Ingersoll-Rand EP50-PE, SSR UP6 50PEI HF50-PE, SSR UP6 40, HP50-PE, HXP50-PE User Manual

...
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI
HF50–PE, EP50–PE, HP50–PE, HXP50–PE
60Hz
This manual contains important safety information and must be made available to personnel who operate and maintain this machine.
OPERATION AND MAINTENANCE MANUAL
C.C.N. : REV. : A DATE : OCTOBER 2008
80445190
AIR COMPRESSOR GROUP
BONDED WARRANTY & REGISTERED START UP

Warranty

The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen months from the date of shipment from the factory, whichever shall first occur. The Purchaser shall be obligated to promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment in accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the
Purchaser or others without Company‘s prior written approval. The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are
limited to those specifically stated within the Company‘s proposal. Unless responsibility for meeting such performance warranties are limited to specified tests, the Company‘s obligation shall be to correct in the manner and for the period
of time provided above. THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on
contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment. The purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company
in writing of its intention to do so. Any such use of Equipment will be at Purchaser‘s sole risk and liability.
Note that this is Ingersoll Rand standard warranty. Any warranty in force at the time of purchase of the compressor or negotiated as part of the purchase order may take precedence over this warranty.
Register on–line at http://air.ingersollrand.com
Ingersoll Rand Air Solutions Group
Global Aftermarket Division
800–B Beaty Street
Davidson, NC 28036
1–800–526–3615
CONTENTS & ABBREVIATIONS
1
CONTENTS 1 CONTENTS
2 FOREWORD
3 DECALS
8 SAFETY
10 GENERAL INFORMATION
12 INSTALLATION / HANDLING
OPERATING INSTRUCTIONS 21 GENERAL 22 ELECTRO–PNEUMATIC 29 INTELLISYS 40 MAINTENANCE
47 TROUBLE SHOOTING
ABBREVIATIONS & SYMBOLS
#### Contact Ingersoll Rand for serial number
–>#### Up to Serial No. ####–> From Serial No. * Not illustrated
{ Option
NR Not required AR As required SM Sitemaster/Sitepack HA High ambient machine WC Watercooled machine AC Aircooled machine ERS Energy recovery system T.E.F.C. Totally enclosed fan cooled motor (IP55) O.D.P. Open drip proof (motor)
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PEhttp://air.ingersollrand.com
2

FOREWORD

The contents of this manual are considered to be proprietary and confidential to Ingersoll Rand and should not be reproduced without the prior written permission of Ingersoll Rand.
Nothing contained in this document is intended to extend any promise, warranty or representation, expressed or implied, regarding the Ingersoll Rand products described herein. Any such warranties or other terms and conditions of sale of products shall be in accordance with the standard terms and conditions of sale for such products, which are available upon request.
This manual contains instructions and technical data to cover routine operation and scheduled maintenance tasks by operation and maintenance staff. Major overhauls are outside the scope of this manual and should be referred to an authorised Ingersoll Rand service department.
The design specification of this machine has been certified as complying with E.C. directives. Any modification to any part is absolutely prohibited and would result in the CE certification and marking being rendered invalid.
All components, accessories, pipes and connectors added to the compressed air system should be: . of good quality, procured from a reputable manufacturer and, wherever possible, be of a type approved by Ingersoll Rand. . clearly rated for a pressure at least equal to the machine maximum allowable working pressure. . compatible with the compressor lubricant/coolant. . accompanied with instructions for safe installation, operation and maintenance.
Details of approved equipment are available from Ingersoll Rand Service departments.
The use of non–genuine spare repair parts other than those included within the Ingersoll Rand approved parts list may create hazardous conditions over which Ingersoll Rand has no control. Therefore Ingersoll Rand does not accept any liabilitity for losses caused by equipment in which non–approved repair parts are installed. Standard warranty conditions may be affected.
The intended uses of this machine are outlined below and examples of unapproved usage are also given, however Ingersoll Rand cannot anticipate every application or work situation that may arise.
IF IN DOUBT CONSULT SUPERVISION.
This machine has been designed and supplied for use only in the following specified conditions and applications: . Compression of normal ambient air containing no known or detectable additional gases, vapours. or particles . Operation within the ambient temperature range specified in the GENERAL INFORMATION section of this manual.
The use of the machine in any of the situation types listed in table 1:– a) Is not approved by Ingersoll Rand, b) May impair the safety of users and other persons, and c) May prejudice any claims made against Ingersoll Rand.
TABLE 1
Use of the machine to produce compressed air for: a) direct human consumption b) indirect human consumption, without suitable filtration and purity checks.
Use of the machine outside the ambient temperature range specified in the GENERAL INFORMATION SECTION of this manual.
Use of the machine where there is any actual or foreseeable risk of hazardous levels of flammable gases or vapours.
THIS MACHINE IS NOT INTENDED AND MUST NOT BE USED IN POTENTIALLY EXPLOSIVE ATMOSPHERES, INCLUDING SITUATIONS WHERE FLAMMABLE GASES OR VAPOURS MAY BE PRESENT.
Use of the machine fitted with non Ingersoll Rand approved
components.
Use of the machine with safety or control components missing or disabled.
Ingersoll Rand reserves the right to make changes and improvements to products without notice and without incurring any obligation to make such changes or add such improvements to products sold previously.
The company accepts no responsibility for errors in translation of
this manual from the original English version.
© COPYRIGHT 2008 INGERSOLL RAND COMPANY
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE http://air.ingersollrand.com
DECALS 3

