FM/1 Series
Time Switches
APPLICATIONS
The FM/1 series of time switches are designed for control of heating, ventilating, air conditioning, refrigeration, lighting, security, circulating pumps, spas or any electrical load requir­ing 24-hour or 7-day scheduling.
WIRING
Verify input voltage stated on back of unit. Use 1/4” quick con­nects and make connections in accordance with the wiring diagram shown and applicable code requirements. When using 24V units, it is important to use transformers that will
supply the required 24 volts AC to terminals 1 & 2.
TECHNICAL DATA
Supply Voltage: 24, 120 and 240VAC, 60Hz models
Quartz: 24V AC/DC, 120 and 240VAC 50/60 Hz
Switch Type: SPDT
Switch Rating: 21A/250VAC resistive
Power Consumption:
Ambient Temp. Range: –40°F to 180°F, synchronous units
Terminals: 1/4” spade terminals
24V: 0.1VA; 120V: 0.5VA; 240V: 1.0VA
–20°F to 140°F, quartz units
Terminal Connections
Contacts shown in “Off” position (trippers pushed inward)
“On” position (trippers pushed outward) will close contacts 3 & 4
MOUNTING
The standard FM/1 units can be flush mounted (mounting kit with screws available) or surface mounted inside a panel. A printed circuit board mounting base is also available. An indoor or outdoor enclosure is available for stand-alone mounting. In addition, unit is also available in DIN housing for flush or surface mounting (see MIL72, Digi 20 or Digi 42 data sheets). Optional clear plastic dust cover is available.
Reserve Carryover:
Weight: Approximately 3 oz.
NOTE: 24V quartz unit will operate on 6VDC, 12VDC,
or 24VDC
7 days for quartz units
Page 2
Dimensions
FM/1 synchronous/quartz
PROGRAMMING WITH MANUAL OVERRIDE SWITCH
AUTOMATIC MODE
In order to operate the time switch module in the automatic mode, the manual switch must be in the center position (auto­matic) - see diagram.
MANUAL MODE
With the manual switch selector lever the selected programs can be overridden. In the lower position, marked “O”, termi­nals 3 and 5 are permanently closed. In the upper position, marked “I”, terminals 3 and 4 are permanently closed (see diagram).
Override Mode
TIME SETTING
TO SET THE CURRENT TIME (AND DAY OF WEEK ON 7 DAY UNITS), TURN THE MINUTE HAND CLOCKWISE. DO NOT SET THE TIME BY ROTAT­ING “OUTER” DIAL.
Turn the minute hand clockwise until the day of the week (7-day timer) and the time of day on the outer dial is aligned with the triangle marker on the inner dial (two o'clock position).
Example for 7-day program dial Monday 10:30 AM. Turn the minute hand clockwise until Monday 10:30 AM is aligned with the triangle on the inner dial. The hour and minute hand will show exactly 10:30.
Example for 24-hour program dial 10:30 AM. Turn the minute hand clockwise until 10:30 AM is aligned with the triangle on the inner dial. The hour and the minute dial will show exact­ly 10:30.
PROGRAMMING
7-Day (SW, QRW Models)
The weekly program dial reflects the seven days of the week and AM/PM imprints for each day.
The time switch is programmed by pushing the captive trip­pers to the outer ring position for the entire period that the load is to be turned “ON”, i.e., two hours for each tripper on the 7-Day dial. When the tripper is pushed to the inside, the switch is in the “OFF” position.
3-way manual override switch
I = permanent ON
= automatic
0 = permanent OFF
24-Hour (ST, QRT Models)
The 24-Hour dial has quarter-hour divisions and AM/PM indi­cations.
The time switch is programmed by pushing the captive trip­pers to the outer ring position for the entire period that the load is to be turned “ON”, i.e., fifteen minutes for each trip­per on the 24-Hour dial. When the tripper is pushed to the inside, the switch is in the “OFF” position.
Intermatic Incorporated • Spring Grove, IL 60081 • www.intermatic.com
300GR10020
Page 3
PROGRAMMING SHEET
Rotate the outer dial slowly in a clockwise direction, until the right corresponding day segment on the dial is approaching the arrowhead printed on the inside edge of the dial. Do not attempt to rotate the dial or the clock hands in an anti-clockwise direction.
Now rotate the minute hand with your finger, in a clockwise direction, so that you set the correct time within the day segment. Note that the clock hands are set within a 12-hour printed ring, and the outer dial is printed with the 24 hour clock. The illustrations show the clock set at 6:00 a.m. (fig. 1) and 6:00 p.m. (fig. 2) on Monday. Ensure that you are setting current time accurately with regard to the outer 24 hour dial.
Tappets should be pushed to the outer edge of the dial for a programmed ON instruction, and left set to the inner edge of the dial for a programmed OFF instruction. All tappets between the desired ON and OFF times must be pushed to the outer edge of the dial. Each tappet switches the output for a two-hour period. Figure 3 shows the timeswitch set for 8:00a.m. ON – 18:00 (6:00p.m.) OFF Monday – Saturday and no switching programmed on Sunday.
