Ingersoll-Rand EP50-PE, SSR UP6 50PEI HF50-PE, SSR UP6 40, HP50-PE, HXP50-PE, SSR UP6 50PE User Manual
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI
HF50–PE, EP50–PE, HP50–PE, HXP50–PE
60Hz
This manual contains
important safety information
and must be made available
to personnel who operate and
maintain this machine.
OPERATION AND MAINTENANCE MANUAL
C.C.N.:
REV.: A
DATE: OCTOBER 2008
80445190
AIR COMPRESSOR GROUP
BONDED WARRANTY & REGISTERED START UP
Warranty
The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in
material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen
months from the date of shipment from the factory, whichever shall first occur. The Purchaser shall be obligated to
promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the
Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement
part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment
in accordance with good industry practices and has complied with specific recommendations of the Company.
Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the
manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company shall
not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the
Purchaser or others without Company‘s prior written approval.
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are
limited to those specifically stated within the Company‘s proposal. Unless responsibility for meeting such performance
warranties are limited to specified tests, the Company‘s obligation shall be to correct in the manner and for the period
of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time
provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on
contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company
in writing of its intention to do so. Any such use of Equipment will be at Purchaser‘s sole risk and liability.
Note that this is Ingersoll Rand standard warranty. Any warranty in force at the time of purchase of the compressor
or negotiated as part of the purchase order may take precedence over this warranty.
Register on–line at http://air.ingersollrand.com
Ingersoll Rand Air Solutions Group
Global Aftermarket Division
800–B Beaty Street
Davidson, NC 28036
1–800–526–3615
CONTENTS & ABBREVIATIONS
1
CONTENTS
1CONTENTS
2FOREWORD
3DECALS
8SAFETY
10GENERAL INFORMATION
12INSTALLATION / HANDLING
OPERATING INSTRUCTIONS
21– GENERAL
22– ELECTRO–PNEUMATIC
29– INTELLISYS
40MAINTENANCE
47TROUBLE SHOOTING
ABBREVIATIONS & SYMBOLS
####Contact Ingersoll Rand for serial number
–>#### Up to Serial No.
####–> From Serial No.
*Not illustrated
{Option
NRNot required
ARAs required
SMSitemaster/Sitepack
HAHigh ambient machine
WCWatercooled machine
ACAircooled machine
ERSEnergy recovery system
T.E.F.C. Totally enclosed fan cooled motor (IP55)
O.D.P.Open drip proof (motor)
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PEhttp://air.ingersollrand.com
2
FOREWORD
The contents of this manual are considered to be proprietary and
confidential to Ingersoll Rand and should not be reproduced without
the prior written permission of Ingersoll Rand.
Nothing contained in this document is intended to extend any
promise, warranty or representation, expressed or implied, regarding
the Ingersoll Rand products described herein. Any such warranties or
other terms and conditions of sale of products shall be in accordance
with the standard terms and conditions of sale for such products, which
are available upon request.
This manual contains instructions and technical data to cover
routine operation and scheduled maintenance tasks by operation and
maintenance staff. Major overhauls are outside the scope of this
manual and should be referred to an authorised Ingersoll Rand service
department.
The design specification of this machine has been certified as
complying with E.C. directives. Any modification to any part is
absolutely prohibited and would result in the CE certification and
marking being rendered invalid.
All components, accessories, pipes and connectors added to the
compressed air system should be:
. of good quality, procured from a reputable manufacturer and,
wherever possible, be of a type approved by Ingersoll Rand.
. clearly rated for a pressure at least equal to the machine maximum
allowable working pressure.
. compatible with the compressor lubricant/coolant.
. accompanied with instructions for safe installation, operation and
maintenance.
Details of approved equipment are available from Ingersoll Rand
Service departments.
The use of non–genuine spare repair parts other than those
included within the Ingersoll Rand approved parts list may create
hazardous conditions over which Ingersoll Rand has no control.
Therefore Ingersoll Rand does not accept any liabilitity for losses
caused by equipment in which non–approved repair parts are installed.
Standard warranty conditions may be affected.
The intended uses of this machine are outlined below and examples
of unapproved usage are also given, however Ingersoll Rand cannot
anticipate every application or work situation that may arise.
IF IN DOUBT CONSULT SUPERVISION.
This machine has been designed and supplied for use only in the
following specified conditions and applications:
. Compression of normal ambient air containing no known or
detectable additional gases, vapours. or particles
. Operation within the ambient temperature range specified in the
GENERAL INFORMATION section of this manual.
The use of the machine in any of the situation types listed in
table 1:–
a) Is not approved by Ingersoll Rand,
b) May impair the safety of users and other persons, and
c) May prejudice any claims made against Ingersoll Rand.
TABLE 1
Use of the machine to produce compressed air for:
a) direct human consumption
b) indirect human consumption, without suitable filtration and purity
checks.
