Intermatic 158ET10367 User Manual

®
ET100 SERIES
Electronic 24 Hour Time Switches
With Battery Carryover
INCLUDING MODELS:
ET101C (SPST) ET103C (DPST) ET105C (SPDT)
OWNER/INSTALLER INSTRUCTION MANUAL
Specifications
CLOCK VOLTAGE: 120 V.A.C., 60 Hz.
AM ON
5:20
POWER CONSUMPTION: 3.0 Watts Max. (ET101C) &
(ET105C)
5.0 Watts Max. (ET103C) CONTACT CONFIGURATION: SPST model ET101C DPST model ET103C, & SPDT model ET105C. SWITCH RATING: (Per Pole for ET103C)
• 30 Amps Inductive/Resistive, 24/120/240 V.A.C., 60 Hz.
• 20 Amps Resistive - 28 V.D.C.,
• 1 H.P. 120 V.A.C., 60 Hz.
• 2 H.P. 240 V.A.C., 60 Hz.
• 5 Amps Tungsten, 120/240 V.A.C., 60 Hz.
• 20 Amps Ballast 277 V.A.C., 60 Hz.
Description
The Intermatic Electronic 24 Hour Time Switch automatically switches loads according to a preset daily schedule.
This time switch is designed to directly switch loads up to 30 amps and to switch resistive or inductive loads up to the time switch rat­ing. For use as a control timer in applications requiring 24 hour load control such as lighting, heating, air conditioning systems, pumps, etcetera. Up to eight set points or events (4 ON/4 OFF) can be preset. this schedule will repeat on a daily basis. The program can be overridden by using the MANUAL position.
SWITCH RATINGS: ET105C N.O. N.C. CONTACT 20 AMP 10 AMP Resistive and 28 VDC.
General Purpose 120-240 VAC 1 H.P. 1/4 H.P. MOTOR 120 V.A.C. 2 H.P. 1/2 H.P. MOTOR 240 V.A.C. 5 Amp - TUNGSTEN 120-240 V.A.C. 20 Amp 3 Amp BALLAST 120-277 V.A.C.
SET POINTS (EVENTS): 8 total (4 ON/4 OFF). BATTERY POWERED CLOCK OPERATION: 3 Years minimum (AA industrial grade alkaline supplied with time switch) MIN. “ON” or “OFF” TIME: 1 minute. MAX. “ON” or “OFF” TIME: 23 hours 59 minutes. SHIPPING WEIGHT: 2,5 Lbs. (1.1 Kg) CASE: Drawn steel; 7-3/4” (19.7 cm) high, 5” (12.7 cm) wide, 3” (7.6 cm) deep; gray finish w/lockable spring hasp. KNOCKOUTS: Combination 1/2 - 3/4” (one on back and each side, two on bottom). WIRE SIZE: AWG #10 through #18.
General Safety Information
WARNING: Disconnect all power before installing or servicing this time switch or its connected loads.
1. Follow all local electrical and safety codes, National
Electric Code (NEC), as well as Occupational Safety and Health Act (OSHA).
2. If the power disconnect point is out of sight, lock it in the “OFF”
position and tag it to prevent unexpected application of power.
3. This time switch case must be grounded.
4. Do not exceed the maximum current carrying capacity of this
time switch.
5. Always replace the plastic insulator covering the terminal
before turning power “ON”.
Installation
WARNING: DISCONNECT THE POWER TO THE TIME SWITCH AND THE LOADS BEFORE INSTALLING THIS TIME SWITCH.
1. Mount the time switch in the desired location using the three mounting holes which are provided. Mount the time switch at eye level, if possible, providing sufficient room to the left of the enclosure for the cover to swing open fully. (See Figure #1 and Figure #2). The time switch mechanism does not need to be removed from the enclosure to mount the time switch since the top mounting hole is a slotted type mounting hole. Secure a screw or other fastener at eye level. The head of the screw or fastener should be slightly larger than the narrow portion of the slotted hole to ensure that the time switch is securely held in place. The remaining two mounting holes are accessible without removing the time switch mechanism and will provide secure and permanent mounting of the time switch.
2. If you do remove the mechanism, refer to Figure #1 and remove the mechanism from the case by depressing the catch at the top of the case and pulling out.
CAUTION; DO NOT TOUCH THE CIRCUIT BOARD COMPONENTS SINCE STATIC DISCHARGE COULD DAMAGE THE MICROPROCESSOR.
3. Replace the mechanism in the case if it has been removed.
4. Lift the left side of the insulator off of the retaining post and pivot it up and away to expose the terminal strip.
5. Strip the supply and load wires by removing 1/2 inch of insulation. DO NOT USE ALUMINUM WIRE. (See figure #3, #4 or #5). Insert the wire ends under the proper terminal plates and tighten the screws firmly. Use AWG #10 through #18. Connect ground wire to grounding terminal at bottom of case.
6. Replace the plastic insulator.
7. Be sure that the battery is functioning properly. this can be checked by making sure the display is visible. If the display has scrambled information, press the RESET switch and hold for three to five seconds. Note that the battery can easily be replaced without removing the time switch mechanism or field wiring. simply press in and downward (in the direction of the arrow) on the battery cover which is identified with the word “Battery”. It is recommended that the battery be replaced with a “AA” industrial grade alkaline cell at two to three year intervals as part of the normal time switch maintenance observing battery polarity markings when installing. No other maintenance is required.
FIG. #1
Mounting Holes
Knockouts
FIG. #2
NOTE: For 120 Volt loads only since the timer voltage is 120 VAC
a jumper can be added between terminals 2 and 3 to supply load power.
CAUTION: Do not use jumper if load(s) are not 120V. because the load can be damaged. Supply separate power of the correct voltage to terminal 3.
8. Place the selector switches in the “MANUAL” and “RUN” positions.
9. Reapply power to the time switch.
Install Jumper Only If Timer Input and Load Voltage Are The Same, Otherwise provide a separate source of load power to terminal 3.
FIG. #3
ET101C SPST
Loading...
+ 2 hidden pages