Interlogix AP450 User Manual

AP450 Motion Sensors Installation Instructions
Direct sunlight on the sensor
Description
The AP450 sensors (models AP450 and AP450A) are passive infrared motion detectors that are highly sensitive to moving infrared sources. They feature superior immunity to RFI, vibration, static electricity, temperature changes, and other false alarm sources.
The sensors provide jumper-selectable sensitivity, range, and LED settings. The masks included allow the coverage pattern to be modified for a wide variety of applications.
Heat sources in the field of view (heaters, radiators, etc.)
Strong air drafts onto the sensor (fans, air conditioning
etc.)
Large animals (dogs, cats) in a field of view The unit should be mo
unted at a height of 6 to 10 feet (1.8 to
3.0m).
Caution: You must be free of static electricity before handling
sensor circuit boards. Touch a grounded, bare metal surface before touching circuit boards or wear a grounding strap.
Figure 1: Exploded view
Cover plate
Housing screw
LED
Cover
Parts
The following parts are included:
AP450 or AP450A sensor
Three factory-installed jumpers
Two plastic masks
Sheet of adhesive masking labels
Cardboard undercrawl window mask
One screw to secure the housing cover
Base
Figure 2: Detection pattern
10.0 ft.(3.0m) maximum
8.0 ft.(2.4m) typical
6.0 ft. (1.8m) minimum 8 ft. (2.4m)
25 ft. (7.6m)
50 ft. (15.2m)
50 ft. (15.2m)
Mounting the sensor
1. To remove the cover plate, insert a flat-bladed screwdriver between the notch on the top of the cover plate and the cover. Pry up the cover plate. See Figure 1 above.
Remove the housing screw that holds the cover to the
Selecting a mounting location
2. base, insert a flat-bladed screwdriver into the slot above
Install the unit so that the expected movement of an intruder will be across the detection pattern. See Figure 2 below.
the screw hole. Pry the cover off the base. See Figure 1 above.
Avoid possible false alarm sources such as:
P/N 1038277 REV C 17MAY11 1
3. Pull up on the top edge of the electronics module while rocking down on the lower edge to remove the module from the base. Be careful not to touch the pyroelectric sensor located on the bottom of the module. See Figure 3 below.
Select mounting holes for corner or wall mounting. Use the
4. base as a template for marking screw hole locations on the wall. See Figure 3 below.
Strip the cable for 2 inches (5cm) and pull it through the
5. cable entry hole(s) and strain relief. Make sure that the cable has slack in the wall. See Figure 3 below.
Use screws and wall anchors, if necessary, to attach the
6. base to the wall.
7. Select the appropriate coverage pattern. See “Selecting the covera
ge pattern” below
8. Replace the electronics module by lining up the notches on the module with the module notch guides and press the top of the module down until it snaps into the module guides. See Figure 3 below.
Strip 1/4 inch (0.6cm) of insulation from each wire. Insert
9. each wire into the appropriate terminal and tighten screws. See Figure 7 on page 3.
10. Set the sensitivity, range and LED jumpers for the application desired. See Figure 7 and “Setting the sensitivit
y, range, and LED” on page 3

Selecting the coverage pattern

The coverage pattern for the unit can be modified to fit specific applications by masking off mirror curtains. Curtains should be masked to avoid sources of false alarms, such as heaters, air conditioners, and windows.
If necessary, use one or more of the following methods to modify the coverage pattern:
Use one or both of the plastic masks provided to mask off large areas of coverage as shown in Figure 4 below.
Mask the appropriate mirror curtains with the adhesive
• labels provided. See the example shown in Figure 5 below. Do not use shar
p objects to remove unwanted
labels. If necessary, carefully peel the label off.
Use the cardboard undercrawl window mask to improve false alarm immunity in the presence of objects within 5 feet (1.5m) and directly under the sensor. See Figure 6 on
e 3.
pag
Figure 4: Plastic masks
21
To replace the cover, insert the closing tabs at the bottom
11. of the cover into the guides at the bottom of the base and snap the cover down. Insert the screw. Fit the hole in the cover plate over the LED and snap the cover plate into place. See Figure 1 on page 1.
Figure 3: Base
Cable strain
relief
Flat wall mount
knockout
Corner mount
knockout
Corner mount
knockout
Electronics
module
Pyroelectric
sensor
Corner mount
knockout
Corner mount
knockout
Module guide
Corner mount
knockout
Module notch
guide
Mirror
Flat wall mount
knockout
Corner mount
knockout
Cable entry
holes
1
2
Figure 5: Adhesive labels
A
91
2 34567 8
1
8
7
2 3456789
A
6
5
1
2
3
4
B
B
9
2 AP450 Motion Sensors Installation Instructions
6: Cardboard undercrawl window mask
A
Figure
7.9 ft.
(2.4m)
5.0 ft.
(1.5m)
Figure 7: Wiring and jumpers
AP450 (Form C)
NC NOC
0V +12V
J1 J2
50FT
BI
33FT
STD
RANGE
SENS
ALARM
10Ω
TAM PER
LED/
SPARE
OFF/
REMOTE
LED
J3
ON
LED
P450A (Form A)

