International comfort products DFS2A318J2A, DFS2A324J2A, DFS2H318J2A, DFS2H324J2A Installation, Start-up And Service Instructions Manual

Cooling Model DFS2A318J2A
DFS2A324J2A
Heat Pump DFS2H318J2A
DFS2H324J2A
Installation, Start-Up, and Service Instructions
SAFETY CONSIDERATIONS ...................... 1
GENERAL ..................................... 1-7
INSTALLATION .............................. 7-14
Indoor Unit Installation ........................ 7
Outdoor Unit Installation ........................ 9
Power Supply ................................ 10
Leak Test ..................................... 10
Wiring Diagrams ........................... 12-13
START-UP .................................... 14
System Checks ................................ 14
CARE AND MAINTENANCE ....................... 14
Outdoor Units ................................. 14
Indoor Units ................................... 14
To Clean the Indoor Unit Front Panel ............ 14
To Clean Indoor Coil ........................... 14
Air Filters for Indoor Units ...................... 14
SERVICE ....................................... 15
TROUBLESHOOTING ........................ 16-19
Page
421 01 9219 00 I
Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed
by trained service personnel.
When working on the equipment, observe precautions in the literature mid on tags, stickers, mid labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment.
51302618919-B NOV 06
DFS2A/H 2X09, 2X12
Duct Free Systems
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and
NOTE are used to identifylevels of hazard serious- ness. The signal word DANGER is only used on
product labels to signify an immediate hazard. The
signal words WARNING, CAUTION, and NOTE will
be used on product labels and throughout this manu-
al and other manuals that may apply to the product.
DANGER - immediate hazards which will result in se-
vere personal injury or death.
WARNING - Hazards or unsafe practices which could
result in severe personal injuryor death.
CAUTION - Hazards or unsafe practices which may re-
sult in minor personal injury or product or property damage.
NOTE - Used to highlight suggestions which will result in
enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect.
There mav be more than one disconnect switch.
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
Signal Words on Product Labeling Signal words are used in combination with colors and/or
pictures on product labels.
GENERAL
These instructions cover the installation, start-up and servicing of DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units
cooling only and heat pump duct free systems. See Table 1 for parts included. See Tables 2 and 3 for Physical Data.
SYSTEM REQUIREMENTS
IMPORTANT: The Indoor units & the inter units cable voltage is 30 VDC.
IMPORTANT: Each refrigerant line must be insulated Separately. See line sizing requirements in able 2.
Consult local building codes and National Electrical Code (NEC, U.S.A.) for special installation requirements.
Max. cable length. Total voltage drop should not exceed 1V. Therefore max. length:
For #18 AWG 24.3 Feet (7.4 m) For #16 AWG 37.7 Feet (11.5 m) For #14 AWG 50.0 Feet (18 111)
Use only type "G" or "C" fuses. Use single length power cable without extension. Allow sufficient space for airflow
clearance on condensing units for wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2 for minimum required
distances between unit and walls or ceilings.
Indoor and outdoor units should be installed at a Mini- mum length of 10 ft. apart. Maximum line length of 50 ft.
and veltical separation of 30 ft.
Do not install indoor units near a direct source of heat such as direct sunlight, steam or flame.
UNTF COMPONENT DAMAGE
Failure to follow this caution may result in damage to unit
components.
Do not bu_ more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical
rise to the valve connections on the outdoor units. If more than
the recommended length is buried, refrigerant may migrate to the cooler buried section duNlg extended periods of system
shutdown.
Fig, 1 -- DFC2A/H318, 324 Outdoor Unit Clearances
Table 1--Parts List -- High Wall Units
ITEM QTY
Mounting Bracket
Long Screws
Outdoor Sensor
Connecting
Cable
Absorption Cushions
Electric Terminals
DIAGRAM
2X1
DFF2A/DFF2H 09, 12
2X8
2X1
(Available for HEAT PUMP ONLY)
2X8
Remote Controller
Mounting Bracket
Remote Controller
and Batteries
Insulation for
Indoor Fittings
Owner's Manual
2X
1 Mounting
Bracket with 2 screws
2X1
2X1
2X1
Wall-mounted
Receiver RTX
(OPTIONAL)
(Not Included)
NADA001TW
Table 2--Physical Data - Cooling Only
INDOOR UNIT 2 X DFF2AH12JIA
COOLING CAPACITY (Btuh) SEER 2 X 11,400
SYSTEM CHARGE (Ib)* 2 X 3.1
MOISTURE REMOVAL (pt/hr) 2 X 4.5
AIRFLOW (3 Speeds) 2 X 350 / 2 X 280 / 2 X 220
High / Med. / Low Cfm DIMENSIONS LxHxW (in.) 32 3/32x10 15/64x7 9/32 32 3/32x10 15/64x7 9/32
REFRIGERANT TYPE R-22 R-22 NET WEIGHT (Ib) 2 X 19.0 2 X 19.0
OUTDOOR UNIT
TUBE CONNECTIONS Vert Lift/Vert Drop/Max Length (ft)
NOMINAL LINE SIZING Mixed Phase...Suction (in.)
COMPRESSOR TYPE DIMENSIONS LxHxW(in.)
NET WEIGHT (Ib) METERING TYPE
LEGEND
2 X DFF2AH09JIA
2 X 9,000
13.0 2X2.4 2X2.6
2X350/2X280/2X220
DFC2A318J2A DFC2A324J2A
30/30/50 30/30/50
1/4...1/2 1/4...1/2
Panasonic-2R13S126A6F Panasonic-2P17SR126B1A
35.5 X 49.5 X 12.6 35.5 X 49.5 X 12.6 226 228
Piston (Accurator) Piston (Accurator)
Accurator is non-serviceable
13.0
SEER -- Seasonal Energy Efficiency Ratio *Units are shipped with a factory charge based on 25 ft of refrigerant lines.
