperature (°F)
80
Continuous
70
61ºF
60
Operation
Cooling
Continuous
Operation
61ºF
50
40
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
421 08 9205 00 14
Outdoor Temperature (°F)
Figure 8 - 12k 230V System Operating Envelope
SYSTEM OPERATING ENVELOPE CONTINUED
Heating
5ºF
75ºF
19ºF
86ºF
118ºF
Cooling
5ºF
118ºF
120
110
100
90
80
Continuous
Indoor Temperature (°F)
70
Operation
86ºF
Cooling
Continuous
Operation
61ºF
60
50
40
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (°F)
61ºF
Figure 9 - 18k 230V System Operating Envelope
120
110
100
F)
°
90
86ºF
80
Continuous
70
Indoor Temperature (
60
Operation
61ºF
50
40
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Figure 10 - 24k AC 230V System Operating Envelope
15 421 08 9205 00
Outdoor Temperature (°F)
SYSTEM OPERATING ENVELOPE CONTINUED
Heating
50ºF
75ºF
5ºF
86ºF
118ºF
120
110
100
F)
°
90
80
70
Indoor Temperature (
Continuous
Operation
86ºF
Cooling
Continuous
Operation
61ºF
60
50
40
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
Outdoor Temperature (°F)
61ºF
Figure 11 - 24k HP 230V System Operating Envelope
421 08 9205 00 16
ELECTRICAL DATA
Cooling Only
Operating
System Voltage
Unit
Size
9 K 115 -1 - 60 127/103 9.76 25.00 0.17 30 12 K 115 -1 - 60 127/103 11.20 25.00 0.17 30 15 25 12 K 208/230-1-60 253/187 7.30 16.50 0.25 21 208/230 0.19 15 10 15 18 K 208/230-1-60 253/187 10.86 27.00 0.62 60 208/230 0.32 20 15 25 24 K 208/230-1-60 253/187 11.71 41.00 0.62 60 208/230 0.45 35 16 25
Heat Pump
9 K 115-1-60 127/103 9.76 20.00 0.17 30 12 K 115-1-60 127/103 11.20 20.00 0.17 30 15 25 12 K 208/230-1-60 253/187 7.30 16.50 0.25 21 208/230 0.19 15 10 15 18 K 208/230-1-60 253/187 10.86 27.00 0.62 60 208/230 0.32 20 15 25 24 K 208/230-1-60 253/187 12.50 41.00 0.62 60 208/230 0.45 35 17 25
* Permissible limits of the voltage range at which the unit will operate satisfactorily Indoor fan powered from outdoor unit.
LEGEND FLA - Full Load Amps LRA - Locked Rotor Amps MCA - Minimum Circuit Amps RLA - Rated Load Amps MOCP- Maximum Over Current Protection
Voltage*
MAX /
MIN
Compressor Outdoor Fan Indoor Fan{
RLA LRA FLA W VOLTS FLA W
115 0.38 15
115 0.38 15
MCA
13 20
13 20
WIRING
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum
over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only copper conductors with a minimum 300 volt rating and 2/64inch thick insulation must be used.
MAX
FUSE/ CB Amp (MOCP)VOLT-PH-HZ
Control Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64inch thick insulation, must be used as the communication wire from from the outdoor unit to the indoor unit.
To minimize voltage drop of the control wire, use the following wire size and maximum lengths shown in the chart below.
Wire Size
18 AWG 50 ft. (15 m) 16 AWG 50 ft (15) to 100 ft. (30 m)
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Be sure to comply with local codes while running wire from indoor unit to outdoor unit.
Every wire must be connected firmly. Loose wiring may cause terminal to overheat or result in unit malfunction. A
Length
ft (m)
CAUTION
fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
No wire should be allowed to touch refrigerant tubing, compressor or any moving parts.
Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through hole in the conduit panel.
17 421 08 9205 00
CONNECTION DIAGRAMS
DLC4 18K~24K Outdoor Unit Terminal Block
Control
from
Outdoor
Unit
DLF4 18K~24K Indoor Unit Terminal Block
DLC4/DLF4 18K~24K 208/230-1-60 Connection Diagram
CONNECTING CABLE
OUTDOOR TO INDOOR
Power from
Outdoor Unit
Power to
Indoor Unit
Main Power
Supply
Main Power
Supply
Power from
Outdoor Unit
Power to
Indoor Unit
Control to
Indoor Unit
CAUTION
Attention
Use Copper Conductors Only With Minimum 300 Volt, 2/64" Thick Insulation.
Utilisez seulement des conducteurs en cuivre d'un minimum de 300 volt d'une isol at ion d' èpaisseur de 2/64".
Power from
Outdoor Unit
DLC4/DLF4 12K 208/230-1-60 Connection Diagram
Control to
Indoor Unit
Control from
Outdoor Unit
Power from
Outdoor Unit
CONNECTING CABLE
OUTDOOR TO INDOOR
Power to
Indoor Unit
Power to
Indoor Unit
Main Power
Supply
Main Power
Supply
DLC4 12K Outdoor Unit Terminal Block
DLF4 12K Indoor Unit Terminal Block
CAUTION
Attention
Use Copper Conductors Only With Minimum 300 Volt, 2/64" Thick Insulation.
Utilisez seulement des conducteurs en cuivre d'un minimum de 300 volt d'une isolation d' èpaisseur de 2/64".
N S L GND N S L GND
NLGND
DLC4H6 9K-12K Heat Pump Outdoor Unit
Terminal Block
DLF4H6 9K-12K Heat Pump Indoor Unit
Terminal Block
Main Power
Supply
Main Power
Supply
DLC4H6/DLF4H6 9K-12K 115-1-60 Heat Pump Connection Diagram
CONNECTING CABLE
OUTDOOR TO INDOOR
Power to
Indoor Unit
Control to
Indoor Unit
Power to
Indoor Unit
Power from
Outdoor Unit
Control from Outdoor Unit
Power from
Outdoor Unit
CAUTION
Attention
Use Copper Conductors Only With Minimum 300 Volt, 2/64" Thick Insulation.
Utilisez seulement des conducteurs en cuivre d'un minimum de 300 volt d'une isol at ion d' èpaisseur de 2/64".
DLC4A6/DLF4A6 9K~12K 115-1-60 Cooling Only Connection Diagram
DLC4A6 9K~12K Outdoor Unit Terminal Block
CONNECTING CABLE
OUTDOOR TO INDOOR
Power to
Indoor Unit
Power to
Indoor Unit
Power from
Outdoor
Unit
Power from
Outdoor
Unit
Control to
Indoor Unit
Control
from
Outdoor
Unit
Main
Power
Supply
Main Power Supply
DLF4A6 9K~12K Indoor Unit Terminal Block
CAUTION
Attention
Use Copper Conductors Only With Minimum 300 Volt, 2/64" Thick Insulation.
Utilisez seulement des conducteurs en cuivre d'un minimum de 300 volt d'une isol at ion d' èp aisseur de 2/64".
N S L L N GND N S L GND
Ground Ground
115-1-60 Low V DC 115-1-60 115-1-60 115-1-60 115-1-60 Low V DC 115-1-60
Ground Ground
115-1-60 Low V DC 115-1-60 115-1-60 Low V DC 115-1-60
Ground
115-1-60 115-1-60
L2 S L1 GND L2 S L1 GND
Ground Ground
208/230-1-60 Low V DC 208/230-1-60 208/230-1-60 Low V DC 208/230-1-60
L2 L1 GND
Ground
208/230-1-60 208/230-1-60
L2SL1L1L2GND L2SL1GND
Ground Ground
208/230-1-60 Low V DC 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Low V DC 208/230-1-60
NOTE: Polarity of power wires muct match original connection on outdoor unit.
Figure 12 - Connection Diagrams
421 08 9205 00 18
A13080
19 421 08 9205 00
CONNECTION DIAGRAMS
WIRING DIAGRAMS
A13081
DLF4A609/12
DLC4A609/12
Figure 13 - 9K / 12K Cooling Only 115−1−60
20 421 08 9205 00
CONNECTION DIAGRAMS
A13082
DLF4H609/12J1
A
DLC4H609/12J1
A
Figure 14 - 9K / 12K Heat Pump Only 115−1−60
421 08 9205 00 21
CONNECTION DIAGRAMS
DIAGRAMS CONTINUED
A13083
DLF4H612K1
A
DLC4H612K1
A
Figure 15 - 12k Heat Pump Only 230−1−60
22 421 08 9205 00
CONNECTION DIAGRAMS
A13084
DLF4A618/24K1
A
DLC4A618/24K1
A
Figure 16 - 18K / 24K 230−1−60
REFRIGERATION SYSTEM DIAGRAMS
GAS SIDE
TINU ROODTUOTINU ROODNI
HEAT EXCHANGE (EVAPORATOR)
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
Muffler
Discharge
Suction
COMPRESSOR
Accumlator
HEAT EXCHANGE (CONDENSER)
Capillary
Figure 17 - Refrigeration System Diagram DLC/DLF4A6 Cooling Only
9k / 12k 115v; 12k / 18k 230v
TINU ROODTUOTINU ROODNI
reniartSreniartS
COOLING
A13086
GAS SIDE
3-WAY VALVE
HEAT EXCHANGE (EVAPORATOR)
LIQUID SIDE
2-WAY VALVE
Figure 18 - Refrigeration System Diagram DLC/DLF4H6
Refrigerant Pipe Diameter: 9k / 12k Liquid: 1/4” (6.4 mm) Gas: 3/8” (9.5 mm)
18k Liquid: 1/4” (6.4 mm) Gas: 1/2” (12.7 mm)
Discharge
Suction
COMPRESSOR
12k / 18k 230v
4-Way valve
Muffler
Accumlator
HEAT EXCHANGE (CONDENSER)
Capillary reniartSreniartS
COOLING
HEATING
A13087
23 421 08 9205 00
REFRIGERATION SYSTEM DIAGRAMS CONTINUED
INDOOR OUTDOOR
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
Muffler
Discharge
Suction
COMPRESSOR
Accumlator
Electronic Expansion Valve
HEAT EXCHANGE (CONDENSER)
Strainer
Figure 19 - Refrigeration System Diagram DLC/DLF4A6 Cooling Only
24k 230v
TINU ROODTUOTINU ROODNI
COOLING
A13088
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
3-WAY VALVE
LIQUID SIDE
2-WAY VALVE
Muffler
Discharge
Suction
COMPRESSOR
Accumlator
4-Way valve
Expansion valve
HEAT EXCHANGE (CONDENSER)
reniartSreniartS
COOLING
HEATING
Figure 20 - Refrigeration System Diagram DLC/DLF4H6
9k / 12k 115v; 24k 230v
Refrigerant Pipe Diameter: 9k / 12k Liquid: 1/4” (6.4 mm) Gas: 3/8” (9.5 mm)
24k Liquid: 1/4” (6.4 mm) Gas: 1/2” (12.7 mm)
24 421 08 9205 00
A13089
SYSTEM EVACUATION AND CHARGING
t
Deep Vacuum Method
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
(1.) Completely tighten flare nuts A, B, C, D, connect
manifold gage charge hose to a charge port of the low side service valve. (See Fig. 21.)