Setting the sensitivity, range, and LED

The unit provides three jumpers to set sensitivity (J1), range (J2) and LED (J3). See Figure 7 below.

Sensitivity (J1)

BI = Bi-Curtain Mode (factory default). Increases false alarm
immunity in smaller areas. Requires the intruder to pass through two curtains to trigger an alarm. Do not use for single curtain applications or ranges under 5 feet (1.5m).
STD = Standard Sensitivity. Use for most wide-angle or single curtain applications. Requires the intruder to pass through only one curtain to trigger an alarm.

Range (J2)

Program J2 for range under 33 feet (10.1m, factory default for AP450A) or to 50 feet (15.2m, factory default for AP450).
It is important to program the sensor correctly for optimum sensitivity. Walk test the sensor regularly by walking across the fields of view and checking that the LED lights and that the opening relay is indicated back at the control panel.
NC COM
0V +12V
10Ω
J1
SENS
BI
STD
J2
50FT
33FT
RANGE
OFF
J3
ON
LED

Pet alley application

To create a detection-free area close to the floor, mount the unit 3.5 feet (1.1m) above the floor, upside down (sensor window towards the ceiling). The cardboard undercrawl window mask should be in place to reduce exposure to the ceiling. As shown in Figure 8 below, pets are free to roam
ow the mounting height of the unit without causing an
bel alarms.
Figure 8: Pet alley

LED (J3)

You can change the LED from enabled (factory default) on the AP450 sensor (does not apply to the AP450A) to remote controlled, by moving jumper J3 to the OFF/Remote position. The LED can then be enabled remotely by applying a 0V potential to terminal 8.
AP450 Motion Sensors Installation Instructions 3
3.5 ft. (1.1m)

Operation information

The relay contacts will open and the LED will turn on (if enabled) every time an alarm occurs. The unit should be allowed to settle for at least one minute after power-up before walk testing. When walk testing, walk across the curtains, not directly toward or away from the unit.

Maintaining the sensor

When installed and used properly, the unit provides years of service with minimum maintenance. To ensure proper operation, you should walk test the unit annually.
Clean the inside of the unit with a soft bristled brush or compressed air. Clean the outside with a damp (water) cloth as needed to keep it free of dust and dirt. Always test the unit
after cleaning.
Figure 9: Dimensions
4.0"
102mm
Dimensions: Width Depth Height
Number of curtains 9 View angle 89° Detection range 50' (15.2m) max.
2.8" (71mm)
2.0" (51mm)
4.0" (102mm)

Regulatory information

Listings C-UL US

Ordering information

Model # Loop type Electrical
configuration
AP450A Closed Normally
Closed
AP450 Open or Closed Normally
Closed or Normally Open (SPDT)
The unit shall be connected to a UL Listed power supply or control unit capable of providing a minimum of 4 hours standby power. The equipment shall be installed in accordance with NFPA 70. The unit shall be tested at least once a year.
Comments
Form A
Form C w/tamper
2.8"
71mm
2.0"
51mm

Specifications

Input voltage 9 to 15VDC (12V nom.) Peak to peak ripple 2V max at 12VDC Current consumption 15mA max. Mounting height 6' to 10' (1.8m to 3m) Target speed range 0.7' to 13.0' (0.2m to 4.0m)/sec. Relay rating w/10
ohms in series Alarm time 2.5 sec. min. Tamper switch rating 100mA at 28VDC Operating temperature 0° to 131° F (-18° to 55° C) Relative humidity 93% max. non-condensing Weight 4.25 ounce (120 g)
50mA at 28VDC

Contact information

www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customer-
support
Copyright © 2011 UTC Fire & Security. All rights reserved.
4 AP450 Motion Sensors Installation Instructions
Loading...