Interlogix AP750-ID User Manual

AP750-ID Installation Instructions

Description

The AP750-ID is an addressable PIR device that interfaces with the PinPoint® system. This system provides flexible and reliable two-way communication between the device and the controller.
Figure 1: Exploded view
1
10
2
3
4
5
6
7
8
9

Selecting a location

Mount the unit:

On a rigid vibration-free surface.
6 to 10 feet (1.8 to 3m) high, but at least 6 inches (15cm) from the ceiling.
So the expected movement of an intruder is across the fields of the detection pattern. See Figure 2 below.
Figure 2: Detection pattern
33.0 ft.(10.1m)
10.0 ft.(3.0m) maximum
8.0 ft.(2.4m) nominal
6.0 ft.(1.8m) minimum
8.0 ft.(2.4m)
50.0 ft.(15.2m)
33.0 ft.(10.1m)
25.0 ft.(7.6m)
50.0 ft.(15.2m)
10.0 ft.(3.0m)

Parts included

• PIR detector
Two plastic masks
One screw to secure the to the wall mounting bracket
• Wall mounting bracket
Sheet of adhesive masking labels
• Cardboard undercrawl window mask

Do not locate the unit:

On a surface exposed to moisture.
Where it may be exposed to false alarm sources such as: direct sunlight, heat sources (heater, radiators, etc.) in the field of view, strong air drafts (fans, air conditioner, etc.).
P/N 1036045 • REV C • 16MAY11 1
Where the ambient temperature is below 32° F (0°C) or above 131°F (55°C).

Mounting the unit

1. Separate the PIR unit from the mounting bracket by inserting a small, flat-bladed screwdriver between the tabs at the bottom of the unit and turning the screwdriver to push the tabs apart. See Figure 1 on page 1.
ution: You must be free of static electricity before handling
Ca
sensor circuit boards. Touch a grounded, bare metal surface before touching circuit boards or wear a grounding strap.
2. Select the coverage pattern and set the sensitivity and range switches. See Figure 6 on page 3, Selecting the
age Pattern, and Setting the Sensitivity and Range
Cover Switches.
3. Set the PinPoint address DIP switches. See Figure 6 on page 3.
If necessar
y, use one or more of the following methods to
modify the coverage pattern:
Use one or both of the plastic masks provided to mask off large areas of coverage as shown in Figure 3 below.
Mask the appropriate mirror curtains with the adhesive
• labels provided. See the example shown in Figure 4
below. Do not use shar
p objects to remove unwanted
labels. If necessary, carefully peel the label off.
Use the cardboard undercrawl window mask as shown in Figure 5 below. The undercrawl mask allows objects to be
ed within 5 feet of, or directly below, the detector.
plac
Figure 3: Plastic masks
1
2
Note: Units are shipped with DIP switches set to 255. This
is an invalid address. The unit will not communicate with the control panel until a valid address has been set. Refer to the NX-2192 manual to determine the correct address setting for each unit.
4. Remove the appropriate knockout mounting and wiring holes on the mounting bracket for either corner or flat wall mounting and PinPoint wiring.
Note: Holes near the tamper actuator are not mounting
knockouts.
5. Pull the PinPoint wiring through the wiring knockout hole. Use screws and wall anchors, if necessary, to attach the mounting bracket to the wall. Do not over-tighten.
6. Strip 1/4 inch (6.4mm) of insulation from the PinPoint wires. Connect the wiring to the appropriate screw terminals and tighten the screws. See Figure 6 on page 3.
Be careful not to catch the wiring as you snap the unit to
7. the mounting bracket.
8. Test the unit when the PinPoint system is completely installed and the control panel is powered.
1
Figure 4: Adhesive labels
A
B
B
7
6
Figure 5: Undercrawl mask
1
324567
2
1
2 3 4567
A
5
4
2
1
2
3

Selecting the coverage pattern

The coverage pattern for the unit can be modified to fit specific applications by masking off mirror curtains. Curtains should be masked to avoid sources of false alarms, such as heaters, air conditioners, and windows. Open the unit by pushing the opening tab up. See Figure 6 on page 3.
2 AP750-ID Installation Instructions
7.9 ft (2.4m)
5.0 ft (1.5m)
6: Detector back
ON APEMS
1 2 3 4 5 6 7 8
Figure
Tamper switch
OUT IN
- + - +
ON APEMS
Opening tab
Terminal block
DIP switches
Switch settings:
33'(10.1m) STD
Note: T
he LED only lights if the unit is placed in Walktest Mode by the installer and the unit is enrolled in the system.