Use of the machine outside the ambient temperature range
specified in the GENERAL INFORMATION SECTION of this manual.
Use of the machine where there is any actual or foreseeable risk of
hazardous levels of flammable gases or vapours.
THIS MACHINE IS NOT INTENDED AND MUST NOT BE
USED IN POTENTIALLY EXPLOSIVE ATMOSPHERES,
INCLUDING SITUATIONS WHERE FLAMMABLE GASES OR
VAPOURS MAY BE PRESENT.
Use of the machine fitted with non Ingersoll Rand approved
components.
Use of the machine with safety or control components missing or
disabled.
Ingersoll Rand reserves the right to make changes and
improvements to products without notice and without incurring any
obligation to make such changes or add such improvements to
products sold previously.
The company accepts no responsibility for errors in translation of
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
DECALS4
POWERINSPECT
Every X months, if sooner than required by
operating hours
CLEAN
CHANGE / REPLACE
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PEhttp://air.ingersollrand.com
DECALS5
ANSI SYMBOLS
GRAPHIC FORM AND MEANING OF ANSI SYMBOLS
DANGER
INTAKE AIR. Can contain carbon monoxide or other contaminants. Will cause serious injury or death. Ingersoll Rand
air compressors are not designed, intended or approved for breathing air. Compressed air should not be used for
breathing air applications unless treated in accordance with all applicable codes and regulations.
WARNING
HAZARDOUS VOLTAGE. Can cause serious injury or death. Disconnect power and bleed pressure from tank before
servicing. Lockout/Tagout machine. Compressor must be connected to properly grounded circuit. See Grounding
Instructions in manual. Do not operate compressor in wet conditions. Store indoors.
RISK OF FIRE OR EXPLOSION. Electrical arcing from compressor components can ignite flammable liquids and
vapors which can result in serious injury. Never operate the compressor near flammable liquids or vapors. If used to
spray flammable materials, keep compressor at least 20ft away from the spray area.
HIGH PRESSURE AIR. Rusted tanks can cause explosion and severe injury or death. Receiver under perssure.
Operator should relieve tank pressure before performing maintenance. In addition to automatic drain, operate manual
drain valve weekly. Manual drain valve located at bottom of the tank.
MOVING PARTS. Can cause serious injury. Do not operate with guards removed. Machine may start automatically.
Disconnect power before servicing. Lockout/Tagout machine.
HOT SURFACES. Can cause serious injury. Do not touch. Allow to cool before servicing. Do not touch hot
compressor or tubing.
EXPOSED MOVING BELTS AND SHEAVES.
Can cause severe injury or death.
Do not operate without guard in place. Disconnect power before servicing.
Lockout/Tagout machine.
http://air.ingersollrand.com
Air flow exhaust may contain flying debris.
Safety protection should be worn at all times.
Pinch point hazard.
Keep hands clear.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
6
60 Hz Units
DECALS – ANSI
VIEW BACK
VIEW FRONT
VIEW LEFT
VIEW RIGHT
INSIDE PACKAGE
INSIDE STARTER DOOR
VIEW TOP
ItemccnQty.DescriptionItemccnQty.Description
1323435191Decal, warning contaminated air
2931665021Decal, replacement filter element
3931664601Decal, coolant drain
Hazard that WILL cause DEATH, SEVERE INJURY or substantial
property damage if ignored. Instructions must be followed precisely to
avoid injury or death.
WARNING!
Hazard that CAN cause DEATH, SEVERE INJURY or substantial
property damage if ignored. Instructions which must be followed
precisely to avoid injury or death.
CAUTIONS!
Cautions call attention to instructions which must be followed
precisely to avoid damaging the product, process or its surroundings.
NOTES
Notes are used for supplementary information.
BREATHING AIR PRECAUTION
Ingersoll Rand air compressors are not designed, intended or
approved for breathing air. Compressed air should not be used for
breathing air applications unless treated in accordance with all
applicable codes and regulations.
General Information
Ensure that the operator reads and understands the decals and
consults the manuals before maintenance or operation.
Ensure that the Operation and Maintenance manual is not removed
permanently from the machine.
Ensure that maintenance personnel are adequately trained,
competent and have read the Maintenance Manuals.
Do not point air nozzles or sprayers toward anyone.
Compressed air and electricity can be dangerous. Before
undertaking any work on the compressor, ensure that the electrical
supply has been isolated and the compressor has been relieved of all
pressure.
Wear eye protection when operating or servicing compressor.
All persons positioned near to operating machinery should be
equipped with hearing protection and given instructions on its use in
accordance with workplace safety legislation.
Make sure that all protective covers are in place and that the
canopy/doors are closed during operation.
The specification of this machine is such that the machine is not
suitable for use in flammable gas risk areas.
Installation of this compressor must be in accordance with
recognised electrical codes and any local Health and Safety Codes.