Table 3_Physical Data - Heat Pump
INDOOR UNIT 2 X DFF2AH09JIA 2 X DFF2AH12JIA
COOLING CAPACITY (Btuh) 2 X 9,000 2 X 11,400
SEER 13.0 13.0
HEATING CAPACITY (Btuh) 17,200 23,600
HSPF 7.7 7.7
SYSTEM CHARGE (Ib)* 2 X 2.4 2 X 3.1
MOISTURE REMOVAL (pt/hr) 2 X 2.6 2 X 4.5
AIRFLOW (3 Speeds) 2 X 350/2 X 280/2 X 220 2 X 350/2 X 280/2 X 220
High / Med. / Low Cfm
DIMENSIONS LxHxW (in.) 32 3/32x10 15/64x7 9/32 32 3/32x10 15/64x7 9/32 REFRIGERANT TYPE R-22 R-22
NET WEIGHT (Ib) 2 X 19.0 2 X 19.0
OUTDOOR UNIT
TUBE CONNECTIONS
Vert Lift/Vert Drop/Max Length (ft)
NOMINAL LINE SIZING
Mixed Phase...Suction (in.)
COMPRESSOR TYPE DIMENSIONS LxHxW(in.)
SHIPPING WEIGHT (Ib) METERING TYPE
LEGEND Accurator is non-serviceable
DFC2A318J2A DFC2A324J2A
30/30/50 30/30/50
1/4...1/2 1/4...1/2
Panasonic-2R13S126A6F Panasonic-2P17SR126B1A
35.5 X 49.5 X 12.6 35.5 X 49.5 X 12.6 226 228
Piston (Accurator) Piston (Accurator)
HPSF -- Heating Seasonal Performance Factor SEER -- Seasonal Energy Efficiency Ratio
*Units are shipped with a factory charge based on 25 ft of refrigerant lines, NOTE: Standard Ambient Operating Limitations - 55 [_F to 125 0F (12.7 [_C to 51.6 [_C).
NOTES:
ICP
I. DIMENSIONS IN INCHES, [ ] ARE IN MILLIMETERS - DO NOT SCALE. 2, _ DIRECTION OF AIR FLOW. 3, REFRIGERANT, DRAIN AND POWERCONNECTIONS
MAY BE MADEREAR (LEFT OR RIGHT), LEFT SIDE, RIGHT SIDE, OR BOTTOMLEFT.
[TOP VIEW]
- 3.94 [I00] MIN.
/ \
/
4
[I00] MIN. 11.81 [300] MIN.
MINIMUM CLEARANCE FOR SERVICE AND AIR FLOW
E
INLET AIR
I
F
I I I I I I I I I I I
[ LEFTSIDEVIEW
F]LTERS
(OPEN COVER FOR ACCESS)
IFRONTVIEWI
IRIGHT SIDE VIEW J
3.0 DIA [76] A
FOR REFRIGERANT, DRAIN,
POWERAND SIGNAL LINES
-EVAPORATOR COIL
INLET AIR
I_ COOLING
IN
BEAF_NG%
NOCKOUT FOR LEFT SIDE
REFRIGERANT, DRAIN, POWER AND SIGNAL LINES
f
IIIIAIRS_II
"A" LINFRARE[ REMOTEOVERRIDE SWITCH
DRAIN 0.625 [15.B] - 2B'FLEX BOSE,
MALE BARB CONNECTION (PLASTIC)
[BOTTOM VIEW]
i SUCTION LINE CONNECTION
"G" MALE FLARE
A
I_L_
I' _ J rJ L_OU_OUNECONNECTION
"H" MALE FLARE
,/
KNOCKOUTFOR BOTTOM REFRIGERANT,DRAIN,POWER AND SIGNAL LINES
KNOCKOUT FOR RIGHT SIDE REFRIGERANT, DRAIN, POWER
lAND SIGNAL LINES
E
1
o o
m
r-
m
z 0
=
m
m
I A I B E C I D I E I F I G I Ji I J2 I
UNIT SIZE
DFC2A318J2AI 4_n I 43 ln_ t _gR 796177F
DFC2A324J2AI49_36 I 4.3 t69 I 28.6 Z261 7.7_
DFC2H324J2A " "
ICP
,971 I 641 ,410, 612261 0 ,
oi ,;
i
I _ w
I '
AIR DISCHARGE
Mim TOP VIEW
6" [0,15M]
Min.
