Interlogix RCR-50 User Manual

PrecisionLine RCR-50
Dual Technology Motion Sensor
Installation Instructions
Description
The RCR detector combines range-controlled radar (RCR) technology with a passive infrared (PIR) system to increase false alarm immunity by allowing it to sense human-sized objects within a specified range. Both the RCR and PIR systems must be triggered to set off an alarm, unless in radar- only mode.
The detector is designed to use a 12VDC power supply provided by a UL Listed alarm control panel.
Features
The detector provides the following features:
High-security (radar-only) mode - Internal jumper
allows you to disable the PIR, and use the radar-only mode to detect intruders faster. This mode can be used for covert installations (mounted behind ceiling panels or walls).
Selectable range up to 50 feet (15.2m) - Internal jumper
allows radar range selection to optimize coverage.
LED indicator - A multi-color LED provides detector
status.
Tamper switch - Activated when the pins on the circuit
board are removed from the terminal sockets on the base.
50’
40’
(12.2m)
(12.2m)
(15.2m)
90°
40’
50’
(15.2m)
15°
Radar Viewing Area PIR Viewing Area
4°
floor line
Top V iew
30’
(9.1m)
20’
(6.1m)
0’
20’
(6.1m)
30’
(9.1m)
Side View
7’
2.1m
60° 30°
0°
Figure 1. Coverage Patterns
PrecisionLine RCR-50
Parts
The following parts are included:
RCR detector
1 screw to join the case halves
3 factory-installed jumpers
Selecting a Location for the Detector
The detector can be mounted in a corner or on a flat wall. Use the following guidelines to determine the best location to install the detector:
Mount the detector so the expected movement of an intruder is across the detection pattern. See Figure 1.
Mount the detector on a stable surface 7 to 9 feet (2.1 to
2.7m) high.
DO NOT mount the detector within 2 feet (0.6m) of metallic objects or within 5 feet (1.5m) of florescent lights.
DO NOT place objects in front of the detector that may prevent a clear line of sight. (Not applicable in radar-only mode.)
Avoid locations that expose the detector to possible false alarm sources such as:
– Moving or vibrating objects (fans, pulleys, conveyor belts) – Electronic fields (electric motors, high voltage equipment) – Water spray or corrosive environments – Heat sources in the field of view (heaters, radiators) – W indows in the field of view – Strong air drafts on the detector (fans, air conditioners)
When installing multiple detectors:
– DO NOT mount detectors facing each other . – Mount detectors at least 20 feet (6.1m) apart. – Use shorter range settings to avoid overlapping radar
coverage. – Mounting detectors back to back is not recommended, but
if an application requires such mounting, use the 20-foot (6.1m) range and walk test the installation to ensure proper operation.
Figure 2. Detector (Exploded)
COM
TMPR NO
TMPR
SPR
1
Installing the Detector
All wiring must conform to the National Electric Code (NEC) and/or local codes having jurisdiction.
Important: DO NOT use this device for safety interlock applications.
T o install the detector:
Terminal sockets
1. Run the security system wiring to the detector location.
2. T o remove the front cover/electronic module, remove the nameplate and loosen the screw if necessary. To remove the nameplate, insert a small screwdriver into one of the nameplate side slots and gently push in and pry up with the screwdriver. See Figure 2. Then press down on the top of the front cover with one hand, while holding the sides at the top of the back cover and squeezing in and pulling back with the other hand.
CAUTION
You must be free of all static electricity before handling sensor circuit boards. Touch a grounded, bare metal surface befor e touching circuit boards or wear a grounding strap.
3. If necessary , set the jumpers on the circuit board. See Setting the Jumpers.
4. Remove the appropriate wiring and mounting knockouts from the back cover. The detector can be mounted on a flat wall or in a corner. See Figure 3.
5. Pull the wires through the knockout holes and use screws to attach the base to the wall. Use screw anchors if necessary .
Corner-mount knockouts
Flatwall-mount knockout
Strain relief
Wiring knockout
Flat-wall mount knockout
Figure 3. Detector Base
Wire
Corner-mount knockouts
6. Strip 1/4 inch (6.4mm) of insulation from each wire.
7. Run each wire through the strain relief and under the appropriate screw terminals on the base and tighten the screws. See Figure 3.
8. Line up the tabs on the bottom of the cover/electronic module with the corresponding tabs on bottom of the base and snap the cover/electronic module firmly down onto the base.
9. Tighten the screw and replace the nameplate. See Figure 2.
10. Apply power. The green LED should light for approxi­mately 25 seconds and then go out.
11. Walk test the coverage pattern as follows: – Walk throughout the intended coverage area. – Verify the detector alarms. See Understanding the LED.
Note
Most units walk test more accurately if the person testing waits 10 seconds between tripping the unit and walking again. This allows the detector to stabilize between trips.
J2
Range
Figure 4. Main Circuit Board
J4
J3
Radar only
LED Disable
2
PrecisionLine RCR-50
Loading...
+ 2 hidden pages