Interlogix RCR-REX Installation Manual

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide
Introduction
This is the Interlogix RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Instructions for models RCR-REX-W, RCR-REX-B, and RCR-REX-G.
Installation
Figure 2: Remove the circuit board and cradle
Determine if the sensor will be ceiling or wall mounted. Avoid locating the sensor between double doorways where objects can be inserted through a crack to gain unauthorized entry.
CAUTION: When handling the sensor, do not touch the lens
window.
To install the sensor, do the following:
1. To open the front cover, insert a small screwdriver into the bottom of the locking tab and pull upward (Figure 1).
Figure 1: Open the cover
CAUTION: You must be free of static electricity before handling
sensor circuit boards. Touch a grounded, bare metal surface before touching circuit boards or wear a grounding strap.
2. Remove the screw holding the circuit board (PCB) cradle axle to the back housing and carefully remove the circuit board with cradle from the housing (Figure 2).
3. Route wiring to the sensor mounting location. If you are using the wall plate, pull the wires through the cable entry hole (Figure 3).
Figure 3: Mounting and wiring access
4. Insert the mounting screws into the back (wall mount) or top (ceiling mount) mounting screw holes to fasten the back housing and wall plate, if used, to the wall or ceiling (Figure 3).
5. Reinstall the PCB/cradle and secure in place with the PCB axle screw (Figure 2).
6. Complete wiring connection (See Wiring on page 2).
7. Swing the front cover in place and walk test the sensor for appropriate coverage and function (see Initial power up on page 4.
© 2018 UTC Fire & Security. All rights reserved. 1 / 7 P/N 466-5444 REV A 8NOV18
Wiring
This section provides examples of different wiring options. The options are all shown in the failsafe mode.
Note: Failure to spike protect the sensor may result in shortening
the life of the relay contacts.
RCR-REX and a Keycard Reader
Basic Hook-up
Figure 4 shows the basic hook-up for the RCR-REX, a power supply and a magnetic lock. When the sensor sees motion, power is removed from the magnetic lock.
Figure 4: Basic hook-up
CAUTION: For DC powered systems, if the door lock does not
contain a diode across the coil winding, install a diode across the door lock to prevent degradation of the lock relay contacts. The diode should have a current rating greater than the maximum lock current. Install the diode so that the cathode end with the bar is connected to the positive side of the coil.
Spike Protection
Many magnetic locks and electric door strikes have built in spike (diode) protection. If the lock is not spike protected, install a bridge rectifier, such as a KBL005, between the relay contacts and the magnetic lock/door strike as shown in Figure 5.
Figure 5: Spike Protection
Figure 6 shows the wiring normally used when a keycard reader is on one side of the door and the RCR-REX is on the other side of the door. Both swiping a keycard or the detection of motion by the RCR-REX will remove power from the magnetic lock.
Figure 6: RCR-REX and a keycard reader
Monitor Door Contacts (first option)
In the monitor door contacts mode, a person entering the
sensor’s field of view will activate the relay and timer. Door
contacts connected to terminal D will monitor if the door is open or closed. If the relay timer gets to ten seconds or less (if set for 16 seconds or greater) and the door is still open, the RCR-REX internal sounder will activate. The sounder will also active if the door is opened without first activating the sensor or keycard input. The sounder will remain on until the door is closed or by someone moving in the field of view (Figure 7).
Figure 7: Monitor door contacts (first option)
2 / 7 P/N 466-5444 REV A 8NOV18
Monitor Door Contacts (second option)
If the sensor is activated but the door is not opened, the relay will drop out after ten seconds. If the sensor is activated and the door is opened, and then closed, the relay will drop out after two seconds. This prevents unauthorized people from entering (Figure 8).
Figure 8: Monitor door contacts (second option)
R (input) Arm
This pin is used to enable and disable the unit with an external signal. The unit will be disabled when R is grounded for more than 10 seconds. Thereafter, when R is ungrounded, the unit will be enabled. Motion detected by the unit up to 10 seconds after R is grounded and at least 100 milliseconds after R is ungrounded will start the relay timer.
This pin must be switched with a dry contact or an open collector transistor referenced to COM (ground).
S (input) Sounder
This pin allows external control of the sounder that takes precedence over all other sounder modes. If the unit is powered up with S ungrounded, then the unit assumes that S is unused.
Whenever S is grounded after power up, the unit assumes that S is being used to externally activate the sounder. Thereafter, when S is ungrounded for at least 100 milliseconds, the sounder will unconditionally turn on and stay on until S is grounded.
Panic Button
Many fire codes require a panic button to be part of the installation. The RCR-REX has an X (external) input (see X (input) external) for a normally open panic button or an internal timer panic button. When X input is grounded, the door will open. Two normally open devices may be connected to the X input (Figure 9).
Figure 9: Panic Button
NC, C, NO (I/O) Monitor Relay Section
Connect the monitor relay terminals across the normally closed contacts (NC) of the door switch and across the access control system. If there is no access control system, connect the normally closed contacts of the door switch across the monitor relay terminals.
This pin must be switched with a dry contact or an open collector transistor referenced to COM (ground).
X (input) External
This pin can be used by card readers, keypads, remote push buttons, and key locks to cause the sensor to start a timing cycle.
If X is pulled to ground for at least 500 milliseconds and less than 3 seconds, the lock/monitor relay will unlock the door and the lock timer will start as if a person walked into the detection area. If X is grounded for more than 3 seconds, then the relay will stay in the unlocked state until X is allowed to go high. When X goes high and if the door is still open, the sounder will produce a beeping tone and the relay will remain in the unlocked state until the door closes. When the door closes, the relay will lock the door and shunt the door switch.
This pin must be switched with a dry contact or an open collector transistor referenced to COM (ground).
D (input) Door
This pin is used to detect the state of the door switch. The door switch must be connected between pins D and COM (ground). If the unit is powered up with D ungrounded, the unit assumes that D is unused. If D is ever grounded after the unit is powered up, the unit assumes that D is being used to sense door position and the sounder will beep (if enabled) when the door is left open.
If used, this pin must be switched with a dry contact or an open collector transistor referenced to COM (ground). See S2-7 (door monitor mode) on page 4.
P/N 466-5444 REV A 8NOV18 3 / 7
Loading...
+ 4 hidden pages