Ingersoll-Rand EP 20 SE, HXP 25 SE, HP 20 SE, HXP 20 SE, EP 25 SE Operators/instruction Manual Options

...
Before installation or starting the compressor for the
APDD 567A
®
first time, this manual should be studied carefully to obtain a clear knowledge of the unit and of the duties to be performed while operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the air compressor at all times.
EP/HP/HXP 20 SE EP/HP/HXP 25 SE
OPERATORS/ INSTRUCTION MANUAL OPTIONS
September 1998
BONDED WARRANTY & REGISTERED START UP
AIR COMPRESSOR GROUP

Warranty

The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months (see extended airend warranty) from the date of placing the Equipment in operation or eighteen months (see extended airend warranty) from the date of shipment from Davidson, NC, whichever shall first occur. The Purchaser shall be obligated to promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed maintained and operated such Equipment in accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the manufacturers have conveyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company’s prior written approval.
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are limited to those specifically stated within the Company’s proposal. Unless responsibility for meeting such performance warranties are limited to specified tests, the Company’s obligation shall be to correct in the manner and for the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company in
writing of its intention to do so. Any such Equipment will be at Purchaser’s sole risk and liability.
Limitation or Liability
The remedies of the Purchaser set forth herein are exclusive, and the total liability of the Company with respect to this contract or the Equipment and services furnished hereunder, in connection with the performance or breach thereof, or from the manufacture, sale, delivery, installation, repair or technical direction covered by or furnished under this contract, whether passed on contract, warranty negligence, indemnity, strict liability or otherwise, shall not exceed the purchase price of the unit of Equipment upon which such liability is based.
The Company and its suppliers shall in no event be liable to the Purchaser, any successors in interest or any beneficiary or assignee of this contract for any consequential, incidental, indirect, special or punitive damages arising out of this contract or any breach thereof, or any defect in, or failure of, or malfunction of the Equipment hereunder, whether based upon loss of use, lost profits or revenue, interest, lost goodwill, work stoppage, impairment of other goods, loss by reason of shutdown or non-operation, increased expenses of operation, cost of purchase of replacement power or claims of Purchaser or customers of Purchaser for service interruption whether or not such loss or damage is based on contract, warranty, negligence, indemnity, strict liability or otherwise.
The Ingersoll-Rand Company Rotary Screw Air Compressor that has been filled prior to its original shipment from Ingersoll-Rand Company with ULTRA COOLANT and which has been operated solely on ULTRACOOLANT thereafter shall have its AIREND warranted for twenty four (24) months from the date of placing the COMPRESSOR in operation or thirty (30) months from the date of shipment, whichever occurs first.
Except for the above warranty period, the standard warranty provisions shall apply and the conditions outlined herein are understood to be a supplement to the standard Ingersoll-Rand Company warranty.
©INGERSOLL-RAND COMPANY
EXTENDED AIREND WARRANTY
ROTARY SCREW AIR COMPRESSOR
This unit was purchased from:
_______________________________________________ _______________________________________________ _______________________________________________
Ingersoll-Rand Company reserves the right to make changes or add improvements without notice and without incurring any obligation to make such changes or add such improvements to products sold previously.
Number of units on order: __________________________ Customer Order Number: __________________________ Ingersoll-Rand Company Order Number: ______________
For ready reference, record the serial number and model number of your unit here:
Serial Number: ___________________________________ Model Number:___________________________________
TYPICAL UNIT
1