The use of plastic bowls on line filters can be hazardous. Their
safety can be affected by either synthetic lubricants, or the additives
used in mineral oils. Ingersoll –Rand recommends that only filters with
metal bowls should be used on a pressurised system.
If more than one compressor is connected to one common
downstream plant, effective isolation valves must be fitted and
controlled by work procedures, so that one machine cannot accidently
be pressurised / over pressurised by another.
Compressed air must not be used for a direct feed to any form of
breathing apparatus or mask.
The discharged air contains a very small percentage of compressor
lubricant and care should be taken to ensure that downstream
equipment is compatible.
If the discharged air is to be ultimately released into a confined
space, adequate ventilation must be provided.
When using compressed air always use appropriate personal
protective equipment.
All pressure containing parts, especially flexible hoses and their
couplings, must be regularly inspected, be free from defects and be
replaced according to the Manual instructions.
Compressed air can be dangerous if incorrectly handled. Before
doing any work on the unit, ensure that all pressure is vented from the
system and that the machine cannot be started accidentally.
Avoid bodily contact with compressed air.
All safety valves located in the separator tank must be checked
periodically for correct operation.
Do not over–pressurize the receiver tank or similar vessels beyond
design limits.
Do not use a receiver tank or similar vessels that fail to meet the
design requirements of the compressor. Contact your distributor for
assistance.
Do not drill into, weld or otherwise alter the receiver tank or similar
vessels.
Materials
The following substances are used in the manufacture of this
machine and may be hazardous to health if used incorrectly:
. preservative grease
. rust preventative
. compressor coolant
AVOID INGESTION, SKIN CONTACT AND INHALATION OF
FUMES
Transport
When loading or transporting machines ensure that the specified
lifting and tie down points are used.
Lifting equipment must be properly rated for the weight of the
compressor.
Do not work on or walk under the compressor while it is suspended.
Compressed air
Compressed air can be dangerous if incorrectly handled. Before
doing any work on the unit, ensure that all pressure is vented from the
system and that the machine cannot be started accidentally.
WARNING
Imposing a normal or emergency stop on the compressor will
only relieve presure upstream of the minimum pressure valve on
top of the separator tank.
If maintenance work is required downstream of this valve, ensure
that all pressure is relieved at the process vent point external to
the compressor
Ensure that the machine is operating at the rated pressure and that
the rated pressure is known to all relevant personnel.
All air pressure equipment installed in or connected to the machine
must have safe working pressure ratings of at least the machine rated
pressure.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE, HXP50–PEhttp://air.ingersollrand.com
Electrical
Keep all parts of the body and any hand–held tools or other
conductive objects, away from exposed live parts of the compressor
electrical system. Maintain dry footing, stand on insulating surfaces
and do not contact any other portion of the compressor when making
adjustments or repairs to exposed live parts of the compressor
electrical system.
WARNING
Any electrical connections or adjustments should only be
made by a suitably qualified electrician
Close and lock all access doors when the compressor is left
unattended.
Do not use extinguishers intended for Class A or Class B fires on
electrical fires. Use only extinguishers suitable for class BC or classABC fires.
Attempt repairs only in clean, dry, well lighted and ventilated areas.
Connect the compressor only to electrical systems that are
compatible with its electrical characteristics and that are within it’s rated
capacity.
Condensate disposal
As waste water regulations vary by country and region it is the
responsibility of the user to establish the limitations and regulations in
their particular area. Ingersoll Rand and its associated distributors are
happy to advise and assist in these matters.
For further information, consult Material Data Sheets
for ULTRA Coolant.
SAFETY
9
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE, HP50–PE,
HXP50–PE
10
http://air.ingersollrand.com
GENERAL INFORMATION
PIPING AND INSTRUMENTATION – Electro–pneumatic and Intellisys Units
36
37
41
M
38
40
39
28
20
DRYER
OPTION
27
35
11
10
P
27
29
23
9
34
31
8
30
KEY
22
1
22292783
Rev F
3
21
2
5
M
4
12
16
26
INTELLISYS (OPTION)
REPLACES ITEM 12
13
19
33
17
T
6
18
15
7
24
25
INTELLISYS (OPTION)
REPLACES ITEMS 10 & 11
14
T
32
MODULATION (OPTION)
PIPING LEGEND
A
B
C
D
E
F
G
1. Filter, air
2. Valve, inlet
3. Valve, solenoid (load)
4. Airend assembly
5. Motor
6. Tank, separator
7. Separator elements
8. Valve, minimum pressure
9. Aftercooler
10.Gauge, pressure
11.Switch, discharge pressure
12.Switch, temperature
13.Filter, coolant
14.Thermostat
15.Cooler
16 Relay, overload, Motor
17.Valve, safety
18.Valve, drain
19.Screen, scavenge
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
20 Valve, solenoid (blowdown)
21.Orifice
22 Indicator, air restriction
23.Electric drain valve (EDV – condensate)
24.Valve solenoid (line/sump), Intellisys Option
25.Transducer pressure, Intellisys Option, replaces 10 and 11
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
http://air.ingersollrand.com
KEY
INSTALLATION / HANDLING
13
APre filter
BCompressor and cooling air intake
CStarter box
DCooling air exhaust
E1.5” NPT air discharge
FCustomer power inlet
GFork lift openings
(Fork lift hole covers must be installed after unit is in place to
reduce noise and ensure proper cooling of package)
NOTES
1. Coolant (lubricant) fill quantity (approximate) 5.5 US gallons
(21 litres).
