Ingersoll-Rand TEM6A0B24H21S, TEM6A0C48H41S, TEM6A0B30H21S, TEM6A0D48H41S, TEM6A0D60H51S Installer's Manual

...
Page 1
Installer’s Guide
Convertible Air Handlers 2 — 5 Ton
TEM6A0B24H21S TEM6A0B30H21S TEM6A0C36H31S TEM6A0C42H41S TEM6A0C48H41S TEM6A0D48H41S TEM6A0C60H51S TEM6A0D60H51S
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
January 2016
The TEM6 series air handler is designed for installation in a closet, utility room, alcove, basement, crawlspace or attic. These versatile units are applicable to air conditioning and heat pump applications. Several models are available to meet the specific requirements of the outdoor equipment. Field installed electric resistance heaters are available.
SSAAFFEETTYY WWAARRNNIINNGG
18-GF74D1-1F-EN
Page 2
SAFETY SECTION AIR HANDLERS
IImmppoorrttaanntt:: This document contains a wiring diagram,
a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
IImmppoorrttaanntt:: These instructions do not cover all
variations in systems nor provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
WWAARRNNIINNGG
HHAAZZAARRDDOOUUSS VVOOLLTTAAGGEE!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorr ddeeaatthh.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd..
CCAAUUTTIIOONN
GGRROOUUNNDDIINNGG RREEQQUUIIRREEDD!!
FFaaiilluurree ttoo iinnssppeecctt oorr uussee pprrooppeerr sseerrvviiccee ttoooollss mmaayy rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. RReeccoonnnneecctt aallll ggrroouunnddiinngg ddeevviicceess.. AAllll ppaarrttss ooff tthhiiss pprroodduucctt tthhaatt aarree ccaappaabbllee ooff ccoonndduuccttiinngg eelleeccttrriiccaall ccuurrrreenntt aarree ggrroouunnddeedd.. IIff ggrroouunnddiinngg wwiirreess,, ssccrreewwss,, ssttrraappss,, cclliippss,, nnuuttss,, oorr wwaasshheerrss uusseedd ttoo ccoommpplleettee aa ppaatthh ttoo ggrroouunndd aarree rreemmoovveedd ffoorr sseerrvviiccee,, tthheeyy mmuusstt bbee rreettuurrnneedd ttoo tthheeiirr oorriiggiinnaall ppoossiittiioonn aanndd pprrooppeerrllyy ffaasstteenneedd..
WWAARRNNIINNGG
LLIIVVEE EELLEECCTTRRIICCAALL CCOOMMPPOONNEENNTTSS!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorr ddeeaatthh.. FFoollllooww aallll eelleeccttrriiccaall ssaaffeettyy pprreeccaauuttiioonnss wwhheenn eexxppoosseedd ttoo lliivvee eelleeccttrriiccaall ccoommppoonneennttss.. IItt mmaayy bbee nneecceessssaarryy ttoo wwoorrkk wwiitthh lliivvee eelleeccttrriiccaall ccoommppoonneennttss dduurriinngg iinnssttaallllaattiioonn,, tteessttiinngg,, sseerrvviicciinngg,, aanndd ttrroouubblleesshhoooottiinngg ooff tthhiiss pprroodduucctt..
WWAARRNNIINNGG
PPRREESSSSUURRIIZZEEDD RREEFFRRIIGGEERRAANNTT!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn ppeerrssoonnaall iinnjjuurryy SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. DDoo nnoo uussee nnoonn-­aapppprroovveedd rreeffrriiggeerraannttss oorr rreeffrriiggeerraanntt ssuubbssttiittuutteess oorr rreeffrriiggeerraanntt aaddddiittiivveess..
CCAAUUTTIIOONN
SSHHAARRPP EEDDGGEE HHAAZZAARRDD!!
FFaaiilluurree ttoo ffoollllooww tthhiiss CCaauuttiioonn ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. BBee ccaarreeffuull ooff sshhaarrpp eeddggeess oonn eeqquuiippmmeenntt oorr aannyy ccuuttss mmaaddee oonn sshheeeett mmeettaall wwhhiillee iinnssttaalllliinngg oorr sseerrvviicciinngg..
CCAAUUTTIIOONN
HHAAZZAARRDDOOUUSS VVAAPPOORRSS!!
FFaaiilluurree ttoo ffoollllooww tthhiiss ccaauuttiioonn ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. EEqquuiippmmeenntt ccoorrrroossiioonn ddaammaaggee.. TToo pprreevveenntt sshhoorrtteenniinngg iittss sseerrvviiccee lliiffee,, tthhee aaiirr hhaannddlleerr sshhoouulldd nnoott bbee uusseedd dduurriinngg tthhee ffiinniisshhiinngg pphhaasseess ooff ccoonnssttrruuccttiioonn oorr rreemmooddeelliinngg.. TThhee llooww rreettuurrnn aaiirr tteemmppeerraattuurreess ccaann lleeaadd ttoo tthhee ffoorrmmaattiioonn ooff ccoonnddeennssaattee.. CCoonnddeennssaattee iinn tthhee pprreesseennccee ooff cchhlloorriiddeess aanndd fflluuoorriiddeess ffrroomm ppaaiinntt,, vvaarrnniisshh,, ssttaaiinnss,, aaddhheessiivveess,, cclleeaanniinngg ccoommppoouunnddss,, aanndd cceemmeenntt ccrreeaatteess aa ccoorrrroossiivvee ccoonnddiittiioonn wwhhiicchh mmaayy ccaauussee rraappiidd ddeetteerriioorraattiioonn ooff tthhee ccaabbiinneett aanndd iinntteerrnnaall ccoommppoonneennttss..
CCAAUUTTIIOONN
CCOOIILL IISS PPRREESSSSUURRIIZZEEDD!!
•• CCooiill iiss pprreessssuurriizzeedd wwiitthh aapppprrooxxiimmaatteellyy 88––1122 ppssii ddrryy aaiirr aanndd ffaaccttoorryy cchheecckkeedd ffoorr lleeaakkss..
•• CCaarreeffuullllyy rreelleeaassee tthhee pprreessssuurree bbyy rreemmoovviinngg tthhee rruubbbbeerr pplluugg oonn tthhee lliiqquuiidd lliinnee..
•• IIff nnoo pprreessssuurree iiss rreelleeaasseedd,, cchheecckk ffoorr lleeaakkss..
