International Comfort Products CRLPELEV001A00, CRLPELEV004A00, CRLPELEV007A00, CRLPELEV009A00 Installation Manual

High Altitude Gas Conversion Kit
Gas Heating/Electric Cooling
3 to 15 Ton Small Rooftop Units
Accessory LP (Liquid Propane)
Installation Instructions
PART NO. CRLPELEV001A00-CRLPELEV004A00,
CRLPELEV007A00-CRLPELEV009A00

TABLE OF CONTENTS

PACKAGE CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . .2
LP (Liquid Propane) Kit. . . . . . . . . . . . . . . . . . . . . . . . .2
High Altitude Kit (Natural Gas) . . . . . . . . . . . . . . . . . .2
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . .2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
LP CONVERSION KIT INSTALLATION . . . . . . . . . . .4
from Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Step 2 — Modify Burner/Valve Assembly . . . . . . . .5
Step 3 — Re-install Burner Assembly. . . . . . . . . . . .6
Step 5 — Check Unit Operation
and Make Necessary Adjustments . . . . . . . . . . . .8
HIGH ALTITUDE CONVERSION KIT
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Step 1 — Remove Burner Section from
Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Step 2 — Modify Burner/Valve Assembly . . . . . . . .8
Step 3 — Re-install Burner Assembly. . . . . . . . . . . .8
Step 4 — Check Unit Operation and
Make Necessary Adjustments . . . . . . . . . . . . . . . .9
IMPORTANT: Read these instructions completely before attempting to install this accessory.
Table 1 — Unit Usage
CARRIER MODELS
Check positions 7-8 on unit dataplate for unit size.
MODEL UNIT SIZES NOMINAL TONS
48FC 04-07 3-6 48GC 04-06 3-5 48TC 08-16 7.5-15 48HC 07-14 6 -12.5 48KC 04-06 3-5 48LC 04-12 3-10
BRYANT MODELS
Check positions 6-7 on unit dataplate for unit size.
MODEL UNIT SIZES NOMINAL TONS
582K 04-07 3-6 581K 04-06 3-5
580J 08-16 7.5-15 581J 07-14 6-12.5 582J 04-06 3-5
ICP MODELS
Check positions 6-7 on unit dataplate for unit size.
MODEL UNIT SIZES NOMINAL TONS
RGV 036-072 3-6
RGW 036-060 3-5
P
RGS 089-180 7.5-15 RGH 072-150 6-12.5 RGX 036-060 3-5
IMPORTANT: The accessories described in this instal­lation instructions manual are suitable for use on the models listed below. DO NOT ATTEMPT TO INSTALL ON MODELS AND SIZES NOT INCLUDED IN THESE TABLES.
Catalog No. 04-53480200-01 Printed in U.S.A. Form IIK-CRLPELEV01-07 Pg 1 8-18 Replaces: IIK-CRLPELEV01-06
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PACKAGE CONTENTS