2. Recommended clearance in front of control panel door 42 inches
(1067 mm) or minimum as required by the latest national electrical
codes (NEC) or applicable local codes.
3. Recommended clearances on left and right sides 36 inches
(914mm).
4. Minimum recommended clearance for the rear of the compressor
is to be 6 inches (152mm).
5. External piping shall not exert any unresolved moments or forces
on the unit. Use pipe size as large or larger at discharge connection.
6. There should be no plastic or pvc piping attached to this unit or used
for any lines downstream.
7. Any field installed ducting to and from the compressor cannot add
more than 1/2 inch (12.5mm) water gauge total air resistance.
Ducting is not recommended for the dryer cooling air inlet and outlet
openings.
8. Do not pipe into a common header with a reciprocating compressor,
unless the reciprocating compressor utilizes a discharge pulsation
damper.
9. Sizing of electrical components not supplied by Ingersoll Rand is
the responsibility of the customer and should be done in accordance
with the information on the compressor data plate and national and
local electrical codes.
H .25 Inch female NPT moisture separator drain.
J Emergency stop button
K Primary compressor service door
L 4 holes, 0.67 Inch (17mm) diameter
M 4 holes, 0.47 Inch (12mm) diameter
N Dryer cooling air intake
NOTE
All dimensions are in millimetres (inches) unless otherwise stated.
Ensure that the correct fork lift truck slots or marked lifting points are
used whenever the machine is lifted or transported.
UNPACKING
The compressor will normally be delivered with a polythene cover.
If a knife has to be used to remove this cover ensure that the exterior
paintwork of the compressor is not damaged.
Ensure that all transport and packing materials are discarded in a
manner prescribed by local codes.
NOTE
Units are shipped with transit locking bolt in place. Prior to
running the unit the shipping bolt must be removed and the belt
tension checked. Loosen, remove and discard 10mm shipping
bolt. For belt tensioning procedure refer to Maintenance section.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
14
INSTALLATION / HANDLING
1
4
2
T5750
Revision 02
07/04
KEY
1. Compressor
2. Air Dryer
3. Air Receiver
4. Compressed air filters
5. System demand points
NOTE
Items [2] to [5] are optional or may be existing items of plant. Refer
to your Ingersoll Rand distributor / representative for specific
recommendations.
LOCATION IN THE PLANT
Note:
Ensure that the unit is wired for proper voltage before installation.
4
3
CAUTION
The use of plastic bowls on line filters and other plastic air line
components can be hazardous. Their safety can be affected by
either synthetic coolants or the additives used in mineral oils.
Ingersoll Rand recommends that only filters with metal bowls
should be used on any pressurised system.
CAUTION
Before starting machine remove shipping bolt and discard
CAUTION
The standard compressor unit is not suitable for operation in
temperatures liable to cause freezing as Condensate water is
liable to be produced in the after cooler and receiver where fitted.
Refer to your Ingersoll Rand distributor for further information.
5
The compressor can be installed on any level floor capable of
supporting it. A dry, well ventilated area where the atmosphere is clean
is recommended. A minimum of 6 inches (150mm) should be left at the
rear and 3ft (1m) at the sides of the machine for adequate service
access and ventilation.
Adequate clearance needs to be allowed around and above the
machine to permit safe access for specified maintenance tasks.
Ensure that the machine is positioned securely and on a stable
foundation. Any risk of movement should be removed by suitable
means, especially to avoid strain on any rigid discharge piping.
CAUTION
Screw type compressors [1] should not be installed in air
systems with reciprocating compressors without means of
isolation such as a common receiver tank. It is recommended that
both types of compressor be piped to a common receiver using
individual air lines.
DISCHARGE PIPING
Discharge piping should be at least as large as the discharge
connection of the compressor. All piping and fittings should be suitably
rated for the discharge pressure.
It is essential when installing a new compressor [1], to review the
total air system. This is to ensure a safe and effective total system. One
item which should be considered is liquid carryover. Installation of air
dryers [3] is always good practice since properly selected and installed
they can reduce any liquid carryover to zero.
It is good practice to locate an isolation valve close to the
compressor and to install line filters [4].