©2016 Trane
18-GF74D1-1F-EN
Page 3
SSAAFFEETTYY SSEECCTTIIOONN AAIIRR HHAANNDDLLEERRSS
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
FFiibbeerrggllaassss dduusstt aanndd cceerraammiicc ffiibbeerrss aarree bbeelliieevveedd bbyy tthhee ssttaattee ooff CCaalliiffoorrnniiaa ttoo ccaauussee ccaanncceerr tthhrroouugghh iinnhhaallaattiioonn.. GGllaasssswwooooll ffiibbeerrss mmaayy aallssoo ccaauussee rreessppiirraattoorryy,, sskkiinn,, oorr eeyyee iirrrriittaattiioonn.. PPRREECCAAUUTTIIOONNAARRYY MMEEAASSUURREESS
•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt
•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr
•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg-­sslleeeevveedd,, lloooossee ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyee pprrootteeccttiioonn
•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg,, rriinnssee wwaasshheerr tthhoorroouugghhllyy
•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr--oouutt,, aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnss rreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUssee tthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr iinn tthheessee ssiittuuaattiioonnss FFIIRRSSTT AAIIDD MMEEAASSUURREESS
•• EEYYEE CCOONNTTAACCTT:: FFLLUUSSHH EEYYEESS WWIITTHH WWAATTEERR TTOO RREEMMOOVVEE DDUUSSTT.. IIFF SSYYMMPPTTOOMMSS PPEERRSSIISSTT,, SSEEEEKK MMEEDDIICCAALL AATTTTEENNTTIIOONN..
•• SSKKIINN CCOONNTTAACCTT:: WWAASSHH AAFFFFEECCTTEEDD AARREEAA GGEENNTTLLYY WWIITTHH SSOOAAPP AANNDD WWAARRMM WWAATTEERR AAFFTTEERR HHAANNDDLLIINNGG.. TThhiiss wwaarrnniinngg ccoommpplliieess wwiitthh ssttaattee ooff CCaalliiffoorrnniiaa llaaww,, PPrrooppoossiittiioonn 6655..
NNoottee:: Air handlers have been evaluated in accordance
with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent.“SUITABLE FOR MOBILE HOME USE.”
NNoottee:: Condensation may occur on the surface of the air
handler when installed in an unconditioned space. When units are installed in unconditioned spaces, verify that all electrical and refrigerant line penetrations on the air handler are sealed completely.
NNoottee:: The manufacturer recommends installing ONLY
A.H.R.I approved, matched indoor and outdoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance, and the best overall system reliability.
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
TThhiiss aapppplliiaannccee iiss nnoott ttoo bbee uusseedd bbyy ppeerrssoonnss ((iinncclluuddiinngg cchhiillddrreenn)) wwiitthh rreedduucceedd pphhyyssiiccaall,, sseennssoorryy,, oorr mmeennttaall ccaappaabbiilliittiieess,, oorr llaacckk ooff eexxppeerriieennccee aanndd kknnoowwlleeddggee,, uunnlleessss tthheeyy hhaavvee bbeeeenn ggiivveenn ssuuppeerrvviissiioonn oorr iinnssttrruuccttiioonn..
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
CChhiillddrreenn sshhoouulldd bbee ssuuppeerrvviisseedd ttoo eennssuurree tthhaatt tthheeyy ddoo nnoott ppllaayy wwiitthh tthhee aapppplliiaannccee..
IImmppoorrttaanntt:: Installation of this unit shall be made in
accordance with the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements.
IImmppoorrttaanntt:: Air handlers do not require repositioning of
the coil or drain pan for upflow or horizontal left applications. See the downflow and horizontal right installation sections for application instructions.
18-GF74D1-1F-EN
3
Page 4
Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Instructions . . . . . . . . . . . . . . . . . . . 5
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data . . .. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance and Electrical Data . . . . . . . . . . . 12
Minimum Airflow CFM . . . . . . . . . . . . . . . . . . . . 19
Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heater Pressure Drop Table . . . . . . . . . . . . . . . . 22
Subcooling Adjustment . . . . . . . . . . . . . . . . . . 22
Subcooling Adjustment for
TEM6A0C48H41 & TEM6A0C60H51 . . . . . . . 22
Coil Conversion Instructions. . . . . . . . . . . . . . . 23
Coil Conversion . . . . . . . . . . . . . . . . . . . . . . . . . 28
Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . 36
4
18-GF74D1-1F-EN
Page 5
Features
Table 1. Standard Features
• MULTI-POSITION UPFLOW, DOWNFLOW, HORIZONTAL LEFT AND HORIZONTAL RIGHT
• PAINTED FINISH ON GALVANIZED STEEL EXTERIOR WITH FULLY INSULATED CABINET THAT MEETS R4.2 VALUE
• STURDY POLYCARBONATE DRAIN PANS
– The TEM air handler has factory installed drain pans and
is shipped for upflow and horizontal left applications
• 208/230 VAC OPERATION
• VARIABLE-SPEED DIRECT DRIVE BLOWER.
• FACTORY INSTALLED R-410A THERMAL EXPANSION VALVE
• ALL ALUMINUM COIL
• BOTTOM RETURN
• MEETS THE MINIMUM LEAKAGE REQUIREMENTS FOR THE FLORIDA AND CALIFORNIA BUILDING CODES
Table 2. Optional Accessories
• 4,5,8,10,15,20, and 25 KW SINGLE PHASE ELECTRIC HEATERS
– Circuit breakers available on single phase 4, 5, 8, 10,
15, 20, and 25 KW heaters
– Lugs available on single phase 4, 5, 8, and 10 KW
heaters
– Lugs available on three phase 10 and 15 KW heaters
• SINGLE POINT POWER ENTRY KIT (for 15 and 20 KW heaters)
• SUPPLY DUCT FLANGE KIT
• DOWNFLOW SUB-BASE KITS - TAYBASE185, TAYBASE235, TAYBASE260
• SLIM FIT FILTER BOX KIT — BAYSF1185AAA, BAYSF1235AAA, BAYSF1265AAA
Installation Instructions
1. UUnnppaacckkiinngg
Carefully unpack the unit and inspect the contents for damage. If any damage is found at the time of delivery, proper notification and claims should be made with the carrier.
Check the rating plate to assure model number and voltage, plus any kits match with what you ordered. The manufacturer should be notified within 5 days of any discrepancy or parts shortage.
2. LLooccaattiioonn
The air handler should be centrally located and may be installed in a closet, alcove, utility room, basement, crawl space or attic. Minimum clearances must be met.
IIMMPPOORRTTAANNTT:: The downflow sub-base may be
required with electric heat applications. See minimum clearance table.
The unit must be installed in a level position to ensure proper condensation drainage. Make sure the unit is level in both directions within 1/8" on either side.
When the unit is installed in a closet or utility room, the room should be large enough, and have an opening to allow replacement of the unit. All servicing is done from the front and a clearance of 21" is needed for service unless the closet door aligns with the front of the air handler.
If you are installing the unit in an unconditioned space such as an attic or crawl space, you must ensure that the area provides sufficient air circulation to prevent moisture collection on the cabinet during high dew point conditions. A drain pan must be installed under the entire unit when it is installed in or above a finished ceiling or in an unconditioned space.
3. DDuucctt WWoorrkk
The duct work should be installed in accordance with the NFPA No. 90A "Installation of Air Conditioning and Ventilating systems" and No. 90B "Residential Type Warm Air Heating and Air Conditioning Installation."
The duct work should be insulated in accordance with the applicable requirements for the particular installation as required by HUD, FHA, VA the applicable building code, local utility or other governing body.