LP (Liquid Propane) Kit

ACCESSORY PART NO.
CRLPELEV003A00
(LP Only)
CRLPELEV004A00
(LP Only)
CRLPELEV009A00
(LP Only)
COMMON CONTENTS QTY PART NUMBER
ELBOW, 1/8” NPT x 90° 1 CA05RA001 ELBOW, STREET 1/8” NPT x 90° 1 CA15RA001 NIPPLE, 1/8” PIPE x 3/4” 1 CA01CA001 NIPPLE, 1/8” PIPE x 1-1/2” 1 CA01CA006 NIPPLE, 1/8” PIPE x 3-1/2” 1 CA01CA020 SWITCH, LP PRESSURE 1 HK02LB008 WIRE, BROWN 1 99WG7373XC200918 SPRINGS, LP CONVERSION 2 EF39ZW023 LABEL, LP CONVERSION KIT
RATING PLATE LABEL, LP RESPONSIBILITY 1 48TM501014 LABEL, HIGH-ALT.
RESPONSIBILITY
Package Contents CRLPELEV003 and 004A00 Only
CRLPELEV003, 004A00 ONLY QTY PART NUMBER
LABEL, GAS VALVE LP CONV 1 48TM501013 LABEL, UNIT WARNING (LP) 1 48TM501012
Package Contents CRLPELEV009A00 Only
CRLPELEV009A00 ONLY QTY PART NUMBER
LABEL, GAS VALVE LP CONV 1 48TM504835 LABEL, UNIT WARNING (LP) 1 48TM504836 SWITCH, TEMPERATURE
ACTUATED
SIZE QTY PART NUMBER
46 5 LH32RF080 47 5 LH32RF079 48 5 LH32RF076 49 5 LH32RF073 50 5 LH32RF070 51 5 LH32RF067 52 5 LH32RF065 53 5 LH32RF060 54 5 LH32RF055 55 5 LH32RF052 51 10 LH32RF067 52 10 LH32RF065 53 10 LH32RF060 54 10 LH32RF055 55 10 LH32RF052
ORIFICES
1 48TM502595
1 48TM501015
1 HH18HA147

High Altitude Kit (Natural Gas)

ACCESSORY PART NO.
CRLPELEV001A00
(Natural Gas Only)
CRLPELEV002A00
(Natural Gas Only)
CRLPELEV007A00
(Natural Gas Only)
CRLPELEV008A00
(Natural Gas Only)
COMMON CONTENTS QTY PART NUMBER
LABEL, HIGH-ALT. RESPONSIBILITY
LABEL, NG CONVERSION KIT RATING PLATE
SIZE QTY PART NUMBER
31 5 LH32RF120 32 5 LH32RF116 33 5 LH32RF113 35 5 LH32RF110 36 5 LH32RF105 37 5 LH32RF104 38 5 LH32RF102 39 5 LH32RF103 44 5 LH32RF086 45 5 LH32RF082 36 10 LH32RF105 37 10 LH32RF104 38 10 LH32RF102 39 10 LH32RF103 40 10 LH32RF098 41 10 LH32RF096 42 10 LH32RF094 43 10 LH32RF089
ORIFICES
1 48TM501015
1 48TM502594

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and la­bels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Recognize safety information. This is the safety-alert sym­bol . When you see this symbol on the unit and in instruc­tions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert sym­bol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAU­TION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
2