2' [0.6M]
,,g _,
/
LM MJ
FRONT VIEW
MINIMUM CLEARANCE_ SEE NOTE 1
"A"
1
0.7
[18MM] --
NOTES: 1 REQUIRED CLEARANCES, WITH COIL FACING WALL -ALLOW 6 MINIMUM
1 1 WITH COIL FACING WALL - ALLOW 6 MINIMUM CLEARANCE ON COiL SIDE & END
AND 2 FEET MINIMUM CLEARANCE ON COMPRESSOR END FAN SIDE
12 WITH FAN FACING WALL -ALLOW 2 MINIMUM CLEARANCE ON FAN SIDE AND 6 ON COIL END,
AND 2 FEET MINIMUM CLEARANCE ON COMPRESSOR END COiL SIDE 13 ALLOW 2 FEET MINIMUM CLEARANCE OVER THE TOP OF UNIT 14 WITH MULTI-UNITAPPUCATtON, ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF
OTHER 2 DIMENSIONS iN PARENTHESIS ARE IN METRIC 3 BRACKET WITH 1 125 DiA HOLE FOR FIELD POWER SUPPLY
FIELD POWER CONNECTION &
CONTROL CONNECTION
UNDER THIS COVER
"P' DIA. VAPOR LINE ::
FLARESERVICECONNECTIONPORT N _ _
.25" FLARE CONNECTION _ 31
SERVICE PORT _. (FROM LIQUID LINE) _1_ t
.25" FLARE CONNECTION_ _/_t_i "-_
"R" DIA. LIQUID LINE __
FLARE CONNECTION : ---1
P" DIA. VAPOR LINE
FLARE CONNECTION
SERVICE PORT 31
25' FLARE CONNECTION _
SERVICE PORT
(FROM LIQUID LINE)
.25" FLARE CONNECTION
"R" DIA. LIQUID LINE __ . FLARE CONNECTION
-- SEE NOTE 3
°TYP
"K2"
"J2 .... M"
=TYP
"KI"
VIEW '_A'_
_EJ _> o-I _m o o_
m
mcm
;0
Zoo mc
co m o m co
, rn
<
4. If refrigerant line route no. 1,2 or 4 are used, use a small saw blade to carefully remove the corresponding plastic
covering on the side panel.
5. Run the outdoor sensor cable, electrical cable, refrigerant lines, and drainage tube through the hole.
6. Fill the remaining wall hole gap with an appropriate seal- ant material.
J
J
Fig. 2 -- Indoor Unit Clearances
INSTALLATION
Plan the installation carefully to avoid component failures and make installation easier.
Indoor Unit Installation
REFRIGERANT LINE ROUTING -- The refrigerant lines may be routed in any of the four directions shown in Fig. 3.
INSTALL THE MOUNTING BRACKET
1. Carefully remove the mounting bracket, which is con- nected to the back of the indoor unit's base with screws.
2. Position the mounting bracket on the wall and level it us- ing a spirit level (see Fig. 2 for minimum required clear- ance distances).
3. Mark the four drilling holes on the wall, as they appear in Fig. 4.
4. Drill the holes, insert the wall plugs and use four long screws to attach the mounting bracket to the wall.
5. Check that the bracket is leveled and securely fastened to the wall.
DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS
To make the connections between the indoor and outdoor units, drill a 2.5-in. hole through the wall for the refrigerant lines,
drainage hose and control cable passage as shown in Fig. 5.
1. Mark the center of the hole to be drilled according m the re- fiigerant line routblg used and dimensions shown in Fig. 4.
2. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least 1/2" lower than the
opening on the inside.
3. Make sure the drainage hose is at the bottom side of the hole.
Fig. 3 -- Refrigerant Lines
09, 12
G-2
09, 12
G-2 ALL DIMENSIONS ARE iN mm
Fig. 4 -- Mounting Bracket DFF2A/DFF2H 09, 12
ALL DIMENSIONS ARE IN inches
(Optiona_ for NEAT PBNP BYSTEfB$}
OUTDOOR SENSOR CABLE REFRIGERANT
\ LINES
_ t/2.1N. MIN
INDOOR _.tl] OUTDOOR ELECTRICAL
- - _ - - CABLE TUBE
Fig. 5 -- Drill Holes
_T_lrAI -- DRAINAGE
G
WIRE THE INDOOR UNIT
1. Strip the cables back 1/4 inch.
2. Remove the unit's front panel by lifting the lower part and pulling it gently outward and upward. See Fig. 6.
3. Remove the two screws from the control box cover and take off the cover. See Fig. 7. Save the screws to reassem-
ble.
NOTE: In general wiring the indoor unit does not require the removal of the grille frame but in case of need do as follow:
4. Remove the two screws from the air discharge opening. Save the screws to reassemble. See Fig. 7A.
Pull downwards and outwards on the bottom of the grille and gently raise the frame of the top of the unit.
Once all covers are off, mount the unit onto the wall mount- ing bracket. See Fig. 8.
NOTE: Leave covers off until after the Making Drainage Connections section.
Route the interconnecting unit's electric cable and the out- door sensor cable towards the lower right hand corner of the
indoor unit.
Make sure that the wires are connected in accordance with the wiring diagram on the inside of the unit front cover or
within this instruction manual.
Secure the control cables to the strain relief.
For heat pump systems only, connect the outdoor sensor TH3 to its mating black terminal. See Fig. 9.
J
j_
/
f
Fig. 6 -- Remove Grille Insert
Fig. 7 -- Remove Control Cover
Fig. 7a -- Remove the screws from the air discharge
opening.
Mount the indoor unit on the mounting bracket
FIRE HAZARD Failure to follow this warning could result in personal
injury, death and or property damage. Make sure that all wires and screws are firmlv fastened.
REASSEMBLE
1. Connect the display connector to the display panel printed circuit board.
2. Put the control box cover and grille frame back on using the appropriate screws (Steps 3 and 4 of Wire the Indoor Unit section). Put the grille insert back on.
Model-2 X 12 DIP Switches location
Model-2 X 09 DIP Switches location
Model-2 X 12 DIP Switches location
Model-2 X 09 DIP Switches location
HEAT PUMP
(on the control box side)
HEAT PUMP
(on the control box side)
COOLING ONLY
(on the control box side)
COOLING ONLY
(on the control box side)
Standard Dip Switches status from the factory
_ili;
Gently push with the arrow direction
Fig. 8 -- Indoor Unit Mounting
Inter unit
terminal block
30VDC
Display
TH3
(Heat Pump Only)
Inter unit cable clamp
Fig. 9 -- Outdoor Sensor Connection
ATTACH THE REMOTE CONTROLLER MOUNTING
BRACKET
1. Use the two screws supplied with the controller to attach the mounting bracket to the wall in the location selected
by the customer (see Fig. 10).