ISO SYMBOLS

GRAPHIC FORM AND MEANING OF ISO SYMBOLS
Prohibition / Mandatory Information / Instructions Warning
Use fork lift truck from this side only. RESET Do not use fork lift truck from this side.
Emergency stop. On (power). Off (power).
AUTOMATIC RESTART MAINTENANCE MAINTENANCE PROHIBITED
FRAGILE KEEP DRY THIS WAY UP
USE NO HOOKS NO SIDE CLAMPS HOURS
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
DECALS4
POWER INSPECT
Every X months, if sooner than required by
operating hours
CLEAN
CHANGE / REPLACE
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE http://air.ingersollrand.com
DECALS 5

ANSI SYMBOLS

GRAPHIC FORM AND MEANING OF ANSI SYMBOLS
DANGER
INTAKE AIR. Can contain carbon monoxide or other contaminants. Will cause serious injury or death. Ingersoll Rand air compressors are not designed, intended or approved for breathing air. Compressed air should not be used for
breathing air applications unless treated in accordance with all applicable codes and regulations.
WARNING
HAZARDOUS VOLTAGE. Can cause serious injury or death. Disconnect power and bleed pressure from tank before servicing. Lockout/Tagout machine. Compressor must be connected to properly grounded circuit. See Grounding
Instructions in manual. Do not operate compressor in wet conditions. Store indoors.
RISK OF FIRE OR EXPLOSION. Electrical arcing from compressor components can ignite flammable liquids and vapors which can result in serious injury. Never operate the compressor near flammable liquids or vapors. If used to
spray flammable materials, keep compressor at least 20ft away from the spray area.
HIGH PRESSURE AIR. Rusted tanks can cause explosion and severe injury or death. Receiver under perssure. Operator should relieve tank pressure before performing maintenance. In addition to automatic drain, operate manual
drain valve weekly. Manual drain valve located at bottom of the tank.
MOVING PARTS. Can cause serious injury. Do not operate with guards removed. Machine may start automatically. Disconnect power before servicing. Lockout/Tagout machine.
HOT SURFACES. Can cause serious injury. Do not touch. Allow to cool before servicing. Do not touch hot compressor or tubing.
EXPOSED MOVING BELTS AND SHEAVES. Can cause severe injury or death. Do not operate without guard in place. Disconnect power before servicing. Lockout/Tagout machine.
http://air.ingersollrand.com
Air flow exhaust may contain flying debris. Safety protection should be worn at all times.
Pinch point hazard. Keep hands clear.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
6
60 Hz Units
DECALS – ANSI
VIEW BACK
VIEW FRONT
VIEW LEFT
VIEW RIGHT
INSIDE PACKAGE
INSIDE STARTER DOOR
VIEW TOP
Item ccn Qty. Description Item ccn Qty. Description
1 32343519 1 Decal, warning contaminated air
2 93166502 1 Decal, replacement filter element 3 93166460 1 Decal, coolant drain
4 32343501 1
5 22248538 2 Decal, pinch hazard 6 23038474 1 Decal, Ingersoll Rand signature
7
23353170 1 Decal, maintenance parts
8 30286686 1 Decal, notice rotation
9 32343543 1 Decal, notice air discharge
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE http://air.ingersollrand.com
Decal, dual voltage (if needed)
horizontal 27.5“
10 93171262 2 Decal, notice lift here
11 32343493 1 Decal, overload setting IEC starter 12 SPEC 1 Specifications, compressor package
13 81295883 1 Decal, facia – Electro–Pneumatic
81295891 1 Decal, facia – Intellisys 14 32017469 1 Decal, voltage 120/1/60
15 32017436 1 Decal, voltage 230/3/60
32018475 1 Decal, voltage 200/3/60
32236481 1 Decal, voltage 380/3/60
60 Hz Units
DECALS – ANSI
7
VIEW BACK
VIEW FRONT
VIEW LEFT
VIEW RIGHT
INSIDE PACKAGE
INSIDE STARTER DOOR
VIEW TOP
Item ccn Qty. Description Item ccn Qty. Description
32017444 1 Decal, voltage 460/3/60
32177305 1 Decal, voltage 575/3/60 16 32343527 1 Decal, warning high pressure
17 32343535 3 Decal, warning moving belts
18 32343550 4 Decal, warning exposed fan 19 32343568 2 Decal, warning hazardous voltage
20 32343584 1 Decal, warning hot surface
21 22182372 1 Decal, wiring schematic
Full Voltage 60Hz
22182349 1 Decal, wiring schematic
Star Delta 60Hz
22182364 1 Decal, wiring schematic
Full Voltage Intellisys 60Hz
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PEhttp://air.ingersollrand.com
22182356 1 Decal, wiring schematic
Star Delta Intellisys 60Hz
22 32343907 1 Decal, lock and tag out 23 32343899 1 Decal, warning flying debris
24 22115703 1 Tag, rotation 60Hz
25 22436760 4 Tag, shipping bracket 26 22064562 1 Decal, aircare
27 30286686 1 Decal, rotation arrow
28 22181663 1 Decal, condensate drain
29 81296196 1 Decal, maintenance schedule
8