It is a requirement for air dryers covered under Aircare that correctly
sized Ingersoll Rand pre and afterfilters are installed.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
http://air.ingersollrand.com
INSTALLATION / HANDLING
60Hz
UP640
UP6 50PE
125
(8.5)
115
(7.9)
208
(5.89)
UP6 50PEI
150
(10.3)
140
(9.6)
201
(5.70)
200
(13.8)
190
(13.1)
167
(4.73)
60HzUP6 40
HF50–PEEP50–PEHP50–PEHXP50–PE
COMPRESSOR115125150200115125150200
Maximum operating pressure
psig (barg)
Factory set reload pressure
psig (barg)
Flow rate
cfm (m3/min)
115
(8.0)
105
(7.2)
188
(5.32)
125
(8.5)
115
(7.9)
185
(5.24)
150
(10.3)
140
(9.6)
170
(4.81)
200
(13.8)
190
(13.1)
143
(4.05)
115
(8.0)
105
(7.2)
212
(6.02)
15
Maximum airend discharge
temperature
Ambient operating
temperature
min.max.
MOTOR
Motor enclosureODPTEFCODPTEFC
Nominal power40HP50HP
Speed1775 RPM1775 RPM
Frame324T324T326T326T
Insulation classF
COOLING SYSTEM – Air cooled
Cooling air flow3100 ft3/min (87.8m3/min)3900 ft3/min (110m3/min)
Dryer cooling air flow1200 ft3/min (34m3/min)
Maximum ∆ P in air ducts0.5 inWg (12.7mmH2O) (not recommended for dryer openings)
Compressed air outlet ∆T
Cooling air outlet ∆T
Dryer cooling air outlet ∆T
GENERAL DATA
Residual coolant content3ppm (3 mg/m3)
Separator vessel capacity3.7 US gallons (14 liters)
Coolant capacity5.5 US gallons (21 liters)
Sound pressure level to
CAGI–PNEUROP
(Non–dryer unit)
Weight – base mount unit2326 lbs
Weight – dryer option unit2576 lbs
36 F(+2 C ) ? 105 F(+40 C)36 F(+2 C ) ? 115 F(+46 C)
15 F (8.3 C)15 F (8.3 C)
40 F (22 C)42 F (23 C)
69 dB(A)69 dB(A)
(1055 kg)
(1168 kg)
2436 lbs
(1105 kg)
2686 lbs
(1218 kg)
216 F (102 C)
11 F (6 C)
2384 lbs
(1081 kg)
2634 lbs
(1194 kg)
2476 lbs
(1123 kg)
2726 lbs
(1236 kg)
CAUTION
230/460 Dual voltage machines are fitted with a decal to advise
the correct supply voltage as connected from the factory.
Factory units wired for 230V supply can be re–wired to 460V
supply voltage by re–wiring the main drive motor and the fan
motor as shown on the electrical schematic AND by replacing
the fan motor starter CCN 22395800 - 50HP with CCN 22395792
- 50 HP (shipped loose). The main motor overload and the fan
motor starter overload settings should be adjusted accordingly –
reference the IEC decal mounted inside the starter door. Also,
the transformer primary voltage connections will need to be
re–wired for the new supply voltage.
Re–wiring should only be effected by a competent Electrician.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
16
COMPRESSOR115125150200115125150200
Maximum operating pressure
psig (barg)
Factory set reload pressure
psig (barg)
Flow rate
cfm (m3/min)
INSTALLATION / HANDLING
60HzUP6 30E–HAUP6 40–HA
125
(8.5)
115
(7.9)
125
(3.54)
150
(10.3)
140
(9.6)
112
(3.17)
200
(13.8)
190
(13.1)
92
(2.61)
115
(8.0)
105
(7.2)
188
(5.32)
125
(8.5)
115
(7.9)
185
(5.24)
150
(10.3)
140
(9.6)
170
(4.81)
(13.8)
(13.1)
(4.05)
200
190
143
Maximum airend discharge
temperature
Ambient operating
temperature
min. →max.
MOTOR
Motor enclosureODPTEFCODPTEFC
Nominal power30HP40HP
Speed1775 RPM
Frame324T324T326T326T
Insulation classF
COOLING SYSTEM – Air cooled
Cooling air flow3100 ft3/min (87.8m3/min)3900 ft3/min (110m3/min)
Dryer cooling air flow1200 ft3/min (34m3/min)
Maximum ∆P in air ducts0.5 inWg (12.7mmH2O)(not recommended for dryer openings)
Compressed air outlet ∆T
Cooling air outlet ∆T
Dryer cooling air outlet ∆T
GENERAL DATA
Residual coolant content3ppm (3 mg/m3)
Separator vessel capacity3.7 US gallons (14 liters)
Coolant capacity5.5 US gallons (21 liters)
Sound pressure level to
CAGI–PNEUROP
(Non–dryer unit)
Weight – base mount unit2326 lbs
(1055 kg)
Weight – dryer option unit2576 lbs
(1167 kg)
40_F (22_C)42_F (23_C)
69 dB(A)69 dB(A)
2436 lbs
(1105 kg)
2686 lbs
(1218 kg)
216_F (102_C)
36_F(+2_C ) → 122_F(+50_C)
15_F (8.3_C)
11_F (6_C)
2384 lbs
(1081 kg)
2634 lbs
(1194 kg)
2476 lbs
(1123 kg)
2726 lbs
(1236 kg)
CAUTION
230/460 Dual voltage machines are fitted with a decal to advise
the correct supply voltage as connected from the factory.