2. Install batteries in the remote control.
3. Place remote control into remote control mounting brack- et.
4. For remote control operation, refer to the unit Owner's Manual.
REMOTE CONTROL
MOUNTING BRACKET
Fig. 10- Attach Mounting Bracket to the Wall
(OPTIONAL)
NADA001TW
Use only "L" type sealed, dehydrated copper refrigerant tubing. No other type of tubing may be used. Use of other types of tubing
will void the manufacturer's warranty.
Do not open service valves or remove protective caps from tubing ends until all the connections are made.
Bend tubing with special bending tools to avoid the formation of sharp bends. Take care to avoid kinks or flattening of the tubing.
Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system.
Avoid sags in the suction line to prevent the formation of oil traps.
Insulate each tube with 3/8-in. walled thermal pipe insulation. Inserting the tubing into the insulation before
making the connections will save time and improve
installation The suction and mixed-phase lines should never come in direct contact.
POWER SUPPLY
HIGH/LOW
Fig. 11 --Wall Mounted Unit- RTX
Outdoor Unit Installation NOTE: The outdoor unit must be installed on a solid surface
(mounting base).
1. Place the rubber absorption cushions (supplied with the outdoor unit) under the unit's feet to prevent vibrations.
2. Fasten the outdoor unit legs to the mounting base, as shown in Fig. 12. The cushion goes between the legs and the mounting base.
3. Be sure that the unit is leveled.
MAKE REFRIGERANT PIPING CONNECTIONS (OUT- DOOR UNIT) -- To connect the refrigerant lines:
Make sure to properly identify and separate between the piping and control cables coming from indoor unit No. 1 and the piping
and cables coming from indoor unit No. 2
TH3 SENSOR
(HEAT PUMP ONLY)
METAL CONDUIT
CONNECTION PLATE
POWER SUPPLY
CABLE
INTER UNIT CABLE
4 ABSORPTION CUSHION TO
BE PUT UNDER EACH LEG
Fig. 12 -- Legs Mounting Base and Wiring Outdoor
Units
Models: DFC2A/H318J2A, DFC2A/H324J2A
PLASTIC CONTROL
COVER
INDOOR UNIT 2 X 09, 2 X 12
OFF ON ,_ T[MEI_
IR RECEIVER FILTER
Fig. 12A -- Indoor unit LED's and Wiring
AUTO/OFF
_=)FILTEJ
Operation push button for automatic operation (23°C/73°F),
turning the a/c OFF, canceling the malfunction indication,
and resetting the filter LED.
SERVICE LED
FLARING AND CONNECTING REFRIGERANT LINES
1. Remove the protective cap from the flare fitting.
2. Remove the protective cap from the tubing and cut to the required length. Be sure that the cut is perpendicular and
clean, without burrs.
3. Slip the flare nut on the tubing and flare the tube end using standard flaring tools.
4. Tighten the nut until resistance is met. Mark the nut and the fitting. Using a suitable wrench tighten an additional V4
turn. Use the following specified torque, according to con- nection size:
Mixed-Phase line: Suction line:
1/4 in.-(12.3 fit-lb.) 1/2 in.-(36 fit-lb.)
Both refrigerant lines need to be insu-
lated separately
NOTE: The service valves on the outdoor unit must remain closed until all 4 connections have been made.
EVACUATE TUBING AND CHARGE THE SYSTEM -- When all the fittings are connected, air must be expelled, then
refrigerant charge nmst be checked and adjusted. Follow the steps below.
1. Open the service port cap on the suction line valve (large valve of unit No. i).
2. Connect the vacuum pump to the service port of unit No.
1 via the pressure gage and evacuate to 500 microns to
eliminate contamination and moisture.
3. Disconnect the vacuum pump. Unit should maintain 500 microns for 5 minutes.
4. Remove the service port caps from the mixed-phase valve and suction line valve
5. Open the mixed-phase valve (small valve) with an Allen wrench.
6. Open the suction line valve (large valve) with an Allen wrench.
7. To evacuate and charge unit No. 2 repeat steps 1 thru 6.
8. The outdoor unit is supplied with sufficient R-22 re-
frigerant for up to 25 ft. lineset length. Add 0.9 oz. of
refrigerant for each additional 3 ft. of tubing length.
9. Make sure that the valves are properly opened. Be careful not to open them more than required as this may damage
the thread.
10. Replace the service port cap. Using refrigerant oil, lubri- cate the cap beam and hand tighten until resistance is met.
Use a suitable wrench to tighten the cap by an additional
1/2 turn.
Power Supply -- See Tables 4 and 5 for electrical data and Fig. 13-14 for system wiring diagrams.
Leak Test -- Leak test all fittings with appropriate test equipment.
10
Table 4_Electrical Data, Indoor Units -- 30VDC
UNIT VOLTAGE MCA* MOCP* FULL FAN MO- COM- COMPRESSOR
LOAD TOR PRESSOR LOCKED ROTOR AMPS AMPS AMPS AMPS
DFF2AH 09JIA 30VDC N/A N/A 1.8 1.1 N/A N/A DFF2HH 12JIA 30VDC N/A N/A 1.8 1.5 N/A N/A
LEGEND
MCA Minimum Circuit Amps MOCP - Maximum Overcurrent Protection
* If indoor unit is powered from outdoor terminN block, the MOCP for the
outdoor unit is for both sections
NOTE: Specifications and performance data are subject to change with-
out notice.