(2.) Connect charge hose to vacuum pump.
(3.) Fully open the low side of manifold gage. (See Fig.
22)
(4.) Start vacuum pump
(5.) Evacuate using either deep vacuum or triple
evacuation method.
(6.) After evacuation is complete, fully close the low side
of manifold gage and stop operation of vacuum pump.
(7.) The factory charge contained in the outdoor unit is
good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.1 oz. per foot of extra piping up to allowable maximum length listed in physical data.
(8.) Disconnect charge hose from charge connection of
the low side service valve.
(9.) Fully open service valves B and A.
(10.) Securely tighten caps of service valves.
Outdoor Unit
Service Valve
CAUTION
Refrigerant
Low Side
A
High Side
B
Figure 21 - Service Valve
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 23)
Triple Evacuation Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 24 and proceed as follows:
Indoor Uni
C
D
A07360
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
Figure 23 - Deep Vacuum Graph
(1.) Pump system down to 28 in. of mercury and allow
pump to continue operating for an additional 15
minutes. (2.) Close service valves and shut off vacuum pump. (3.) Connect a nitrogen cylinder and regulator to system
and open until system pressure is 2 psig. (4.) Close service valve and allow system to stand for 1
hr. During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture. (5.) Repeat this procedure as indicated in Fig. 24. System
will then be free of any contaminants and water
vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
Manifold Gage
500 microns
Low side valve
Charge hose
Low side valve
High side valve
Charge hose
Figure 22 - Manifold
421 08 9205 00 25
Vacuum pump
A07361
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Figure 24 - Triple Evacuation Method
Final Tubing Check IMPORTANT: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
REMOTE CONTROL AND FUNCTIONS
ON/OFF
(1)
Press to start or stop operation
AUTO
FAN
AIR
HEALTH
OPER
X-FAN
HUMIDITY
FILTER
TURBO
(1) (2)
(3)
(5)
ON/OFF
FAN
HOUR
ON/OFF
MODE
(4)
(6)
(2) MODE Press to select operation mode
(AUTO/COOL/DRY/FAN/HEAT)
(3) - : Press to decrease temperature setting (4) +: Press to increase temperature setting (5) FAN
Press to set fan speed
(6) Horizontal Swing
Press to activate horizontal swing or set louver positions
(7) HEALTH|SAVE (Not Available)
(8) Vertical Swing (Not Available) (9) X-FAN
Press to activate or deactivate DRY function
(10) TEMP Press to alternate between set point and room temperature display (11) TIMER Press to set TIMER ON/ TIMER OFF (12) TURBO
Press to activate or deactivate TURBO mode
(13) SLEEP
Press to activate or deactivate SLEEP mode
(14) LIGHT
Press to activate or deactivate display panel light
(7)
(9)
(12)
X-FAN
TURBO
(10)
(13)
TEMP
SLEEP
TIMER
LIGHT
(8)
(11)
(14)
A12390
Remote Control
26 421 08 9205 00
Remote Control Display
3
1
MODE DISPLAY
AUTO COOL DRY FAN HEAT
8
4
10
15
2
11
6
9
5
SLEEP
14 1312
7
A12391
NOTE: Symbols shown in this manual are for the purpose of demonstration. During actual operation, only the relevant symbols are displayed.
1. TRANSMISSION INDICATOR: Illuminates when re- mote control transmits signals to the indoor unit.
2. This symbol appears when the unit is turned on by the remote control, and disappears when the unit is turned off.
3. FAN SPEED DISPLAY: Indicates the set fan speed. AUTO is displayed when unit is running in AUTO mode.
4. MODE DISPLAY: Indicates the current operation mode “AUTO”, “COOL”, “DRY”, “FAN ONLY”, or “HEAT”
5. SLEEP DISPLAY: Indicates unit is running in SLEEP mode.
6. TEMPERATURE DISPLAY: Temperature setting from 61F (16C) to 86F (30C) will be displayed. If FAN mode is selected, there will be no temperature displayed. During DEFROST operation, H1 will be displayed. During SAVE mode, SE will be displayed.
7. Left/Right Louver Swing: Not available on these models.
8. HEALTH/SAVE: HEALTH is not available. SAVE is available on sizes 18k and 24k. SAVE mode can be applied to cooling mode and when set point is less than 80F (27C).
9. SETTING ON / OFF TIMES: 0.5 to 24 hours.
10. TURBO DISPLAY: Displayed when unit is running in TURBO mode.
11. DRY COIL DISPLAY: Indicates unit is running in DRY COIL mode where the fan continues to run after the unit is shut off to dry the coil.
12. TEMPERATURE DISPLAY: Displays set point or room temperature.
13. SWING DISPLAY: Sets louver position or set louvers to continuously move for better air distribution.
14. LIGHT DISPLAY: Indicates if LED display on the front panel is illuminated or not.
15. LOCK DISPLAY: Indicates if remote control is locked.
Battery Installation
Two AAA 1.5 v alkaline batteries (included) are required for operation of the remote control.
To install or replace batteries :
1. Slide the back cover off the control to open the battery compartment.
2. Remove old batteries if you are replacing the batter­ies.
3. Insert batteries. Follow the polarity markings inside the battery compartment.
4. Replace battery compartment cover.
A08299
NOTE:
1. When replacing batteries, do not use old batteries or a different type battery. This may cause the remote control to malfunction. 2.If the remote is not going to be used for several weeks, remove the batteries. Otherwise battery leakage may damage the remote control.
3. The average battery life under normal use is about 6 months.
4. Replace the batteries when there is no audible beep from the indoor unit or if the Transmission Indicator fails to light.
421 08 9205 00 27
FUNCTION AND CONTROLS
Description of Each Control Operation
Temperature Parameters
Indoor preset temperature (TIndoor ambient temperature (T
Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory function is available, for the first energization, if the compressor is at stop before de−energization, the compressor will be started without a 3minute lag; if the compressor is in operation before deenergization, the compressor will be started with a 3−minute lag; and once started, the compressor will not be stopped within 6 minutes regardless of changes in room temperature;
Cooling Mode
Working Conditions and Cooling Process. When T
amb . Tpreset, the unit will enter cooling operation, in
which case the indoor fan, the outdoor fan and the compressor will work and the indoor fan will run at preset speed. When Tamb v Tpreset 3.6F , the compressor will stop, the outdoor fan will stop with a time lag of 30 seconds (60 seconds for 30k and 36k units), and the indoor fan will run at preset speed. When T
preset 3.6F < Tamb. < Tpreset +1.8F, the unit will
remain at its previous state. Under this mode, the four−way valve will be de−energized and temperature can be set within a range from 61F to 86F. If the compressor is shut down for some reason, the indoor fan and the swing device will operate at original state.
Figure 25 - Cooling Mode
PROTECTION Antifreeze Protection
Under cooling and dehumidifying mode, 6 minutes after the compressor is started: If Tevap v35.6°F, the compressor will operate at reduced frequency. If Tevap v30.2°F is detected for duration of 3 minutes, the compressor will stop, and after 60 seconds, the outdoor fan will stop; and under cooling mode, the indoor fan and the swing motor will remain at the original state.
evap. 42.8°F and the compressor has remained at OFF for
If T at least 3 minutes, the compressor will resume its original operation state.
preset)
amb.)
Total current up and frequency down protection
If Itotal vA, frequency rise will be allowed; if Itotal B, frequency rise will not be allowed; if I will run at reduced frequency; and if I
total C, the compressor total D, the compressor
will stop and the outdoor fan will stop with a time lag of 30s. Lag will be 60s for size 30 and 36 units.
Total Current Table
Unit Size - V
9k115V 10A 12A 14A 16A 12K115V 14A 16A 18A 20A 12K230V 6A 7A 8A 9A 18k230V 8A 9A 10A 11A 24K230V 10A 11A 12A 13A
A B C D
Variables
Heating Mode
Working Conditions and Heating Process
amb. v Tpreset +3.6°F , the unit enters heating mode, in
If T which case the four−way valve, the compressor and the outdoor fan will operate simultaneously, and the indoor fan will run at preset speed in the condition of preset cold air prevention.
amb. Tpreset +9°F , the compressor will stop, the outdoor
If T fan will stop with a time lag of 60s, and the indoor fan will stop after 60second blow at low speed
preset +3.6°F < Tamb. < Tpreset +9°F , the unit will maintain
If T its original operating status. Under this mode, the four−way valve is energized and temperature can be set within a range of 61°F 86°F. The operating symbol, the heating symbol and preset temperature are revealed on the display.
Defrost Mode
Condition and Defrost Process When Toutdoor amb hour, if Toutdoor tube
. ≥41°F and the compressor has run for 3
< 0°F is continuously detected for 1
minute, the unit will enter defrost. [Note: the accumulated time is cleared if one of the below condition is met. Toutdoor ambient > 41°F, the compressor starts up after switching to cooling or dry mode, when defrosting is finished; for other situations besides above conditions, the accumulated time will not be cleared (including the unit stops when reaching the temperature point, the unit stops for protection, switching to fan mode, et. )] When duration of successive heating operations is more than 45 minutes, or accumulated heating time IS more than 90 minutes, and one of the following conditions is reached, the unit will enter the defrost mode after 3 minutes.
Toutdoor amb. >41°F, Toutdoor tube v28.4°F
a.
b. 28.4°F vToutdoor amb. <41°F, Toutdoor tube v21.2°F
c. 23°F
vToutdoor amb. <28.4°F, Toutdoor tube v17.6°F
d. 14°FvTouter amb. <23°F, Touter tube Tcompensatorys
v(Toutdoor amb. 5.4°F)
Toutdoor amb.>14°F Touter tube Tcompensatorys v(Toutdoor amb.
e.
5.4°F)
After energization, for the first defrost, T is not the first defrost, Tcompensation will be determined by
outdoor pipe when defrost ends.