Factory units wired for 230V supply can be re–wired to 460V
supply voltage by re–wiring the main drive motor and the fan
motor as shown on the electrical schematic AND by replacing
the fan motor starter CCN 22395800 - 50 HP with CCN 22395792 -
50 HP (shipped loose). The main motor overload and the fan
motor starter overload settings should be adjusted accordingly –
reference the IEC decal mounted inside the starter door. Also,
the transformer primary voltage connections will need to be
re–wired for the new supply voltage.
Re–wiring should only be effected by a competent Electrician.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
http://air.ingersollrand.com
INSTALLATION / HANDLING
DRYER OPTION TECHNICAL INFORMATION 60Hz
General
Refrigerant typeR404A
Refrigerant charge
kg (lbs)
Refrigerant oilEmkarate RL32CF or Texaco Capella HFC32
Control settings
Hot gas setting
barg (psig)
High pressure switch setting
barg (psig)
Fan pressure switch setting
on/off
barg (psig)
Performance
(2) (3)
Dew point temperature at rated
conditions and flow
(3)
30 / 40HP50HP
41_F (5_C)
(4)
1.8 (0.84)
72 – 74 (5.0 – 5.1)
425 (29.3)
225 / 175 (15.5 / 12.1)
17
50_F (10_C)
Maximum ∆P across dryer
barg (psig)
(1)
In accordance with PNEUROP PN8NTC2.3
(2)
In accordance with ISO 7183 at the modified rated conditions.
(3)
60Hz machines: 85_F ambient, 125 psig inlet.
(4)
40hp 200v unit dewpoint is 50_F (10_C)
2.2 (0.15)3.0 (0.21)
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
18
ELECTRICAL DATA – ALL UNITS SSR UP6–40
Standard voltage200V230V380V460V575V
PACKAGE
Motor enclosureODPTEFCODPTEFCODPTEFCODPTEFCODPTEFC
Power (nominal)40HP
Full load current at maximum
pressure
Full load current at maximum
pressure with dryer option
Starting current FV (STAR)706.1 (264.5)614 (230)367 (135.2)307 (115)245.6 (92)
Starting current FV (STAR)
with dryer option
Starting time FV (STAR)3–5 Sec (7–10 Sec)
Starts per hour (maximum)6
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
20
INSTALLATION / HANDLING
1. If a circuit breaker is selected it should only be a magnetic trip type,
set above the anticipated starting current of the machine, but below the
maximum prospective fault current for the circuit. The circuit breaker
or fuseable disconnect must be capable of breaking the prospective
fault current at its terminals.
2. PVC/PVC Type Calculated using the following conditions:
i) PVC insulated cable, armoured, copper conductors.
ii) Cable clipped to a wall, in free air.
iii) Ambient temperature of 104_F (40_C) and relative humidity of 40%.
iv) 65ft (20m) cable run.
v) Volt drop limited to –10% during starting, –5% during normal
running.
vi) Protected by the circuit breaker listed above.
If there are any deviations from the above, or special regulations
apply, the installation must be planned by a competent, qualified
engineer.
NOTE
All data applies to standard product only.
ELECTRICAL DATA
An independent electrical isolator or disconnect should be installed
adjacent to the compressor.
Feeder cables/wires should be sized by the customer/electrical
contractor to ensure that the circuit is balanced and not overloaded by
other electrical equipment. The length of wiring from a suitable
electrical feed point is critical as voltage drops may impair the
performance of the compressor.
Feeder cables / wires connections to isolator or disconnect should
be tight and clean.
The applied voltage must be compatible with the motor and
compressor data plate ratings.
The control circuit transformer has different voltage tappings.
Ensure that these are set for the specific applied voltage prior to
starting.
CAUTION
Never test the insulation resistance of any part of the machines
electrical circuits, including the motor without completely
disconnecting the electronic controller (where fitted).
CAUTION
Ensure that the motor, blower and dryer fan rotate in the
correct direction as indicated by direction arrows, and on
drawing.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – GENERAL
21
GENERAL OPERATION
The compressor is an electric motor driven, single stage screw
compressor, complete with accessories piped, wired and baseplate
mounted. It is a totally self contained air compressor package.