3095897
Table 5_Electrical Data, Outdoor Units -- 115, 1-60
UNIT VOLTAGE MCA* MOCP* FULL FAN MO- COM- COMPRESSOR
LOAD TOR PRESSOR LOCKED ROTOR AMPS AMPS AMPS AMPS
DFC2A 318J2A II5VAC 19.8 25 18 1.00 7.2 42
DFC2H 324J2A II5VAC 24.6 30 22.2 1.00 9.3 58
LEGEND
MCA Minimum Circuit Amps MOCP * Maximum Overcurrent Protection
If indoor unit is powered from outdoor terminal block, the MOCP for the outdoor unit is for both sections.
NOTE: Specifications and performance data are subject to change with-
out notice.
3095897
11
INDOOR UNIT ®
THlt tTi2 TH3
J6J7 J8
J18
1._2
Jt4
12
PPE _
lTo_
Jll
i._2 F-1
.._j ,, K9
L-J F-I
-L,'d K7
TAC 671 Main
_J Board
TAC 670 control
5130252398i-A
TB
FAN -, -_-_
H.LT.V - _RE_O
-12V BLK RED *_0VDC
r N MOTO
FAN1 BLUE
_IFAN2RgO J4 r_
FAN3 BLK
_ s
II OND;
II
I I
I1
LI N_
115VAC
Main AC Supply
Models2 X 09/ 2 X 12 WiringDiagramHeatpump
OUTDOOR UNIT
BL. L._
®
i NLW
iiRv__,
COMP
DC RT_
:673
' Boarc K_
® j
GREEN
GREEN
_BR
*BR
*BLUE
*BLUE
*G_YEL
®
BLK
N BLUE
DC_ LI BR
_GREEN
0
TH3
RVS
BLK
BLK
ILTVI
*BLUE
cc@
_--_f_ _ TB
COMP.
v *OR
GND
FAN
MOTOR
TH3
RVS
BLK _ BLK
BLK
®
TB 1 _ J1
K3
TAC673
:o_1 Relay Board
o
GREEN GREEN
co(i)
FAN
MOTOR
®
TB
-_yEt.
_w__ - FAN
/_{!_ _ H.LT.V
RED 12V
J1 BLK*12V
+30v WH
J4 J3
RED+30VDC FANI BLUE BU_OCRTN i
YEL VSP FAN2 REO
BLOC -- _,j 14_-F,J
MOTOR _ FAN3 B_K
TAC672B
INDOOR UNITQ
J8 J7 J6
JIB ___
K5rTq t
-L_
Lr_LL,,Id
J_-" ljl:
STEF
K8 !,LL_
K9 i_L_
TAO 671 Main
Board
TAC670 control
LEGEND
CC -Compressor Capacitor COMP*Compressor
FC -Fan Capacitor GND *Ground
RVS *Reversing Valve Sehoid HLTV -HeatingLow Tamp.Valve
TB -Terminal Block BLDC * brushless DC TH 1 =Return airsensor TH 2 -Indoor coil sensor TH3 -Outdoor coil sensor
(_ - Indoor unit 1 circuit
(_) = Indoor unit 2circuit
"" -16 AWG _ -14 AWG * =12 AWG
ALL OTHER WIRES 18 AWG
0 - Splice
* Terminal(Unmarked)
-- Factory Wiring
...... Field Control Wiring
_._ Field Power Wiring
Fig, 13 -- System Wiring Schematic DFF2HHO9J1A, DFF2HH12J1A FAN COIL WITH DFC2H318J2A, DFC2H324J2A Condensing Unit
INDOORUNIT®
J6J7 J8
JiB
F-_._ FAN
LJ
_K_._--i'-_K_LLB.L._V
L- _ RVS
l._J
LJ
_
+30V WH
-]K8 FAN1 BLU J._J _'-_ K8 FAN 2 _
K7i'-I
TAB 671 Main
Board
TAC 670 contro{
51302523982-A
TB
r! _ "RE_
_EN
TB®
_BLDC
_ MOTOR
GND
L1N_
115VAC
Main ACSupply
Models2X 09/ 2X 12 Wiring DiagramCoolingOnly
OUTDOOR UNIT
BL_ L_
®
J1 TB 1 J [
FAN
TAB 673
Relay Board
GREEN
GREEN
BR _BR
BLUE
BLUE
'GR/YEL
; ®
BLK
BLUE
DC_ L1 BR
_GREEN
cc(
! 'B
COMP.
_OR
GND
0 BLK
BLK _BLUE
GR_EL
-] BLK
®
TB1 Jl
BLK
BL KI TAC 673
L
(9
GREEN
i GREEN
ccQ
COMP, Q
BOE'I:
FC@
FAN FAN
MOTOR MOTOR
INDOOR UNITQ
O
TB
OR
"RED R_I
TB_
RE_* 30VDC
y_L VSp
BLD_
MOTOR
m H,L.'KV
:L RMS
RED+12V
BLK-12V
+3OV WH
FAN1 BL_
FAN2 RED
;ifTHI
J8 J7 J6
J18 ___
K5r73 l
KL_L,,.LJ
--_,2d
K9 iLLJ
K_i,L;J
TAB 674 Main
Board
TAC678control
LEGEND
CC -Compressor Capacitor
BOMP-Compressor
FC -Fan Capacitor GRD -Ground TB -Terminal Block BLDB * brushless DB
TR t -Return airsensor TH2 -Indoor coil sensor
-Indoorunitl circuit
_) - Indoor unit 2 circuit
-16AWG rk4 AWG
-42 AWG
_L OTHER WIRES 48 AWG
0 * Splice
* Terminal(Unmarked)
-- Factory Wiring
...... Field Control Widng
_._ Field Power Wiring
Fig. 14 -- System Wiring Schematic DFF2AHO9JIA, DFF2AH12JIA FAN COIL WITH DFC2H318J2A, DFC2A324J2A Condensing Unit
START-UP
System Checks
1. Conceal the tubing where possible.
2. Make sure that the drainage tube slopes downward along
its entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall.