T
outdoor pipe >35.6°F; Tcompensation = 0°F
a. T
b. Toutdoor pipe v35.6°F; Tcompensation = 5.4°F
compensation = 0°F. If it
28 421 08 9205 00
During defrost, if operation time for compressor doesn’t reach 3 minutes, the condenser will not defrost in the next 2 hours. At the time of defrost the compressor stops operation, and 30 seconds later, the outdoor fan stops operation. In an additional 30 seconds, the 4way valve will stop operation. 30 seconds later, compressor will increase it’s frequency to 85 Hz for defrosting. Defrost will last for 450 seconds, or until the outdoor pipe ≥ 50°F. When defrost is complete the compressor will decrease its frequency. 30 seconds later the compressor will stop operation. In 30 seconds the 4−way valve will be started up. 60 seconds later the compressor and outdoor fan will operate.
PROTECTION Cold air prevention
The unit is started under heating mode (the compressor is ON): In the case of T
indoor amb. <75.2°F : if Ttube v107.6°F and
the indoor fan is stopped, the indoor fan will begin to run at low speed with a time lag of 2 minutes. Within 2 minutes, if T
tube >104°F, the indoor fan also will run at low speed; and
after 1minute operation at low speed, the indoor fan will be ramped to operation at a preset speed. Within 1−minute of low speed operation or 2minutes of nonoperation, if
tube>108°F, the fan will run at preset speed.
T In the case of Ti
ndoor amb. ≥ 75°F: if Ttube v108°F, the
indoor fan will run at low speed, and after one minute, the indoor fan will be ramped to preset speed. Within one−minute low speed operation, if T tube>107.6°F, the indoor fan will be ramped to preset speed. Note: T
indoor amb. indicated in and refers to, the
indoor ambient temperature before the command to start the compressor is performed, or after the unit is withdrawn from defrost and the defrost symbol is cleared.
Total current up and frequency down protection
If the total current I I
total X frequency rise will not be allowed; if Itotal Y, the
compressor will run at reduced frequency; and if I
total W, frequency rise will be allowed; if
total Z, the
compressor will stop and the outdoor fan will stop with a time lag of 30s.
Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the fourway valve and the electric heater will stop. Under the mode, temperature can be set within a range of 61°F 86°F.
AUTO Mode
Working conditions and Auto mode process: Under AUTO mode, standard cooling temperature T 77°F and standard heating temperature T Once energized, if T heating mode; if 68°F < T
amb 68°F, the unit will be started under
amb.< 77°F, the unit will run under fan
preset is 64.4°F.
mode and the run indicator will be bright; and if T
preset is
amb 77°F,
the unit will be started under cooling mode. Under AUTO mode, if T
amb.wTpreset is detected, the unit will
select to run under cooling mode, in which case the preset temperature is 77°F; if T
amb.vTpreset −3.6°F, the compressor
will stop, the outdoor fan will stop with a time lag of 1 minute, and the indoor fan will run at preset speed. If T
preset
–(3.6°F)< Tamb.< Tpreset , the unit will remain in its original state.
Under AUTO mode, if Tamb. vTpreset +3.6°F is detected, the unit will select to run under heating mode, in which case the preset temperature is 64.4°F; if T
amb.wTpreset +9°F, the
compressor will stop, the outdoor fan will stop with a time lag of 1 minute, and the indoor fan will blow residual heat; and if T
preset +3.6°F < Tamb. < Tpreset +9°F, the unit will remain in its
original state. The coolingonly unit will run under fan mode. Under AUTO mode, if 68°F
< Tamb. < 77°F, the unit will
remain in its original state.
Protection
In cooling operation, protection is the same as that under the cooling mode.
In heating operation, protection is the same as that under the heating mode.
When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will remain unchanged for at least 6 minutes.
Common Protection Functions and Fault Display under
COOL, HEAT, DRY and AUTO Modes
Overload protection
T tube : measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat exchanger under heating mode.
1) Cooling overload
tube v 125.6°F, the unit will return to its original
a. If T operation state. b. If T tube w 131°F, frequency rise is not allowed.
c. If T tube w136.4°F, the compressor will run at reduced frequency. d. If T
tubew143.6°F, the compressor will stop and the indoor
fan will run at preset speed.
2) Heating overload a. If T
tubev125.6°F, the unit will return to its original operation
state. b. If T
tube w131°F, frequency rise is not allowed.
c. If T tube w136.4°F, the compressor will run at reduced frequency. d. If
T tubew143.6°F, the compressor will stop and the indoor
fan will blow residual heat and then stop.
Exhaust temperature protection of compressor
If exhaust temperature
w208.4°F, frequency is not allowed to
rise. If exhaust temperature
w217.4°F, the compressor will run at
reduced frequency. If exhaust temperature If exhaust temperature
w230°F, the compressor will stop.
w194°F and the compressor has
stayed at stop for at least 3 minutes, the compressor will resume its operation.
Communication fault
If the unit fails to receive correct signals for 3 minutes, a communication fault will be registered and the whole system will stop.
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at a stop for at least 3 minutes, the compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
421 08 9205 00 29
Overload protection
If temperature sensed by the overload sensor is over 239°F, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds. If the temperature drops below 203°F, the overload protection will be reset. If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at a stop for at least 3 minutes, the compressor will resume its operation. Faults of temperature sensors
Description of Sensors Faults
Indoor Ambient Temperature
Indoor Tube Temperature
Outdoor Ambient Temperature
Outdoor Tube Temperature
Exhaust
Overload
The sensor is open or short-circuited for 30 consecutive seconds
The sensor is open or short-circuited for 30 consecutive seconds
The sensor is open or short-circuited for 30 consecutive seconds
The sensor is open or short-circuited for 30 consecutive seconds, and no detection is performed within 10 minutes after defrost begins
After the compressor has run for 3 minutes, the sensor is open or short-circuited for 30 consecutive seconds
After the compressor has run for 3 minutes, the sensor is open or short-circuited for 30 consecutive seconds
(9) UpandDown Swinging Control
When the power is turned on, the up−and−down motor will first move the air deflector to 0 counterclockwise. The air outlet will be closed. After starting the machine, if you don’t set the swinging function, heating mode and autoheating mode, the upanddown air deflector will move to D clockwise; under other modes, the up−and−down air deflector will move to L1. If you set the swing function when you start the machine, then the deflector will swing between L and D. The air deflector has 7 swing states: Location L, Location A, Location B, Location C, Location D, Location L to Location D, stop at any location between LD (the included angle between L~D is the same). The air deflector will be closed at 0 location, and the swing is function only works if the indoor fan is running.
Figure 26 - Swing Angles for Heating and Cooling
NOTE: Refer to Appendix Tables on pages 60-62 for sensor information.
Other Controls (1) ON/OFF
Press the remote button ON/OFF: the on−off state will be changed once each time you press the button.
(2) Mode Selection:
Press the remote button MODE, then select: AUTO, COOL, DRY, FAN, HEAT, or AUTO.
(3) Temperature Setting Option Button
Each time you press the remote button TEMP+ or TEMP−, the setting temperature will be up or down by 1°F. Regulating Range: 61−86°F , the button is useless under the AUTO mode.
(4) Time Switch
You can start and stop the machine according to the setting time with the remote controller.
(5) SLEEP State Control
a. When the indoor unit is in the COOL or DRY mode, and the SLEEP mode has been set, after about 1 hour, the presetting T will raise 1.8°F. It will raise another 1.8°F again after 2 hours. It will raise 3.6°F in 2 hours, then it will run on at the setting temperature and fan speed. b. When the indoor unit is in the HEAT mode, and the Timer has been set, after about 1 hour, the presetting T will reduce
1.8°F, and it will reduce another 1.8°F again after 2 hours. It will reduce 3.6°F in 2 hours, then it will run on at the setting temperature and blower speed. c. The set point stays the same under the FAN mode and AUTO mode.
(6) Indoor Fan Control
The Indoor Fan can be set to HIGH, MED, LOW by remote control, and the Indoor Fan will be respectively run at high, medium, low speed. It can also be set as AUTO. In moisture removal mode, the Indoor Fan will be set to low speed.
(7) Buzzer Control
The buzzer will send a “Beep” sound when the indoor unit is powered up or receives the information sent by the remote control or there is a button pushed.
(8) Auto button
If the controller is on, it will stop when the button is pressed. If the controller is off, it will start when the button is pressed. The swing light will be on, and the main unit will run based on the remote controls current settings.
(10) Display
a. Operation pattern and mode pattern display All the display patterns will display for a time when the unit is powered on, the operation indication icon will display in red under standby status. When the machine is started by remote controller, the indication icon will light and display the current operation mode (the mode light includes: Cooling, Heating and Dry). If you press the light button, all the display icons will go dark. b. Double8 display According to the settings of the remote control, the display may show the current temperature (the temperature scope is from 61°F to 86°F) on the indoor ambient temperature. The heating and air supply temperature will display 77°F under automode, the temperature will display 64°F under the heating mode, and the temperature will display H1 under the defrosting mode.(If you set the Celsius temperature display, the display will show according to Celsius temperature)
(11) Protection function and failure display
E2: Freezeproofing E4: Exhaust protection E5: Over−current protection E6: Communication failure E8: Overload protection F1: Indoor ambient sensor start and short circuit (continuously measured failure for 30S) F2: Indoor evaporator sensor start and short circuit (continuously measured failure for 30S) F3: Outdoor ambient sensor start and short circuit (continuously measured failure for 30S) F2: Outdoor condenser sensor start and short circuit (continuously measured failure for 30S, and not measured within 10 minutes after defrosted) F5: Outdoor exhaust sensor start and short circuit (continuously measured failure for 30S after the compressor has operated 3 minutes) H3: Overload protection of compressor H5: Module protection PH: Highvoltage protection PL: Lowvoltage protection P1: Nominal cooling and heating P2: Maximum cooling and heating P3: Medium cooling and heating P0: Minimum cooling and heating
(12) Drying Function
You may start or stop the dry function under the cooling and dry modes. Automatic heating and air modes do not support the dry function).
30 421 08 9205 00
(13) Memory function when interrupting the power supply Memory content: mode, swing function, light, set temperature and blower speed. After power is interrupted, the machine will start according to the content of the memory automatically. If the last remote control command has not set a timed function, the system will remember the last remote control command and operate accordingly. If the last remote control command has set a timed function and the power supply is interrupted before the time expires, the system will remember the timed function of the last remote control command, the timed time will be recounted from power on. If the last remote control command has set a timed function, the time is up and the system is started or stopped according to the set time when the power supply is interrupted, the system will remember the operation status before the power supply was interrupted, and not carry out the timed action; The time clock will not be remembered.
Detection of Temperature Sensor Malfunction
Indoor Temperature Sensor Malfunctions of the temperature sensor can be detected at any time. Indoor Pipe Temperature Sensor During defrost, a temperature sensor malfunction will not be detected. Five minutes after finishing defrost, the system will again begin to detect temperature sensor malfunctions. At all other times, a temperature sensor malfunction will be detected when:
1. A shortcircuit occurs to the temperature sensor for 30 seconds: The temperature sensor overheats. In this case to protect the system, the entire unit will stop. At the same time, the temperature protection and temperature sensor malfunction will be shown.