SAFETY

DANGER!
Hazard that WILL cause DEATH, SEVERE INJURY or substantial
property damage if ignored. Instructions must be followed precisely to avoid injury or death.
WARNING!
Hazard that CAN cause DEATH, SEVERE INJURY or substantial
property damage if ignored. Instructions which must be followed precisely to avoid injury or death.
CAUTIONS!
Cautions call attention to instructions which must be followed
precisely to avoid damaging the product, process or its surroundings.
NOTES
Notes are used for supplementary information.
BREATHING AIR PRECAUTION
Ingersoll Rand air compressors are not designed, intended or approved for breathing air. Compressed air should not be used for breathing air applications unless treated in accordance with all
applicable codes and regulations.
General Information
Ensure that the operator reads and understands the decals and consults the manuals before maintenance or operation.
Ensure that the Operation and Maintenance manual is not removed permanently from the machine.
Ensure that maintenance personnel are adequately trained, competent and have read the Maintenance Manuals.
Do not point air nozzles or sprayers toward anyone.
Compressed air and electricity can be dangerous. Before undertaking any work on the compressor, ensure that the electrical supply has been isolated and the compressor has been relieved of all pressure.
Wear eye protection when operating or servicing compressor.
All persons positioned near to operating machinery should be equipped with hearing protection and given instructions on its use in accordance with workplace safety legislation.
Make sure that all protective covers are in place and that the canopy/doors are closed during operation.
The specification of this machine is such that the machine is not suitable for use in flammable gas risk areas.
Installation of this compressor must be in accordance with recognised electrical codes and any local Health and Safety Codes.
The use of plastic bowls on line filters can be hazardous. Their safety can be affected by either synthetic lubricants, or the additives used in mineral oils. Ingersoll –Rand recommends that only filters with metal bowls should be used on a pressurised system.
If more than one compressor is connected to one common downstream plant, effective isolation valves must be fitted and controlled by work procedures, so that one machine cannot accidently be pressurised / over pressurised by another.
Compressed air must not be used for a direct feed to any form of breathing apparatus or mask.
The discharged air contains a very small percentage of compressor lubricant and care should be taken to ensure that downstream equipment is compatible.
If the discharged air is to be ultimately released into a confined space, adequate ventilation must be provided.
When using compressed air always use appropriate personal protective equipment.
All pressure containing parts, especially flexible hoses and their couplings, must be regularly inspected, be free from defects and be replaced according to the Manual instructions.
Compressed air can be dangerous if incorrectly handled. Before doing any work on the unit, ensure that all pressure is vented from the system and that the machine cannot be started accidentally.
Avoid bodily contact with compressed air.
All safety valves located in the separator tank must be checked periodically for correct operation.
Do not over–pressurize the receiver tank or similar vessels beyond design limits.
Do not use a receiver tank or similar vessels that fail to meet the design requirements of the compressor. Contact your distributor for
assistance.
Do not drill into, weld or otherwise alter the receiver tank or similar vessels.
Materials
The following substances are used in the manufacture of this machine and may be hazardous to health if used incorrectly: . preservative grease . rust preventative . compressor coolant
AVOID INGESTION, SKIN CONTACT AND INHALATION OF FUMES
Transport
When loading or transporting machines ensure that the specified lifting and tie down points are used.
Lifting equipment must be properly rated for the weight of the compressor.
Do not work on or walk under the compressor while it is suspended.
Compressed air
Compressed air can be dangerous if incorrectly handled. Before doing any work on the unit, ensure that all pressure is vented from the system and that the machine cannot be started accidentally.
WARNING
Imposing a normal or emergency stop on the compressor will only relieve presure upstream of the minimum pressure valve on top of the separator tank. If maintenance work is required downstream of this valve, ensure that all pressure is relieved at the process vent point external to the compressor
Ensure that the machine is operating at the rated pressure and that the rated pressure is known to all relevant personnel.
All air pressure equipment installed in or connected to the machine must have safe working pressure ratings of at least the machine rated pressure.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE http://air.ingersollrand.com
Electrical
Keep all parts of the body and any hand–held tools or other conductive objects, away from exposed live parts of the compressor electrical system. Maintain dry footing, stand on insulating surfaces and do not contact any other portion of the compressor when making adjustments or repairs to exposed live parts of the compressor electrical system.
WARNING
Any electrical connections or adjustments should only be made by a suitably qualified electrician
Close and lock all access doors when the compressor is left unattended.
Do not use extinguishers intended for Class A or Class B fires on electrical fires. Use only extinguishers suitable for class BC or class ABC fires.
Attempt repairs only in clean, dry, well lighted and ventilated areas.
Connect the compressor only to electrical systems that are compatible with its electrical characteristics and that are within it’s rated capacity.
Condensate disposal
As waste water regulations vary by country and region it is the responsibility of the user to establish the limitations and regulations in their particular area. Ingersoll Rand and its associated distributors are happy to advise and assist in these matters.
For further information, consult Material Data Sheets for ULTRA Coolant.
SAFETY
9
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE,
HXP50–PE
10
http://air.ingersollrand.com

GENERAL INFORMATION

PIPING AND INSTRUMENTATION – Electro–pneumatic and Intellisys Units
36
37
41
M
38
40
39
28
20
DRYER OPTION
27
35
11
10
P
27
29
23
9
34
31
8
30
KEY
22
1
22292783 Rev F
3
21
2
5
M
4
12
16
26
INTELLISYS (OPTION)
REPLACES ITEM 12
13
19
33
17
T
6
18
15
7
24
25
INTELLISYS (OPTION)
REPLACES ITEMS 10 & 11
14
T
32
MODULATION (OPTION)
PIPING LEGEND
A B C D E
F G
1. Filter, air
2. Valve, inlet
3. Valve, solenoid (load)
4. Airend assembly
5. Motor
6. Tank, separator
7. Separator elements
8. Valve, minimum pressure
9. Aftercooler
10.Gauge, pressure
11.Switch, discharge pressure
12.Switch, temperature
13.Filter, coolant
14.Thermostat
15.Cooler 16 Relay, overload, Motor
17.Valve, safety
18.Valve, drain
19.Screen, scavenge
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
20 Valve, solenoid (blowdown)
21.Orifice 22 Indicator, air restriction
23.Electric drain valve (EDV – condensate)
24.Valve solenoid (line/sump), Intellisys Option
25.Transducer pressure, Intellisys Option, replaces 10 and 11
26.Sensor temperature, Intellisys Option, replaces 12
27.Moisture separator
28.Compressor air discharge
29.Condensate discharge
30.Compressor air inlet
31.Valve, solenoid, (modulation option)
32.Valve, solenoid, (modulation option)
33.Valve, shuttle, (modulation option)
34.Valve, modulation (modulation option)
35.Sensor, temperature, dryer (option) thermometer or thermistor–Intellisys
36.Valve, expansion, dryer (option)
37.Filter, refrigerant, dryer (option)
GENERAL INFORMATION
11
38.Condenser, dryer (option)
39.Evaporator, dryer (option)
40.Refrigerant compressor, dryer (option)
41.Hot gas bypass valve, dryer (option)
A Air/Coolant B Air C Coolant D Condensate E Component boundary F Refrigerant G Option
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
12