TABLE OF CONTENTS

0.0 SAFETY AND WARNINGS
0.1 safety instructions
0.2 safety precautions
0.3 decals
1.0 RECEIPT OF EQUIPMENT
1.1 inspection
1.2 unpacking and handling
1.3 tools
2.0 INSTALLATION
2.1 ventilation
2.2 foundation requirements
2.3 piping
2.4 electrical installation
2.5 outdoor sheltered installation
3.0 INTELLISYS
3.1 emergency stop switch
3.2 power on light
3.3 power indicator light
3.4 push buttons
3.5 setpoint procedure
3.6 warnings
3.7 alarms
4.0 SYSTEMS
4.1 general systems
4.2 aircooled compressors
4.3 coolant system
4.4 compressed air system
4.5 coolant/air separation system
4.6 electrical system
4.7 capacity control
5.0 MAINTENANCE
5.1 maintenance schedule
5.2 maintenance records
5.3 maintenance procedures
5.4 sheave alignment
5.5 v-belts
5.6 belt tension adjustment
5.7 shaft seal replacement
5.8 inlet air filter
5.9 coolant filter element
5.10 coolant
5.11 separator tank scavenge check valve/orifice/screen
5.12 temperature control valve element
replacement
5.13 coolant separator element
5.14 cooler cores: cleaning
5.15 motor lubrication
5.16 long term storage
5.17 coolant/lubricant changeout
5.18 intellisys removal
5.19 coolant hoses
5.20 airend discharge hose
6.0 TROUBLE SHOOTING
7.0 OPTIONS
7.1 remote start/stop
7.2 remote start/stop, PORO
7.3 sequencer control
8.0 REFERENCE DRAWINGS
8.1 electrical schematic - full voltage
8.2 electrical schematic - star-delta
8.3 electrical schematic - full voltage remote mounted starter
8.4 foundation plan - enclosed
8.5 foundation plan - unenclosed
8.6 foundation plan - outdoor modification
8.7 basic flow schematic - full voltage
8.8 basic flow schematic - full voltage with
modulation
8.9 basic flow schematic - star-delta
8.10 basic flow schematic - star-delta with
modulation
8.11 typical system flow diagrams
9.0 MAINTENANCE RECORD
GENERAL INFORMATION
Weight: See foundation plan, Section 8.0
Cooling Air Flow: See foundation plan, Section 8.0
Ambient Temperature Limit: 35°F to 115°F (2°C to 46°C)
Coolant: Factory Filled SSR Ultra Coolant
Coolant Change: 8000 hours or two years, whichever
comes first
Coolant Capacity: Tank only: 0.75 gal. (2.8 liters)
Complete System: 1.70 gal. (6.4 liters)
Discharge Temperature Limit: 228°F (109°C)
Power Inlet Wiring: Recommended conduit: metallic
flexible Greenfield, or equivalent,
Tools: U.S. Standard and metric are required
to perform maintenance
2
3

0.0 SAFETY AND WARNINGS

0.1 SAFETY INSTRUCTIONS Before you install this air compressor you should take the time to carefully read all the instructions contained in this manual.

Electricity and compressed air have the potential to cause severe personal injury or property damage.
Before installing, wiring, starting, operating or making any adjustments, identify the components of the air compressor using this manual as a guide.
The operator should use common sense and good working practices while operating and maintaining this unit. Follow all codes, pipe adequately, understand the starting and stopping sequence. Check the safety devices by following the procedure contained in this manual.
Maintenance should be done by qualified personnel, adequately equipped with proper tools. Follow the maintenance schedules as outlined in the operators manual to ensure problem free operation after start up.
Safety instructions in the operators manual are bold-faced for emphasis. The signal words DANGER, WARNING and CAUTION are used to indicate hazard seriousness levels as follows:
Danger is used to indicate the presence of a hazard which
D! DANGER
! WARNING
! CAUTION
NOTICE
WARNING
COMPRESSED AIR AND ELECTRICITY ARE DANGEROUS.
BEFORE DOING ANY WORK ON THIS UNIT, BE SURE THE ELECTRICAL SUPPLY HAS BEEN CUT OFF–LOCKED & TAGGED AND THE ENTIRE COMPRESSOR SYSTEM HAS BEEN VENTED OF ALL PRESSURE.
1. Do not remove the covers, loosen or remove any fittings, connections or devices when this unit is in operation. Hot liquid and air under pressure that are contained within this unit can cause severe injury or death.
2. The compressor has high and dangerous voltage in the motor starter and control box. All installations must be in accordance with recognized electrical codes. Before working on the electrical system, be sure to remove voltage from the system by use of a manual­disconnect-switch. A circuit breaker or fuse safety switch must be provided in the electrical supply line leading to the compressor.
Those responsible for installation of this equipment must provide suitable grounds, maintenance clearance and lightning arrestors for all electrical components as stipulated in O.S.H.A. 1910.308 through
1910.329.
3. Do not operate the compressor at higher discharge pressure than those specified on the Compressor Nameplate or motor overload will occur. This condition will result in compressor motor shutdown.
4. Use only safety solvent for cleaning the compressor and auxiliary equipment.
5. Install a manual shut off valve (isolation type) in the discharge line. When a safety valve is installed between the isolation valve and the compressor, it must have sufficient capacity to relieve the full capacity of the compressor(s).
6. Whenever pressure is released through the pressure relief valve, it is due to excessive pressure in the system. The cause for the excessive pressure should be investigated immediately.
7. Before doing any mechanical work on the compressor:
a.) Shut the unit down.
b.) Electrically isolate the compressor by use of the manual disconnect switch in the power line to the unit. Lock and tag the switch so that it cannot be operated.
c.) Vent pressure from the compressor and isolate the unit from any other source of air.
8. There can be adverse effects if compressor lubricants are allowed to enter plant air systems.
Air line separators, properly selected and installed, will minimize any liquid carry­over.
The use of plastic bowls on line filters without metal guards can be hazardous. From a safety standpoint, metal bowls should be used on any pressurized system. Review of your plant air line system is recommended.
9. When a receiver is installed, it is recommended that occupational safety and health standards as covered in the Federal Register, Volume 36, number 105, part 11, paragraph 1910.169 be adhered to in the installation and maintenance of this receiver.
10. Before starting the compressor, its maintenance instructions should be thoroughly read and understood.
11. After maintenance functions are completed, covers and guards must be replaced.

