Installation & Operating Instructions
PC/LM Series
WARNING
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or
servicing.
• More than one circuit breaker or disconnect switch may be required to de-energize the
equipment before servicing.
• Use #22 - #12 AWG wire - COPPER conductors ONLY. Rated 90°C Min.
• Installation and/or wiring must be in accordance with national and local electrical code
requirements.
• For outdoor locations, raintight, or wet locations, conduit hubs that comply with requirements
of the UL514B (standard for fitting for conduit and outlet boxes) are to be used.
• Photoelectric sensor shall be directly mounted to enclosure using standard conduit
connection means.
• When photoelectric sensor is mounted in a remote location, wiring shall be routed separately
from Class 1 wiring.
• When photoelectric sensor is mounted in a remote location and routed with Class 1 wiring,
the wiring insulation shall be rated for the minimum voltage of the Class 1 wiring.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
Risk of Fire or Electric Shock
NOTICE
• The warranty will be void if the wrong voltage is applied. Connect the wires in accordance with
the wiring diagram.
MOUNTING THE LightMaster MODULE
There are multiple mounting options for the LightMaster module. Follow the applicable guidelines for the
appropriate mounting method for your facility.
• Surface Mount in a control panel or enclosure
with a standard DIN rail
• Place the top two protruding guides located
on the back of the unit over the top lip of
the DIN Rail and snap into place.
• Mount as a Stand alone unit
• Mount the LightMaster in a TYPE 3R indoor/
outdoor enclosure.
NOTE: Also available: LM2 Series system with included
TYPE 3R enclosure.
Dimensions
DESCRIPTION
The LightMaster PC Series Lighting Control system independently controls one or two circuits based on the amount
of natural light in an area. When the detected light drops
below the congured foot-candle setting, LightMaster turns
circuits ON. When natural light rises above the setting,
LightMaster turns circuits OFF. Each circuit has adjustable
time delay dials from 0 to 100 seconds to prevent unwanted switching caused by headlights, lightning, and other
conditions. LightMaster can be used with LS2 high-range
opaque sensors for typical outdoor dusk-to-dawn applications or with LS1 clear sensors for indirect light applications.
MOUNTING THE LightMaster SENSORS:
Follow these guidelines to mount the LS1 or LS2 sensor.
• If sensor is mounted directly to enclosure of con-
troller, use standard conduit connection means.
• If sensor is mounted remotely from controller, either
route sensor wiring separately from class 1 wiring
or use wiring for sensor rated for the minimum voltage of adjacent class 1 wiring.
• The light level sensor can be mounted indoors or
outdoors.
• It must be mounted vertically with the wires facing
down.
• The wiring length should not exceed 330 feet and
should not be run in close proximity to current carrying wires.
• If you are using the sensor for dusk/dawn sensing,
position the sensor with the arrow facing a wall.
• If you are using the sensor to control interior light-
ing, awnings, or shades, position the sensor with
the arrow facing away from the building towards
the sunlight.
• Be sure to position the sensor so unwanted light-
ing, such as car headlights, will not inuence it.

TECHNICAL DATA:
Input Voltage: 120 VAC, 60 Hz
Resistive Rating: 10 Amp, 120-277 VAC per circuit
Ballast Rating: 8A @ 120-277 VAC
Output Relay: SPDT “isolated” contacts for each
circuit
Power Consumption: 2.5 VA
Humidity Range:
Control Unit 0 to 95% RH non-condensing
Sensor 0 to 100% RH
Weight: 8.5 oz
Mounting: Surface & DIN rail
(TYPE R enclosures available)
Light Sensitivity Adj.: .2 to 50 Foot Candles w/LS-1 sen-
sor
50 to 1000 F.C. w/LS-2 sensor
Time Delay Before
Switching: Adjustable 0 to 100 seconds
ADJUSTING LIGHT LEVEL and TIME DELAY CONTROLS
The amount of natural light present in an area can affect the
way the sensor performs. Be sure to account for the light
when conguring the LightMaster settings. If you have a
2-channel unit, be sure to adjust both channel controls to the
applicable settings.
1. Turn the light-level control(s) to the desired setting(s). See
the gure below for an illustration of the foot-candle levels
at various control settings.
12 FC
with LS1
Sensor
25 FC
37 FC
235 FC
with LS2
Sensor
465 FC
700 FC
WIRING INSTALLATION CHECKLIST
• Make sure the control has its own independent circuit for
the power supply.
• Be sure the power supply to the unit is from a circuit different from the load.
• INDUCTIVE LOADS should have a suitable VARISTOR and
RC network across the supply terminals to reduce voltage
spikes.
• DC INDUCTIVE LOADS should have a diode across their
terminals to eliminate back EMF of the inductor.
• In areas with frequent lightning occurrences, a surge suppressor should be installed.
WIRING INSTALLATION
Be sure to only connect the supply voltage designated on the
unit.
Terminal Connections
3-4 and 6-7 closes on light level decreasing below setpoint
M
~
INPUT NO COM NC NO COM NC
CH 1 CH 2
SENSOR
{
3 4 51 2 6 7 8 9 10 11
Jumper required between 9 and 10
0,2
FC
50
(50 FC) (1000 FC)
0,2
FC
50
2. Turn the time delay control(s) to the desired delay duration.
See gure below for an illustration of the seconds of delay
at various control settings. The delay begins when the red
LED changes (on or off).
50 SEC
25 SEC
0
SEC
75 SEC
100
STATUS INDICATION
A red LED for the corresponding circuit illuminates when the
natural light level is below the congured foot-candle level.
Follow this procedure to complete the wiring for the LightMaster.
1. Connect the power wires to terminals 1 and 2.
2. Connect power wire to switch common wire.
3. Connect the wire from the switch’s normally open contact(s)
to the load(s) or contactor coil(s) that are going to be controlled.
4. Mount the sensor to a junction box within 330 feet of the
control.
5. Connect the sensor wires to terminals 10 and 11.
6. Jumper terminals 9 and 10.
Wiring Multiple PC2s to One Sensor
Jumper
Terminal 9
to 10
on last unit or
if only one
PC2 is
installed
7. Note: Up to 10 modules may be wired to one sensor.
INTERMATIC INCORPORATED
Spring Grove, Illinois 60081-9698 U.S.A.
PRINTED IN MEXICO
www.intermatic.com
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic
ONE YEAR LIMITED WARRANTY
Incorporated will repair or replace it, at its sole option, free of charge. This warranty is extended to the original
household purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused
by accident, dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject
to unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance with
instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and
batteries; (f) the finish on any portion of the product, such as surface and/or weathering, as this is considered
normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL
DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY IS IN
LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE
WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE,
ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL BE
OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW
LIMITATIONS ON THE DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATION MAY NOT
APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was
purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by:
Intermatic Incorporated, Customer Service 7777 Winn Rd., Spring Grove, Illinois 60081-9698. For warranty
service go to: http://www.Intermatic.com or call 815-675-7000.