2200 Series Magnetic Contacts
g
Installation Instructions
Description
This installation instruction applies to the following models:
2202A, 2202AU, 2204A, 2204AD, 2204AU, 2205A, 2205AU,
2207A, 2207AD, 2207AU, and 2207AH.
Mounting
To mount models 2202A, 2202AU, 2204A, 2204AD, 2204AU,
2205A, 2205AU, 2207A, 2207AD, and 2207AU, do the
following:
1. Secure the switch to the floor with appropriate fasteners
(wood or masonry). Be sure to position the switch where it
will not interfere with traffic.
2. Attach the magnet on the door so that it lines up with the
switch when the door is closed. There is a 2-inch (1-inch for
AD models) make distance between the switch and magnet to
allow for door operational tolerance.
To mount model 2207AH, do the following:
1. Secure the switch to the floor with appropriate fasteners
(wood or masonry). Be sure to position the switch where it
will not interfere with traffic.
2. Attach an ohmmeter to the common and closed loop leads.
The meter should read INFINITY with the magnet away from
the switch.
3. Align the switch and magnet so the labels read in the same
direction. Contact is polarity-sensitive.
4. Bring the magnet toward the switch until the meter again
reads INFINITY. Mark this point, and position the magnet
between these two marks.
5. Attach the magnet directly to the door or with an L-bracket
(GE Part Number 1912). See Ordering information for the
model's make distance between the switch and magnet to
allow for door operational tolerance.
Figure 1. A and AD models
2.00 in.
5.08 cm
3.50 in.
8.89 cm
3.50 in.
8.89 cm
2.25 in.
5.71 cm
Figure 2. AU models
2.10 in.
5.33 cm
3.125 in.
7.94 cm
3.50 in.
8.89 cm
0.44 in.
1.10 cm
1.50 in.
3.81 cm
1.50 in.
3.81 cm
1.50 in.
3.81 cm
0.81 in.
2.06 cm
1.50 in.
3.81 cm
Magnet included
part number 1958
1.50 in.
3.81cm
Magnet included
part number 1982
2.125 in.
5.4 cm
Figure 3. 2207AH model
Mounting Holes
0.156 in. dia.
SENTROL
2.00 in.
5.08 cm
3.00 in.
7.62 cm
3.50 in.
8.89 cm
1.50 in.
3.81 cm
1.00 in.
2.54 cm
1.50 in.
3.81 cm
Magnet included
part number 1920
0.50 in.
1.27 cm
2 2200 Series
Installation Instructions
Ordering information
Part Loop type Electrical Lead type Finish Nominal Magnet
number config. gap (make)*
2202A-L Closed NO 18 in. (45.7 cm) stainless armored cable Aluminum 360 Up to 3 in. (7.6 cm) 1958
2202AU-L Closed NO 18 in. (45.7 cm) stainless armored cable Aluminum 360 Up to 3 in. (7.6 cm) 1982
2204A-L Open or closed SPDT 18 in. (45.7 cm) stainless armored cable Aluminum 360 Up to 3 in. (7.6 cm) 1958
2204AD-L Open or closed DPDT 18 in. (45.7 cm) stainless armored cable Aluminum 360 Up to 1.5 in. (3.8 cm) 1958
2204AU-L Open or closed SPDT 18 in. (45.7 cm) stainless armored cable Aluminum 360 Up to 3 in. (7.6 cm) 1982
2205A-L Closed NO 36 in. (91.4 cm) stainless armored cable Anodized Up to 3 in. (7.6 cm) 1958
2205AU-L Closed NO 36 in. (91.4 cm) stainless armored cable Anodized Up to 3 in. (7.6 cm) 1982
2207A-L Open or closed SPDT 36 in. (91.4 cm) stainless armored cable Anodized Up to 3 in. (7.6 cm) 1958
2207AD-L Open or closed DPDT 36 in. (91.4 cm) stainless armored cable Anodized Up to 1.5 in. (3.8 cm) 1958
2207AU-L Open or closed SPDT 36 in. (91.4 cm) stainless armored cable Anodized Up to 3 in. (7.6 cm) 1982
2207AH-L Open or closed SPDT 36 in. (91.4 cm) stainless armored cable Anodized 0.75 in. (1.9 cm) min., 1920
2.5 in. (6.3 cm) max.
Accessories
1949-L Floor-mount bracket for replacing ADEMCO and EPC switches
1912-L Aluminum L-bracket for 1920 magnet
* Gap specifications are nominal and may vary ± 20%. Gap specifications are for contact to make. Break distance approximately 1.1 to 1.5 times make.
Specifications
Form A:** 2202A, 2202AU, 2205A, 2205AU
Voltage: 100 V AC/DC max.
Current: 0.5 A max.
Power: 7.5 W max.
Form C: 2204A, 2204AD, 2204AU, 2207A, 2207AD, 2207AU,
2207AH
Voltage: 30 VAC/VDC max.
Current: 0.25 A max.
Power: 3.0 W max.
Listings:
C-UL-US 2202A, 2202AU, 2204A, 2204AU, 2205A, 2205AU,
2207A, 2207AU, 2207AH
** European Union specifications: 48 VAC/VDC max., 0.5 A
Lead functions
Form C Models: 2204A, 2204AD, 2204AU, 2207A, 2207AD,
2207AU, 2207AH
Lead color Function
Black Common
White Closed loop (NO)
Red Open loop (NC)
CAUTION Each electrical rating is an individual
maximum and cannot be exceeded!
12345 SW Leveton Drive
GE Security
Tualatin, OR 97062
503-692-4052
Tech Support: 888-437-3287
www.gesecurity.com