2. An open circuit of the temperature sensor occurs for 30s: The unit will stop and the temperature sensor malfunction will be displayed
Frequency Control
When starting the compressor, or when conditions have varied due to the changes in the room, the frequency must be initialized according to the DD value of the indoor unit and the Q value of the indoor unit. Q value: Indoor unit output determined from indoor unit volume, air flow rate and other factors.
Compressor Protection Function
When turning the compressor from OFF to ON, the system will ramp the frequency up from a lower starting limit to protect the compressor.
Figure 27 - Compressor Frequency (When the
compressor is turned off, it cannot be turned back on for
3 minutes, except after defrost.
Discharge Pipe Control
The discharge pipe temperature is used as the compressor’s internal temperature. If the discharge pipe temperature rises above a certain level, the operating frequency upper limit is set to keep this temperature from going up further.
Input Current Control
Detects an input current with the current transformer as the compressor is running, and sets the upper frequency limit from the input current. In the case of a heat pump, this control is the upper limit control function of the frequency, which takes priority over the lower limit of four way valves activation compensation.
Freezeup Protection Control
During cooling operation, the signals being sent from the indoor unit allow operating frequency limitation and then prevent freezing of the indoor heat exchanger.
Heating Peakcut Control: HeatPump Only
During heating operation, the signals being sent from the indoor unit allow operating frequency limitation and prevent abnormally high pressure.
Defrost Control: Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrost time must be complete or the outdoor heat exchanger temperature must be more than its preset value when finishing.
Conditions for Starting Defrost
The starting conditions must be determined by the outdoor air temperature and heat exchanger temperature. When the system is in heating operation, 6 minutes after the compressor is started, and more than 44 minutes of accumulated time has passed since the start of the operation or end of defrost.
Conditions for Canceling Defrost
The heat exchanger temperature must be between (39°F72°F)
Fan Control Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control in cooling operation
5. Speed control when frequency adjustment function is working
6. Fan control in forced operation
7. Fan control in indoor/outdoor unit silent operation
8. Fan control in powerful mode
9. Fan control in normal operation
Fan OFF Control when Stopped
Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Speed Control in indoor/outdoor unit silent operation
1. When in Cooling Operation When the outdoor air temperature is lower than 99°F, the speed tap must be set to Low.
2. When in Heating Operation When the outdoor air temperature is higher than 39°F, the speed tap must be set to Low (only for heat pump model).
421 08 9205 00 31
TROUBLESHOOTING
Precautions for Performing Inspections and Repairs
Be cautious during installation and maintenance. Follow all rules and regulations to avoid electric shock and to prevent injury or damage.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
Static Maintenance
Static Maintenance is maintenance during deenergization of the indoor unit. For static maintenance, make sure that the unit is deenergized and the plug is disconnected.
Dynamic Maintenance
Dynamic maintenance is the maintenance during energization of the unit. Before dynamic maintenance, check the electricity and ensure that there is a good ground. Check if there is electricity on the case and copper pipe of the indoor unit with a voltage tester.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
A large−capacity electrolytic capacitor is used in the outdoor unit controller (inverter). When the power supply is turned off, charge (charging voltage DC280V to 380V) remains and takes a long time to discharge. Do Not open the outdoor unit for 20 minutes after power has been turned OFF.
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power. At times, such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position. Diagnose troubles according to the trouble diagnosis procedure as described below. Also refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.
No. Trouble Shooting Procedure
1 Confirmation 2 Code displays interpretation of error codes. 3 Basic System Check
WARNING
Confirmation:
1. Confirmation of Power Supply: Confirm that the power breaker operates normally and provides power
2. Confirmation Voltage: Confirm that voltage is AC 220240 ±10%. If voltage is not in this range, the unit may not operate normally.
32 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Display and Interpretation of Error Codes:
This unit has onboard diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the temperature display. Error codes are also displayed on the outdoor unit microprocessor board with colored LED lights. The table below explains the error codes for both units.
Diagnostic Codes
DLC/DLF4(A,H)6 9k / 12k, 115v
Malfunction
Indoor PCB Malfunction EE Replace indoor main board
Anti-freeze Protection E2 Outdoor ambient temperature is too low
System overload protection H4 Check for dirty or blocked heat exchangers
Indoor motor malfunction H6 Check motor mounting and wiring
Indoor pipe temperature sensor malfunction F2 Measure the resistance value in the sensor
Return air temperature sensor malfunction F1 Measure the resistance value in the sensor
Indoor board malfunction UF Replace indoor main board
Compressor overload protection H3 Check overload wiring
Compressor start-up failure Lc
Outdoor fan motor failure UH Check outdoor motor
Low voltage protection E5 Check incoming power
4-way valve malfunction U7 Replace 4-way valve
Compressor phase detection error U1 Replace outdoor main board
Compressor speed reduction H7
Current detection malfunction U5 Replace outdoor main board
Outdoor ambient temperature sensor malfunction
Discharge temperature sensor malfunction (out of range)
Discharge temperature sensor malfunction (open or shorted)
Condenser temperature sensor malfunction (open or shorted)
Heat sink over-temperature P8
DC over-current UU --
Heat sink temperature sensor malfunction P7 Replace outdoor main board
Low charge F0 Check for leaks
DC input voltage is too high PH Check incoming power supply
DC input voltage is too low PL Check incoming power supply
Communication malfunction E6 Check wiring connection
Indoor and outdoor unit mismatched UA Check system combination
Remarks:
Error Code
on indoor unit
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
F3 Measure the resistance value in the sensor
E4 Measure the resistance value in the sensor
F5 Measure the resistance value in the sensor
F4 Measure the resistance value in the sensor
Is outdoor ambient temperature out of system operating range? Is heat sink blocked or damaged?
4 minutes after the compressor has stopped due to a protection error, an error code will be displayed. To display other errors, press the LIGHT button six (6) times within four (4) seconds.
NOTE: Refer to Appendix Tables on pages 60-62 for sensor information.
Repair Method/Cause
421 08 9205 00 33
TROUBLESHOOTING (CONTINUED)
Diagnostic Codes
DLC/DLF4(A,H)6 12K, 230v
Malfunction
Indoor PCB Malfunction EE Replace indoor main board
Anti-freeze Protection E2 Outdoor ambient temperature is too low
System overload protection H4 Check for dirty or blocked heat exchangers
Indoor motor malfunction H6 Check motor mounting and wiring
Indoor pipe temperature sensor malfunction F2 Measure the resistance value in the sensor
Return air temperature sensor malfunction F1 Measure the resistance value in the sensor
Indoor board malfunction UF Replace indoor main board
Compressor overload protection H3 Check overload wiring
Compressor start-up failure Lc
Outdoor fan motor failure UH Check outdoor motor
Low voltage protection E5 Check incoming power
4-way valve malfunction U7 Replace 4-way valve
Compressor phase detection error U1 Replace outdoor main board
Compressor speed reduction H7
Current detection malfunction U5 Replace outdoor main board
Outdoor ambient temperature sensor mal function
Discharge temperature sensor malfunction (out of range)
Discharge temperature sensor malfunction (open or shorted)
Condenser temperature sensor malfunction (open or shorted)
Heat sink over temperature P8
DC over-current H5 --
Heat sink temperature sensor malfunction P7 Replace outdoor main board
Low charge F0 Check for leaks
DC input voltage is too high PH Check incoming power supply
DC input voltage is too low PL Check incoming power supply
Communication malfunction E6 Check wiring connection
Indoor and outdoor unit mismatched UA Check system combination
Error Code on in
door unit
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
F3 Measure the resistance value in the sensor
E4 Measure the resistance value in the sensor
F5 Measure the resistance value in the sensor
F4 Measure the resistance value in the sensor
Is outdoor ambient temperature out of system operating range? Is heat sink blocked or damaged?
Repair Method/Cause
NOTE: Refer to Appendix Tables on pages 60-62 for sensor information.
34 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Diagnostic Codes
DLC/DLF4(A,H)6 18k24k, 230v
Malfunction
System high pressure protection E1
Anti-freeze Protection E2 Outdoor ambient temperature is too low
Discharge temperature sensor malfunction (out of range)
Low voltage protection E5 Check incoming power
Communication malfunction E6 Check wiring connection
System overload protection E8 Refer to Service Manual
Indoor board malfunction U8 Replace indoor main board
Indoor motor malfunction H6 Check motor mounting and wiring
Missing jumper from indoor board C5
Return air temperature sensor malfunction F1 Measure the resistance value in the sensor
Indoor pipe temperature sensor malfunction F2 Measure the resistance value in the sensor
Outdoor ambient temperature sensor malfunc tion
Condenser temperature sensor malfunction (open or shorted)
Discharge temperature sensor malfunction (open or shorted)
Overload limit, compressor speed reduction F6 Refer to Service Manual
Over current compressor speed reduction F8 System voltage is too low or system voltage is high
Compressor discharge temperature high, compressor speed reduction
Over voltage protection PH Check incoming power supply
Current detection malfunction U5 Replace outdoor main board
Compressor current protection P5 Refer to Service Manual. Check inverter board.
Defrosting H1 H1 signal normal operation
Compressor overload protection H3 Check overload wiring
System overload protection H4 Checked for dirty or blocked heat exchangers
IPM protection H5 IPM module over temperature, low voltage, silica grease problem
PFC (power factor correction) board protec tion
Compressor speed reduction H7
Ambient temperature cut off range H0 Refer to Service Manual (overload, high temperature, cutout)
Compressor start-up failure LC
Compressor phase detection error U1 Replace outdoor main board
Error Code
on indoor unit
Poor heat exchange. Are the coils clogged or blocked? Is the ambi ent temperature out of system range?
E4 Measure the resistance value in the sensor
No jumper on controller or installed improperly or damaged. Corres ponding circuit on main board has malfunction.
F3 Measure the resistance value in the sensor
F4 Measure the resistance value in the sensor
F5 Measure the resistance value in the sensor
Load is too great
F9
HC Refer to Service Manual
Ambient temperature too high Refrigerant is low Electric expansion valve malfunction
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
Check if the resistance of the compressor and the resistance to ground is normal. If the resistance is normal, the outdoor main board may be defective.
Repair Method/Cause
NOTE: Refer to Appendix Tables on pages 60-62 for sensor information.
421 08 9205 00 35
TROUBLESHOOTING (CONTINUED)
Malfunction Analysis
Note: When replacing the controller, make sure to insert the jumper into the new controller, otherwise the unit will display C5
Tripped breaker or blown fuse
The air condi­tioner does not react after it is powered (after the power is applied, the buzzer does not sound and the remote startup has no response)
Air conditioner can not start up
The remote con troller does not receive signals (after it is powered, the buzzer will sound, unless it has malfunction)
The breaker trips immediately when it is set to ON.