0.2 SAFETY PRECAUTIONS

SAFETY PRECAUTIONS
BEFORE PROCEEDING, READ CAREFULLY BEFORE INSTALLING THE
COMPRESSOR OR PERFORMING ANY MAINTENANCE
will cause severe
injury, death, or substantial property damage if the warning is ignored.
Warning is used to indicate the presence of a hazard which injury, death, or substantial property damage if the warning is ignored.
Caution is used to indicate the presence of a hazard which personal injury or property damage if the warning is ignored.
Notice is used to notify people of installation, operation, or maintenance information which is important but not hazard-related.
can cause severe
will or can cause minor
personal
personal
WARNING
4
Failure to adhere to these recommendations can result in mechanical failure, property damage and serious injury or death. All air and water inlet, and air and water discharge pipework to and from the inlet and discharge port connections must take
into account vibration, pulsations, temperature, maximum pressure applied, corrosion and chemical resistance. In addition, it should be noted that lubricated compressors will discharge some oil into the air stream; therefore, compatibility between discharge piping, system accessories and software must be assured.
For the foregoing reasons, the use of plastic piping, soldered copper fittings and rubber hose as discharge piping is not recommended. In addition, flexible joints and/or flex lines can only be considered for such purposes if their specifications fit the operating parameters of the system.
It is the responsibility of the installer and owner to provide the appropriate service pipework to and from the machine.
WARNING
CHECK HIGH AIR TEMPERATURE
There is a high discharge air temperature shutdown function built into the Intellisys on each compressor. It is factory pre-set at 228°F (109°C). This function should be checked at regular intervals for proper operation, once a month is recommended. The procedure is:
1. Block off the cooling air discharge.
2. The compressor discharge temperature will rise at a rapid rate. Shutdown should occur when the discharge temperature reaches the pre-set maximum discharge air temperature setting of the Intellisys. The display should indicate “HIGH AIREND TEMP” and the alarm light will be illuminated.
The actual temperature at which shutdown occurs should be recorded for comparison to the Intellisys set point and with similar future test results.
SAFETY SHUTDOWN
!
!
!
“Ingersoll-Rand air compressors are not designed, intended, or approved for breathing air applications. Ingersoll-Rand does not approve specialized equipment for breathing air application and assumes no responsibility or liability for compressors used for breathing air services.”