There is a three-position switch
built in to the face of the dial. For automatic timed control, governed by the tappet settings, the switch should be left in the middle position (as illustrated). The output can be switched ON at any time, by moving the switch lever to the top position, marked with "I" on the dial. Alternatively, the output can be switched OFF at any time, by moving the switch lever to the lower position, marked with "0" on the dial. The manual override is a fixed selection – the output will remain ON or OFF (as selected), until the switch lever is moved back to the middle timed position, marked with a
on the dial.
7 Day analogue timeswitches
Fig. 1
Fig. 2
Fig. 3
Set time and day
Setting switching times
Manual override
Page 4
www.intermatic.com
Energy ControlsEnergy Controls
Mechanical
Timer Modules
FM1STUZ-120U
Features:
•21ASPDTswitch
•96CaptiveTripp ers
•1⁄4in.quick-connectterminals
•NoiseImmune—Idealforrobust
applications
FM/1 Series
24-Hour, 7-Day
Applications:
The FM/1 series mechanical timer modules are designed to be placed inside a
machinecontrolpanel,circuitboard,orotherequipment.Itoffersupto21Amp
switching designed for control of heating, ventilating, air conditioning, refrigeration,
lighting,security,circulatingpumps,spasoranyelectricalloadrequiring24-houror
7-day scheduling.
Specifications:
Size: 3.25 in. H x 3.25 in. W x 2.25 in. D Supply Voltage: 24, 120, 240 VAC Power Consumption: 1 VA Switch Rating: SPDT Resistive: 21 Amp Tun gsten: 1350 W Inductive: 1 HP, 125 VAC; 2 HP, 240 VAC Wiring Connections: 1⁄4in.quick-connectterminals Operating Temperature Range:“S”models–40ºFto185ºF(–40ºCto85ºC)
“Q”models–20ºFto131ºF(–20ºCto55ºC)
Installation: Stand alone or with Indoor/Outdoor enclosure Panel: Surface mounting
Min Switch Model Switch Battery ON/OFF Output Number Override Program Backup Time Volts AC Type/Amps
FM1STUZ-120U No 24 Hr. No 15 Minutes 120 SPDT/21 FM1STUZ-24U No 24 Hr. No 15 Minutes 24 SPDT/21 FM1STUZ-240U No 24 Hr. No 15 Minutes 240 SPDT/21 FM1SWUZ-120U No 7 Day No 2 Hours 120 SPDT/21 FM1SWUZ-24U No 7 Day No 2 Hours 24 SPDT/21 FM1SWUZ-240U No 7 Day No 2 Hours 240 SPDT/21 FM1STUZH-120U Yes 24 Hr. No 15 Minutes 12 0 SPDT/21 FM1STUZH-24U Yes 24 Hr. No 15 Minutes 24 SPDT/21 FM1STUZH-240U Yes 24 Hr. No 15 Minutes 240 SPDT/21 FM1SWUZH-120U Yes 7 Day No 2 Hours 120 SPDT/21 FM1SWUZH-24U Yes 7 Day No 2 Hours 24 SPDT/21 FM1SWUZH-240U Yes 7 Day No 2 Hours 240 SPDT/21 FM1QTUZH-120U Yes 24 Hr. Yes 15 Minutes 120 SPDT/21 FM1QTUZH-24U Yes 24 Hr. Yes 15 Minutes 24 SPDT/21 FM1QTUZ-120U No 24 Hr. Yes 15 Minutes 120 SPDT/21 FM1QTUZ-24U No 24 Hr. Ye s 15 Minutes 24 SPDT/21 FM1QTUZ-240U No 24 Hr. Yes 15 Minutes 240 SPDT/21 FM1QWUZ-120U No 7 day Yes 2 Hours 120 SPDT/21 FM1QWUZ-240U No 7 day Yes
2 Hours 24
0
SPDT/21 FM1QWUZH-120U Yes 7 Day Yes 2 Hours 120 SPDT/21 FM1QWUZH-240U Yes 7 day Yes 2 Hours 240 SPDT/21 FM1QWUZH-BW-24U Yes 7 day Yes 2 Hours 24 SPDT/21 FM1STUZH220/50 Ye s 24 Hr. No 15 Minutes 220 SPDT/21
(50 Hz)
FM1STUZ220/50 No 24 Hr. No 15 Minutes 220 SPDT/21
(50 Hz)
0.25 lbs .01 kg
C2 2.2-17 7
LR3730
UL917
H VA C / R
21
Page 5
How to set Intermatic FM1 timers
The FM1 series timer can be wired and programmed for different purposes.
Since the timer has NO NC terminals, the best way to proceed is to 1) wire your timer 2) turn power on 3) move 10 tripper pins outward, 4) leave rest of tripper pins inward.
5) Then manually rotate dial to watch when load turns on-off.
If timer model has manual override button, then move override switch to each of 3 positions and repeat same test. These actions will reveal correct wiring and switch setting for your purpose.
Other Intermatic Modular timers
http://waterheatertimer.org/Intermatic-trippers-and­parts.html#PB
7-day timer dial: each tripper is 2 hours 24 hour dial: each tripper is 15 minutes