The breaker trips after a few minutes when it is set to ON
No power
Fuse of controller burnt out
The transformer connection is loose or has a bad contact or the trans­former has malfunctioned
Controller is broken
Remote controller is short of power
Remote controller malfunction
Receiver loose or poor connection
Receiver is broken
Measure insulation resistance to ground to see if there is any leakage.
The circuit or a part of the air conditioner has malfunctioned. Measure the insula­tion resistance or eliminate the malfunc­tion. If the breaker itself has a malfunction, then replace the breaker.
Check power supply circuit.
Change controller fuse
Fasten the wiring; measure the output voltage of the transformer, if it is incorrect, change the trans­former
Change remote controller
Change batteries
First, press the manual switch but­ton AUTO, if there is no re­sponse,check based on the above methods. If it runs normally after pressing the button,check again whether the installation po­sition and the connection wire of the reception head is correct. If it is correct,then replace the receiver or the remote controller.
Power voltage is too low
36 421 08 9205 00
Check the voltage. If it is lower than 10% of the rated voltage, check the cause, and repair.
TROUBLESHOOTING (CONTINUED)
Improperly set temperature
If cooling or heating load is matched to unit
Malfunction of refrigerant flow
Heat insulation for the connection pipes of the indoor unit and the out
Poor COOL (HEAT) operation
door unit is bad.
Adjust set temperature
Check the forecasted load of cooling (heating)
The refrigerant has leakage or is insufficient
Leakage between the high pres
sure and the low pressure in
side the compressor
Malfunction of fourway valve
Blocked capillary or failure of metering device
Make sure that heat insulation for the thick and thin pipes
is good. Heat insulation must also be provided for the
joint and the exposed part of the copper pipe .
Fix the leak and recharge the system.
Replace the compressor
Replace the fourway valve
Replace the capillary or metering device
Block of outdoor heat ex
changer
Air filter were blocked
Fan speed was set too slow
Air circulation is insufficient
Fan rotation speed becomes
low
The installation position of the outdoor unit is not
appropriate.
The outdoor temperature is too high.
Too much air migration. People
come in and out too frequently. There are heating devices indoors.
Clean the dust accumulated on the surface of the heat exchanger.
Clean the filter
Set the fan speed to high or
middle speed
Capacitor
damage
Motor damage
Good ventilation must be provided for the installation of the outdoor unit.
Properly install the rainproof plate or the sunproof plate. If the maximum cool air still can not meet the requirement, it is suggested to replace the air
Replace the
capacitor
Replace the motor
conditioner.
Minimize air migration, try not to use
electrical appliance with large quantity of heat
421 08 9205 00 37
TROUBLESHOOTING (CONTINUED)
The windings of the indoor fan motor are open or the over heat protection has kicked in.
Replace the fan motor or the defective part.
The fan does not run when it is set to supply air.
In the cooling and heating mode, the compressor runs, but the outdoor fan does not run.
In the cooling and heating mode, outdoor fan runs, but compressor doesn’t run
The builtin heat protection of the motor kicks in frequently because the motor is abnormal.
Wrong connection
The fan capacitor has open circuit or is damaged.
The outdoor fan motor is damaged.
Wrong connection
The outdoor fan capacitor is damaged.
Run capacitor of compressor malfunction
The voltage is too low or too high.
Replace the fan motor
Make the correct connection based on the circuit drawing.
Replace the fan capacitor with the same type and same specification.
Replace the fan motor
Make the correct connection based on the circuit drawing.
Replace the fan capacitor
rosserpmocehtecalpeRrosserpmocfonoitcnuflaM
Replace the capacitor
Voltage should be + or 10% or less if it is more,
check cause and repair. Manostat is recommended
The compressor is
too hot and leads to the activation of the protector.
Wrong wire connection
The protector itself has malfunction.
The refrigerant is not enough or is too much.
The capillary is blocked or the metering device has malfunctioned and the temperature rises.
The compressor does not run smoothly or is stuck. The air discharge valve is damaged
The protector itself has malfunction.
Connect according to the circuit diagram.
Use the multimeter to check whether the contact of the compressor is on when it is not overheated. If it is not on, then replace the protector
Adjust the volume of the refrigerant
Replace the capillary or metering device
Replace the compressor
Replace the protector
38 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
The torque of the swing motor is not
enough
The swing fan
does not run.
In cool, heat
mode, the out-
door unit and
compressor will
not run.
Water leakage
Wrong connection
First, check whether the connection is
wrong. If no, replace the parts
The controller is damaged(IC2003 is
damaged, the swing relay can not
close, etc)
Controller malfunction (IC2003
broken, creepage of parallel capaci
tor of relay loop, relay is broken etc.)
Wire loose or wrong connection
Improper setting of temperature
Change controller
Correctly wire according to the drawing
Adjust setting temp.
Drainage pipe blocked or broken Change drainage pipe
Rewrap and make it tight.Air gap in refrigerant pipe insulation
Fan of indoor unit contacts other parts
Adjust fan location
Abnormal sound
and shake
Foreign object in indoor unit
Compressor shakes too much
Refrigerant pipes are touching
Inner mounting plates are touching
Louver of outdoor unit touches
outer case.
Abnormal sound inside compressor
Take out the foreign object
Adjust support washer of compressor,
and tighten loosen screws
Separate the touching pipeline.
1. Tighten screws.
2. Stick absorbing clay between plates.
Adjust location of louver.
Change compressor
421 08 9205 00 39
TROUBLESHOOTING (CONTINUED)
Analysis or processing of some of the malfunction display:
5 Compressor over load protection
1 Compressor discharge protection
Possible causes: shortage of refrigerant; blockage of air filter; poor ventilation or air flow short circuit of condenser; the system has noncondensing gas (such as air, water etc.); blockage of capillary assembly (including filter); malfunction of metering device; leakage inside fourway valve causes incorrect opera­tion; malfunction of compressor; malfunction of protection relay; malfunction of discharge sensor; outdoor temperature too high.
Processing method: refer to the malfunction analysis in the above section.
2 Low voltage overcurrent protection
Possible cause: Sudden drop of supply voltage.
3 Communication malfunction
Processing method: Check if communicating signal cable is connected reliably.
4 Sensor open or short circuit
Processing method: check whether sensor is normal, connec­ted with the corresponding position on the controller and if dam­age of lead wire is found.
Possible causes: insufficient or too much refrigerant; blockage of capillary or metering device and increase of suction temp.; im­proper running of compressor, stuck bearing, damage of dis­charge valve; malfunction of protector.
Processing method: adjust refrigerant amount; replace the ca­pillary or metering device; replace the compressor; use univer­sal meter to check if the contactor of compressor is fine when it is not overheated, if not replace the protector.
6 System malfunction
i.e. overload protection. When tube temperature (check the tem­perature of outdoor heat exchanger when cooling and check the temperature of indoor heat exchanger when heating) is too high, protection will be activated.
Possible causes: Outdoor temperature is too high when cooling; insufficient outdoor air circulation; refrigerant flow malfunction. Please refer to the malfunction analysis in the previous section for handling method.
7 IPM Module protection
Precessing method: Once the module malfunction happens, if it persists for a long time and cannot be self cancelled, cut off the power and turn off the unit, and then reenergize the unit again after about 10 min. After repeating the procedure for several times, if the malfunction still exists, replace the module.
40 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Basic System Check
Applicable for 09 & 12K model (1) Capacitor charge fault (Fault with outdoor unit)(AP1 below refers to the outdoor control panel) Main Check Points:
Use AC voltmeter to check if the voltage between
terminal L and N on the wiring board is within 210 AC
~240 VAC.
Is the reactor (L) correctly connected? Is the connec-
tion loose or disconnected? Is the reactor (L) dam-
Fault diagnosis process:
aged?
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two ends of electrolytic
capacitor
Voltage higher than 200V?
N
Measure the AC voltage between terminal L and N on wiring XT (power supply)
Voltage within 210VAC2 50VAC
Y
Shut down the power and wait 20 minutes; or
use DC voltmeter to measure the voltage on
on the two ends of capacitor , until the voltage is lower than 20V
Check the
connection of the reactor
(L in the Electrical
Wiring Diagram)
Y
N
Fault with the voltage
testing circuit on
control panel AP1
Shut down the power and repair the power supply to restore the range 210VAC~250VAC
Replace the control
panel AP1
power on and restart the unit
N
If the fault is eliminated?
Y
If the wiring of reactor
L is normal?
Y
Replace the control
panel AP1
End
421 08 9205 00 41
Connect the reactor according to Elec
N
trical Wiring Diagram correctly
Reenergize and turn on the unit
N
If the fault is eliminated?
Y
TROUBLESHOOTING (CONTINUED)
IPM Protection, Out−of−step Fault, Compressor Phase Over current (AP1 below refers to the outdoor control panel)
Main check points:
Is the connection between control panel AP1 and
compressor COMP secure? Loose? Is the connec­tion in correct order?
Is the voltage input of the machine within normal
range? (Use AC voltmeter to measure the voltage between terminal L and N on the wiring board XT)
Is the compressor coil resistance normal? Is the in-
sulation of compressor coil against the copper tube in good condition?
Is the working load of the machine too high? Is the charge volume of refrigerant correct?
Fault diagnosis process:
42 421 08 9205 00
Energize and
switch on
IPM protection
occurs after the machine has run for a period of time?
p
Please confirm:
1. If the indoor and outdoor heat exchangers are dirty? If they are
obstructed by other
objects which affect
the heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting in that the system
pressure is too high
and exceeds the
permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system pressure is too high?
5. Other conditions
resulting in that the
system pressure
becomes too high.
Refer to the Electrical Wiring Diagram and check if the connection between AP1 and COMP is loose and if the connection order is correct.
Use AC voltmeter to measure the voltage between
Y N
terminal L and N on the wiring board XT)
Voltage between
Y
the two ends of electrolytic
capacitor is
higher than 250V
N
Stop the unit and disconnect the power supply. Then, check the connection of capacitor C2 according to Electrical Wiring Diagram.
Remove the wires on the two ends of capacitor C2. Then, use capacitance meter to measure the capacitor C2. Verify as per the Parameters Sheet.
If capacitor C2 is failed?
N
If there is any
abnormality
described above?
N
between the two ends of
capacitor C2, until the
voltage is lower than 20V
Y
control panel AP1
If the voltage
between terminal L and N on wiring
board XT is within 210VAC~250VAC?
