Intermatic PG2000 User Manual

INSTALLATION INSTRUCTIONS
CAUTION: Turn off power to the electric service or panel and to equipment to be protected
before installing any Surge Protection Device. All wiring should be done by a qualified electrician and comply with the National Electric Code and local electric codes.
INSTALLA TION
1. Test and verify system voltage to assure proper m odel select ion of Surge Protection Device (SPD). Refer to the wiring configurations and voltages on page 2 and 3 for additional information.
2. Turn Power OFF
3. Remove the knockout fr om the power bus, load center or equipment panel that will position the SPD for the shortest wire lead distance. Note that the shorter the lead length between the SPD and the connection point, the better the protect ion.
4. Open the hinged cover on the PanelGuard unit by unscrewing the lock ing bolts in the cover.
5. Select and remove the appropriate knock out on t he PanelGuard cabinet.
6. Connect the mounting plates to the back of the PanelGuard cabinet using the connector s provided.
7. Mount the PanelGuard cabinet to a rigid surface. I f the mounting position prevents direct connection to the load center or equipment panel, conduit must be used to comply with the national Electric Code.
8. Twist or ty-wrap all lead wires to eliminate space or gaps between them. Route the wire leads from the PanelGuard cabinet to the power panel.
9. Cut each wire lead to the proper length. DO NOT coil extra wire length.
10. Connect the GREEN wire lead to the system ground.
11. Connect the W HITE wire lead (when included) to the system neutral bus. When installing at a main panel, the neutral bus may be the same as the ground bus.
12. Connect each phase wire, BLACK or RED, to the power bus. All models have internal line fusing. Select a method of connection that comp lies with local electric code and the National Electric Code. Make sure that the phase wires have the correct voltage level between them. Note that for the 240 volt High Leg Delta, the wire lead for the High Leg is colored RED, and must be connected to t he phase that measures approximately 208 volts to neutral and to ground. Failure to comply with this instruction will result in failure of the SPD and void the warranty.
13. If remote monitoring is used, r emove the ½” knockout and connect wire leads to the terminal strip located in the monitoring section of the PanelGuard cabinet. Be sure to comply with local and national wiring codes for the voltage of the monitoring circuit. Refer to the wiring diagram on page 3.
14. Check all connections for proper tig htness or torque. Observe the suggest ed t orque values published by the manufacturer when circuit breakers or separ ate disconnect devices are used.
15. Close and secure the hinged cover using the locking bolt s pr ovided with the cover.
16. Turn Power on.
17. Make sure that each Protection Status indicator on t he PanelGuard is ON recheck each installation step listed above.
18. Make sure that the Alarm Warning indicator on the PanelGuar d is O FF recheck each installation step listed above.
19. For troubleshooting assistance, call Int er m atic at 800-391-4555.
.
. If not, turn power off and
. If not, turn power of f and
Load Center
or equipment
or equipment
Transformer
or equipment
WIRING CONFIGURATIONS
120 VAC Single Phase
Transformer
Secondary
120/240 VAC Single (Split) Phase
Transformer
Secondary
120/208 VAC Three Phase WYE
Secondary
120/240 VAC Three Phase Delta High Leg Delta
Transformer Secondary
or equipment
L1
Black
N
White
G
Green
Use of Circuit Breakers is optional
Load Center
L1
Black
L2
Black
White
N
Green
G
Use of Circuit Breakers is optional
Load Center
L1
Black
L2
Black
L3
Black
White
N
Green
G
Use of Circuit Breakers is optional
Load Center
L1
Black
L2
Red
L3
Black
White
N
Green
G
PanelGuard
PanelGuard
PanelGuard
PanelGuard
VOLTAGE CONFIGURATION CONF I RMAT ION MODE VOLTAGE
Line to Neutral 120 Line to Ground 120
VOLTAGE CONFIGURATION CONF I RMAT ION MODE VOLTAGE
Line to Line 240 Line to Neutral 120 Line to Ground 120
VOLTAGE CONFIGURATION CONF I RMAT ION MODE VOLTAGE
Line to Line 208 Line to Neutral 120 Line to Ground 120
VOLTAGE CONFIGURATION CONF I RMAT ION MODE VOLTAGE
Line to Line 240 Line to Neutral 120 High Leg to Neutral 208 Line to Ground 120 High Leg to Ground 208
Use of Circuit Breakers is optional
Loading...
+ 2 hidden pages