0.3 DECALS

WARNING
!
Exposed fan blade. Can cause severe injury.
Do not operate with covers removed. Disconnect power.Lock and tag.
INGERSOLLrAND ®
39558788
39559646
39544150
WARNING
!
Exposed moving parts. Can cause severe injury or death.
Stay clear or moving parts when machine is operating.
INGERSOLLrAND ®
WARNING
!
Hazardous voltage. Can cause severe injury or death.
Disconnect power before servicing. Lockout/Tagout machine.
INGERSOLLrAND ®
CAUTION
!
Incorrect lifting of machine can cause injury or property damage.
Lift only from base channels.
INGERSOLLrAND ®
NOTICE
Rotation.
INGERSOLLrAND ®
This section contains representative examples of decals which will be appearing throughout this manual and are applied to the compressor unit. If for some reason a decal is defaced, painted over, or parts are replaced, we
recommend that you obtain a replacement kit as listed in the spare parts section of the Parts List Manual (Form APDD 568).
39540174
39540232
5
Condensate drain.
NOTICE
INGERSOLLrAND®
Lift here.
NOTICE
INGERSOLLrAND®
NOTICE
Motors MUST be greased
periodically. See Operators
Manual for procedure.
39570098
39540273
NOTICE
For detailed
regulation adjustment
instructions refer
to Operators/
Instruction Manual.
INGERSOLLrAND ®
39540208
39541081
39570098
NOTICE
To obtain satisfactory compressor
operation and maintenance a
minimum of 3 feet clearance on 3
sides is required 3-1/2 feet is
required in front of the control panel
(or minimum required by latest
National Electrical code or applicable
local codes).
Refer to the Instruction / Operators
Manual before performing any
maintenance.
INGERSOLLrAND ®
39540158
Condensate drain.
NOTICE
INGERSOLLrAND®
39541081
6
DANGER
!
Discharge air.
Can contain carbon monoxide or
other contaminants. Will cause
severe injury or death.
Do not breathe this air.
INGERSOLLrAND ®
39557236
RIGHT SIDE VIEW
CAUTION
!
Use of incorrect coolant can cause
system contamination.
Use only SSR ULTRA COOLANT.
INGERSOLLrAND ®
Electrical power inlet.
NOTICE
INGERSOLLrAND®
39544150
NOTICE
Rotation.
INGERSOLLrAND ®
WARNING
!
Hot surface.
Can cause severe injury.
Do not touch. Allow to cool before
servicing.
INGERSOLLrAND ®
39541362
39540273
WARNING
!
Hazardous voltage. Can cause
severe injury or death.
Only use factory supplied inlet for
incoming power.See Operators/
Instruction manual.
INGERSOLLrAND ®
39543764
39543921
NOTICE
Filler Cap.
Use only recommended
coolant.
Read instruction book
before servicing.
39543921
WARNING
!
High pressure air.
Can cause severe injury or death.
Relieve pressure before removing filter
plugs / caps, fittings or covers.
INGERSOLLrAND ®
39541354
Lift here.
NOTICE
INGERSOLLrAND®
Lift here.
NOTICE
INGERSOLLrAND®
CAUTION
!
IMPROPER COOLANT FILTER REPLACEMENT
WILL CAUSE COMPRESSOR DAMAGE.
REPLACE FILTER ELEMENT AFTER FIRST
150 HOURS OF OPERATION; AND EVERY 1200
HOURS THEREAFTER OR WHEN COOLANT IS
CHANGED.
INGERSOLLrAND ®
39557244
39540240
39540273
39540265
7
8
WARNING
!
Hazardous voltage. Can cause
severe injury or death.
Disconnect power before servicing.
Lockout/Tagout machine.
INGERSOLLrAND ®
39540174
39838396 (UNITS W/FV STARTER)
39838412 (UNITS W/SD STARTER)
39845037 (UNITS W/REMOTE FV STARTER)
39539127 (S/2 FV)
39539135 (S/2.3, S/3 FV)
39539150 (S/4 FV)
39567656 (S/2 SD)
39539143 (S/2.3, S/3 SD)
UNITS W/BUILT-ON STARTER
ONLY

1.0 RECEIPT OF EQUIPMENT

IMPORT ANT
READ THIS
LOST OR DAMAGED GOODS
THOROUGHLY INSPECT THIS SHIPMENT
IMMEDIA TELY UPON ARRIV AL
OUR RESPONSIBILITY FOR THIS SHIPMENT
CEASED WHEN THE CARRIER SIGNED
BILL OF LADING
If goods are received short or in damaged condition, it is important that you notify the carrier and insist on a notation of the loss or damage across the face of the freight bill. Otherwise no claim can be enforced against the transportation company.
If concealed loss or damage is discovered, notify your carrier at once and request an inspection. This is absolutely necessary. Unless you do this the carrier will not entertain any claim for loss or damage. The agent will make an inspection and grant a concealed damage notation. If you give the transportation company a clear receipt for goods that have been damaged or lost in transit, you do so at your own risk and expense.
WE, AT I-R, ARE WILLING TO ASSISTYOU IN EVERY POSSIBLE MANNER TO COLLECT CLAIMS FOR LOSS OR DAMAGE, BUT THE WILLINGNESS ON OUR PART DOES NOT MAKE US RESPONSIBLE FOR COLLECTION OF CLAIMS OR REPLACEMENT OF MATERIAL. THE ACTUALFILING AND PROCESSING OF THE CLAIM IS YOUR RESPONSIBILITY.
Ingersoll-Rand Company Davidson, North Carolina
APDDGFO-99-79
SPREADER
BARS

1.1 INSPECTION

When you receive the compressor please inspect it closely . Any indication of careless handling by the carrier should be noted on the delivery receipt especially if the compressor will not be immediately uncrated. Obtaining the delivery man’s signed agreement to any noted damages will facilitate any future insurance claims.