4. CCoonnddeennssaattee DDrraaiinn
The unit is supplied with primary and auxiliary condensate drains that have 3/4" NPT connections. The primary drain must be trapped outside the unit and piped in accordance with applicable building codes. Do not reduce the drain line size less than the connection size on the drain pan. Condensate should be piped to an open drain or to the outside. All drains must pitch downward away from the unit a minimum of 1/4" per foot of line to ensure proper drainage.
IIMMPPOORRTTAANNTT:: If cleanout Tee is used, stand pipe
must be sealed/capped.
Insulate the primary drain line to prevent sweating where dew point temperatures may be met. (Insulation is optional depending on climate and application needs.)
18-GF74D1-1F-EN
5
Page 6
CFM SELECTION LIGHT
DIP SWITCHES
DIP SWITCHES (TYPICAL SETTINGS)
COOLING
HEATING
AIRFLOW
FAN OFF
DELAY
AUXILARY
HEAT SPEEDS
OFF OFF
50%
80%
100% if necessary
50%
Dehumidify Warm Air Heating
Fast Coil Cooling Fast Coil Heating
Efficiency
7.5
minutes
3
minutes
1
minute
FAN OPERATION (CFM)
as required
COMPRESSOR OPERATION ON
OFF
FFeeaattuurreess
5. RReeffrriiggeerraanntt PPiippiinngg
Refrigerant piping external to the unit shall be sized in accordance with the instructions of the manufacturer of the outdoor equipment.
6. MMeetteerriinngg DDeevviiccee
All units are shipped and installed with an internally-checked, non-bleed TXV designed for air conditioning or heat pump operation. Some outdoor models may require a start assist kit. See outdoor unit for more information.
7. BBlloowweerr
This unit is supplied with a variable speed motor with a direct drive blower wheel which can obtain various air flows. The unit is shipped with factory set cooling and heating air flows. Performance tables are available for additional airflow settings. Disconnect all power to the unit before making any adjustments to the airflow settings. Be sure to check the air flow and the temperature drop across the evaporator coil to ensure sufficient air flow.
8. AAiirrffllooww AAddjjuussttmmeenntt
CCAAUUTTIIOONN
EEQQUUIIPPMMEENNTT DDAAMMAAGGEE!!
FFaaiilluurree ttoo ffoollllooww tthhiiss pprroocceedduurree mmaayy rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee.. DDiissccoonnnneecctt ppoowweerr ttoo tthhee aaiirr hhaannddlleerr bbeeffoorree cchhaannggiinngg ddiipp sswwiittcchh ppoossiittiioonnss..
Blower speed changes are made on the ECM Fan Control. The ECM Fan Control controls the variable speed motor.
There is a bank of 8 dip switches. The dip switches work in pairs to match the airflow for the outdoor unit size (tons). cooling airflow adjustment, Fan off­delay options, and heating airflow adjustment. The switches appear as shown in Figure 2, p. 6
Figure 1. ECM Fan Control
Figure 2. Dip Switches
If the airflow needs to be increased or decreased, see the Airflow Label on the air handler or Blower Performance Table.
Be sure to set the correct airflow for cooling and heating.
Switches 1–4 Cooling Airflow
Switches 5–6 Fan Off Delay Options
Switches 7–8 Auxiliary Heat
IInnddoooorr BBlloowweerr TTiimmiinngg
IIMMPPOORRTTAANNTT:: Leave dip switches 5 and 6 in the “as-
shipped” positions during system start­up and check out. Afterwards, adjust as desired.
Table 3. Cooling Off — Delay Options
SWITCH SETTINGS SELECTION NOMINAL
5 — OFF 6 — OFF NONE SAME
5 — ON 6 — OFF 1.5 MINUTES 100%
5 — OFF 6 — ON 3 MINUTES 50%
5 — ON 6 — ON ENHANCED
(a)
Default setting
(b)
This ENHANCED MODE selection provides a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. The graph shows the ramping process.
(b)
AIRFLOW
50–100%
(a)
6
Figure 3. Enhanced Mode
9. WWiirriinngg
18-GF74D1-1F-EN
Page 7
FFeeaattuurreess
Consult all schematic and pictorial wiring diagrams of this unit and the outdoor equipment to determine compatibility of wiring connections and to determine specific requirements.
All field wiring to the air handler should be installed in accordance with the latest edition of the National Electric Code NFPA No. 70 and any local codes. Check rating plates on unit for rated volts, minimum circuit ampacity and maximum over current protection. Supply circuit power wiring must be 75 degree C (167 degree F) minimum copper conductors only. Copper supply wires shall be sized to the National Electric Code or local code requirements, whichever is more stringent.
The unit is shipped wired for 230/240 Volt AC 60 HZ 1 Phase Operation. If the unit is to be operated at 208 VAC 60HZ, follow the instructions on the indoor unit wiring diagram to change the low voltage transformer to 208 VAC operation (Ensure unit is properly grounded).
Class 2 low voltage control wiring should not be run in conduit with power wiring and must be separated from power wiring unless class 1 wire with proper voltage rating is used.
Low voltage control wiring should be 18 Awg, color coded (105 degree C minimum). For lengths longer than 100ft., 16 Awg wire should be used. Make certain that separation of control wiring and power wiring has been maintained.
10. AAiirr FFiilltteerr
To protect the coil, blower and other internal parts from excessive dirt and dust an air filter must be installed before air enters the evaporator coil. A remote filter must be installed. Consult the filter manufacturer for proper sizing and maximum velocity requirements.
IImmppoorrttaanntt:: Air filters shall meet the test requirements
in UL 900.
11. TThheerrmmoossttaatt
Select a thermostat that is commonly used with HP
or AC single stage heating/cooling with electric heat. The thermostat will energize the fan on a demand for heat or cool.
Install the thermostat on an inside wall, away from drafts, lights or other heat sources in a location that has sufficient air circulation from other rooms being controlled by the thermostat.
12. SSeeqquueennccee ooff OOppeerraattiioonn CCoooolliinngg ((CCoooolliinngg oonnllyy))
When the thermostat calls for cooling, the circuit from R to G is completed. The blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
CCoooolliinngg ((hheeaatt ppuummpp))
When the thermostat calls for cooling, the circuit from R to G is completed. The blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
Circuit R to O energizes the reversing valve to the cooling position.
HHeeaattiinngg ((hheeaatt ppuummpp))
When the thermostat calls for heating, the circuit from R to G is completed and the blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
18-GF74D1-1F-EN
7
Page 8
FFeeaattuurreess
In the heating mode, the reversing valve of the outdoor unit is not energized.
If the indoor temperature continues to fall, the R to W circuit is completed energizing the electric heat contactor(s).
HHeeaattiinngg ((eelleeccttrriicc hheeaatt oonnllyy))
NNoottee:: The thermostat must be setup to bring the
blower on when the electric heat is energized.
When the thermostat calls for heating, the circuit from R to G is completed and the blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat. The circuit from R to W is completed energizing the heating contactor(s).
DDeeffrroosstt
Supplemental heat during defrost can be provided by connecting the X2 (black) wire from the outdoor unit to W1 or W2 at the indoor unit. This will prevent cold air from being discharged from the indoor unit during defrost.
