TX-6310-01-1 Carbon Monoxide Alarm Manual
Figure 1: Alarm features
WARNING: After seven years from initial power up, this alarm
will beep two times every 30 seconds to indicate that it is time
to replace the alarm. Replace the alarm immediately! It will not
detect CO in this condition.
Red Alarm LED
Green Power LED
Alarm sounder
Attention: Please take a few minutes to thoroughly read this
guide which should be saved for future reference and passed
on to any subsequent owner.
The TX-6310-01-1 CO alarm is only compatible with Simon XT
panels with firmware v1.4 or higher. Refer to the panel
installation instructions for revision verification details. It is
currently not compatible with other control panels. Please
contact Technical Support for any questions regarding
compatibility.
Test/Hush button
Description
The TX-6310-01-1 wireless carbon monoxide (CO) alarm
monitors the levels of CO gas and gives early warning when
potentially dangerous levels exist. It does not detect fire,
smoke, or any other gas. If a dangerous concentration of CO is
detected by patented and field-proven electrochemical sensor,
an LED indicator illuminates and an internal siren is activated
in temporal 4 pattern. The CO alarm also transmits an alarm
signal to the control panel within 15 seconds of detecting
dangerous concentration of CO gas. The control panel
activates its internal siren and reports the alarm condition to
the central monitoring station (if the system is monitored). The
CO alarm also detects low battery, wall tamper, and sensor
end-of-life. These trouble codes are transmitted to the control
panel. The alarm automatically resets when CO is no longer
detected.
The TX-6310-01-1 wireless CO alarm is Listed and compliant
with the ANSI/UL 2034 standard for CO alarms. It is intended
for residential indoor dwelling unit applications and other areas
approved by the authority having jurisdiction (AHJ). It is not
intended for use in industrial applications.
To help identify the date to replace the alarm, an area has
been reserved on the side of the alarm. Write the “replace by”
date (seven years from power up) with a permanent marker in
the area provided.
Alarm location
CO alarms should be mounted in or near bedrooms and living
areas. We recommend that you install an alarm on each level
of your home.
When choosing your installation locations, make sure you can
hear the alarm from all sleeping areas. If you install only one
CO alarm in your home, install it near bedrooms, not in the
basement or furnace room.
Place the alarm out of reach of children. Under no
circumstances should children be allowed to handle the CO
alarm.
Figure 2: Recommended locations
Dining
Locations to avoid
Improper location can affect the sensitive electronic
components in this alarm. To avoid causing damage to the
unit, to provide optimum performance, and to prevent
unnecessary nuisance alarms:
• Do not install in kitchens, garages, or furnace rooms that
may expose the sensor to substances that could damage
or contaminate it.
• Do not install in areas where the temperature is colder
than 40°F (4.4°C) or hotter than 100°F (37.8°C) such as
crawl spaces, attics, porches, and garages.
• Do not install within 5 ft. of heating or cooking appliances.
(We recommend 15 ft. to prevent nuisance alarms.)
Kitchen
Living room
Bedroom
Bedroom
Bedroom
© 2011 UTC Fire & Security. All rights reserved. 1 / 8 P/N 466-2393 • REV A • ISS 14FEB11
• Do not install near vents, flues, chimneys, or any
forced/unforced air ventilation openings.
• Do not install on metal surfaces.
• Avoid mounting in areas with a large quantity of metal or
electrical wires.
• Do not install near ceiling fans, doors, windows, or areas
directly exposed to the weather.
• Do not install in dead air spaces, such as peaks of vaulted
ceilings or gabled roofs, where CO may not reach the
sensor in time to provide early warning.
• Do not install near deep-cell large batteries. Large
batteries have emissions that can cause the alarm to
perform at less than optimum performance.
• Do not obstruct the vents located on the alarm. Do not
place the alarm where drapes, furniture, or other objects
block the flow of air to the vents.
Battery installation and replacement
Note: Place the control panel into sensor test mode prior to
replacing the batteries. If the control panel is not in sensor test
mode during battery replacement, an alarm/tamper condition
may be indicated.
To install or replace the batteries in this alarm:
1. Slide the alarm body off of the mounting plate.
2. If replacing batteries, remove the old batteries and
properly dispose of them as recommended by the battery
manufacturer.
3. Install the new batteries. Note the polarity illustration in the
battery compartment (see
Figure 3: Batteries
Figure 3 below).
Figure 4: Sliding the alarm on the mounting plate
Alarm mounting guide
Alarm mounting guide
5. Perform a sensor/RF test with the control panel. See “RF
communication test” on page 3
When replacing the batteries, use one of the following
approved brands:
• Duracell MN1500 or MX1500
• Energizer E91
Note: For battery replacement information, see interlogix.com.
Use of a different battery may have a detrimental effect on the
alarm operation.
Note: Constant exposures to high or low humidity may reduce
battery life.
After installing or changing the batteries, reinstall your alarm.
Test your alarm by using the Test/Hush button and check that
the green Power LED is on.
Mounting the alarm
Note: Verify RF performance prior to permanently mounting
the alarm. See “RF communication test” on page 3.
The CO alarm can be wall mounted or ceiling mounted.
_
+
Battery compartment
_
W
X
X
X
X
X
X
A
X
X
X
R
X
X
X
N
X
X
X
I
X
X
X
N
X
X
X
G
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4. Slide the alarm body back onto the mounting plate.
Note: The mounting plate will not close if all three
batteries are not installed.