1.2 UNPACKING AND HANDLING

The compressor package has been mounted on a base which provides for forklifting between the two side channels to facilitate handling during shipment. Care in positioning the forklifts is important because the location of the center of gravity is strongly affected by the location of the compression module and drive motor.
FORKLIFT PADDING
WILL REDUCE SCRATCHES
AND MARS
Slings can be used to lift the crates, but spreader bars must be used to prevent the slings from exerting a force against the sides of the crates.

1.3 TOOLS

Remove compressor unit from wooden skid. Acrowbar and hammer will be needed.
9

2.0 INST ALLATION

AIR INTAKE
CHEMICALS
METAL
FILINGS
PAINT
SPRAY
OVERSPRAY
Do not use plastic pipe, soldered copper
fittings or rubber hose for discharge piping.
WARNING
Never elevate the compressor unit
above the floor level. This may allow air
to enter the cabinet under the base.
Performance will be affected.
NOTICE
!
!
36” (.9 m)
42” (1.06 m) OR
CODE MINIMUM
10

2.1 VENTILATION

Oil flooded rotary air compressors produce large amounts of heat. Because of this large heat production, the compressor must be placed in a room with adequate ventilation. Aroom in which the amount of air that is drawn in and exhausted is equal to or greater than the cooling fan air flow requirement for the compressor that is installed.
If heated air from the compressor exhaust is allowed to recirculate back to the compressor, the compressor will overheat and shut down. This heat must be exhausted from the room. You should take this into consideration when you decide where to place the compressor within your plant. Consider that the required maintenance clearance is 3 ft (.9 m) all around the compressor. However 42” (1.06m), or minimum required by latest NEC or applicable local codes, must be maintained in front of control panel.
Ambient temperatures higher than 115°F (46°C) should be avoided as well as areas of high humidity.
Consider also the environment surrounding or near the compressor. The area selected for the location of the compressor should be free of dust, chemicals, metal filings, paint fumes and overspray.
DUST

2.2 FOUNDATION REQUIREMENTS

Refer to the foundation plan for the particular model compressor to be installed. See Section 8.0.
The compressor can be installed on any level floor that is capable of supporting it. Compressor weights are listed on the foundation plans.
When sound transmission is of particular importance it is often helpful to install a sheet of rubber-fabric-matting, or cork under the compressor to reduce the possibility of resonant sounds being transmitted or amplified through the floor.
36”
(.9 m)