13. OOppeerraattiioonnaall aanndd CChheecckkoouutt PPrroocceedduurreess
To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts document of the outdoor unit. After installation has been completed, it is recommended that the entire system be checked against the checkout list located at the back of this document. See “Checkout Procedures,” p. 36
14. MMaaiinntteennaannccee
The system air filter(s) should be inspected, cleaned or replaced at least monthly. Make certain that the access panels are replaced and secured properly before placing the unit back in operation. This product is designed for dependable service; however, periodic maintenance should be scheduled and conducted by trained professional service personnel. This service should be conducted at least annually, and should include testing and inspection of electrical and refrigerant components. The heat transfer surface should be cleaned. The blower motor is permanently lubricated for normal operating conditions.
8
18-GF74D1-1F-EN
Page 9
Field Wiring
Sing le St age, C o o lin g On ly
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
B
Y
R
G
B
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
White
W2
O
Y1
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
Y2
BK
WH/BLK
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In AC s yst em s for mult iple s tages of e lectric heat , jumper W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
Sing le St age, HP
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
R
B
O
Y
X2
R
G
B
O
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
Black
White
W2
O
Y1
Y2
BK
Optional
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In s ystem s fo r m u ltiple stage s of electric he a t, jum per W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
18-GF74D1-1F-EN
9
Page 10
2 St age, 2 Step, Coo lin g O n ly
The rm o
stat
Air H andler
Outdoor
Unit
R
G
B
W1
W2
B
Y1
R
G
B
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
White
W2
O
Y1
Y2
BK
Y2
Y2
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In AC s yst em s for mult iple s tages of e lectric heat , jumper W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
2 St age, 2 Step, HP
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
R
B
O
Y1
X2
R
G
B
O
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
Black
White
W2
O
Y1
Y2
BK
Optional
Y2Y2
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In s ystem s fo r m u ltiple stage s of electric he a t, jum per W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
FFiieelldd WWiirriinngg
10
18-GF74D1-1F-EN
Page 11
Electrical Data
18-GF74D1-1F-EN
11
Page 12
Performance and Electrical Data
Table 4. Air Flow Performance
TEM6A0B24, TEM6A0B30 COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
1.5
2
2.5
3
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
353 CFM/
ton
401 CFM/
ton
451 CFM/
ton
343 CFM/
ton
390 CFM/
ton
439 CFM/
ton
300 CFM/
ton
340 CFM/
ton
383 CFM/
ton
323 CFM/
ton
367 CFM/
ton
413 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
533
52
611
65
684
81
687
82 789 104 884 135 752
92 859 128 963 172 959 169
1097
240
1192
304
497
78
580
95 668 115 672 115 798 145 887 177 749 123 861 172 973 223 962 217
1100
296
1150
331
461 104 548 125 644 148 648 149 780 183 882 230 729 167 863 211 995 263 974 263
1100
343
1115
354
425 130 517 155 611 182 614 182 735 216 845 274 691 211 830 242 967 291 940 297
1034
363
1031
361
390 157 486 185 570 215 571 215 663 246 751 290 636 241 727 268 844 308 816 311
858 341
856 339
Table 5. Air Flow Performance
TEM6A0B24, TEM6A0B30 HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
1.5
2
2.5
3
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
394 CFM/
ton
448 CFM/
ton
493 CFM/
ton
393 CFM/
ton
446 CFM/
ton
491 CFM/
ton
350 CFM/
ton
398 CFM/
ton
437 CFM/
ton
338 CFM/
ton
384 CFM/
ton
422 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
599
58
680
72
748
89
785
97 904 131 980 167 866 125 995 171
1099
220
1010
174
1154
246
1245
305
571
88 665 109 746 118 790 128 902 179 972 216 870 162 988 222
1086
274
1001
224
1151
312
1167
322
539 117 641 145 682 163 773 175 912 219 990 268 866 215
1005
271
1098
328
1018
275
1135
350
1127
346
502 146 610 178 545 208 735 223 894 253 974 308 833 263 986 309
1065
362
1000
315
1066
361
1067
361
462 175 572 209 326 240 674 253 809 281 863 324 750 286 872 325 918 353 888 331
905 345
927 352
12
18-GF74D1-1F-EN
Page 13
Table 6. Air Flow Performance
TEM6A0C36, TEM6A0C42 COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
2.5
3
3.5
4
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW SETTING
300 CFM/
ton
341 CFM/
ton
384 CFM/
ton
319 CFM/
ton
363 CFM/
ton
408 CFM/
ton
315 CFM/
ton
357 CFM/
ton
402 CFM/
ton
308 CFM/
ton
350 CFM/
ton
394 CFM/
ton
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
761
63
862
82
962 106
961 106
1092
146
1231
196
1104
150
1258
209
1418
286
1238
199
1412
282
1570
393
755
98
861 120
963 147
962 147
1093
192
1231
249
1105
197
1258
263
1415
347
1238
253
1410
344
1528
436
719 131
834 158
948 190
947 189
1082
240
1221
301
1094
245
1248
317
1401
406
1229
306
1398
404
1473
466
654 163
781 196
915 234
914 233
1060
288
1203
353
1072
293
1229
369
1379
462
1210
357
1378
462
1406
483
560 193
700 235
863 279
862 279
1026
337
1175
404
1039
343
1201
421
1348
516
1182
408
1349
517
1326
488
Table 7. Air Flow Performance
TEM6A0C36, TEM6A0C42 HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
2.5
3
3.5
4
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
341 CFM/
ton
379 CFM/
ton
417 CFM/
ton
381 CFM/
ton
424 CFM/
ton
466 CFM/
ton
348 CFM/
ton
386 CFM/
ton
425 CFM/
ton
338 CFM/
ton
375 CFM/
ton
413 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
860
77
949
98
1042
122
1147
154
1277
204
1409
260
1222
180
1361
240
1497
316
1360
239
1511
325
1659
420
863 115
953 138
1046
166
1149
203
1279
259
1409
323
1224
232
1362
300
1478
372
1361
299
1489
380
1605
463
838 154
937 180
1036
212
1141
253
1272
314
1401
383
1216
285
1354
358
1449
420
1353
358
1456
426
1535
488
788 193
906 224
1015
259
1123
303
1255
368
1384
442
1200
336
1337
415
1408
461
1336
415
1412
464
1450
494
707 232
852 269
980 308
1094
353
1228
421
1357
500
1174
388
1310
471
1356
494
1309
470
1355
493
1349
483
18-GF74D1-1F-EN
13
Page 14
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
Table 8. Air Flow Performance
TEM6A0C48, TEM6A0C60 COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
3
3.5
4
5
(a)
Factory Default Setting
(b)
Airflow must not exceed 1800 cfm in horizontal right, horizontal left, and downflow applications due to condensate blowoff. The 5 ton high tap shall not be used in these applications.