Y
Restartthe unit. Before
protection occurs,
use DC voltmeter to
measure the voltage
between the two
ends of electrolytic
capacitor on control
panel AP1
The connection
of capacitor C2
is loose.
N
Stop the unit and disconnect the power supply. Wait 20 minutes, or use DC voltmeter to measure the voltage
Replace the capacitor C2. Then, energize and start the unit.
Replace the
Take corrective actions according to Technical
Y
Service Manual, and
then energize and start
the unit.
Replace the
control panel AP1
Check the supply voltage and restore it to
210VAC~250VAC
N
Y
N
If the unit can
work
normally?
Reconnect the capacitor C2 according to Electrical Wiring Diagram. Then, Restart the unit.
If the unit can
work normallv?
If the unit can
work normally?
N
If the unit can
work normally?
N
Y
Y
Y
Y
If the connection between AP1 and COMP is unsecure or the connection order is wrong?
Use ohmmeter to measure the resistance between the three terminals on compressor COMP, and compare the measurements with the
compressor resistance on
Service Manual.
Use ohmmeter to measure the resistance between the two
terminals of compressor
COMP and copper tube.
Y
421 08 9205 00 43
Connect the control panel A
P1 and compressor COMP correctly according to the Electrical Wiring Diagram. Then, energize and start the unit.
If the
resistance is
normal?
Resistance higher
than 500M ?
Replace the
control panel
N
Y
AP1
END
Replace the compressor
COMP
N
If the unit can
work
normally?
Y
TROUBLESHOOTING (CONTINUED)
High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit)
Detection:
Is outdoor ambient temperature in normal range°? Are the outdoor and indoor fans operating normally? Is the heat dissipation environment inside and out-
side the unit good?
Fault diagnosis process:
Overheat and high
temperature protection
Normal protection, please operate
Is outdoor ambient temperature higher than 127°F
N
20 minutes after the complete
unit is powered off.
Y
it after the outdoor ambient temp erature is normalized.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
N
Does the outdoor fan work normally?
Y
Replace the control panel AP1
End
Y
N
Improve the heat dissipation environ ment of the unit
1. Check if the fan terminal OFAN is connected correctly
2. Resistance between any two terminals is measure by an ohm meter and should be less than 1K Ohm.
Replace the fan
capacitor C1
Replace the outdoor fan
44 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Startup failure (following AP1 for outdoor unit control board)
Detection
Whether the compressor wiring is connected correctly? Is the compressor broken? Has the compressor stopped long enough before restart
Fault diagnosis process:
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Y
Does startup fail?
Y
Are the wires for the compressor connected
correctly? Is connection sequence right?
Y
Replace the control panel AP1
N
If the fault is eliminated?
N
Restart it up after 3 minutes
Connect the wires as
N
per the connection diagram
421 08 9205 00 45
N
Replace the compressor
Y
End
TROUBLESHOOTING (CONTINUED)
Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Detection:
Is the system pressure too high? Is the input voltage too low?
Fault diagnosis process:
Out of step occurs once the
unit is powered on.
Is stop time of the
compressor longer than
3 minutes?
Are the wires for the compressor connected
correctly? Is connection sequence right?
Is the connection made in clockwise
Connect the
wires correctly
direction?
Replace the control
panel AP1
If the fault is eliminated?
Replace the compressor
Out of step occurs in
operation
Is the outdoor fan working
normally?
Is the outdoor unit blocked
by foreign objects?
Replace the
control panel AP1
If the fault is eliminated?
Replace the compressor
Check if the fan terminal
OFAN is connected correctly
Remove foreign objects
Replace the fan
capacitor C1
Replace the outdoor fan
End
End
46 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Detection:
Is the PMV connected well or not? Is the PMV damaged? Has refrigerant leaked?
Fault diagnosis process:
20 minutes after the
complete unit is
powered off
Is the terminal FA for the
electronic expansion valve
connected correctly?
Resistances between the first four pins close to the terminal hole and the fifth pin are almost the same, less than 100 ohm.
Replace the electronic
expansion valve
If the fault is eliminated?
Replace the
control panel
AP1
Connect the
wires correctly
421 08 9205 00 47
If the fault is eliminated?
Refrigerant leakage. Refill
the refrigerant
End
TROUBLESHOOTING (CONTINUED)
Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit)
Detection:
Check if the reactor (L) of the outdoor unit and the
PFC capacitor are broken
Fault diagnosis process:
Start
Check wiring of the reactor (L) of the outdoor unit and the PFC capacitor
Whether there is any
damage or
shortcircuit?
N
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
N
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the reactor by an ohm meter
Whether there is any damage
or short−circuit?
Y
The capacitor is
short circuited and
Y
the capacitor
should be replaced
Replace the reactor
Y
Replace it as per the
wiring diagram and
reconnect the wires
Restart the unit If the fault is eliminated?
Restart the unit
If the fault is eliminated?
N
Y
N
If the fault is eliminated?
Y
N
Replace the control
panel AP1
End
48 421 08 9205 00
N
Y
TROUBLESHOOTING (CONTINUED)
Communication malfunction: (following AP1 for outdoor unit control board)
Detection:
Is there any damage to the indoor unit main board
communication circuit? Is communication circuit damaged?
Are the indoor and outdoor units connection wire,
and indoor and outdoor units inside wiring correct or not, is there any damage?
Fault diagnosis process:
Start
The AP1 voltage detection circuit is at fault
If the fault is eliminated?
Check wiring inside of the indoor and outdoor
Y
N
Check the communication
circuit of the outdoor unit
Y
units
Are wires broken?
N
The communication
circuit is abnormal
Did the equipment operate normally before the failure
occured?
Y
Y
Replace the main board
AP1 of the outdoor unit
N
Check the wiring of the indoor and outdoor units with reference to the
wiring diagram
N
Is the connection right?
N
Correctly connect the
corresponding wires for
the indoor and outdoor units with reference to
the wiring diagram
If the fault is eliminated?
Replace the main board of the indoor unit
Y
421 08 9205 00 49
N
If the fault is eliminated?
N
End
Y
Y
TROUBLESHOOTING (CONTINUED)
Application for 18 & 24K model
Confirm the malfunction type according to the malfunction indicator of indoor/outdoor unit and malfunction sheet (usually the sheet will be stuck on the electric box cover or top cover of the unit).
As long as there is a malfunction, the indicator of the outdoor controller board will display the corresponding malfunction directly; Some malfunctions will be displayed on the indoor unit directly and some malfunctions will be seen on the remote controller by pressing light button for 4 times in 3 seconds.
In the below malfunction diagnosis process, “Y” means “Yes”, “N” means “No”;
In the below malfunction diagnosis process, controller board AP1 is for outdoor controller board;
Before proceeding to the malfunction check, discharge the electrolytic capacitor according to the method mentioned be­fore and make sure the voltage is below 20V. Otherwise, it may cause electric shock or brake the controller board!
50 421 08 9205 00
TROUBLESHOOTING (CONTINUED)
Capacitor charging malfunction (outdoor unit malfunction)
D5
j J j J
Detection:
Detect if the voltage of L and N terminal of wiring
board is between 210AC ~ 240AC by AC volt meter;
Is reactor (L) well connected? Is connection wire
loose or disconnected? Is reactor (L) damaged?
Malfunction diagnosis process:
D6 D16 D30
Turn on the unit and wait 1 minute
Use DC voltmeter to measure the voltage on the two ends of electrolytic capacitor
Voltage higher than 200V?
N
Measure the AC voltage between terminal L and N on wiring board XT(power supply)
Voltage within
210VAC~250VAC?
Y
Shut down the power and wait 20 minutes; or use DC voltmeter to measure the voltage on the two ends of capacitor (test3), until the voltage is lower than 20V
Check the connection of reactor (L in the Electrical Wiring Diagram)
Y
N
Fault with the voltage testing circuit on control panel AP1
Shut down the power and repair the power supply to restore the range 210VAC~250VAC
Replace the control panel AP1
power on and restart the unit
N
If the fault is eliminated?
Y
If the wiring of reactor L is normal?
Y
Replace the control panel AP1
End
N
421 08 9205 00 51
Connect the reactor according to Electrical Wiring Diagram correctly
Reenergize and turn on the unit
N
If the fault is eliminated?
Y
TROUBLESHOOTING (CONTINUED)
IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (outdoor unit malfunction)
Outdoor unit malfunction indicator status
Malfunction D5 D6 D16 D30
IPM protection j k j J
Desynchronizing
malfunction
Compressor
overcurrent
j k J k
j k j j
Detection:
If control board AP1 and compressor COMP are well
connected? If they are loose? If the connection se­quence is correct?
Is voltage input in the normal range (Test the voltage
between L, N of wiring board XT by DC voltage meter)?
If coil resistance of compressor is normal?
If the work load of unit is heavy? If the refrigerant
charging is appropriate?
Malfunction diagnosis process:
52 421 08 9205 00
Energize and switch on
IPM protection
occurs after the machine has run for
a period of time?
Please confirm:
1. If the indoor and outdoor heat exchangers are dirty? If they are obstructed by other objects which affect the heat exchange of indoor and outdoor unit.
2. If the indoor and outdoor fans are working normally?
3. If the environment temperature is too high, resulting in that the system pressure is too high and exceeds the permissible range?
4. If the charge volume of refrigerant is too much, resulting in that the system pressure is too high?
5. Other conditions resulting in that the system pressure becomes too high.
Use AC voltmeter to measure the
Y
voltage between terminal L and N on the wiring board XT)
If the voltage
between terminal L and N on wiring
board XT is within
210VAC~250VAC?
N
Check the supply voltage and restore it to 210VAC~250VAC
Y
Restart the unit. Before
Voltage between
Y
the two ends of electrolytic
capacitor (test3) is higher than
250V
N
Stop the unit and disconnect the power supply. Then, check the connection of capacitor C2 according to Electrical Wiring Diagram.
protection occurs,use DC voltmeter to measure the voltage between the two ends of electrolytic capacitor on control panel AP1 (test3)
The connection
of capacitor C2 is loose.
N
Reconnect the capacitor C2
Y
according to Electrical Wiring Diagram. Then, Restart the unit.
If the unit can
work normally?
Y
N
Remove the wires on the two ends of capacitor C2. Then, use capacitance meter to measure the capacitor C2. Verify as per the Parameters Sheet.
If capacitor C2 is failed?
N N
Stop the unit and disconnect the power supply. Wait 20 minutes, or use DC voltmeter to measure the voltage between the two ends of capacitor C2, until the voltage is lower than 20V
Replace the capacitor
Y
C2. Then, energize and start the unit.
Replace the control panel AP1
N
If the unit can work normally?
If the unit can work normally?
Y
Y
Refer to the Electrical Wiring Diagram and check if the connection between AP1 and COMP is loose and if the connection order is correct.