GENERAL

FIRING TUBE
NOx BAFFLE
These models are shipped from the factory equipped to op­erate with natural gas at elevations up to 2000 ft (610 m). The units must be modified if installed at elevations above 2000 ft (610 m), or if operated with liquid propane.
For installations in Canada, the input rating must be derat­ed by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
Seven different gas conversion kits are available, as shown in Package Contents table. Each kit contains a particular range of orifice sizes plus other hardware and labels neces­sary for converting the unit. Refer to Tables 2-5 to determine the recommended orifice size based on the nominal heat size, fuel type, and elevation. Knowing this orifice size, it is possi­ble to select the proper Kit Accessory Part Number from Package Contents table.
IMPORTANT: If Low NOx units are converted to LP gas, the Low NOx baffle must be removed. (See Fig. 1.) The convert­ed unit will no longer be classified as a Low NOx unit. For in­stallation simplicity, it is suggested that the LP Conversion Kit be used with standard units only.
AVERTISSEMENT
FEU, EXPLOSION, EMPOISONNEMENT PAR CAR­BON DE MONOXYDE, RISQUE DE DOMMAGE ÀL­APROPRIÉTÉ
La négligeance de suivre l’avis suivant, peut causer des blessures personnelles, la mort ou du dommage à la pro­priété.
Cette trousse de conversion doit être installée par un Entre­preneur qualifié, selon les instructions du fabricant et doit se conformer à toutes les exigences et tout les codes perti­nents de l’autorité compétente. L’Entrepreneur qualifié est responsable, et doit s’assurer de bien suivre les instructions dans cet avis. L’installation sera considèrèè conforme et rencontrant les spécifications et instructions du fabriquant qui sont inclus dans la trousse, seulement aprés vérification de l’opération de la fournaise convertie.
WARNING
EXPLOSION, PERSONAL INJURY HAZARD Failure to follow this warning could result in personal inju-
ry or death. Two-Stage Gas Valve - Unit is designed to operate at see
Tables 6-8 of manifold pressure with propane gas. Single-Stage Gas Valve - Unit is designed to operate at a
10.-in. wc of manifold pressure with propane gas.
Fig. 1 — Low NOx Baffle Location
WARNING
FIRE, EXPLOSION, CARBON MONOXIDE POISON­ING, PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal inju­ry, death or property damage.
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. The qualified service agency is respon­sible for the proper installation of this kit. The installation is not proper and complete until the operation of the convert­ed furnace is checked as specified in the manufacturer’s in­structions supplied in the kit.
WARNING
FIRE, EXPLOSION, ELECTRICAL HAZARD Failure to follow this warning could result in personal inju-
ry, death or property damage. Gas supply MUST be shut off before disconnecting electri-
cal power and proceeding with conversion.
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal inju-
ry or death. Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect switch. Tag disconnect switch with suitable warning label.
3
WARNING
GAS VALVE
INLET PRESSURE
TAP SET SCREW
MANIFOLD
GAS VALVE
MANIFOLD PRESSURE
TAP SET SCREW
FIRE HAZARD Failure to follow this warning could result in personal
injury, death, and/or property damage. Inlet pressure tap set screw must be tightened and
1
/8-in. NPT pipe plug must be installed to prevent gas leaks.
WARNING
FIRE HAZARD Failure to follow this warning could result in personal
injury, death, and/or property damage. Manifold pressure tap set screw must be tightened and
1
/8-in. NPT pipe plug must be installed to prevent gas leaks.
Attach Responsibility Label Here (Inside Panel)
Attach WARNING Label Here
Burner Access Panel
Attach Conversion Kit Rating Plate Label Here (Inside Panel)
Gas Val ve
Fig. 2 — Typical Base Unit
4. Slide out burner section side panel.
5. Disconnect gas piping at unit gas valve.
6. Remove wires connected to gas valve. Mark each wire.
7. Remove igniter and sensor wires. Mark each wire.
8. For units with burner sections as shown in Fig. 3, remove the 2 screws that attach the burner rack to the vestibule plate. For units with burner sections as shown in Fig. 4 and 5 remove the 4 screws that hold the manifold to the sheet metal brackets.
BURNER RACK MOUNTING SCREWS (1 OF 2 SHOWN)
Attach Gas Valve Converstion to LP Label here
GAS VALVE MANUAL SHUTOFF
GAS VALV E BRACKET
Check that your unit model number agrees with Table 1.

LP CONVERSION KIT INSTALLATION

IMPORTANT: Before starting installation of this acces­sory, check your unit’s dataplate for model and size and compare to the Unit Usage table on page 1. If your unit’s size designation exceeds the largest size listed for your model, STOP. This accessory is not for use on your unit. Consult with your sales office for the correct accessory part number for use on your unit.

Step 1 — Remove Burner Section from Base Unit

1. Shut off main gas supply to unit.
2. Shut off power to unit and install lockout tag.
3. Remove burner access panel. (See Fig. 2.)
MANIFOLD PRESSURE TA P
Fig. 3 — Gas Section Details (Small Chassis Shown)
9. Remove the gas valve bracket.
10. Slide the burner rack or manifold out of the unit.
11. For small chassis units only-inspect the inlet of the heat exchanger tubes for presence of V-shaped NOx baffles. (See Fig. 1.) If baffles are present, they must be removed prior to converting unit for propane gas. Using needle nose pliers, remove NOx baffles. Squeeze sides of the baffle, if necessary, to remove from the heat exchanger tubes.
IMPORTANT: If this unit will be converted back to natural gas at a later time, these baffles should be retained for reuse. Otherwise the baffles may be dis­carded.
4