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
(b)
HIGH
AIRFLOW
SETTING
324 CFM/
ton
368 CFM/
ton
423 CFM/
ton
314 CFM/
ton
357 CFM/
ton
411 CFM/
ton
298 CFM/
ton
339 CFM/
ton
389 CFM/
ton
305 CFM/
ton
347 CFM/
ton
399 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
991
89
1120
118
1282
162
1116
117
1263
156
1449
218
1207
140
1368
190
1564
264
1534
251
1740
344
1995
484
985 133
1119
167
1286
219
1114
165
1266
212
1458
287
1208
193
1374
252
1577
343
1545
328
1758
444
2022
629
974 186
1110
224
1281
280
1105
222
1261
273
1456
352
1201
252
1370
315
1577
411
1545
394
1762
518
2030
717
984 237
1116
279
1280
343
1111
277
1261
334
1449
421
1203
311
1367
381
1567
484
1536
467
1745
594
2005
783
994 303
1122
333
1282
402
1117
331
1263
392
1447
496
1207
366
1367
448
1561
570
1531
550
1734
684
1987
828
Table 9. Air Flow Performance
TEM6A0C48, TEM6A0C60 HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
3
3.5
4
5
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
360 CFM/
ton
400 CFM/
ton
440 CFM/
ton
348 CFM/
ton
387 CFM/
ton
426 CFM/
ton
338 CFM/
ton
375 CFM/
ton
413 CFM/
ton
326 CFM/
ton
362 CFM/
ton
398 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
1097
112
1215
142
1333
178
1232
147
1366
189
1500
238
1364
188
1509
241
1659
305
1637
295
1814
381
1990
481
1094
160
1216
196
1338
238
1234
202
1373
252
1511
311
1370
251
1520
315
1674
395
1652
383
1834
493
2017
625
1086
216
1210
255
1333
300
1228
261
1369
314
1510
377
1366
313
1519
382
1676
466
1653
453
1839
570
2025
713
1092
271
1211
314
1331
365
1229
322
1366
381
1502
449
1363
379
1511
453
1662
541
1641
528
1820
645
2000
779
1099
326
1215
369
1332
428
1233
377
1365
447
1498
529
1363
446
1506
535
1654
632
1632
618
1807
730
1982
826
14
18-GF74D1-1F-EN
Page 15
Table 10. Air Flow Performance
TEM6A0D48, TEM6A0D60 COOLING AIRFLOW PERFORMANCE, WET COIL, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
3
3.5
4
5
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
323 CFM/
ton
367 CFM/
ton
415 CFM/
ton
315 CFM/
ton
358 CFM/
ton
404 CFM/
ton
309 CFM/
ton
351 CFM/
ton
396 CFM/
ton
295 CFM/
ton
335 CFM/
ton
379 CFM/
ton
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
979
87
1111
124
1252
165
1111
124
1259
167
1419
223
1241
161
1407
218
1583
296
1478
249
1671
344
1880
476
978 126
1113
168
1259
214
1113
168
1266
217
1428
279
1248
210
1416
273
1593
359
1487
307
1681
412
1892
556
959 170
1101
215
1254
264
1101
215
1261
267
1425
334
1243
259
1413
328
1594
422
1486
365
1684
479
1900
635
922 217
1075
265
1239
314
1075
265
1246
317
1411
389
1227
309
1399
383
1586
485
1474
423
1678
545
1902
714
867 269
1036
317
1212
364
1036
317
1220
368
1386
444
1201
359
1373
437
1570
547
1452
481
1635
565
1760
650
Table 11. Air Flow Performance
TEM6A0D48, TEM6A0D60 HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATER
OUTDOOR UNIT SIZE
(TONS)
3
3.5
4
5
(a)
Factory Default Setting
SPEED
SETTING
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
HIGH
LOW
NORMAL
(a)
HIGH
AIRFLOW
SETTING
360 CFM/
ton
400 CFM/
ton
440 CFM/
ton
347 CFM/
ton
386 CFM/
ton
424 CFM/
ton
351 CFM/
ton
390 CFM/
ton
429 CFM/
ton
327 CFM/
ton
363 CFM/
ton
400 CFM/
ton
DIP SWITCH SETTING
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
ON ON OFF ON
ON ON OFF OFF
ON ON ON OFF
OFF ON OFF ON
OFF ON OFF OFF
OFF ON ON OFF
ON OFF OFF ON
ON OFF OFF OFF
ON OFF ON OFF
OFF OFF OFF ON
OFF OFF OFF OFF
OFF OFF ON OFF
AIRFLOW
POWER
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
EXTERNAL STATIC PRESSURE
1087
111
1205
139
1322
175
1219
143
1351
184
1482
232
1405
201
1555
262
1703
334
1625
294
1797
384
1970
495
1091
153
1213
186
1333
227
1228
191
1363
237
1495
291
1417
256
1568
323
1717
403
1639
359
1812
459
1986
581
1081
199
1211
234
1332
279
1226
240
1363
290
1497
349
1418
311
1572
385
1723
472
1644
424
1820
533
1999
667
1055
249
1198
283
1321
332
1213
289
1351
344
1489
408
1408
367
1567
447
1722
540
1641
489
1822
606
2010
740
1015
301
1173
333
1297
384
1189
339
1328
397
1471
466
1385
422
1553
509
1665
560
1630
554
1750
615
1910
680
18-GF74D1-1F-EN
15
Page 16
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
Table 12. Electrical Data
TEM6A0B24, TEM6A0B30 HEATER DATA
240 Volt 208 Volt
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Amps per
Heater
Circuit
Minimum
Circuit
Ampacity
Heater Model No.
No. of
Circuits/
Phases
Capacity
kW BTUH kW BTUH
No Heater 2.8 * 4 15 2.8 * 4 15
BAYHTR1504BRKC BAYHTR1504LUGB
BAYHTR1505BRKC BAYHTR1505LUGB
BAYHTR1508BRKC BAYHTR1508LUGB
BAYHTR1510BRKC BAYHTR1510LUGB
BAYHTR1516BRKA Circuit 1
(a)
BAYHTR1516BRKA Circuit 2
BAYHTR3510LUG
BAYHTR3515LUG
1/1
1/1
1/1
1/1
2/1
1/3
1/3
3.84 13100 16.0 24 25 2.88 9800 13.8 21 25
4.80 16400 20.0 29 30 3.60 12300 17.3 25 25
7.68 26200 32.0 44 45 5.76 19700 27.7 38 40
9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
9.60 32800 23.1 32 35 7.20 24600 20.0 28 30
14.40 49100 34.6 46 50 10.80 36900 30.0 41 45
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
Maximum
Overload
Protection
Table 13. Electrical Data
TEM6A0C36, TEM6A0C42 HEATER DATA
240 Volt 208 Volt
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Amps per
Heater
Circuit
Minimum
Circuit
Ampacity
Heater Model No.