Walk testing

A Walktest Mode for testing the unit operation and coverage pattern is provided. Use the following instructions to walk test the unit:
50'( 15.2m ) BI

Setting the sensitivity and range switches

There are switches on the back of the unit for setting sensitivity and range, as shown in Figure 6 above.
Use the foll for an application:

Mode

owing to determine the appropriate switch settings
BI=Bi-curtain Mode (factory default) increases false
alarm immunity in smaller areas and requires the intruder to pass through two curtains to trigger an alarm. Do not use for single curtain applications or ranges under 5 feet (1.5m).
STD=Standard Mode is used for wide-angle or single­curtain applications. It requires the intruder to only pass through one curtain to trigger an alarm.
1. Ensure the unit is enrolled in the PinPoint system.
2. Lift the unit from the bracket until the tamper switch opens to enable the Walktest Mode.
3. When the unit is remounted on the bracket, the unit remains in the Walktest Mode for 3-4 minutes. If additional time is required, depressing and releasing the tamper switch will reset the Walktest timer. Depending on switch settings (see “Selecting the coverage pattern” on page 2),
alktest Mode allows the unit to alarm whenever one
the W or two curtain areas are entered. The LED visible on the front cover lights to indicate an alarm.
4. Walk test the detection pattern and make any necessary adjustments.
5. Replace and walk test the unit to verify the unit is communicating with the control panel.
Note: After Walktest Mode times out (3 to 4 minutes), the
unit returns to normal operating mode. In normal operating mode, the unit will alarm no more often than once every 3 minutes, and the LED is disabled to reduce voltage loss on the PinPoint bus.

Maintenance

Note: Operation in the Standard Curtain Mode is UL 639
Listed for the specified ranges of 33 feet (10.1m) and 50 feet (15.2m). For operation in Bi-curtain Mode, the unit is UL 639 Listed for 30 feet (9.1m) of range only. For ranges from 30 to 50 feet (9.1 to 15.2m), the unit is not UL 639 Listed but will provide detection within 6 steps or 14 feet (4.3m) across the plane of coverage. UL has not tested the 6 steps or 14 foot (4.3m) detection.
When installed and used properly, the unit provides years of service with minimal maintenance. To ensure proper operation, you should walk test the unit annually as described in Walk Testing.
Clean the inside of the unit with a soft bristled brush or compressed air. Clean the cover with a damp (water) cloth as needed to keep it free of dust and dirt. Always test the unit after cleaning.

Range

Program switch for range under 33 feet (10.1m) (factory default) or to 50 feet (15.2m). It's important to program the unit correctly for optimum sensitivity. Walk test the unit regularly by walking across the fields of view and checking that the LED lights and that an alarm is indicated at the control panel. See “Walk testing” below.
AP750-ID Installation Instructions 3

Pet alley application

To create a detection-free area close to the floor, mount the unit 3 feet (0.9m) above the floor, upside down (detector window towards the ceiling). The undercrawl mask should be in place to reduce exposure to the ceiling. Coverage distance is 25 feet in Bi-curtain Mode.
As shown in Figure 7 below, pets are free to roam below the mounting height of the unit without causing alarms.
Figure 7: Pet alley
3 ft. (0.9m)

Specifications

Housing material Flame retardant ABS
Operating voltage 8 to 27V (as supplied by NX-2192)
Current draw 250μA typical average 3 mA with LED
momentarily on
Transmit condition Alarm, tamper
Detection range 50 feet (15.2m)
Mounting height 6 to 10 feet (1.8 to 3m)
Number of curtains 7
Operating temperature 32 to 131° F (0 to 55° C)
Relative humidity 10 to 90% non-condensing
Maximum line length 10,000 feet (3km)
Dimensions: Width Depth Height
Color White
2.9 inch (7.4cm)
2.2 inch (5.6cm)
5.1 inch (12.9cm)

Regulatory information

Listings UL 639
FCC compliance (Class A & B)
Certification
This device complies with Part 15 of the FCC rules. Operation is
subject to the following two conditions:
1 This device may not cause harmful interference.
2 This device must accept any interference received, including interference that may cause undesired operation.

Product ordering

Product Description
AP750-ID An addressable, passive infrared motion sensor for use
with the NX-2192 PinPoint Bus Interface.

Contact information

www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customer-
support
Copyright © 2011 UTC Fire & Security. All rights reserved.
4 AP750-ID Installation Instructions
Loading...