2.3 PIPING

The use of plastic bowls on line filters without metal guards can be hazardous. Their safety can be affected by either synthetic lubricants or the additives used in mineral oil. From a safety standpoint, metal bowls should be used on any pressurized system. Review of your plant air line system is recommended.
The built-in aftercooler reduces the discharge air temperature well below the dew point (for most ambient conditions), therefore, considerable water vapor is condensed. To remove this condensation, each compressor with built-in aftercooler is furnished with a combination condensate separator/trap.
ISOLATION
VALVE
DRIP LEG
ISOLATION
VALVE
ISOLATION
VALVE
STRAINER
TRAP
NOTE: SEPARATE LINES GOING TO THE  RECEIVER
DRIP
LEG
ROTARY
COMPRESSOR
PRESSURE
GAUGE
SAFETY
VALVE
ISOLATION 
VALVE
RECIPROCATING
COMPRESSOR
DRIP
LEG
SAFETY
VALVE
Careful review of piping size from the compressor connection point is essential. Length of pipe, size of pipe, number and type of fittings and valves must be considered for optimum efficiency of your compressor.
It is essential when installing a new compressor to review the total plant air system. This is to ensure a safe and effective total system.
Liquid water occurs naturally in air lines as a result of compression. Moisture vapor in ambient air is concentrated when pressurized and condenses when cooled in downstream air piping.
Moisture in compressed air is responsible for costly problems in almost every application that relies on compressed air. Some common problems caused by moisture are rusting and scaling in pipelines, clogging of instruments, sticking of control valves, and freezing of outdoor compressed air lines. Any of these could result in partial or total plant shutdown.
Compressed air dryers reduce the water vapor con­centration and prevent liquid water formation in compressed air lines. Dryers are a necessary companion to filters, aftercoolers, and automatic drains for improving the productivity of compressed air systems.
NOTICE
!
2.3 PIPING (Continued)
200
160
120
80
40
0
DEW POINT
without Aftercooling
100°F/38°C (with Aftercooler)
35°F /1.7°C (Refrigerated Dryer)
-40°F/-40°C (Desiccant Dryer)
Gallons of Water/24
hours/1000 acfm
ROTARY
COMPRESSOR
A dripleg assembly and isolation valve should be mounted near the compressor discharge. Adrain line should be connected to the condensate drain in the base.
IMPORT ANT: The drain line must slope downward from the base to work properly.
NOTE: For ease of inspection of the automatic drain trap operation, the drain piping should include an open funnel.
It is possible that additional condensation can occur if the downstream piping cools the air even further and low points in the piping systems should be provided with driplegs and traps.
IMPORT ANT: Discharge piping should be at least as large as the discharge connection at the compressor enclosure. All piping and fittings must be suitable for the maximum operating temperature of the unit and, at a minimum, rated for the same pressure as the compressor sump tank.
DISCHARGE PIPING WITH AFTERCOOLER
Do not use the compressor
to support the discharge pipe.
ROTARY-RECIP IN PARALLEL
MOISTURE CONTENT OF COMPRESSED AIR
11
Two types of dryers, refrigerated or desiccant, are used
ISOLATION
VALVE
ISOLATION
VALVE
STRAINER
TRAP
DRIP
LEG
ROTARY
COMPRESSOR
PRESSURE
GAUGE
SAFETY
VALVE
ISOLATION 
VALVE
ROTARY
COMPRESSOR
DRIP
LEG
1FU 2FU 3FU 4FU/5FU
Transformer Primary Primary Secondary Secondary
Rating Fuse Fuse Fuse Fuse
(VA) (Amp) (Amp) (Amp) (Amp)
230 2.0 2.0 2.0 2.0 330 2.5 2.5 3.2 2.0
FUSE TABLE
to correct moisture related problems in a compressed air system. Refrigerated dryers are normally specified where compressed air pressure dew points of 33°F (1°C) to 39°F (4°C) are adequate. Desiccant dryers are required where pressure dew points must be below 33°F (1°C).
Contact your local Ingersoll-Rand distributor for assistance in selecting correct Ingersoll-Rand filtration or drying products.
NOTE: Screw type compressors should not be installed in air systems with reciprocating compressors without a means of pulsation isolation, such as a common receiver tank. We recommend both types of compressor units be piped to a common receiver utilizing individual air lines.
When two rotary units are operated in parallel, provide an isolation valve and drain trap for each compressor before the common receiver.