Step 2 — Modify Burner/Valve Assembly

SINGLE STAGE AND TWO STA GE HIGH REGULATOR COVER SCREW
REGULATOR ADJUST SCREW
REGULATOR SPRING
OUTLET PRESSURE TAP
REGULATOR ADJUST SCREW
LOW REGULATOR COVER SCREW (TWO STAGE ONLY)
REGULATOR SPRING
PILOT COVER SCREW
PILOT GASKET
PILOT ADJUST SCREW
1. Separate burners from frame by removing screws.
2. Remove existing gas orifices. Install the new orifices from the gas conversion kit, making sure they match the recommended size from Tables 2-5.
IMPORTANT: Never use Teflon tape to seal gas orifice threads because peeling tape can plug the orifice.
3. Remount burners to support frame.
IMPORTANT: The burners should be positioned in the same order as shipped from the factory. The crossover flame region of the outermost burners are pinched off to prevent excessive gas flow from the sides of the burner assembly. If the pinched crossovers are installed between two burners, the flame will not ignite properly.
4. Remove the plug on the inlet end of the gas valve using a
3
/16-in. hex wrench. (See Fig. 4 and 7 for units using White-Rodgers 36G gas valve and Fig. 5 and 6 for units using White-Rodgers 36H gas valve).
Fig. 4 — LP Pressure Switch Piping (36G Gas Valve
Shown)
1
5. a. For units with 36G valve, install the
/8-in. x 11/2-in. nipple where the plug was removed. (See Fig. 4.) Use pipe thread dope or tape (field-supplied, must be certi­fied for use with propane gas) for all joints, making sure not to get any excess in the pipe or valve. Next, install
1
the
/8-in. x 90 degree elbow, then 1/8-in. x 3/4-in. nipple, followed by the LP Pressure Switch as shown in Fig. 4. For Single-Stage Gas Valves, connect supplied brown jumper wire from the “NO” (Normally Open) terminal on the pressure switch to the terminal where the gray wire was attached. NOTE: Terminals are not marked on Gas Valve. For Two-Stage Gas Valves, connect the supplied brown jumper wire from the “NO” terminal on the pressure switch to terminal “M” on the gas valve. b. For units with 36H valve, install the
1
/8-in. x 3/4-in. nipple where the plug was removed. (See Fig. 5.) Use pipe thread dope or tape (field supplied, must be certified for use with propane gas) for all joints, making sure not to get any excess in the pipe or valve. Next, install the gas valve bracket over nipple, then the elbow, then
1
/8-in. x 31/2-in. nipple, then 1/8-in. x 90
1
/8-in. x 90 degree
degree street elbow, followed by the LP Pressure Switch as shown in Fig. 5. Connect the supplied brown jumper wire from the “NO” terminal on the pressure switch to terminal “MP” on the gas valve.
6. Remove regulator cover screw(s) from gas regulator(s). (See Fig. 7 or 6.) Save regulator cover screws.
7. Using a screwdriver, remove plastic adjust screw(s) from both regulators. (See Fig. 7 or 6.) Save plastic adjust screws.
8. Remove regulator spring(s) (silver) from gas regula­tor(s). (See Fig. 7 or 6.) Discard regulator springs.
9. Install propane gas regulator spring(s) (white) shipped with the kit into the gas regulator(s). (See Fig. 7 or 6.)
10. For two-stage gas valves, install plastic adjust screw into the high stage gas regulator, turn clockwise 13.5 turns. (See Fig. 7 or 6.) Then install plastic adjust screw into the low stage gas regulator, turn clockwise 9.5 turns. Replace regulator cover screws. (See Fig. 7 or 6.)
For single-stage gas valves, install plastic adjust screw into the single-stage gas regulator, turn clockwise 13.5 turns. Replace regulator cover screw. (See Fig. 7.)
Fig. 5 — LP Pressure Switch Piping (36H Gas Valve
Shown)
Fig. 6 — Two-Stage Spring Installation (36H Gas
Valve Shown)
5