No. of
Circuits/
Phases
Capacity
kW BTUH kW BTUH
No Heater 4.3 * 5 15 4.3 * 5 15
BAYHTR1504BRKC BAYHTR1504LUGB
BAYHTR1505BRKC BAYHTR1505LUGB
BAYHTR1508BRKC BAYHTR1508LUGB
BAYHTR1510BRKC BAYHTR1510LUGB
BAYHTR1516BRKA Circuit 1
(a)
BAYHTR1516BRKA Circuit 2
BAYHTR1522BRKA Circuit 1
(a)
BAYHTR1522BRKA Circuit 2
BAYHTR3510LUG
BAYHTR3515LUG
1/1
1/1
1/1
1/1
2/1
2/1
1/3
1/3
3.84 13100 16.0 25 25 2.88 9800 13.8 23 25
4.80 16400 20.0 30 30 3.60 12300 17.3 27 30
7.68 26200 32.0 45 45 5.76 19700 27.7 40 40
9.60 32800 40.0 55 60 7.20 24600 34.6 49 50
9.60 32800 40.0 55 60 7.20 24600 34.6 49 50
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
9.60 32800 40.0 55 60 7.20 24600 34.6 49 50
9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
9.60 32800 23.1 34 35 7.20 24600 20.0 30 30
14.40 49100 34.6 48 50 10.80 36900 30.0 42 45
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
Maximum
Overload
Protection
16
18-GF74D1-1F-EN
Page 17
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
Table 14. Electrical Data
TEM6A0C48, TEM6A0C60 HEATER DATA
240 Volt 208 Volt
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Amps per
Heater
Circuit
Minimum
Circuit
Ampacity
Heater Model No.
No. of
Circuits/
Phases
Capacity
kW BTUH kW BTUH
No Heater 6.8 * 9 15 6.8 * 9 15
BAYHTR1504BRKC BAYHTR1504LUGB
BAYHTR1505BRKC BAYHTR1505LUGB
BAYHTR1508BRKC BAYHTR1508LUGB
BAYHTR1510BRKC BAYHTR1510LUGB
BAYHTR1516BRKA Circuit 1
(a)
BAYHTR1516BRKA Circuit 2
BAYHTR1522BRKA Circuit 1
(a)
BAYHTR1522BRKA Circuit 2
BAYHTR1525BRKA Circuit 1
(a)
BAYHTR1525BRKA Circuit 2
BAYHTR1525BRKA Circuit 3
BAYHTR1525BRKA Circuit 4
BAYHTR3510LUG
BAYHTR3515LUG
1/1
1/1
1/1
1/1
2/1
2/1
4/1
1/3
1/3
3.84 13100 16.0 29 30 2.88 9800 13.8 26 30
4.80 16400 20.0 34 35 3.60 12300 17.3 30 30
7.68 26200 32.0 49 50 5.76 19700 27.7 43 45
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
6.00 20500 25.0 40 40 4.50 15400 21.6 36 40
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
9.60 32800 23.1 36 40 7.20 24600 20.0 33 35
14.40 49100 34.6 51 60 10.80 36900 30.0 45 45
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
Maximum
Overload
Protection
18-GF74D1-1F-EN
17
Page 18
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
Table 15. Electrical Data
TEM6A0D48, TEM6A0D60 HEATER DATA
240 Volt 208 Volt
Heater
Amps per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Amps per
Heater
Circuit
Minimum
Circuit
Ampacity
Heater Model No.
No. of
Circuits/
Phases
Capacity
kW BTUH kW BTUH
No Heater 6.8 * 9 15 6.8 * 9 15
BAYHTR1504BRKC BAYHTR1504LUGB
BAYHTR1505BRKC BAYHTR1505LUGB
BAYHTR1508BRKC BAYHTR1508LUGB
BAYHTR1510BRKC BAYHTR1510LUGB
BAYHTR1516BRKA Circuit 1
(a)
BAYHTR1516BRKA Circuit 2
BAYHTR1522BRKA Circuit 1
(a)
BAYHTR1522BRKA Circuit 2
BAYHTR1525BRKA Circuit 1
(a)
BAYHTR1525BRKA Circuit 2
BAYHTR1525BRKA Circuit 3
BAYHTR1525BRKA Circuit 4
BAYHTR3510LUG
BAYHTR3515LUG
1/1
1/1
1/1
1/1
2/1
2/1
4/1
1/3
1/3
3.84 13100 16.0 29 30 2.88 9800 13.8 26 30
4.80 16400 20.0 34 35 3.60 12300 17.3 30 30
7.68 26200 32.0 49 50 5.76 19700 27.7 43 45
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
6.00 20500 25.0 40 40 4.50 15400 21.6 36 40
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
9.60 32800 23.1 36 40 7.20 24600 20.0 33 35
14.40 49100 34.6 51 60 10.80 36900 30.0 45 45
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
Maximum
Overload
Protection
18
18-GF74D1-1F-EN
Page 19
Minimum Airflow CFM
TEM6A0B24H21S, TEM6A0B30H21S
Heater Minimum Heater Airflow CFM
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB
BAYHTR1508BRKC, BAYHTR1508LUGB
BAYHTR1510BRKC, BAYHTR1510LUGB
BAYHTR1516BRKA
BAYHTR3510LUGC
BAYHTR3515LUGC
TEM6A0C36H31S, TEM6A0C42H41S
Heater Minimum Heater Airflow CFM
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB
BAYHTR1508BRKC, BAYHTR1508LUGB
BAYHTR1510BRKC, BAYHTR1510LUGB
BAYHTR1516BRKA
BAYHTR3510LUGC
BAYHTR3515LUGC
BAYHTR1522BRKA
With Heat Pump Without Heat Pump
550 600
800 600
825 700
1050 850
800 600
900 850
With Heat Pump Without Heat Pump
875 675
875 675
1225 825
1325 1150
875 675
1250 1150
1325 1150
Heater Minimum Heater Airflow CFM
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB
BAYHTR1508BRKC, BAYHTR1508LUGB
BAYHTR1510BRKC, BAYHTR1510LUGB
BAYHTR1516BRKA
BAYHTR3510LUGC
BAYHTR3515LUGC
BAYHTR1522BRKA
BAYHTR1525BRKA
Heater Minimum Heater Airflow CFM
BAYHTR1504BRKC, BAYHTR1504LUGB BAYHTR1505BRKC, BAYHTR1505LUGB
BAYHTR1508BRKC, BAYHTR1508LUGB
BAYHTR1510BRKC, BAYHTR1510LUGB
BAYHTR1516BRKA
BAYHTR3510LUGC
BAYHTR3515LUGC
BAYHTR1522BRKA
BAYHTR1525BRKA
TEM6A0C48H41S, TEM6A0C60H51S
With Heat Pump Without Heat Pump
1200 975
1200 975
1200 975
1200 975
1200 975
1200 975
1350 1125
1500 1350
TEM6A0D48H41S, TEM6A0D60H51S
With Heat Pump Without Heat Pump
1150 975
1150 975
1150 975
1325 1125
1150 975
1375 1125
1375 1125
1375 1125
18-GF74D1-1F-EN
19
Page 20
MMiinniimmuumm AAiirrffllooww CCFFMM
TEM6A0B24H21, TEM6A0B30H21 Airflow Performance with Auxiliary Heat
Airflow Settings
Low ON ON 601
Med-Lo OFF ON 723
Med-Hi ON OFF 851
High
TEM6A0C36H31, TEM6A0C42H41 Airflow Performance with Auxiliary Heat
Airflow Settings
Low ON ON 696
Med-Lo OFF ON 825
Med-Hi ON OFF 1150
High
Dip Switch Settings
Nominal Airflow
Switch 7 Switch 8
OFF OFF 973
Dip Switch Settings
Nominal Airflow
Switch 7 Switch 8
OFF OFF 1298
See following tables for
heater application:
- Pressure Drop for Electrical Heters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
See following tables for
heater application:
- Pressure Drop for Electrical Heters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
TEM6A0C48H41, TEM6A0C60H51 Airflow Performance with Auxiliary Heat