2.4 ELECTRICAL INSTALLATION

Before proceeding further, we recommend that you review the safety data in the front of this manual.
Locate the compressor data plate on the right side of starter box.
The data plate lists the rated operating pressure, the maximum discharge pressure and the electric motor characteristics and power.
Confirm that the line voltage and compressor nameplate voltage are the same and that the standard starter box meets the intent of NEMA 1 guidelines.
Remove the screws and door from the front of the starter box. Confirm that all electrical connections are made and tightened. Confirm that the control transformer is wired correctly for supply voltage. See Figure 2.4-1 on next page for typical control transformer wiring.
12
ROTARY TWO COMPRESSOR SYSTEM
CAUTION
ELECTRICAL INSTALLATION (Continued)
Inspect the motor and control wiring for tightness. Replace the starter box door.
Rotation Check
Locate the rotation decal on the motor.
Drive Motor The correct compressor drive motor rotation is clockwise when viewed from the rear or non-drive end of the motor. See Figure 2.4-2.
!
DRIVE END
NON-DRIVE
END
110V
LINE VOLTS HZ LINE SEC VOLTS LINE
200 60 H4-H5 120 X1-X2
8 X3-X4 8 X4-X5
220/230 60 H3-H5 120 X1-X2
8 X3-X4 8 X4-X5
380 60 H3-H5 120 X1-X2
8 X3-X4 8 X4-X5
440/460 60 H2-H5 120 X1-X2
8 X3-X4 8 X4-X5
575 60 H1-H5 120 X1-X2
8 X3-X4 8 X4-X5
LINE VOLTS HZ LINE SEC VOLTS LINE
220 50 H5-H6 110 X1-X2
8 X3-X4 8 X4-X5
380 50 H4-H6 110 X1-X2
8 X3-X4 8 X4-X5
415 50 H2-H6 110 X1-X2
8 X3-X4 8 X4-X5
550 50 H1-H6 110 X1-X2
8 X3-X4 8 X4-X5
H4
H5
H6
X5
X5
X4 16V C.T.
X4 16V C.T.
FIGURE 2.4-1 TYPICAL CONTROL TRANSFORMER WIRING
If the compressor is operated in the
opposite direction of rotation, airend damage
can result and is not warrantable.
FIGURE 2.4-2 DRIVE MOTOR ROT ATION
13
ELECTRICAL INSTALLATION (Continued)
DANGER
HIGH VOLTAGE
DANGER
LEVER
HASP
TAG
KEY LOCK
NOTICE
Intellisys
Operating Instructions
BEFORE INSTALLING, OPERATING, OR PERFORMING ANY MAINTENANCE ON THIS UNIT, READ AND UNDERSTAND THE INSTRUCTIONS IN THE OPERATORS / INSTRUCTION MANUAL
Remove the starter box door.
The Intellisys will automatically shut the unit down if the compressor rotation is incorrect, and “CHK MTR ROTATION” will appear in the display, also the alarm light will be on. See Section 6.
For the compressor motor rotation check, the motor jogging time must be as short as possible.
After depressing the start button, IMMEDIATELY depress the “EMERGENCY STOP” button. Should the motor rotation be incorrect, put main disconnect in the OFF position, lock and tag. See Figure 2.4-3.
FIGURE 2.4-3 MAIN DISCONNECT
LOCKED AND TAGGED
Interchange any two line connections (L1, L2 or L3) at the starter. Close and fasten the starter box door. Recheck for correct rotation.
Intellisys Operating Instructions
Read and understand the following Intellisys Operating Instructions (See Figure 2.4-4) prior to operating the unit.
NOTE: These instructions are also contained on the decal near the Intellisys panel of the unit.
Before Starting
1. Check coolant level. Add coolant if necessary.
2. Verify that main isolation valve is open.
3. Close main disconnect switch. The “ POWER” light indicates that line and control voltages are available for starting. “UNLOAD” indicator light will be on.
Starting
1. Push “START”. Compressor will start. The compressor
will load automatically and the air pressure will rise
if there is sufficient demand for air.
Stopping
1. Push “UNLOADED STOP”. Compressor will immediately unload and continue to 7 seconds. Compressor will then stop. If compressor is running unloaded when “UNLOADED STOP” is pushed, compressor will stop immediately.
2. Open main disconnect switch.
Stopping - Emergency
1. If there is a need to stop the compressor immediately or if the “UNLOADED STOP” does not stop the com­pressor after 7 seconds, push “EMERGENCY STOP” Compressor will stop immediately.
2. Open main disconnect switch.
run unloaded approximately
14
FIGURE 2.4-4 INTELLISYS OPERATING
INSTRUCTIONS

2.5 OUTDOOR SHELTERED INSTALLATION

Many times a compressor must be installed outside due to jobsite conditions or limited space within a manufacturing facility. When this occurs there are certain items that should be incorporated into the installation to help ensure trouble free operation. These items have been listed below plus Figure 2.5-1 has been included to show a typical outdoor sheltered installation. The unit must be purchased with the Outdoor Modification Option to provide NEMA 4 electrics and a cabinet exhaust on the rear of the unit rather than the top to prevent recir­culation of cooling air.
The compressor should be on a concrete pad
designed to drain water away. If the concrete pad is sloped, then the compressor must be leveled. In order to properly pull cooling air through the aftercooler, the base/skid must be sealed to the concrete pad.
The roof of the shelter should extend a minimum of
4 ft (1.2 m) around all sides of the compressor to pre­vent direct rain and snow from falling on the unit.
Air-cooled machines must be arranged under the
shelter in a way that prevents air recirculation (i.e. hot exhaust back to the package inlet).
If the installation includes more than one compressor,
the hot air exhaust should not be directed towards the fresh air intake of the second unit or an Air Dryer.
If a standard machine is to be installed outside, the
ambient temperature must never drop below 35°F (1.7°C).
Power disconnect switch should be within line of sight
and in close proximity to the unit. N.E.C. and local electrical codes must be followed when installing the power disconnect switch.
Condensate drains must never be allowed to dump on
the ground. Run to a suitable sump for future collection and disposal or separation of lubricant and water mixture.
Incoming power connections must use suitable
connectors for outdoor weather tight service.
A minimum of 3 ft (.9 m) clearance must be allowed
on all four sides of the unit for service access. However 42” (1.06m), or minimum required by latest NEC or applicable local code, must be maintained in front of control panel.
If possible, access by a forklift and/or an overhead
beam hoist should be kept in mind (for eventual service to airend or motor).
If the area around the installation contains fine
airborne dust or lint and fibers etc., then the unit should be purchased with the High Dust Filter Option and TEFC motor.
Some type of protection such as a fence or security
system, should be provided to prevent unauthorized access.
Arrange the machine with the Intellisys con-
troller/starter enclosure facing away from the sun as radiant heat can affect starter/lntellisys performance. Also direct sunlight and UV rays will degrade the membrane touch panel. This is not a warrantable situation.
15
16
FIGURE 2.5-1 TYPICAL OUTDOOR SHELTERED INSTALLATION
INGERSOLrAND
INTELLISYS
• ALARM•• SET OFFLINE AIR PRESURE
• SET ONLINE AIR PRESSURE
• SELECT CONTROL MODE
• SET DISPLAY TIME
• SELECT OPTIONS
•
PACKAGE DISCHARGE PRESSURE •
AIREND DISCHARGE TEMPERATURE •
SUMP PRESSURE •
SEPARATE PRESSURE DROP •
TOTAL HOURS •
LOADED HOURS •
•
•
UNLOAD •
POWER
START
UNLOAD
/LOAD
DISPLAY
SELECT
STOP
UNLOADED
SET
AUTOMATIC
RESTART

