MODEL G8000 Series Mechanical Defrost Timer
Installation Instructions
WARNING
• Turn all power off before servicing this switch or the equipment it
controls.
• Follow local electrical and safety codes, National Electric Code (NEC) and
Occupational Safety and Health Act Codes (OSHA).
• Ground enclosure or bracket in accordance with National Electrical
Code, Canadian Electrical Code, and local requirements.
• Make sure there is no wire insulation under the terminal plate on time
switch connector. Firmly tighten terminal screws.
• Use 90 degree C minimum copper conductors only.
• Reinstall Safety Guard after wiring.
READ AND SAVE INSTALLATION INSTRUCTIONS
Risk of Electric Shock or Fire
Replacing Existing Timer in Enclosure with G8000
Mechanism
1. Disconnect power to the mechanism you want to replace.
2. Disconnect the wires from the old mechanism.
3. Remove the old mechanism from the enclosure.
4. Insert screwdriver into slot on G8000 Defrost Timer and remove it from Intermatic enclosure. See Figure 1.
5. If necessary, snap the tabs off the G8000 Defrost Timer with
your ngers or pliers. See Figure 2.
Installation/Replacing Timer With G8000 Enclosure
1. Take one of these actions.
If you are... Then...
Switching out the G8000
Defrost Timer in a
different enclosure or
bracket,
Mounting G8000
enclosure with the
mechanism,
2. Insert screwdriver into slot on G8000 Defrost Timer and remove mechanism from Intermatic enclosure. See Figure 1.
Perform the applicable G8000
changeout procedure:
• Replacing Existing Timer in
Enclosure with G8000
mechanism
• Replacing Existing Timer with
G8000 on Bracket or Bracket
inside Enclosure
Follow steps 2 through 9.
Tabs (4)
Figure 2. Snapping tabs off mechanism.
6. Snap the mechanism in the applicable enclosure. See Figure 3.
Figure 1. Removing G8000 Defrost Timer from Intermatic enclosure.
3. Install the enclosure in the desired location that provides
adequate space for the enclosure door to swing open fully.
4. Drill the holes and then clean out each hole.
5. Use appropriate mounting hardware as needed.
6. Insert the screw into the top hole and tighten.
7. Hang the enclosure over the top screw.
8. Insert the other screws through the holes in the enclosure and
into the remaining holes in the wall. Tighten the screws.
9. Install the timer in the enclosure. Connect wiring. See
Connecting G8000 Wiring.
Figure 3. Installing the G8000 Defrost Timer.
Replacing Existing Timer with G8000 On Bracket
or Bracket Inside Enclosure
1. Disconnect power to old mechanism you want to replace.
2. Disconnect the wires from the old mechanism
3. Remove the old mechanism from the bracket or the bracket in
the enclosure.
4. Insert screwdriver into slot on G8000 Defrost Timer and remove it from the Intermatic enclosure. See Figure 1.
5. If necessary, snap the tabs off the G8000 Defrost Timer with
your ngers or pliers. See Figure 2.
6. Snap the timer on the bracket as shown in Figure 3, or if
applicable, the snap timer on bracket in the enclosure as
shown in Figures 4 and 5 on the back.
7. Make sure the mechanism is fastened securely on the bracket.
FOR UNITS WITH SOLENOIDS (G8145-00 and G8145-20)
WARNING
Slot lines up
with Bracket
Figure 4. Snap Defrost Timer on bracket.
Figure 5. Installing G8000 in bracket in enclosure
Connecting G8000 Wiring
1. Turn power off at breaker.
2. Remove the retaining screw that secures the plastic insulator.
Set aside the screw for re-use.
3. Strip the wires 1/2 inch.
4. Connect the wires to the proper terminals on the time switch
connector. Tighten screws rmly. See the supplied wire
diagram.
5. Return the plastic insulator to its original position.
6. Reinstall the retaining screw that was previously removed.
TERMINAL BLOCK WIRE COMBINATIONS
TERMINALS WIRE RANGE (AWG) TORQUE (IN-LBS)
LARGE
14-8
SMALL 18-12 9
TERMINAL BLOCK MAY BE USED WITH UP TO TWO WIRES OF THE
SAME TYPE (SOLID OR STRANDED) AND SAME SIZE PER TERMINAL.
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole
option, free of charge. This warranty is extended to the original purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused
by accident, dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart or
otherwise modified; (c) units not used in accordance with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s
and batteries; (f) the finish on any portion of the product, such as surface and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial
installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE
EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO
YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE WARRANTY OF
MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN
THIS LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW
LIMITATIONS ON THE DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or (b) completing a warranty claim on line at
www.intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service 7777 Winn Rd. Spring Grove, Illinois 60081-9698. For warranty service
go to: http://www.intermatic.com or call 815-675-7000.
INTERMATIC INCORPORATED
PRINTED IN MEXICO
40
LIMITED TWO YEAR WARRANTY
SPRING GROVE, ILLINOIS 60081-9698
www.intermatic.com
The defrost terminating solenoid on this defrost control is not intended for
continuous duty operation.
After you complete the G8000 wiring, be sure to perform the
procedure below.
1. Rotate the timer knob counter-clockwise until the tripper
screw is in-line with the time of day pointer.
NOTICE
• Do NOT rotate the timer knob clockwise.
• Turning the knob clockwise can damage the gears in the timer.
2. Connect a voltmeter across solenoid terminals X and 3.
3. Activate power to the timer.
4. Take one of these actions.
If... Then...
Voltage is present at the solenoid terminals,
There is no voltage present at
the solenoid terminals
5. Rotate timer knob until timer transfers power into Defrost
Mode.
6. Determine if voltage is present at solenoid terminals X and 3.
7. Take one of these actions.
If... Then...
Voltage is present at the solenoid terminals,
There is no voltage present at
the solenoid terminals
NOTE: After you have veried that there is no feedback voltage, the procedure is complete.
Risk of Electric Shock or Fire
Risk of Damage to Timer
Turn off power and check
wiring and other system
components for feedback
voltages.
Proceed to step 5.
Turn off power and check
wiring and other system
components for feedback
voltages.
Turn off power to the
defrost timer and disconnect the volt meter from the
solenoid terminals.
158--01455