INSTALLATION / HANDLING

ROTATION
VIEW LEFT
VIEW REAR
VIEW FRONT VIEW RIGHT
DRYER
ROTATION
VIEW TOPVIEW BOTTOM
Note: Dimensions are mm (inches)
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
KEY
INSTALLATION / HANDLING
13
A Pre filter
B Compressor and cooling air intake C Starter box
D Cooling air exhaust
E 1.5” NPT air discharge F Customer power inlet
G Fork lift openings
(Fork lift hole covers must be installed after unit is in place to reduce noise and ensure proper cooling of package)
NOTES
1. Coolant (lubricant) fill quantity (approximate) 5.5 US gallons (21 litres).
2. Recommended clearance in front of control panel door 42 inches (1067 mm) or minimum as required by the latest national electrical codes (NEC) or applicable local codes.
3. Recommended clearances on left and right sides 36 inches (914mm).
4. Minimum recommended clearance for the rear of the compressor is to be 6 inches (152mm).
5. External piping shall not exert any unresolved moments or forces on the unit. Use pipe size as large or larger at discharge connection.
6. There should be no plastic or pvc piping attached to this unit or used for any lines downstream.
7. Any field installed ducting to and from the compressor cannot add more than 1/2 inch (12.5mm) water gauge total air resistance.
Ducting is not recommended for the dryer cooling air inlet and outlet openings.
8. Do not pipe into a common header with a reciprocating compressor, unless the reciprocating compressor utilizes a discharge pulsation
damper.
9. Sizing of electrical components not supplied by Ingersoll Rand is the responsibility of the customer and should be done in accordance with the information on the compressor data plate and national and
local electrical codes.
H .25 Inch female NPT moisture separator drain.
J Emergency stop button K Primary compressor service door
L 4 holes, 0.67 Inch (17mm) diameter
M 4 holes, 0.47 Inch (12mm) diameter N Dryer cooling air intake
NOTE
All dimensions are in millimetres (inches) unless otherwise stated.
Ensure that the correct fork lift truck slots or marked lifting points are
used whenever the machine is lifted or transported.
UNPACKING
The compressor will normally be delivered with a polythene cover.
If a knife has to be used to remove this cover ensure that the exterior paintwork of the compressor is not damaged.
Ensure that all transport and packing materials are discarded in a
manner prescribed by local codes.
NOTE
Units are shipped with transit locking bolt in place. Prior to
running the unit the shipping bolt must be removed and the belt tension checked. Loosen, remove and discard 10mm shipping bolt. For belt tensioning procedure refer to Maintenance section.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
14
INSTALLATION / HANDLING
1
4
2
T5750 Revision 02 07/04
KEY
1. Compressor
2. Air Dryer
3. Air Receiver
4. Compressed air filters
5. System demand points
NOTE
Items [2] to [5] are optional or may be existing items of plant. Refer to your Ingersoll Rand distributor / representative for specific recommendations.
LOCATION IN THE PLANT
Note:
Ensure that the unit is wired for proper voltage before installation.
4
3
CAUTION
The use of plastic bowls on line filters and other plastic air line components can be hazardous. Their safety can be affected by either synthetic coolants or the additives used in mineral oils. Ingersoll Rand recommends that only filters with metal bowls should be used on any pressurised system.
CAUTION
Before starting machine remove shipping bolt and discard
CAUTION The standard compressor unit is not suitable for operation in temperatures liable to cause freezing as Condensate water is liable to be produced in the after cooler and receiver where fitted.
Refer to your Ingersoll Rand distributor for further information.
5
The compressor can be installed on any level floor capable of supporting it. A dry, well ventilated area where the atmosphere is clean is recommended. A minimum of 6 inches (150mm) should be left at the rear and 3ft (1m) at the sides of the machine for adequate service access and ventilation.
Adequate clearance needs to be allowed around and above the machine to permit safe access for specified maintenance tasks.
Ensure that the machine is positioned securely and on a stable foundation. Any risk of movement should be removed by suitable means, especially to avoid strain on any rigid discharge piping.
CAUTION
Screw type compressors [1] should not be installed in air systems with reciprocating compressors without means of isolation such as a common receiver tank. It is recommended that both types of compressor be piped to a common receiver using individual air lines.
DISCHARGE PIPING
Discharge piping should be at least as large as the discharge connection of the compressor. All piping and fittings should be suitably rated for the discharge pressure.
It is essential when installing a new compressor [1], to review the total air system. This is to ensure a safe and effective total system. One item which should be considered is liquid carryover. Installation of air dryers [3] is always good practice since properly selected and installed they can reduce any liquid carryover to zero.
It is good practice to locate an isolation valve close to the compressor and to install line filters [4].
It is a requirement for air dryers covered under Aircare that correctly sized Ingersoll Rand pre and afterfilters are installed.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
INSTALLATION / HANDLING
60Hz
UP6 40
UP6 50PE
125
(8.5)
115
(7.9)
208
(5.89)
UP6 50PEI
150
(10.3)
140
(9.6)
201
(5.70)
200
(13.8)
190
(13.1)
167
(4.73)
60Hz UP6 40