Airflow Settings
Switch 7 Switch 8
Low ON ON 1000
Med-Lo OFF ON 1130
Med-Hi ON OFF 1354
High
Dip Switch Settings
OFF OFF 1596
TEM6A0D48H41, TEM6A0D60H51 Airflow Performance with Auxiliary Heat
Airflow Settings
Switch 7 Switch 8
Low ON ON 997
Med-Lo OFF ON 1129
Med-Hi ON OFF 1350
High
Dip Switch Settings
OFF OFF 1597
Nominal Airflow
Nominal Airflow
See following tables for
heater application:
- Pressure Drop for Electrical Heters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
See following tables for
heater application:
- Pressure Drop for Electrical Heters
- Minimum Heating
Airflow Matrix (on unit
nameplates)
20
18-GF74D1-1F-EN
Page 21
Outline Drawing
Air Handler Model A B C D E F H
TEM6A0B24, 30
TEM6A0C36, 42
TEM6A0C48, 60
TEM6A0D48, 60
All dimensions are in inches
46.77 18.50 16.50 16.75 4.68 7.33 20.09 TXV
51.27 23.50 21.50 21.75 7.01 9.66 24.59 TXV
55.87 23.50 21.50 21.75 4.68 9.66 27.19 TXV
53.87 26.50 24.50 24.75 7.01 9.66 27.19 TXV
18-GF74D1-1F-EN
PRODUCT DIMENSIONS
Flow
Control
Gas Line
Braze
3/4
7/8
7/8
7/8
21
Page 22
Heater Pressure Drop Table
Number of Racks Heater Racks
Airflow
CFM
1800 0.02 0.04 0.06 0.14 BAYHTR1505 1
1700 0.02 0.04 0.06 0.14 BAYHTR1508 2
1600 0.02 0.04 0.06 0.13 BAYHTR1510 2
1500 0.02 0.04 0.06 0.12 BAYHTR1516 3
1400 0.02 0.04 0.06 0.12 BAYHTR3510 3
1300 0.02 0.04 0.05 0.11 BAYHTR3515 3
1200 0.01 0.04 0.05 0.10 BAYHTR1522 4
1100 0.01 0.03 0.05 0.09 BAYHTR1525 4
1000 0.01 0.03 0.04 0.09
900 0.01 0.03 0.04 0.08
800 0.01 0.03
700 0.01 0.02
600 0.01 0.02
Subcooling Adjustment
1 2 3 4 Heater Model No. of Racks
Air Pressure Drop — Inches W.G.
BAYHTR1504 1
System Matched with: Indoor Unit Model No. Outdoor Model No. Subcooling
16 SEER HP — 2 ton TEM6A0C36H31 4TWR6024H1000A
15 SEER HP — 2 ton TEM6A0B24H21
TEM6A0B30H21
15 SEER HP — 3 ton TEM6A0B30H21
TEM6A0C36H31 TEM6A0C42H41
All other matches must be charged per the nameplate charging instructions
4TWX6024H1000A 4A6H6024H1000A
4TWR5024G1000A 4A6H5024G1000A
4TWR5036G1000A 4A6H5036G1000A
13 Degrees
14 Degrees
14 Degrees
Subcooling Adjustment for TEM6A0C48H41 & TEM6A0C60H51
Sub-Cooling Charge Specification For AHRI Rated Performance
OD Equipment Up Flow / Horizontal Down Flow
AC UNIT OD Name Plate OD Name Plate
HP UNIT ≤ 3.5 Tons OD Name Plate OD Name Plate
HP UNIT = 4 and 5 Tons OD Name Plate OD Name Plate
+ 4 Degrees
22
18-GF74D1-1F-EN
Page 23
Coil Conversion Instructions
Table 16. Downflow
Follow the conversion steps when installing the air handler in downflow configuration.
1. Remove the front panels from the air handler. The coil and line set panel do not need to be separated.
2. Remove the fasteners on both sides of the coil.
Note: The TEM6A0C48 and TEM6A0C60 will have a coil retaining
bracket and a shipping bracket. All other coils will have two coil retaining brackets.
3. Remove the two screws holding the center horizontal bracket and rotate out of place. Retain parts.
Figure 4. TEM6A0C48 and TEM6A0C60 Only
Figure 5. All other models
4. For the TEM6A0C48 and TEM6A0C60, remove the drain pan support bracket at the top of the drain pan and discard.
Note: The drain pan support bracket should be removed to avoid
tearing the cabinet insulation.
18-GF74D1-1F-EN
23
Page 24
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Table 16. Downflow (continued)
5. Slide the coil assembly out. Remove and discard the horizontal drain pan.
Figure 6. TEM6A0C48 and TEM6A0C60 Only
Figure 7. All other models
6. On both sides of the cabinet, remove the two screws that hold the coil support brackets and retain for later use. Seal the holes to prevent air leakage.
7. Rotate and lift the two coil support brackets to remove from front slots in cabinet.
Figure 8. All models
24
18-GF74D1-1F-EN
Page 25
Table 16. Downflow (continued)
Left
Right
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
8. Bend the two tabs on each of the coil support brackets. Tabs should be bent inward so they are parallel to the bottom flange.
9. Rotate the unit into the downflow orientation.
10. Pre-drill four clearance holes in the cabinet at dimples located below the location the screws were removed for the coil support brackets. There are two holes per side. See location of holes
11. Replace the center horizontal bracket removed in Step 3. Use the screws retained from Step 3 to attach.
12. Place coil support brackets into the lower set of slots and rotate into place. Push downward to lock into place.
13. Secure each bracket with 2 screws that were previously removed.
Figure 9. All models
Figure 10. All models
18-GF74D1-1F-EN
25
Page 26
Shipping Brackets
Rear View of Coil
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Table 16. Downflow (continued)
14. For the TEM6A0C48 and TEM6A0C60 models, remove the two shipping brackets from the coil and discard.
Note: It is recommended to remove the shipping brackets from the
TEM6A0C48 and TEM6A0C60.
15. Slide the coil assembly back into the air handler cabinet as shown.
16. Remove the appropriate knock out for the condensate piping.
Figure 12. TEM6A0C48 and TEM6A0C60 Only
Figure 11. TEM6A0C48 and TEM6A0C60 Only
Figure 13. All other models
26
18-GF74D1-1F-EN
Page 27
Table 16. Downflow (continued)
17. Replace all panels
Figure 14. TEM6A0C48 and TEM6A0C60 Only
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Figure 15. All other models
18-GF74D1-1F-EN
27
Page 28
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Coil Conversion
Table 17. Horizontal Right
Follow the conversion steps when installing the air handler in horizontal right configuration.
