Intermatic T7802B Owner's Manual

MODEL: T7802B
SEVEN-DAY DIAL TIME SWITCH
4 POLE; Two Normally Open - Two Normally Closed
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATION
40 AMP. RESISTIVE EACH POLE 120V -480V AC.
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR
277V AC. 1000 VA PILOT DUTY EACH POLE 120V - 277V AC.
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER WG1603
CONTACT RATINGS:
208 277V 60 HZ
SUPPLY
LR3730
CLOCK
MOTOR
TO LOADS
GROUND
WIRING DIAGRAM
SCREW
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock motor voltage may be other than load voltage, but must be as specified. For terminal markings, internal wir­ing and contact arrangements refer to wiring diagram above. To form the common poles of a DOUBLE POLE DOUBLE THROW switch, if required, install jumpers (extend supply wires) between terminals 1-6 and 3-8. Use solid or stranded COPPER wire with insulation to suit installation. See table for gauge selection. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pres­sure plate of terminals. Use 3/16 or larger screw driver to tighten terminal screws firmly. REPLACE FRONT
INSULATOR BEFORE TURNING ON ELECTRICITY.
MINIMUM
COPPER
WIRE SIZE
(AWG)
14 12 10
8
MAX. LOAD
(AMP)
15 20 30 40
MIN.
INSUL-
ATION
TEMP(°C)
60 60 60 75
75°C INSULATION MAX. MOTOR
240 V.
2
2 1/2
3 5
LOAD (HP)
SINGLE PHASE
120 V.
1/2
1 2
-
208 V.
N/A
3 PHASE
240 V.
N/A
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE INSULATION CLEARS PRESSURE PLATE
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at day-of-week and time­ of-day when “ON” operations are desired. Tighten tripper screws securely.
2. TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at times when “OFF” operations are desired. Tighten tripper screws securely.
3. TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
4. TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-week and time-of-day (AM or PM) on dial with the TIME POINTER. Some allowance may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TOOPERATESWITCHMANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as
indicated by arrows. This will not affect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--01172