HF50–PE EP50–PE HP50–PE HXP50–PE
COMPRESSOR 115 125 150 200 115 125 150 200
Maximum operating pressure psig (barg)
Factory set reload pressure psig (barg)
Flow rate cfm (m3/min)
115
(8.0)
105
(7.2)
188
(5.32)
125
(8.5)
115
(7.9)
185
(5.24)
150
(10.3)
140
(9.6)
170
(4.81)
200
(13.8)
190
(13.1)
143
(4.05)
115
(8.0)
105
(7.2)
212
(6.02)
15
Maximum airend discharge temperature
Ambient operating temperature min. max.
MOTOR
Motor enclosure ODP TEFC ODP TEFC Nominal power 40HP 50HP Speed 1775 RPM 1775 RPM Frame 324T 324T 326T 326T Insulation class F
COOLING SYSTEM – Air cooled
Cooling air flow 3100 ft3/min (87.8m3/min) 3900 ft3/min (110m3/min) Dryer cooling air flow 1200 ft3/min (34m3/min) Maximum P in air ducts 0.5 inWg (12.7mmH2O) (not recommended for dryer openings) Compressed air outlet T
Cooling air outlet T
Dryer cooling air outlet T
GENERAL DATA
Residual coolant content 3ppm (3 mg/m3) Separator vessel capacity 3.7 US gallons (14 liters) Coolant capacity 5.5 US gallons (21 liters) Sound pressure level to
CAGI–PNEUROP
(Non–dryer unit) Weight – base mount unit 2326 lbs
Weight – dryer option unit 2576 lbs
36 F(+2 C ) ? 105 F(+40 C) 36 F(+2 C ) ? 115 F(+46 C)
15 F (8.3 C) 15 F (8.3 C)
40 F (22 C) 42 F (23 C)
69 dB(A) 69 dB(A)
(1055 kg)
(1168 kg)
2436 lbs
(1105 kg)
2686 lbs
(1218 kg)
216 F (102 C)
11 F (6 C)
2384 lbs
(1081 kg)
2634 lbs
(1194 kg)
2476 lbs
(1123 kg)
2726 lbs
(1236 kg)
CAUTION 230/460 Dual voltage machines are fitted with a decal to advise the correct supply voltage as connected from the factory.
Factory units wired for 230V supply can be re–wired to 460V supply voltage by re–wiring the main drive motor and the fan motor as shown on the electrical schematic AND by replacing the fan motor starter CCN 22395800 - 50HP with CCN 22395792
- 50 HP (shipped loose). The main motor overload and the fan motor starter overload settings should be adjusted accordingly –
reference the IEC decal mounted inside the starter door. Also, the transformer primary voltage connections will need to be re–wired for the new supply voltage.
Re–wiring should only be effected by a competent Electrician.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
16
COMPRESSOR 115 125 150 200 115 125 150 200
Maximum operating pressure psig (barg)
Factory set reload pressure psig (barg)
Flow rate cfm (m3/min)
INSTALLATION / HANDLING
60Hz UP6 30E–HA UP6 40–HA
125
(8.5)
115
(7.9)
125
(3.54)
150
(10.3)
140
(9.6)
112
(3.17)
200
(13.8)
190
(13.1)
92
(2.61)
115
(8.0)
105
(7.2)
188
(5.32)
125
(8.5)
115
(7.9)
185
(5.24)
150
(10.3)
140
(9.6)
170
(4.81)
(13.8)
(13.1)
(4.05)
200
190
143
Maximum airend discharge temperature
Ambient operating temperature min. →max.
MOTOR
Motor enclosure ODP TEFC ODP TEFC Nominal power 30HP 40HP Speed 1775 RPM Frame 324T 324T 326T 326T Insulation class F
COOLING SYSTEM – Air cooled
Cooling air flow 3100 ft3/min (87.8m3/min) 3900 ft3/min (110m3/min) Dryer cooling air flow 1200 ft3/min (34m3/min) Maximum P in air ducts 0.5 inWg (12.7mmH2O) (not recommended for dryer openings) Compressed air outlet ∆T
Cooling air outlet ∆T
Dryer cooling air outlet ∆T
GENERAL DATA
Residual coolant content 3ppm (3 mg/m3) Separator vessel capacity 3.7 US gallons (14 liters) Coolant capacity 5.5 US gallons (21 liters) Sound pressure level to
CAGI–PNEUROP
(Non–dryer unit) Weight – base mount unit 2326 lbs
(1055 kg)
Weight – dryer option unit 2576 lbs
(1167 kg)
40_F (22_C) 42_F (23_C)
69 dB(A) 69 dB(A)
2436 lbs
(1105 kg)
2686 lbs
(1218 kg)
216_F (102_C)
36_F(+2_C ) 122_F(+50_C)
15_F (8.3_C)
11_F (6_C)
2384 lbs
(1081 kg)
2634 lbs
(1194 kg)
2476 lbs
(1123 kg)
2726 lbs
(1236 kg)
CAUTION 230/460 Dual voltage machines are fitted with a decal to advise the correct supply voltage as connected from the factory.
Factory units wired for 230V supply can be re–wired to 460V supply voltage by re–wiring the main drive motor and the fan motor as shown on the electrical schematic AND by replacing the fan motor starter CCN 22395800 - 50 HP with CCN 22395792 -
50 HP (shipped loose). The main motor overload and the fan motor starter overload settings should be adjusted accordingly –
reference the IEC decal mounted inside the starter door. Also, the transformer primary voltage connections will need to be re–wired for the new supply voltage.
Re–wiring should only be effected by a competent Electrician.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
INSTALLATION / HANDLING
DRYER OPTION TECHNICAL INFORMATION 60Hz General
Refrigerant type R404A Refrigerant charge
kg (lbs)
Refrigerant oil Emkarate RL32CF or Texaco Capella HFC32
Control settings
Hot gas setting barg (psig)
High pressure switch setting barg (psig)
Fan pressure switch setting on/off barg (psig)
Performance
(2) (3)
Dew point temperature at rated conditions and flow
(3)
30 / 40HP 50HP
41_F (5_C)
(4)
1.8 (0.84)
72 – 74 (5.0 – 5.1)
425 (29.3)
225 / 175 (15.5 / 12.1)
17
50_F (10_C)
Maximum P across dryer barg (psig)
(1)
In accordance with PNEUROP PN8NTC2.3
(2)
In accordance with ISO 7183 at the modified rated conditions.
(3)
60Hz machines: 85_F ambient, 125 psig inlet.
(4)
40hp 200v unit dewpoint is 50_F (10_C)
2.2 (0.15) 3.0 (0.21)
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
18
ELECTRICAL DATA – ALL UNITS SSR UP6–40 Standard voltage 200V 230V 380V 460V 575V PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC Power (nominal) 40HP Full load current at maximum
pressure
Full load current at maximum pressure with dryer option
Starting current FV (STAR) 706.1 (264.5) 614 (230) 367 (135.2) 307 (115) 245.6 (92) Starting current FV (STAR)
with dryer option
Starting time FV (STAR) 3–5 Sec (7–10 Sec) Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC Minimum fuse rating