5. Seal the hole through which the cables and tubing pass.
6. Connect the air conditioner to the power source and turn it
Oil.
7. Check all air conditioner operating modes. Refer to Own- er's Manual for operating details.
INDOOR UNIT
1. Do all the remote controller buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drainage work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
2. Is noise, drain water or airflow from the unit likely to dis- turb the neighbors?
3. Are there any gas leaks?
EXPLAIN THE FOLLOWING ITEMS TO THE CUSTOMER, WITH THE AID OF THE OWNER'S MANUAL:
1. How to turn the air conditioner on and off; selecting cool- ing, heating and other operating modes: setting a desired
temperature: setting the timer to automatically start and stop air conditioner operation: and the other features of the
remote controller and display panel.
2. How to remove and clean the air filter.
3. How to set the air deflection louver.
4. Explain care and maintenance.
5. Present the Owner's Manual and installation instructions to the customer.
CARE AND MAINTENANCE
The following may be performed by the equipment owner. Outdoor Units
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing recommended maintenance, be sure unit
main pow*erswitch is turned off.
CLEANING COILS -- Coil should be washed out with water or blown out with compressed air. Clean coil annu-
ally or as required by location and outdoor air condi- tions. Inspect coil monthly and clean as required. Fins
are not continuous through coil sections. Dirt and debris may pass through first section, become trapped between
the row of fins and restrict outdoor unit airflow. Use a flashlight to determine if dirt or debris has collected be-
tween coil sections. Clean coil as follows:
1. Turn off unit power and install lockout tag.
2. Using a garden hose or other suitable equipment, flush coil from the outside to remove dirt. Be sure to flush all
dirt and debris from drain holes in base of unit. Fan mo- tors are waterproof.
Indoor Units
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal
injury or death. To avoid the possibility of electric shock, before performing
any cleaning and maintenance operations, always turn off power to the system by pressing the ON/OFF button on the
remote control and turn off the separate disconnect switch located near the unit.
If the indoor unit is on a separate switch, be sure to turn this disconnect off as well.
COMPONENT DAMAGE HAZARD Failure to follow this may result in unit component damage.
Do not wash filter in water over 120°F (to avoid shrinkage). Do not expose filter to fire (to avoid fire damage). Do not expose filter to direct sunlight. Clean filter more frequently when air is extremel'¢ dirty.
ELECTRICAL SHOCK, FIRE COMPONENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and or property damage.
Do not attempt to clean or service components in control box.
To Clean the Indoor Unit Front Panel -- if the front panel of the unit becomes dirty or smudged, wipe the out-side of the panel
with a soft dry cloth. Use a mild liquid deter-gent and wipe off carefully with a dry cloth.
To Clean Indoor Coil -- To clean the coil, remove indoor unit front panel and vacuum the coil fins, using care not to bend or
damage fins.
LUBRICATION -- The indoor-fan, automatic air sweep, and the outdoor-fan motors are factory lubricated and require no oiling.
Air Filters for Indoor Units
COMPONENT DAMAGE HAZARD Failure to follow this caution may result in unit component
damage. Operating your system with dirty air filters may damage the
indoor unit and, in addition, can cause reduced performance, intermittent system operation, frost build up
on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly.
TO REMOVE AIR FILTERS -- Open the unit's front panel by lifting the lower part and pulling it gently outward and upward.
Pull out the filters.
TO CLEAN OR REPLACE FILTERS -- Filters can be vacuumed or washed in warm water. Shake filter to remox, e any
excess water, and replace it back. If the filter has begun to break
14
downoristorn,replaceit.Replacementfiltersareavailable throughalocaldealer.
SERVICE
The following should be performed by a qualified service technician.
Clean Condensate Drains -- (;lean all drains and drain pans at the start of each cooling season. Check the flow by pouring water
into the drain.
Clean or Replace Drain Pan -- The drain pan should only be cleaned or replaced by a qualified service technician.
1. Place a plastic sheet on the floor to catch any water that may spill from the drain pan.
2. Remove the intake grille and distribution assembly.
3. Remove the condensate water in the drain pan by letting water drain into a 3-gallon bucket.
15
TROUBLESHOOTING (Tables 6-8, and Fig. 15)
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Be sure to check for broken wires or loose cable lugs before
troubleshooting system.
Table 6_Service Indicators
LAMP STATUS
1 Flash
INDICATION
Faulty TH1 Sensor
2 Flashes Faulty TH2 Sensor
3 Flashes Low Pressure
4 Flashes High Pressul_e
5 Flashes Low Voltage
6 Flashes High Voltage
CORRECTION ACTION
Check the THI thermistor for correct resistance.
Check for proper connection. Replace thermistor if necessary.
Check the TH2 thermistor for correct resistance. Check for proper connection.
Replace thermistor if necessary.
Check system pressures. Check refrigerant charges. Check thermistors (THI and TH2) for correct resistance.
Check system pressures. Check refrigerant charges. Check thermistors (THI and TH2) for correct resistance.
Check operating voltage. Check electrical connections.
Check operating voltage. Check electrical connections.
