MODEL: T7802B
SEVEN-DAY DIAL TIME SWITCH
4 POLE; Two Normally Open - Two Normally Closed
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATION
40 AMP. RESISTIVE EACH POLE 120V -480V AC.
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR
277V AC. 1000 VA PILOT DUTY EACH POLE 120V - 277V AC.
24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC.
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER WG1603
CONTACT RATINGS:
208
277V
60 HZ
SUPPLY
LR3730
CLOCK
MOTOR
TO
LOADS
GROUND
WIRING DIAGRAM
SCREW
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock
motor voltage may be other than load voltage, but must be as specified. For terminal markings, internal wiring and contact arrangements refer to wiring diagram above. To form the common poles of a DOUBLE POLE
DOUBLE THROW switch, if required, install jumpers (extend supply wires) between terminals 1-6 and 3-8.
Use solid or stranded COPPER wire with insulation to suit installation. See table for gauge selection. To make
power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten terminal screws firmly. REPLACE FRONT
INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14
12
10
8
MAX.
LOAD
(AMP)
15
20
30
40
MIN.
INSUL-
ATION
TEMP(°C)
60
60
60
75
75°C INSULATION MAX. MOTOR
240 V.
2
2 1/2
3
5
LOAD (HP)
SINGLE PHASE
120 V.
1/2
1
2
-
208 V.
N/A
3 PHASE
240 V.
N/A
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at day-of-week and time of-day when “ON” operations are desired. Tighten tripper screws securely.
2. TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at times when “OFF”
operations are desired. Tighten tripper screws securely.
3. TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
4. TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-week and time-of-day
(AM or PM) on dial with the TIME POINTER. Some allowance may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TOOPERATESWITCHMANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as
indicated by arrows. This will not affect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--01172