Intermatic T7401BC Supplementary Manual

MODEL: T7401BC
SEVEN-DAY DIAL TIME SWITCH WITH SPRING WOUND CARRY-OVER MOTOR 4 POLE SINGLE THROW
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
CONTACT RATINGS:
40 AMP. RESISTIVE EACH POLE 120V-480V AC. 40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR 277V AC. 1000 VA PILOT DUTY EACH POLE 120V - 277V AC. 24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC. SINGLE PHASE 28 FLA, 168 LRA (7 1/2 HP) - 208V AC., (10 HP) - 240V AC. 3 PHASE
CLOCK MOTOR: 120 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER 131T68GA
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven day schedule. Clock motor voltage may be other than load voltage, but must be as specified. For terminal markings, internal wiring and contact arrangements refer to wiring dia­gram above. Use solid or stranded COPPER wire with insulation to suit installation. See table for gauge selection. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten terminal screws firmly.
REPLACE FRONT INSULATOR BEFORE TURNING
ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at
day-of-week and time-of-day when
“ON” operations are desired. Tighten tripper
screws securely.
2.
T
O SET “OFF” TIMES,
place dark OFF trippers against edge of CLOCK-DIAL at
times when
“OFF” operations are desired. Tighten tripper screws securely.
3.
TO SKIP DAYS, omit trippers for the day(s) automatic operations is/are not required.
4.
T
O SET DIAL
T
O TIME-OF-DA
Y
,
turn dial CLOCKWISE and align the exact day-of-
week and time-of-day (AM or PM) on dial with the
TIME POINTER. Some allowance
may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY
: Move MANUAL LEVER below CLOCK-DIAL
left or right as indicated by arrows.
This will not af
fect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-
day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY
BEFORE
ANY
BEHIND-THE-INSULA
T
OR WORK.
INTERMA
TIC INCORPORA
TED
SPRING GROVE, ILLINOIS 60081-9698
158TS10996
PRESSURE PLA
TE TERMINAL SCREW MAKE SURE WIRE
INSULATION CLEARS PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX. LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V
.
240 V.
14 12 10
8
15 20 30 40
60 60 60 75
1/2
1 2
-
2
2 1/2
3 5
120 V 60 HZ
TO LOADS
SUPPLY
WIRING DIAGRAM
GROUND SCREW
3 4 5
7 1/2
3 5
7 1/2
10
CLOCK
MOTOR
A
1
2
34
56
7
8
B
LR3730