3.0 INTELLISYS

INTELLISYS CONTROLLER
INGERSOLLrAND
INTELLISYS
17
3.0 INTELLISYS

3.1 EMERGENCY STOP SWITCH

Pressing this switch stops the compressor immediately. Compressor cannot be restarted until switch is manually reset. Turn clockwise to reset.

3.2 POWER ON LIGHT (Inside Starter Box)

Indicates control voltage is available to the control circuit and line voltage is available for starting.
POWER ON

3.3 POWER INDICATOR LIGHT

Indicates voltage is available to the intellisys controller.

3.4 PUSH BUTTONS

START
If the display shows READY TO START, pressing this button will start the compressor. The compressor will start and load automatically if there is a demand for air.
If in the display table press this button to exit the display table. Display will show “CHECKING MACHINE” then “READY TO START”.
EMEG
STOP
UNLOAD
/LOAD
START
STOP
UNLOADED
DISPLAY
SELECT
SET
POWER
POWER
UNLOAD STOP
UNLOAD
/LOAD
START
DISPLAY
SELECT
UNLOAD
/LOAD
DISPLAY
SELECT
UNLOAD
/LOAD
START
STOP
UNLOADED
DISPLAY
SELECT
SET
POWER
Pressing this button will activate the unload stop. If the compressor is running loaded, it will unload. Seven seconds later it will stop. if the compressor is running unloaded, it will stop immediately. Pressing this button with the unit stopped will flash all L.E.D.’s for a light check and flash the software version number in the display.
UNLOAD/LOAD
If the unit is running loaded, pressing this button will cause the unit to unload, the unload indicator light will be on. The unit will not load until the button is pressed again. If the unit is running unloaded, pressing this button will load the unit in the ON/OFF LINE or MOD/ACS control mode previously operating.
18
DISPLAY
SELECT
UNLOAD
/LOAD
START
DISPLAY
SELECT
SET
POWER ON
EMEG
STOP
UNLOAD
/LOAD
START
STOP
UNLOADED
DISPLAY
SELECT
SET
POWER
EMEG
STOP
UNLOAD
/LOAD
START
DISPLAY
SELECT
SET
POWER
3.4 PUSH BUTTONS (Continued)
DISPLAY SELECT
Pressing this button will change the information selected for the display. The display table will be incremented. If the button is held, this display table will scroll. This button can also be used to exit the set point procedure.
NOTE: For readings less than 1 hr., hourmeter display minutes. After 1 hr. the hourmeter displays hours.
SET
PRESSURE SENSOR CALIBRATION (ZEROING) ROUTINE
This routine is entered if the unit is not running and both the up and down arrows button are pressed at the same time. Make sure all pressure is relieved from the compressor before calibration. The display will flash the message “CALIBRATING”. After calibration is completed the display will indicate “READY TO START”. Zeroing should only be done after a pressure sensor has been replaced or any controller change.
The SET button is used to enter the set point procedure. The set button is also used to reset warnings and alarms. Pressing this button once will reset a warning, twice will clear an alarm.
ARROWS
These buttons have several functions. If the Intellisys is in the set point mode, the ARROWS are used to change the set point values. If the unit has multiple alarms or warnings, the ARROWS are used to scroll through these conditions. The ARROWS have a function in the calibration routine, which will be described later.
19
Loading...
+ 49 hidden pages