POWER LED. OFF WHEN SYSTEM IS
OPERATING AND FLASHES WHEN SYSTEM IS IN ERROR
(DOES NOT INDICATE ERROR CODE)
CLEAN FILTER INDICATOR FLASHED AFTER 250 HOURS
OF OPERATION
Fig. 15 -- Indicator Lights
16
OPERATION LED. INDICATES ERROR
Table 7--DFS2A/DFS2H Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion
TEMPERATURE
-4.0
-2.2
-0.4
1,4
3.2
5,0 6,8
8,6
19.4
12.2
14.0
15.8 17,6
19.4
21.2
23.0
24.8 26,6
28.4
39.2
32.0
33.8
35.6
37.4 39,2
41.0
42.8
44.6
46.4
48.2
59.0
51.8
53.6
55.4
57.2
59.0
69.8
62.6
64.4 66,2
68.0
69.8
71.6
73.4
75.2
77.0
78.8
89.6
82.4
84.2
86.0
87.8 89,6
91,4
93.2
NOTE: Resistance tolerance _+ 3%.
TEMPERATURE TEMPERATURE TEMPERATURE MINIMUM MEAN MAXIMUM
(_C) TOLERANCE TOLERANCE RESISTANCE RESISTANCE RESISTANCE
-20 ±2.0 ±1.1 30.89 32.44 34.05
-19 +2.0 +1,1 29.46 30.93 32.45
-19 + 2.0 + 1.1 28.12 29.51 30.94
-17 ± 2.0 ± 1.1 26.84 28.16 29.51
-16 ± 2.0 ± 1.1 25.64 26.88 28.15
-15 +2.0 +1,1 24.49 25.66 26.87
-14 +2.0 +1,1 23.40 24.52 25.66
-13 ±2.0 ±1.1 22.38 23.43 24.50
-12 ±2.0 ±1.1 21.40 22.39 23.41
-11 +2.0 +1,1 20.47 21.41 22.38
-10 + 1.8 + 1.0 19.59 20.48 21.40
-9 ±1.8 ±1.0 18.74 19.59 20.45
-8 ±1.8 ±1.0 17.94 18.74 19.56
-7 +1.8 +1,0 17117 17193 18171
-6 +1.8 +1.0 16.44 17.16 17.90
-5 --+1.8 --+1.0 15.75 16.43 17.13
-4 ±1.8 ±1.0 15.10 15.74 16.40
-3 +1.8 +1.0 14.47 15.08 15.71
-2 + 1.8 + 1.0 13.87 14.46 15.05
-1 ±1.8 ±1.0 13.31 13.86 14.42 O --+1.8 --+1.0 12.77 13.29 13.83 1 +1.8 +1.0 12.25 12.74 13.25 2 +1.8 +1.0 11.75 12.22 12.70
3 --+1.8 --+1.0 11.28 11.73 12.18 4 ±1.8 ±1.0 10.83 11.25 11.68 5 +1.8 +1.0 10.40 10.80 11.21 6 +1,8 +1.0 9.986 10.370 10.76
7 +1.8 +1.0 9.595 9.960 10.33 8 +1.8 +1.0 9.222 9.569 9.921 9 ±1.8 ±1.0 8.866 9.196 9.530
10 ±1.8 ±1.0 8.526 8.840 9.157
11 +1.8 +1.0 8.197 8.496 8.797 12 +1.8 +1.0 7.883 8.167 8.453 13 ±1.8 ±0.6 7.583 7.853 8.125 14 --+1.8 --+0.6 7.296 7.553 7.812 15 +1.8 +0.6 7.022 7.267 7.513
16 +1.6 +0.9 6.761 6.993 7.227 17 ±1.6 --+0.9 6.510 6.731 6.954 18 ±1.6 ±0.9 6.271 6.481 6.693 19 +1.6 +0.9 6.042 6.242 6.444
20 +1.8 +o.6 5.822 6.013 6.205 21 ±1.6 ±0.9 5.611 5.793 5.975 22 ±1.6 ±0.9 5.408 5.581 5.755 23 +1.8 +0.6 5.214 5.379 5.544 24 +1.6 +0.9 5.028 5.185 5.343
25 _+1.8 ±0.9 4.850 5.000 5.150 26 ±1,6 ±0.9 4.675 4.821 4.968 27 +1.6 +o.e 4.508 4.650 4.793 28 +1.8 +0.9 4.347 4.486 4.626
29 ±1,8 ±1.0 4.193 4.329 4.466 30 ± 1.8 ± 1.0 4.046 4.179 4.312 31 +1.8 +1.0 3.904 4.033 4.163
32 +1,8 +1.0 3.767 3.894 4.020 33 ±1,8 ±1.0 3.637 3.760 3.884
34 ±1.8 ±1.o 3.511 3.631 3.752
(_P) (_C) (K_) (K_) (K_)
17
Table 7 --DFS2A/DFS2H Thermistor TH-1, TH-2, and TH-3 Temperature to Resistance Conversion (Cont.)