The 40hp compressor packages are designed to operate in an
ambient range of 35.6_F – 104_F (2_C to 40_C) with a special
option package available to operate in ambient temperatures ranges
from 35.6_F up to 124_F (2_C up to 50_C). The maximum
temperature is applicable to either version up to a maximum
elevation of 3280ft (1000m) above sea level. Above this altitude
significant reduction in maximum allowable ambient temperature is
required.
The 50 hp package is designed for a 115_F (46_C) maximum
ambient.
Compression in the screw type air compressor is created by the
meshing of two (male & female) helical rotors.
The air/coolant mixture discharges from the compressor into the
separation system. This system removes all but a few PPM of the
coolant from the discharge air. The coolant is returned to the cooling
system and the air passes through the aftercooler and out of the
compressor.
Cooling air is moved through the coolers by the cooling fan and
discharged from the machine.
CAUTION
Cooling air is drawn in at the end of the machine package
passing through the filter and cooler before being discharged
from the top of the machine. Care should be taken to avoid
blocking the airflow, or causing any restriction in excess of the
maximum backpressure allowed for ducting.
Do not direct the airflow at face or eyes.
The power transmission from the drive motor to the airend male
rotor is by pulley and belts. The constant auto tensioning system, using
airend mass torque and gas arm, ensures that the belts are always
under the correct tension, eliminating the need for adjustment and
maximizing the life of the belts.
By cooling the discharge air, much of the water vapour naturally
contained in the air is condensed and may be drained from the
downstream piping and equipment.
The coolant system consists of a sump, cooler, thermostatic valve
and a filter. When the unit is operating, the coolant is pressurized and
forced to the compressor bearings.
The compressor load control system is automatic on–off line. The
compressor will operate to maintain a set discharge line pressure and
is provided with an auto restart system for use in plants where the air
demand varies sufficiently to allow a compressor to shut down and
save power. Significant system volume will assist this and is
recommended.
With the dryer option, the dryer will run continuously when the
compressor is automatically off line.
WARNING
When the unit stops running as the result of low air demand,
normally indicated by auto restart light, it may restart and return
to load at any time.
Safety of operation is provided as the compressor will shut down if
excessive temperatures or electrical overload conditions should occur.
CAUTION
This unit is not designed or intended to operate when
contaminated with silicone. Lubricants, greases or other items
containing silicone should not be used on this unit.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
22
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
1. PRESSURE GAUGE
Indicates the system pressure.
WARNING
DO NOT operate the compressor at discharge pressures
exceeding the maximum operating pressure.
2. HOURMETER
Records the total running time of the compressor.
3. EMERGENCY STOP
When depressed will stop the compressor immediately. The ’Power
on’ indicator will remain illuminated. The emergency stop button must
be released before the compressor can be restarted.
4. START/STOP
When switched to the ON position will cause the unit to start and run
in a loaded condition if there is a demand for air. If there is no demand,
the machine will run unloaded before stopping automatically.
When switched to the OFF position, will unload and stop the unit if
it is running. If the unit is in auto restart it will prevent the unit from
re–starting when there is a demand for air.
5. POWER ON (Green)
Indicates the presence of control voltage at the controller.
6. AUTO RESTART (White)
Will illuminate when the machine has shut-down due to low air
demand. The machine will restart and load automatically as soon as the
demand for air returns.
7. FAULT / HIGH AIR TEMPERATURE ALARM (Red)
Turn off electrical Isolator or disconnect. Investigate cause of fault.
8. RESET BUTTON
Press button to reset the control system following compressor trip.
9. DEW POINT INDICATOR (Dryer Option)
Green indicates good dew point. Red indicates dew point above
65_F (18_C) and blue indicates freezing.
PRIOR TO STARTING
1. Make visual check of the machine, ensure that all guards secure
and that nothing is obstructing the proper ventilation of, or free access
to the machine.
2. Check coolant level. Add if necessary.
3. Make sure main discharge valve is open.
4. Turn on electrical isolator or disconnect. The Power on (5) indicator
will light, indicating that line and control voltages are available.
5. Check direction of rotation at initial start or following interruption in
power supply.
WARNING
Make sure that all protective covers are in place.
Cooling air flow exhaust may contain flying debris. Safety
Protection should be worn at all times to avoid injury.
STARTING
1. Push the RESET button (8). The fault indicator (7) will extinguish.
Switch the ON/OFF switch (4) to the ON position. The compressor will
start and then load automatically.
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
http://air.ingersollrand.com
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
23
NORMAL/EMERGENCY STOPPING
1. Switch the ON/OFF switch (4) to the OFF position. The compressor
will unload and stop.
2. Press EMERGENCY STOP button (3) and the compressor will stop
immediately.
3. Turn off electrical isolator or disconnect.
CAUTION
After shutdown never allow unit to stand idle with pressure in
receiver/separator system.
For customers that have interruptions in their incoming power supply
to the compressor and must maintain an uninterrupted supply of
compressed air, the Power Outage Restart Option allows a
compressor to restart automatically 10 seconds (adjustable) after
incoming power is restored.