See note 1
Minimum fuse rating with dryer option See note 1
Minimum wire size AWG See note 2
INSTALLATION / HANDLING
136.0A 125.6A 118.3A 109.2A 71.6A 66.1A 59.2A 54.6A 47.3A 43.7A
143.7A 133.3A 125.2A 116.1A 62.5A 57.9A
744.4 (302.5) 652 (268) 323 (131)
175A 150A 100A 90A 75A 60A
200A 175A 175A 150A 80A 75A
4/0 3/0 2 3 4
ELECTRICAL DATA – ALL UNITS SSR UP6 50PE, UP6 50PEI, HF50–PE, EP50–PE, HP50–PE and HXP50–PE Standard voltage 200V 230V 380V 460V 575V PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC Power (nominal) 50HP Full load current at maximum
pressure
Full load current at maximum pressure with dryer option
Starting current FV (STAR) 876.3 (321.2) 762 (279.3) 461 (169.0) 381 (139.7) 304.8 (111.7) Starting current FV (STAR)
with dryer option
Starting time FV (STAR) 3–5 Sec (7–10 Sec) Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC Minimum fuse rating
See note 1
Minimum fuse rating with dryer option See note 1
Minimum wire size AWG See note 2
170.8A 160.0A 148.5A 139.1A 89.8A 82.2A 74.2A 67.9A 59.4A 55.7A
155.4A 146.0A 77.5A 71.2A
800 (317) 397 (156)
225A 200A 200A 175A 110A 110A 100A 90A 75A 70A
200A 200A 100A 90A
250 4/0 1 2 3
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
INSTALLATION / HANDLING
ELECTRICAL DATA – ALL UNITS SSR UP6–40–HA Standard voltage 200V 230V 380V 460V 575V PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC Power (nominal) 40HP Full load current at maximum
pressure
Full load current at maximum pressure with dryer option
Starting current FV (STAR) 706 (265) 617 (231) 374 (140) 309 (115) 247 (93) Starting current FV (STAR)
with dryer option
Starting time FV (STAR) 3–5 Sec (7–10 Sec) Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC Minimum fuse rating
See note 1
Minimum fuse rating with dryer option See note 1
Minimum wire size AWG See note 2
136.0A 128.3A 119.0A 111.5A 71.6A 65.1A 59.5A 56.9A 47.6A 44.7A
123.5A 116.0A 61.7A 58.1A
652 (268) 323 (131)
175A 150A 90A 75A 60A
175A 150A 80A 75A
4/0 3/0 2 3 4
19
ELECTRICAL DATA – ALL UNITS SSR 30E–HA Standard voltage 200V 230V 380V 460V 575V PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC Power (nominal) 30HP Full load current at maximum
pressure
Full load current at maximum pressure with dryer option
Starting current FV (STAR) 567 (212.4) 493.2 (184.8) 298.5 (111.8) 246.6 (92.4) 197.3 (73.9) Starting current FV (STAR)
with dryer option
Starting time FV (STAR) 3–5 Sec (7–10 Sec) Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC Minimum fuse rating
See note 1
Minimum fuse rating with dryer option See note 1
Minimum wire size AWG See note 2
109.2A 100.9A 95.0A 87.8A 57.5A 53.1A 47.5A 43.9A 38.0A 38.3A
99.5A 92.3A 49.7A 46.1A
516.6 (193.5) 258 (96.7)
150A 125A 125A 125A 75A 75A 60A 60A 50A 50A
150A 150A 75A 75A
3/0 1/0 3 4 6
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
20
INSTALLATION / HANDLING
1. If a circuit breaker is selected it should only be a magnetic trip type, set above the anticipated starting current of the machine, but below the maximum prospective fault current for the circuit. The circuit breaker or fuseable disconnect must be capable of breaking the prospective
fault current at its terminals.
2. PVC/PVC Type Calculated using the following conditions:
i) PVC insulated cable, armoured, copper conductors. ii) Cable clipped to a wall, in free air. iii) Ambient temperature of 104_F (40_C) and relative humidity of 40%. iv) 65ft (20m) cable run. v) Volt drop limited to –10% during starting, –5% during normal running. vi) Protected by the circuit breaker listed above.
If there are any deviations from the above, or special regulations apply, the installation must be planned by a competent, qualified engineer.
NOTE
All data applies to standard product only.
ELECTRICAL DATA
An independent electrical isolator or disconnect should be installed adjacent to the compressor.
Feeder cables/wires should be sized by the customer/electrical contractor to ensure that the circuit is balanced and not overloaded by other electrical equipment. The length of wiring from a suitable electrical feed point is critical as voltage drops may impair the performance of the compressor.
Feeder cables / wires connections to isolator or disconnect should be tight and clean.
The applied voltage must be compatible with the motor and compressor data plate ratings.
The control circuit transformer has different voltage tappings. Ensure that these are set for the specific applied voltage prior to starting.
CAUTION
Never test the insulation resistance of any part of the machines electrical circuits, including the motor without completely
disconnecting the electronic controller (where fitted).
CAUTION
Ensure that the motor, blower and dryer fan rotate in the correct direction as indicated by direction arrows, and on drawing.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – GENERAL
21
GENERAL OPERATION
The compressor is an electric motor driven, single stage screw compressor, complete with accessories piped, wired and baseplate mounted. It is a totally self contained air compressor package.
The 40hp compressor packages are designed to operate in an ambient range of 35.6_F – 104_F (2_C to 40_C) with a special option package available to operate in ambient temperatures ranges from 35.6_F up to 124_F (2_C up to 50_C). The maximum temperature is applicable to either version up to a maximum elevation of 3280ft (1000m) above sea level. Above this altitude significant reduction in maximum allowable ambient temperature is required.
The 50 hp package is designed for a 115_F (46_C) maximum ambient.
Compression in the screw type air compressor is created by the meshing of two (male & female) helical rotors.