1. Remove the front panels from the air handler. The coil and line set panel do not need to be separated.
2. Remove the fasteners on both sides of the coil. Retain the coil retaining brackets and screws.
Note: The TEM6A0C48 and TEM6A0C60 will have a coil retaining
bracket and a shipping bracket. All other coils will have two coil retaining brackets.
3. Remove the two screws holding the center horizontal bracket and rotate out of place. Retain parts.
Figure 16. TEM6A0C48 and TEM6A0C60 Only
Figure 17. All other models
4. Make note of the horizontal drain pan orientation (up/down).
5. For the TEM6A0C48 and TEMA0C60, remove the drain pan support bracket at the top of the drain pan and retain for later use.
Note: The drain pan support bracket should be removed to avoid
tearing the cabinet insulation.
Figure 18. TEM6A0C48 and TEM6A0C60 Only
28
18-GF74D1-1F-EN
Page 29
Table 17. Horizontal Right (continued)
6. Slide the coil assembly out.
7. Change location of the front and rear water diverter brackets by removing the screws on the water diverter brackets that are located on the left side of the coil. Attach the water diverters to the right hand side of the coil using the same screws.
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Important: The coil slabs are different and the mount hole locations
will vary. See the illustrations on the following pages that correspond to the unit tonnage to see the correct mounting position of the water diverter bracket.
Important: The water diverter brackets are not symmetrical and will
vary by tonnage.
Important: There is no change required for the TEM6A0C48 and
TEM6A0C60 water diverters.
Figure 19. TEM6A0C48 and TEM6A0C60 Only
Figure 20. All other models
18-GF74D1-1F-EN
29
Page 30
Remove 2 screws and water diverter bracket
TEM6A0B24 and TEM6A0B30 - Front view
Screw is located in second hole on tube sheet
TEM6A0B24 and TEM6A0B30 - Front view
Replace 2 screws and water diverter bracket
TEM6A0B24 and TEM6A0B30 - Rear view
Remove 2 screws and water diverter bracket
Screw is located in second hole on tube sheet
Replace water diverter bracket
TEM6A0B24 and TEM6A0B30 - Rear view
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Table 17. Horizontal Right (continued)
Figure 21.
Figure 22.
Figure 23.
Figure 24.
30
18-GF74D1-1F-EN
Page 31
Table 17. Horizontal Right (continued)
Remove 3 screws and water diverter bracket
TEM6A0C36 and TEM6A0C42 models -Front view
Screw is located in second hole on tube sheet
Replace 3 screws and water diverter bracket
TEM6A0C36 and TEM6A0C42 models
-Front vi
ew
Remove 3 screws and water diverter bracket
TEM6A0C36 and TEM6A0C42 models -Rear view
Screw is located in uppermost hole on tube sheet
Replace 3 screws and water diverter bracket
TEM6A0C36 and TEM6A0C42 models -Rear view
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Figure 25.
Figure 26.
Figure 27.
Figure 28.
18-GF74D1-1F-EN
31
Page 32
TEM6A0D48 and TEM6A0D60 models
- Front view
Remove 3 screws and water diverter bracket
Screw is located in second hole on tube sheet
TEM6A0D48 and TEM6A0D60 models - Front view
Replace 3 screws and water diverter bracket
TEM6A0D48 and TEM6A0D60 models - Rear view
Remove 3 screws and water diverter bracket
TEM6A0D48 and TEM6A0D60 models
- Rear view
Replace 3 screws and water diverter bracket
Screw is located in second hole on tube sheet
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Table 17. Horizontal Right (continued)
Figure 29.
Figure 31.
Figure 30.
Figure 32.
Important: There is no change required for the TEM6A0C48 and
32
TEM6A0C60 water diverters.
18-GF74D1-1F-EN
Page 33
Table 17. Horizontal Right (continued)
Shipping Brackets
Rear View of Coil
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
8. For the TEM6A0C48 and TEM6A0C60 models, remove the two shipping brackets from the coil and discard.
9. Relocate the horizontal drain pan from the left side of the coil to the right side.
10. Remove the two drain plugs and the drain pan support bracket from the front of the drain pan and insert them in the drains at the rear of the drain pan.
Note: For the TEM6A0C48 and TEM6A0C60, the drain pan
support bracket should have been removed earlier.
Figure 34. TEM6A0C48 and TEM6A0C60 Only
Figure 33. TEM6A0C48 and TEM6A0C60 Only
Figure 35. All other models
Important: When reinstalling coil in Step 12, it is important that the
coil corner locks in place under the tab in the side bracket to support the coil weight horizontally.
18-GF74D1-1F-EN
33
Page 34
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
Table 17. Horizontal Right (continued)
11. Reinstall the drain pan support bracket. The bracket should be located between the two drain plugs as shown.
Note: For the TEM6A0C48 and TEM6A0C60 models only, to avoid
tearing the interior insulation, the drain pan support bracket should be installed after the coil has been put into the unit in Step 12.
12. Slide the coil assembly back into the air handler cabinet.
IMPORTANT: Make sure that the coil corner locks in place under
the tab in the side left bracket to support the coil weight in the horizontal right position.
13. For the TEM6A0C48 and TEMA0C60 only, install the drain pan support bracket on the top of the drain pan opposite the drain ports and as close to the end as possible
Figure 37. TEM6A0C48 and TEM6A0C60 Only
Figure 36. All other models
34
18-GF74D1-1F-EN
Page 35
Table 17. Horizontal Right (continued)
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
14. Replace the center horizontal bracket using screws removed earlier in Step 3.
15. Replace the two coil retaining brackets removed in a previous step.
Note: The TEM6A0C48 and TEM6A0C60 will have only one coil
retaining bracket.
16. Replace all panels.
Figure 38. TEM6A0C48 and TEM6A0C60 Only
Figure 39. All other models
18-GF74D1-1F-EN
35
Page 36
Checkout Procedures
The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in a Checkout Procedure. Confirm all requirements in this document have been met.
All wiring connections are tight and properly secured.
Voltage and running current are within limits.
All refrigerant lines (internal and external to equipment) are isolated, secure, and not in direct contact with each other or structure.
All braze connections have been checked for leaks. A vacuum of 350 microns provides confirmation that the refrigeration system is leak free and dry.
Final unit inspection to confirm factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other or any component when unit runs.
Ductwork is sealed and insulated.
All drain lines are clear with joints properly sealed. Pour water into drain pan to confirm proper drainage.
Supply registers and return grilles are open, unobstructed, and air filter is installed.
Indoor blower and outdoor fan are operating smoothly and without obstruction.
Indoor blower motor set on correct speed setting to deliver required CFM.
Cover panels are in place and properly tightened.
For gas heating systems, manifold pressure has been checked and all gas line connections are tight and leak free.
For gas heating systems, flue gas is properly vented.
System functions safely and properly in all modes.
Owner has been instructed on use of system and given manual.
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2016 Trane
18-GF74D1-1F-EN
Supersedes 18-GF74D1-1E-EN (December 2015)
15 Jan 2016
Loading...