FUNCTION TEST
To test the operation of the Power Outage Restart Option:
1. Slowly open the main isolation valve.
2. Start the compressor.
3 The compressor will load automatically if there is sufficient demand
for air. Allow the compressor to load.
4. Open the main disconnect to remove power from the compressor.
5. Close the main disconnect to reapply power to the compressor.
The horn will sound for ten seconds; then the compressor will start
automatically.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
24
FULL VOLTAGE WIRING SCHEMATIC
SEE NOTES 1 & 2
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
DRYER OPTION
LEGEND
CPTTransformer
EDVValve, electric drain
ESSwitch, emergency stop
FOLOverload, internal fan (option)
1FUFuse, secondary voltage
2FU, 3FU Fuses, primary voltage
4FU,
5FU, 6FU
HATRRelay, high air temperature
HATR
1,2,3
HATSSwitch, high air temperature.
HMHourmeter
1LTLight, power on indicator (Green)
2LTLight, auto restart indicator (White)
3LTFault indicator light (Red)
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
Fuses, dryer fan (option)
Contacts, relay – HATR
DRYER OPTION
1MContactor, main
1Ma, bContacts, aux. main contactor
3MContactor, dryer compressor (option)
4MContactor, dryer fan (option)
MMSStarter & overload, fan motor
MMSaContact, fan motor overload
MODModulation control option
1MTRMotor, compressor
2MTRMotor, fan
3MTRMotor, dryer compressor (option)
4MTRMotor, dryer fan (option)
OLOverload, main motor
OLaContact, main motor overload
1.Approved fused disconnect or circuit breaker per N.E.C.
requirements must be provided by customer.
2.Dashed lines represent wiring by customer.
3.Sizing of electrical components not supplied by Ingersoll Rand is
the responsibility of the customer and should be done in
accordance with the information on the compressor data plate
N.E.C. and local electrical codes.
4.. When changing the supply voltage, ensure that:
a) The motor and the transformer are rewired for the new voltage
b) The motor overload is adjusted to the proper setting.
5.Verify actual motor conditions with motor schematic.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
26
DRYER OPTION
DRYER OPTION
SEE NOTES 1 & 2
STAR – DELTA WIRING SCHEMATIC
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
LEGEND
CPTTransformer
EDVValve, electric drain
ESSwitch, emergency stop
FOLOverload, internal fan (option)
1FUFuse, secondary voltage
2FU, 3FU Fuses, primary voltage
4FU,
5FU, 6FU
HATRRelay, high air temperature
HATR
1,2,3
HATSSwitch, high air temperature.
HMHourmeter
1LTLight, power on indicator (Green)
2LTLight, auto restart indicator (White)
3LTFault indicator light (Red)
1MContactor, main
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
Fuses, dryer fan (option)
Contacts, relay – HATR
1Ma, b, cContacts, aux. main contactor
2MContactor, delta
2Ma, bContacts, aux. delta contactor
3MContactor, dryer compressor (option)
4MContactor, dryer fan (option)
MMSStarter & overload, fan motor
MMSaContact, fan motor overload
MODModulation control option
1MTRMotor, compressor
2MTRMotor, fan
3MTRMotor, dryer compressor (option)
4MTRMotor, dryer fan (option)
3OL
OLOverload, main motor
OLaContact, main motor overload
1.Approved fused disconnect or circuit breaker per N.E.C.
requirements must be provided by customer.
2.Dashed lines represent wiring by customer.
3.Sizing of electrical components not supplied by Ingersoll Rand is
the responsibility of the customer and should be done in
accordance with the information on the compressor data plate
N.E.C. and local electrical codes.
4.. When changing the supply voltage, ensure that:
a) The motor and the transformer are rewired for the new voltage
b) The motor overload is adjusted to the proper setting.
5.Verify actual motor conditions with motor schematic.
http://air.ingersollrand.com
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE,
EP50–PE, HP50–PE, HXP50–PE
28
OPERATING INSTRUCTIONS – ELECTRO–PNEUMATIC
CONTROL PIPING DIAGRAM
10
1
R
P
A
2
6
3
8
6
13
4
6
11
12
9
7
8
14
13
6
18
6
22250039
Revision F
09/06
KEY
1. Pressure gauge
2. Pressure switch
3. Tee
4. Connector
5. Moisture separator
6. Elbow
7. Tee, male run
8. Reducer bushing
9. Blow down solenoid valve
10.Load solenoid valve
11.Indicator air filter
ADAPTER INTO
15
5
A
A
B
THIS PORT
PLUG INTO
THIS PORT
12.Nipple
13.Adaptor
14.Intake valve assembly
15.Separator tank
16.Tee
17.Valve
18.Plug
17.Valve
NOTES:
A. Tubing 3/8 inch
B. Tubing 1/4 inch
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
http://air.ingersollrand.com
Loading...
+ 178 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.