The air/coolant mixture discharges from the compressor into the separation system. This system removes all but a few PPM of the coolant from the discharge air. The coolant is returned to the cooling system and the air passes through the aftercooler and out of the compressor.
Cooling air is moved through the coolers by the cooling fan and discharged from the machine.
CAUTION
Cooling air is drawn in at the end of the machine package passing through the filter and cooler before being discharged from the top of the machine. Care should be taken to avoid blocking the airflow, or causing any restriction in excess of the maximum backpressure allowed for ducting.
Do not direct the airflow at face or eyes.
The power transmission from the drive motor to the airend male rotor is by pulley and belts. The constant auto tensioning system, using airend mass torque and gas arm, ensures that the belts are always under the correct tension, eliminating the need for adjustment and maximizing the life of the belts.
By cooling the discharge air, much of the water vapour naturally contained in the air is condensed and may be drained from the downstream piping and equipment.
The coolant system consists of a sump, cooler, thermostatic valve and a filter. When the unit is operating, the coolant is pressurized and forced to the compressor bearings.
The compressor load control system is automatic on–off line. The compressor will operate to maintain a set discharge line pressure and is provided with an auto restart system for use in plants where the air demand varies sufficiently to allow a compressor to shut down and save power. Significant system volume will assist this and is recommended.
With the dryer option, the dryer will run continuously when the compressor is automatically off line.
WARNING
When the unit stops running as the result of low air demand, normally indicated by auto restart light, it may restart and return to load at any time.
Safety of operation is provided as the compressor will shut down if excessive temperatures or electrical overload conditions should occur.
CAUTION
This unit is not designed or intended to operate when contaminated with silicone. Lubricants, greases or other items containing silicone should not be used on this unit.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
22
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
1. PRESSURE GAUGE
Indicates the system pressure.
WARNING
DO NOT operate the compressor at discharge pressures
exceeding the maximum operating pressure.
2. HOURMETER
Records the total running time of the compressor.
3. EMERGENCY STOP
When depressed will stop the compressor immediately. The ’Power on’ indicator will remain illuminated. The emergency stop button must be released before the compressor can be restarted.
4. START/STOP
When switched to the ON position will cause the unit to start and run in a loaded condition if there is a demand for air. If there is no demand, the machine will run unloaded before stopping automatically.
When switched to the OFF position, will unload and stop the unit if it is running. If the unit is in auto restart it will prevent the unit from re–starting when there is a demand for air.
5. POWER ON (Green)
Indicates the presence of control voltage at the controller.
6. AUTO RESTART (White)
Will illuminate when the machine has shut-down due to low air demand. The machine will restart and load automatically as soon as the demand for air returns.
7. FAULT / HIGH AIR TEMPERATURE ALARM (Red)
Turn off electrical Isolator or disconnect. Investigate cause of fault.
8. RESET BUTTON
Press button to reset the control system following compressor trip.
9. DEW POINT INDICATOR (Dryer Option)
Green indicates good dew point. Red indicates dew point above
65_F (18_C) and blue indicates freezing.
PRIOR TO STARTING
1. Make visual check of the machine, ensure that all guards secure and that nothing is obstructing the proper ventilation of, or free access to the machine.
2. Check coolant level. Add if necessary.
3. Make sure main discharge valve is open.
4. Turn on electrical isolator or disconnect. The Power on (5) indicator will light, indicating that line and control voltages are available.
5. Check direction of rotation at initial start or following interruption in power supply.
WARNING
Make sure that all protective covers are in place. Cooling air flow exhaust may contain flying debris. Safety
Protection should be worn at all times to avoid injury.
STARTING
1. Push the RESET button (8). The fault indicator (7) will extinguish. Switch the ON/OFF switch (4) to the ON position. The compressor will start and then load automatically.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
23
NORMAL/EMERGENCY STOPPING
1. Switch the ON/OFF switch (4) to the OFF position. The compressor will unload and stop.
2. Press EMERGENCY STOP button (3) and the compressor will stop immediately.
3. Turn off electrical isolator or disconnect.
CAUTION
After shutdown never allow unit to stand idle with pressure in receiver/separator system.
For customers that have interruptions in their incoming power supply to the compressor and must maintain an uninterrupted supply of compressed air, the Power Outage Restart Option allows a compressor to restart automatically 10 seconds (adjustable) after incoming power is restored.
FUNCTION TEST
To test the operation of the Power Outage Restart Option:
1. Slowly open the main isolation valve.
2. Start the compressor.
3 The compressor will load automatically if there is sufficient demand for air. Allow the compressor to load.