If the connection
between AP1 and COMP is unsecure
or the connectionorder is wrong?
Use ohmmeter to measure the resistance between the three terminals on compressor COMP, and compare the measurements with the compressor resistance on Service Manual.
Use ohmmeter to measure the resistance between the two terminals of compressor COMP and copper tube.
If there is any
abnormality
described above?
Connect the control panel AP1 and compressor COMP correctly according
Y
to the Electrical Wiring Diagram. Then, energize and start the unit.
If the
resistance is
normal?
Resistance higher than 500M
N
Replace the control panel AP1
END
Take corrective actions
N
according to Technical Service Manual, and
Y
then energize and start the unit.
Replace the control panel AP1
Replace the compressor COMP
If the unit can
work normally?
If the unit can work normally?
NN
Y
Y
N
?
421 08 9205 00 53
TROUBLESHOOTING (CONTINUED)
Diagnosis for high temperature, overload protection (check outdoor unit in cooling mode and check indoor unit in heating mode)
Outdoor unit malfunction indicator status
D5
D6 D16 D30
J j J J
Detection:
If the outdoor ambient temperature is in normal
range;
If the indoor and outdoor fan are running normally; If the heat transfer environment inside and outside
the unit is good (including if the fan speed is too low)?
If the tube temperature sensor of indoor and outdoor
unit is normal?
Malfunction diagnosis process:
High temperature, overload protection
ambient temperature is higher than 127 ºF in
cooling mode?/if the ambient temperature of indoor
and outdoor unit is too high?
If the outdoor
N
Normal protection, please use it after improving ambient temperature
Y
of indoor and outdoor unit
Y
Deenergize the unit and wait for 20min
Replace the control board(replace the outdoor control board in cooling mode, replace the indoor control board in heating mode)
If the heat transfer of outdoor
and indoor unit is good?
N
If the indoor and outdoor
fan work well?
Y
check if the tube temp sensor is normal according to the resistance sheet(check outdoor tube temp in cooling mode, check indoor tube temp sensor in heating mode)
Is the tube temp sensor normal?
N
Replace the tube temperature sensor
Y
Improve the heat transfer environment of the unit
1. Check if fan terminal OFAN is connected well
2. Test if the motors of
N
indoor and outdoor unit are broken
Replace fan capacitor C1
Replace outdoor fan
54 421 08 9205 00
End
TROUBLESHOOTING (CONTINUED)
Diagnosis for failure start up malfunction (outdoor unit malfunction)
Outdoor unit malfunction indicator status
D5
D6 D16 D30
j k j k
Detection:
If the compressor wiring is correct? If the compressor has been off long enough? If the compressor is damaged? If the refrigerant charging is too much?
Malfunction diagnosis process:
Energize the unit
and start it
If the stop time of compressor
is more than 3min?
Y
If the compressor wire COMP(UVW) is
well connected and connection sequence
If the refrigerant charging is
is correct
Y
too much?
If the stop time is not enough and the
N
high and low pressure of system is not balance , please start it after 3min
Improve the connection situation of control board AP1 and
N
compressor COMP, connect it with wiring diagram
Does the unit start
up normally?
N
Y
Charge the refrigerant according to service manual
Does the unit start
up normally?
N
Replace control board AP1
If malfunction is
removed?
N
Replace the
compressor
End
Y
421 08 9205 00 55
TROUBLESHOOTING (CONTINUED)
Diagnosis for compressor synchronization (outdoor unit malfunction)
Outdoor unit malfunction indicator status
D5 D6 D16 D30
j k J k
Detection:
If the system pressure is too high? If the working voltage is too low?
Malfunction diagnosis process:
Synchronization after energizing the unit and starting it
N
If the stop time of
compressor is more than
3min
Y
wire COMP(UVW) is well connected, the
N
Connect wire well
If the compressor
connection sequence forwards to
clockwise direction?
Y
Replace
control board
AP1
Y
Remove
malfunction?
N
Replace
compressor
Synchronization during operation
If the outdoor fan works
normally?
Y
If the radiating of unit is
well?
N
If the input voltage of unit
is normal?
Y
If the refrigerant is too
much?
N
Replace control board AP1
Check if the fan
N
terminal OFAN is connected well
Improve the radiating of unit (clean heat
Y
exchanger and increase ventilation)
Start to run until the
N
power resume normal voltage
Charge the
Y
refrigerant with service manual
Replace fan capacitor C1
Replace outdoor fan
Remove
malfunction?
End
N
Replace compressor
Y
56 421 08 9205 00
End
TROUBLESHOOTING (CONTINUED)
Diagnosis for overload and discharge malfunction (outdoor unit malfunction)
Outdoor unit malfunction indicator status
Malfunction
D5 D6 D16 D30
Overload j k k j
Discharge J j J k
Detection:
If the electronic expansion valve is connected cor-
rectly? Is the expansion valve damage?
If the refrigerant leaked? If the overload protector is damage? If the discharge temp sensor is damage?
Malfunction diagnosis process:
If the overload protector SAT
is well connected?
Under ambient temperature, test the
resistance of overload protector with ohmic
meter, the resistance value<10000
After the unit deenergized for 20min
Y
Y
N
N
Replace overload protector SAT
If the wiring terminal FA of electronic
expansion is well connected?
Y
Check if the coil of electronic expansion is installed on the valve normally
Check if the expansion valve is blocked
Remove
malfunction?
N
Check refrigerant, if there is leakage, please refer to specification
Remove
malfunction?
N
check if the discharge temp
sensor is normal according to the
resistance sheet
N
Replace discharge
N
temp sensor
Connect the wire well according to wiring diagram
Y
Y
421 08 9205 00 57
Y
Replace control board
End
TROUBLESHOOTING (CONTINUED)
Communication malfunction
Outdoor unit malfunction indicator status
D5 D6 D16 D30
j j j k
Detection:
Check if the connection wire and the builtin wiring of
indoor and outdoor unit is connected and not damaged;
If the communication circuit of indoor mainboard is
damaged? If the communication circuit of outdoor mainboard (AP1) is damaged?
Malfunction diagnosis process:
Start
N
Connect wire of indoor and outdoor unit according to circuit diagram
N
If the malfunction
is removed ?
Y
Check if the controller connection wire inside indoor and outdoor electric box is loose
If the connection wire
is normal?
Y
Check communication circuit of outdoor unit
Problem of
communication
circuit
N
Replace indoor mainboard
If the unit is operating
normally before malfunction
Y
Replace outdoor mainboard (AP1)
If the
malfunction is
removed?
Y
N
Check connection wire of indoor and outdoor unit with circuit diagram
Y
N
Connection
correct?
N
Connect wire of indoor and outdoor unit according to circuit diagram
If the malfunction
is removed?
Y
58 421 08 9205 00
End
Y
TROUBLESHOOTING (CONTINUED)
Diagnosis process for outdoor communication circuit (refer to the key detection points of outdoor unit)
Start
Test voltage valueof Test10 position in diagram with voltage meter
Number jumping
N
Y
Test voltage value of Test 13 position in diagram with voltage meter
Y
Number jumping
Y
Test voltage value of Test 10 position in diagram with voltage meter
Number jumping
Y
Test voltage value of Test 12 position in diagram with voltage meter
Number jumping
N
Outdoor unit malfunction
End
N
N
Y
Communication circuit of outdoor unit is normal
421 08 9205 00 59
APPENDIX 1
60 421 08 9205 00
APPENDIX 2
421 08 9205 00 61
APPENDIX 3
62 421 08 9205 00
UNIT REMOVAL PROCEDURES
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than one disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
A large−capacity electrolytic capacitor is used in the outdoor unit controller (inverter). When the power supply is turned off, charge (charging voltage DC280V to 380V) remains and takes a long time to discharge. Do Not open the outdoor unit for 20 minutes after power has been turned OFF.
WARNING
421 08 9205 00 63
REMOVAL PROCEDURE OF INDOOR UNIT 9K 12K 115V
Steps
1. External feature s
2. Removing air filter s
Pull protrusions on lef t
1
and right sides of pane l
wi t h f inge rs and ope n
f ron t panel all the way.
Li ft c en t er s e ct ion o f ai r
2
filter and disengag e
hooks .
If the ON/OFF button is pressed
for 5 seconds, a forced cooling op -
eration will be carried out fo r
approx. 15 minutes .
Air filter
Le ft and righ t f il t er s ar e
interchangeable .
Remove air filter b y
3
pulling forward .
T o re-install, insert air filte r
along the guide .
Hooks
64 421 08 9205 00
Steps
3. Remove front panel
Pull down horizontal louver
1
by pulling it forward s .
Remove horizontal louver by
2
pulling it forward s .
Hook a finger onto the
3
projection part provided
on both sides of the
unit’s panel and open
the panel past the stop.
Support the front panel with one
hand, while removing the rotation
axis at the upper center with the
other hand.
And pull the front panel
forward to remove.
Horizontal louver
Left and right filters are
interchangeable.
To re-install, insert air filter
along the guide.
Remove the front panel
4
from the unit.
Left
Rotary shaft
Right
Rotary shaft
421 08 9205 00 65
Steps
4. Remove electric box cover
Remove the electric box
1
cover mounting screw.
Open electric box cover
upward s .
5. Remov e front case assembly
Remove the 3 screws,
1
in the right and the left sides,
which fix the main body
with the front case.
screws
screws
Screw stoppers inside the
flap which were equipped in
the existing models are not
provided.
Disengage the 3 hooks
2
on the upper part.
In case that the hooks
are not pressed from
above, remove the front
panel and then remove
the grille while pushing
the hook through a
clearance between the
front case and the heat
exchanger.
The front case can be
3
removed by pulling
the upper part forward
and lifting up the
lower part.
Left
Hooks
Center
Right
At the upper part there are 2
hooks in the left and the
right.
Disengage the hooks by
pressing knobs with a
screwdriver.
66 421 08 9205 00
Steps
6. Remove the
Unfasten the hooks at
1
the upper 2 positions.
Unfasten the 3 hooks at
2
the shaft mounting part by pressing them with a flat screwdriver.
Vertical blade
Hook
A set of vertical blade has 6 fins on the assembly.
(It is impossible to replace
only one fin.)
The set of vertical blades is not marked for difference between right and left.
Repeat the same procedure to remove the vertical blade on the other side.
Remove the vertical
3
louver .
Hook
Vertical louver
421 08 9205 00 67
Steps
7. Remove electric box
Disconnect the c able
1
clamp
Disconnect the
2
connection wires.
Terminal board
Connecting wires
Pay attention to the direction
of the retainer of the
thermistor so that the
retainer will not touch the
harness (same as the
existing models.)