TEMPERATURE TEMPERATURE TEMPERATURE TEMPERATURE MINIMUM MEAN MAXIMUM
_F) (L_C) TOLERANCE TOLERANCE RESISTANCE RESISTANCE RESISTANCE
95.0 35 + 1.8 + 1.0 3.391 3.508 3.626 96,8 36 + 2.0 + 1.1 3.275 3.390 3.505
98.6 37 ± 2.0 ± 1.1 3.164 3.276 3.389
100.4 38 ±2.0 ±1,1 3.058 3.167 3.277
102.2 39 +2.0 +1,1 2.956 3.062 3.169
104.0 40 ±2.0 ±1.1 2.857 2.961 3.066
105.8 41 +2.6 +1.1 2.762 2.864 2.966
107.6 42 ±2.0 ±1.1 2.671 2.770 2.870
109.4 43 +2.2 +1.2 2.583 2.679 2.777
111.2 44 ±2.2 ±1,2 2.498 2.593 2.688
113.0 45 + 2.2 + 1.2 2.417 2.509 2.602
114.8 46 ±2.2 ±1.2 2.339 2.429 2.520 116,6 47 +2.2 +1.2 2.264 2.352 2.441 118,4 48 ±2.3 --+1.3 2.192 2.227 2.364
120.2 49 +2.3 +1.3 2.122 2.206 2.291
122.0 50 ±2.3 ±1.3 2.055 2.137 2.220
123.8 51 +2.3 +1.3 1.990 2.070 2.151
125.6 52 ±2.3 ±1.3 1.928 2.006 2.085
127.4 53 +2.3 +1.3 1.867 1.943 2.021
129.2 54 ±2.3 ±1.3 1.809 1.883 1.959
191.0 55 +2.5 +1.4 1.753 1.826 1.900
192.8 56 ±2.5 ±1.4 1.699 1.770 1.842
194.6 57 + 2.5 + 1.4 1.647 1.717 1.787
196.4 56 ±2.5 ±1.4 1.597 1.665 1.734
198.2 59 + 2.5 + 1.4 1.549 1.615 1.683
140.0 6O --+2.5 --+1.4 1.503 1.567 1.633
141.8 61 ±2.7 ±1.5 1.458 1.521 1.585
143.6 62 + 2.7 + 1.5 1.414 1.476 1.539
145.4 63 ± 2.7 ± 1.5 1.372 1.432 1.494
147.2 64 +2.7 +1.5 1.332 1.391 1.451
149.0 65 ±2.7 ±1.5 1.293 1.350 1.409
150.8 66 + 2.9 + 1.6 1.255 1.311 1.369
152.6 67 ± 2.9 ± 1.8 1.219 1.274 1.330
154.4 68 +2.9 +1.6 1.184 1.237 1.292
156.2 69 ±2.9 ±1.6 1.150 1.202 1.256
158.0 76 +2.9 +1.6 1.117 1.168 1.221
NOTE: Resistance tolerance _+ 3%.
_F) (_C) (K_) (K_) (K_)
18
Table 8---General System Troubleshooting Guide
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
Unit Fails to Start. Power supply from outdoor unit to indoor unit is Check for proper connection of power at disconnect.
Only Indoor Fan Works The selected mode is Fan Only, or Cool when Check if the remote control is in the desired mode. If not, select
when Cooling or Heat- heating is desired, the correct mode (refer to User manual). Also note that every 15
ing is Desired. NOTE: minutes (maximum) the compressor will be switched minimally Indoor fan runs contin- on for 3 minutes.
uously in cooling mode.
Only Indoor Fan Motor Overload safety device on compressor is cut out Switch off power and try again after one hour. and Outdoor Fan Motor due to high temperature. are Working. No Cool-
ing and/or Heating Compressor run capacitor is burnt. Replace compressor run capacitor.
Takes Place. Compressor winding shorted. Replace compressor.
No Air Supply at Indoor Indoor fan motor is blocked or turns slowly. 1. Check vottage. Repair wiring if necessary. Unit (Compressor Op- 2. Check indoor fan wheel if tight on motor shaft. Tighten if nec- erates), essary.
Low Capacity. Lack of refrigerant. Ice formation on the evapora- Unit must be charged (according to the nameplate) after Iocal-
In Heat Mode, Only A/C operating in defrost cycle. Wait 10 minutes (maximum) until the unit resumes normal opera- Compressor Runs. Out- tion.
door and Indoor Fan Motors are Stopped.
Water Accumulates Drain pan pipe or hose is clogged or the spout of Disassemble plastic drain pipe from spout of evaporator drain
and Overflows from drain pan is clogged, pan. Flush with clean water. Evaporator Drain Pan.
Unit Does Not Operate The unit is in the Auto, (emergency) mode. Push button once to cancel Auto, (emergency) mode. in Desired Mode.
not connected. Power supply to unit not connected (POWER
LED Off). Fuse blown (POWER LED Off). Reset circuit breaker or replace line fuse.
ON/SEND button has not been pressed. Press ON/SEND button on remote control. Indoor unit does not receive transmitted com- Make sure that nothing is blocking the remote control transmis-
mands, sion to the unit.
Temperature is set to a value which is too high (in Observe the temperature setting on the remote control. Also note Cool mode), that each 15 minutes (maximum), the compressor will be
switched on minimally for 3 minutes.
Indoor fan motor capacitor is burnt. Replace indoor fan motor capacitor. Indoor fan motor winding is burnt. Replace indoor fan motor.
In Heat mode: Delayed start for indoor fan motor. Normal software delay (maximum of 20 sec). Clogged air filters. Clean filters.
tor coil. izing the gas leak. Clogged air filters. Clean filters.
Faulty remote control settings. 1. If remote control symbols respond to the commands correctly,
check the unit ID Code (Standard or Alternative). Refer to "Changing Unit ID Code" in the Owner's Manual.
Remote control low battery. Replace remote control batteries.
The Unit Receives Inter- Common Infrared Code. Modify the Remote Control IR transmission code. ference from Other Re- Refer to "Changing Unit ID Code" inthe Owner's Manual.
mote Control or the Re- mote Control Interferes
with Other Instruments.
IMPORTANT:
The units are designed to work in heat mode only down to -10°C (14 ° F) outdoor ambient temperature. If at starting time outdoor temperature is equal or lower than -10°C (!4°F) the unit wil! not start and the filter led will flash five
(5) times to indicate that low temperature protection is activated.
Manutacturer reserves the right to discontinue, or change at any t_me, speolhCatlOnS or designs without notice and without incurring ObllgBtlons,
2. If Oool commands are OK, but Heat symbol is skipped on LCD, refer to setting the remote to cooling or heat pump on the
Owner's Manual.
3. Replace remote control.
International Comfort Products, LLC
Lewisbur_, Tennessee 37091
19
Loading...