4. Open the main disconnect to remove power from the compressor.
5. Close the main disconnect to reapply power to the compressor. The horn will sound for ten seconds; then the compressor will start automatically.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
24
FULL VOLTAGE WIRING SCHEMATIC
SEE NOTES 1 & 2
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
DRYER OPTION
LEGEND
CPT Transformer EDV Valve, electric drain ES Switch, emergency stop FOL Overload, internal fan (option) 1FU Fuse, secondary voltage 2FU, 3FU Fuses, primary voltage 4FU,
5FU, 6FU
HATR Relay, high air temperature HATR
1,2,3
HATS Switch, high air temperature. HM Hourmeter 1LT Light, power on indicator (Green) 2LT Light, auto restart indicator (White) 3LT Fault indicator light (Red)
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
Fuses, dryer fan (option)
Contacts, relay – HATR
DRYER OPTION
1M Contactor, main
1Ma, b Contacts, aux. main contactor
3M Contactor, dryer compressor (option) 4M Contactor, dryer fan (option) MMS Starter & overload, fan motor MMSa Contact, fan motor overload MOD Modulation control option 1MTR Motor, compressor 2MTR Motor, fan 3MTR Motor, dryer compressor (option) 4MTR Motor, dryer fan (option) OL Overload, main motor OLa Contact, main motor overload
3OL
Overload, dryer compressor (option)
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
LEGEND
1PS Switch, pressure 1RPS Switch, high refrigerant pressure (option) 2RPS Switch, fan pressure (option) RST Switch, reset 1SV Valve, solenoid (load) N.C. 3SV Valve, solenoid (blowdown) N.O. 5SV Valve, solenoid (modulation option) 6SV Valve, solenoid (modulation option) S1 Switch, selector (modulation option) SS Switch, selector Off/On
TDR1
TDR1a Contact, relay – timed TDR1b Contact, relay – instant TR Relay, restart, time delay (6 min) TRa Contact, relay
Relay timed delay (10 sec.)
25
VAR Varistor
Barrier terminal strip
NOTES
1. Approved fused disconnect or circuit breaker per N.E.C. requirements must be provided by customer.
2. Dashed lines represent wiring by customer.
3. Sizing of electrical components not supplied by Ingersoll Rand is the responsibility of the customer and should be done in accordance with the information on the compressor data plate
N.E.C. and local electrical codes.
4.. When changing the supply voltage, ensure that: a) The motor and the transformer are rewired for the new voltage
b) The motor overload is adjusted to the proper setting.
5. Verify actual motor conditions with motor schematic.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
26
DRYER OPTION
DRYER OPTION
SEE NOTES 1 & 2
STAR – DELTA WIRING SCHEMATIC
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
LEGEND
CPT Transformer EDV Valve, electric drain ES Switch, emergency stop FOL Overload, internal fan (option) 1FU Fuse, secondary voltage 2FU, 3FU Fuses, primary voltage 4FU,
5FU, 6FU
HATR Relay, high air temperature HATR
1,2,3
HATS Switch, high air temperature. HM Hourmeter 1LT Light, power on indicator (Green) 2LT Light, auto restart indicator (White) 3LT Fault indicator light (Red) 1M Contactor, main
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
Fuses, dryer fan (option)
Contacts, relay – HATR
1Ma, b, c Contacts, aux. main contactor
2M Contactor, delta 2Ma, b Contacts, aux. delta contactor 3M Contactor, dryer compressor (option) 4M Contactor, dryer fan (option) MMS Starter & overload, fan motor MMSa Contact, fan motor overload MOD Modulation control option 1MTR Motor, compressor 2MTR Motor, fan 3MTR Motor, dryer compressor (option) 4MTR Motor, dryer fan (option)
3OL
OL Overload, main motor OLa Contact, main motor overload
Overload, dryer compressor (option)
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
LEGEND
1PS Switch, pressure 1RPS Switch, high refrigerant pressure (option) 2RPS Switch, fan pressure (option) RST Switch, reset S1 Switch, selector (modulation option) 1S Contactor, star 1Sa, b Contacts, aux. star contactor SS Switch, selector Off/On 1SV Valve, solenoid (load) N.C. 3SV Valve, solenoid (blowdown) N.O. 5SV Valve, solenoid (modulation option) 6SV Valve, solenoid (modulation option)
TD Relay, delta starting (10 sec.) TDa Relay, delay off contact
TDR1
TDR1a Contact, relay – timed
Relay timed delay (10 sec.)
27
TDR1b Contact, relay – instant TR Relay, restart, time delay (6 min) TRa Contact, relay VAR Varistor
Barrier terminal strip
NOTES
1. Approved fused disconnect or circuit breaker per N.E.C. requirements must be provided by customer.
2. Dashed lines represent wiring by customer.
3. Sizing of electrical components not supplied by Ingersoll Rand is the responsibility of the customer and should be done in accordance with the information on the compressor data plate
N.E.C. and local electrical codes.
4.. When changing the supply voltage, ensure that: a) The motor and the transformer are rewired for the new voltage
b) The motor overload is adjusted to the proper setting.
5. Verify actual motor conditions with motor schematic.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
28
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
CONTROL PIPING DIAGRAM
10
1
R
P
A
2
6
3
8
6
13
4
6
11
12
9
7
8
14
13
6
18
6
22250039 Revision F 09/06
KEY
1. Pressure gauge
2. Pressure switch
3. Tee
4. Connector
5. Moisture separator
6. Elbow
7. Tee, male run
8. Reducer bushing
9. Blow down solenoid valve
10.Load solenoid valve
11.Indicator air filter
ADAPTER INTO
15
5
A
A
B
THIS PORT
PLUG INTO
THIS PORT
12.Nipple
13.Adaptor
14.Intake valve assembly
15.Separator tank
16.Tee
17.Valve
18.Plug
17.Valve
NOTES:
A. Tubing 3/8 inch B. Tubing 1/4 inch
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
Loading...
+ 178 hidden pages