To mount the alarm:
1. Slide the alarm body off of the mounting plate. Place the
mounting plate in the desired location, and mark the
location of the two mounting holes. Orient the mounting
plate vertically or horizontally as shown in the following
figures.
Note: The alarm can also be directly mounted to a single
gang box
Figure 5: Vertical mounting
.
Mounting hole
Warni n g
XXXXxxXX X x xxx
XXXXX XXXXxxx
XXXXXXX X XXx x
XXXXXXXXXX x x
XXXXxxXXX x xx
XXXXX XXXX xx
XXXXXXX X XXx x
Mounting latch
XXXXXXXXXX x x
XXXXxxXXX xxx
XXXXX XXXXxx
XXXXXXX X XXx
XXXXXXXXXX
XXXXxxXXX xxx
XXXXX XXXX xx
XXXXXXX X X
XXXXXXXXXXx x
xxxxxxxxxxx
XXXXxxx
xxxxxxxxxxx
Mounting hole
Alarm
procedure
label
2 / 8 P/N 466-2393 • REV A • ISS 14FEB11
Figure 6: Horizontal mounting
Mounting latch
Due to the loudness of the alarm, we suggest that you place
your fingers over the sounder vent while testing your alarm.
Caution: Continuous exposure to the high sound level of this
alarm over an extended period of time may cause hearing loss.
Mounting
hole
XXXXxxXXX x xxx
XXXXXXXXXx xx
XXXXXXX XXXxx
XXXXXXXXXX xx
XXXXxxXXX x xx
XXXXXXXXX x x
XXXXXXX XXXxx
XXXXXXXXXX xx
XXXXxxXXX xxx
XXXXXXXXXx x
XXXXXXX XXXx
XXXXXXXXXX
XXXXxxXXX xxx
XXXXXXXXX x x
XXXXXXX X X
XXXXXXXXXXxx
xxxxxxxxxxx
XXXXxxx
xxxxxxxxxxx
Alarm procedure label
Warni n g
Mounting
hole
2. Insert the two screws provided and secure the mounting
plate to the wall or ceiling surface. (If mounting in
plasterboard or drywall, drill a 3/16 in. hole and use the
plastic anchors provided.)
3. After the mounting plate is secured, slide the alarm over
the mounting plate (see
Figure 4 on page 2).
Important labels provided
Two labels have been provided that have important information
on what to do in case of an alarm. Add the phone number of
your emergency service provider in the space provided. Place
one label next to the alarm after it is mounted, and one label
near a fresh air source such as a door or window.
Programming
The following section provides a general guideline for
programming (learning) the unit into control panel memory.
Refer to the panel documentation for complete programming
details.
To add the CO alarm to panel memory:
1. Set the panel to program mode.
2. Proceed to the Learn/Add Sensors menu.
3. Select the desired sensor number.
4. Trip the wall tamper by removing the alarm body from the
mounting plate.
5. When the panel prompts you for sensor group number,
enter the appropriate group number based on the system
panel.
6. At the panel, exit program mode.
7. Place the alarm body back onto the mounting plate.
Note: Each CO alarm is programmed with a unique ID when
manufactured. The unique ID is enrolled into the control panel
at the time of installation, allowing the CO alarm to
communicate with that specific control panel.
Testing
Note: This unit is sealed. The cover is not removable.
The CO alarm provides three test modes:
Normal CO alarm test. Conducts an internal self test and
•
tests the sounder.
RF communication test. Tests the communication path
•
with the control panel.
CO alarm functional gas test. Tests the functional
•
operation of the CO sensing element.
Normal CO alarm test
1. Wait at least 10 minutes after installation to test the CO
alarm.
2. Make sure the green Power LED is flashing for normal
operation.
3. Set the control panel to sensor test mode.
4. Press and hold the Test/Hush button until the unit beeps
once (approximately 1 second), and then release the
button. If the unit is operating properly, you will hear four
quick beeps, followed by 5 seconds of silence, followed by
four quick beeps.
5. At the control panel, exit sensor test mode.
Note: This test mode does not test communication with the
control panel. You will receive a “Sensor Test Fail or Abort”
message when the control panel exits sensor test mode.
RF communication test
This section provides general guidelines for testing the CO
alarm with the panel. Refer to the specific panel documentation
for complete testing details.
Before testing, ensure that your control panel is set to sensor
test mode. Setting your panel to sensor test mode prevents an
alarm signal from being transmitted to the central monitoring
station (if you have a monitored system).
1. Wait at least 10 minutes after installation to test the CO
alarm.
2. Make sure the green Power LED is flashing for normal
operation.
3. Set the control panel to sensor test mode.
4. Press and hold the Test/Hush button until the unit beeps
two times (approximately 5 seconds), and then release the
button. If the unit is operating properly, you will hear four
quick beeps. The unit will send the RF test packets after
the first four beeps.
5. The control panel will beep and display the number of RF
packets received.
6. At the panel, exit sensor test mode.
WARNING: The control panel must be placed into sensor test
mode while conducting any tests. Placing the control panel into
sensor test mode for all testing helps to protect against false
alarms and unintentional central station reporting.
CO inspection and functional gas test
(for qualified service technicians only)
Note: Consult the most recent version of NFPA 720 for more
information regarding the requirement for functional testing of CO
alarms and/or your Local Authority Having Jurisdiction (AHJ).
P/N 466-2393 • REV A • ISS 14FEB11 3 / 8