Remove the temperature
3
sensor
Remove a screw on the
4
terminal board.
Screw
Earth wire
Heat exchanger thermistor
(R11244)
Take care not to lo o se the clip for the thermistor.
Clip
Heat exchanger thermistor
(R11268)
The electrical box can be
removed instead of
disengaging the terminal
board.
68 421 08 9205 00
Steps
5
6
Remove fan motor s ignal
w ire
Remove a screw on the
electrical box.
fan motor s ignal w ire
Pull up the electrical
7
box forward to remove.
Bottom frame
Hook
421 08 9205 00 69
Steps
8. Remove the refrigerant piping.
1
Lift the indoor unit by a wooden base.
2
Place a plastic sheet under the drain pan as remaining moisture may leak.
Wooden base
Extension drain hose
Connecting wires
CAUTION
If gas leaks, collect all refrigerant
from the unit, then repair the leak. After conducting vacuum drying,
recharge the proper amount of
refrigerant.
CAUTION
Do not contaminate the refrigerant.
(Contaminating with air or other
gas causes abnormal high
pressure in the refrigerating
cycle, and this could result in pipe
rupture or personal injury.)
Drain hose
3
Disconnect the flare nut for gas piping with 2 wrenches.
4
Disconnect the flare nut for liquid piping with 2 wrenches.
In case a drain hose is
buried inside a wall, disconnect
it after the drain hose has been
removed from the wall.
Use two wrenches to
disconnect pipes.
When disconnecting pipes,
cover with caps to prevent
contamination.
70 421 08 9205 00
Steps
9.Remove the
1
Remove the indoor unit from the mounting plate.
2
Release the hook of the piping fixture on the back of the unit.
heat exchanger
.
When disconnecting pipes,
cover with caps to prevent
contamination.
Liquid piping
Gas piping
Auxiliary piping
(R8019)
Piping fixture
421 08 9205 00 71
Steps
3
4
Loosen the 2 screws
at the right and the left,
which fix the Evaporator
Assy.
Auxiliary piping
Widen the auxiliary piping to the extent of 10°~20°.
Pull the heat exchanger
5
to the front side to undo the hooks completely, and then lift it.
Heat exchanger
72 421 08 9205 00
Steps
10. Remove c ross f low blade and f a n
m oto r
Remove c ross f low blad e
and f an m oto r
1 1 . Remove retention ring of bearing.
Bear ing
12 . Re m o v e c r o ss f low blad e an d
m otor s ub - a ssy
421 08 9205 00 73
Steps
13. Remove m otor s ub - a ss y
Remove m otor s ub - a ss y
14 . Re m o v e f an m o t o r
74 421 08 9205 00
REMOVAL PROCEDURE OF OUTDOOR UNIT 9K 12K 115V
Steps
1. Features
1
Loosen the screw of the
Cable Cross Plate sub-
assy and remove it.
Pull down the stop valve
cover and remove it.
Procedure
Points
Cable Cross
Plate sub-assy
2. Remove top panel
1
Loosen the 3 screws
(right, left) and lift
the top panel.
Top panel
421 08 9205 00 75
Steps
Points Procedure
Remove the screws
2
connecting the grille and the panel with a screwdriver and then remove the grille.
Remove the screws
3
connecting the panel and the motor support, chassis and grille with a screwdriver and then remove the outer case.
Remove the screws
4
connecting right side plate and end plate of condenser, grille, valve support and electric box, and then remove the right side plate.
grille
Lift the front panel and
remove it while pushing the
right side panel inwards.
cabinet
right side plate
3.Remove the fan motor
Remove the nut on blade with
1
a wrench and then remove the axial flow blade.
76 421 08 9205 00
axial flow blade
The screw has a reverse
thread.
Remove the propeller
fan.
Steps
2
Remove the 4 tapping screws fixing the motor, pull out the pin of leading wire of motor and then remove the motor. Remove the 2 tapping screws on motor support and 1 screws on electric box, pull it upward and then remove the motor support.
4.Remove the electric box.
Remove the 2 screws fixing the electric box cover with a screwdriver, pull it upward and then remove the electric box cover. Remove the screws fixing the electric box with a screwdriver, loosen the terminal block, pull out the wiring terminal, pull it upward and then remove the electric box.
Fan motor
Procedure
Electrical box
Points
Fan motor fixing frane
5.Remove the partition plate.
The partition plate is fixed to
1 Loosen the 2 screws.
2 The partition plate has a
hook on the lower side. Lift
and pull the partition plate
to remove.
the bottom frame with a hook.
Partition plate
421 08 9205 00 77
Steps
6. Remove compressor
1
Unsolder the pipeline connected to the compressor. (Reclaim all refrigerant before disassembling the pipeline)
Remove the 3 foot nuts on
2
compressor and then remove the compressor.
Procedure
4-Way valve assy
Points
Compressor
Remove the 2 bolts fixing the
3
gas valve, unsolder the joint between the gas valve and suction return pipe then remove the gas valve. (note: When unsoldering the joint, wrap the gas valve with a wet cloth completely to avoid damage to the valve.) Remove the 2 bolts fixing the liquid valve, unsolder the joint between liquid valve and Y-type tube and then remove the liquid valve.
Gas valve and liquid valve
78 421 08 9205 00
REMOVAL PROCEDURE OF INDOOR UNIT 12K 18K 230V
pressed
421 08 9205 00 79
with
removing
with
A
panst the stop.
panel
80 421 08 9205 00
Lift the
the
S
sides
by pulling
the
lifting
421 08 9205 00 81
Remove the temperature sensor; disconnect the connection wires. Remove the ground screw xing the evaporator; disconnect all the wires from the terminal.
Take care not to lose the clip for the thermistor.
82 421 08 9205 00
Remove the pipe clamp
sides which x the evaporator assy. Remove the evaporator assy.
421 08 9205 00 83
Remove the screws from the motor pressure plate and then remove the motor pressure plate.
Remove the motor, blade, and shaft cushion rubber base.
the
P
S
84 421 08 9205 00
REMOVAL PROCEDURE OF OUTDOOR UNIT − 12K 230V
Electric heater band is not shown. Grille in the picture is for reference only.
1. Remove the valve cover
The valve cover has 6
hooks.
stnioPerudecorPspetS
Loosen the screw of the
1
Handle.
Pull down the handle
and remove
it.
2. Remove the top panel
Loosen the 3 screws
1
(front, right, left) and lift
the top panel.
Handle
Top panel
421 08 9205 00 85
3.Remove grille and front panel
Loosen one screw
1
and remove the
discharge grille.
2
Loosen the 5 screws of
the front panel.
stnioPerudecorPspetS
rille
Lift the front panel and remove it while pushing the right side panel inwards.
4.Remove right side plate
1
Remove the 5 screws from the edge between right-side board and condenser and from the valve. Lift to remove the right side plate.
5.Remove the fan motor and Axial fan
1
Remove the screws of the fan with a wrench and then remove the axial flow fan and fan motor.
Fan motor
Axial flow fan
Front panel.
ight side plate
The screw has reverse
threads.
Remove the propeller
.
fan.
86 421 08 9205 00
stnioPerudecorPspetS
Remove the 4 tapping
2
screws fixing the motor. Pull out the lead-out wire and remove the motor. Remove the 2 tapping screws fixing the motor support. Lift to remove the motor support.
6.Remove the electric box
1
Re move the 2 screws fixing the cover of electric box. Lift to remove the cover. Remove the screws fixing the electric box subassembly. Loosen the wire and disconnect the termina Lift to remove the electric box subassembly.
Fan motor
Electric box
Fan motor fixing frane
M4×16
DC fan motor
7.Remove the partition plate
Loosen the 2 screws.
1
The partition plate has
2
a hook on the lower
side. Lift and pull the
partition plate to remove.
Partition plate
The partition plate is fixed to
the bottom frame with a hook.
421 08 9205 00 87
8.Remove the sound blanket
stnioPerudecorPspetS
Lift and remove the
1
sound blanket (top).
Untie the strings and
2
open the sound blanket.
Lift and remove the
3
sound blanket (body) as
it is opened.
4 Pull the sound blanket
(inner) out.
Since the piping ports on
the sound blanket are
torn easily, remove the
blanket carefully.
9.Remove four way valve coil
Loosen the screw of the
1
four way valve coil.
Sound blanket
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to break
the pipes by pressing it
excessively with pliers when
withdrawing it.
Caution
Piping may be hot.
Take precautions to avoid burns.
Magnet coil
88 421 08 9205 00
10.Remove compressor
1
Unbraze the capillary, valve, and outlet pipe of condenser
Remove the 2 screws fixing the
2
gas valve. Unbraze the gas valve and suction pipe and remove the gas valve.
(Note: it is necessary to wrap the gas valve when unbrazing.
Remove the 2 screws fixing liquid valve. unbraze the connecting liquid valve and remove the liquid valve.
3
Unbraze the pipe connected
to the compressor.
stnioPerudecorPspetS
4-way valve assy
Remove the 3 footing
4
screws of the compressor and remove the compressor.
Capillary Sub-Assy
Compressor
421 08 9205 00 89
REMOVAL PROCEDURE OF OUTDOOR UNIT − 18K 230V
Electric heater band is not shown.
Remove the screws used
cover upward
Remove the screws used
Handle
Valve cover
90 421 08 9205 00
Remove the screws xing
s p
421 08 9205 00 91
L
f f
F
threads
remove all wires from the terminals and then pull the electric box upwards to remove it.
F
b
92 421 08 9205 00
blanket.
Remove
S
I
blanket.
421 08 9205 00 93
Reclaim
unbraze
Piping may be hot. Take precautions to avoid burns.
Remove
C
S
94 421 08 9205 00
C
C
421 08 9205 00 95
REMOVAL PROCEDURE OF INDOOR UNIT − 24K 230V
Outside view drawing
e
clasp
the
the
pressed
louver
Clasp
it
96 421 08 9205 00
Remove
Draw out the axial bush. Bend the guide louver slightly and then remove it.
with one
removing
with the
the panel past the stop.
l
axial bush
louver
421 08 9205 00 97
Remove
the service
Lift the service cover
e
Remove the 5 screws in the right and left sides, where fixed to the main body with the front grille.
clasps
clasps
clasps
removed by pulling the upper part forward and lifting up the lower part.
Clasp
,
clasps at right
side
clasps
98 421 08 9205 00
c
Remove the temperature sensor.
Disconnect the connection wires.
Remove the ground screw xing the evaporator.
Disconnect all the wires from the terminal.
Take care not to lose the clip for the thermistor.
Remove the
on
421 08 9205 00 99
the p c
at sides
ing e
assy, and then remove
evaporator.
100 421 08 9205 00
Loading...