Ingenium is a vanguard company dedicated since
1998 to the design, development and manufacturing of the highest domotics technology.
From the beginning we have been conscious of
the necessity to approach this emergent market
with high standards of quality and focusing on
R&D. This allows us to innovate without neglecting the manufacturing process while making us
confident of our effort. Our focus causes that
every year more people approach our system.
Our system BUSing® totally open and free of royalties, allows other manufacturers to design equipment under our standards and specifications, as
well as the development of integrations on other
devices or gateway with other standards.
Our products are versatile and intuitive, guaranteeing comfort, security and energy efficiency
without forgetting design; basic pillars on which
our concept of domotics is founded. This is how
we elaborate our catalogue.
BUSing® General Requirements
• It is strictly recommended to use shielded and flexible
cable for the wiring of the data BUS (Cable BUSing®).
• In no case should be used the power wiring pipes for
wiring BUS or inputs signals, because it is SELV signals.
• Ingenium is not responsible for the improper functioning of the system in the case of making a star-wiring
BUS. It is recommended that BUS topology is used.
• The number of required power supplies can vary depending on wiring distances between devices and the
installation in general.
• Ingenium always recommend the use of protection,
both in electrical line and telephone line, to prevent
possible damage by power surges.
• To ensure the proper functioning of communications,
especially in electrically noisy installations, an EndBUS device must be placed in the beginning and another one at the end of the bus line.
This technical manual has been developed to provide the necessary assistance in the installation to
those companies that held the BUSing®Partner o
are BUSing®Installer certify and who also work with
INGENIUM's BUSing® Communications Equipment.
• The BUSing® Certificates are obtained by taking training courses that INGENIUM organizes periodically.
• For more information contact us:
(+34) 985 118 859 - tecnico@ingeniumsl.com
In the following pages you will fin detailed characteristics and techniques, a brief description and a
connection sketch for INGENIUM’s equipment.
• The end of the manual shows examples of different
types of installations: centralized, distributed, mixed,
prolonged and extended; besides several integrations
schemes with devices from other companies.
• It also includes information on programming software
developed by INGENIUM, the BUSing® Development
System (SIDE), as well as the APPs to control BUSing®
installations.
• The system is virtually unlimited, and can count up to
255 devices or nodes per line, up to 255 lines. It represents more than 65,000 devices with more than
300,000 outputs in the same installation.
• It is fully scalable and new devices can be always
added in an already existing installation. Installed devices can be also reprogrammed at any time.
• The communications protocol, BUSing®, can be wired
(4-wire BUS) or wireless (868 MHz frequency, grouped
in our WINGS-RF trademark).
Both types can coexist in the same installation establishing communications between different ways of
communication.
• Both the programming and implementation must be
carried out exclusively by installers / integrators who
are certified BUSing®.
For movement detection with concealed installation.
• Detects movement through solid, non-metallic objects
(brick, wood, etc)
• Detects minimum movements
• Hidden installation in false ceilings or walls
• Autonomous operation (no BUSing® required)
• Automatic reset after detection
• Adjustable timer from pulse to 17 min.
• Adjustable sensitivity up to 12m
• Size: 100 x 75 x 35mm
Description
This is an autonomous device (no BUSing®required). It is designed to be connected to the lighting in transit areas, such
as bathrooms, hallways or corridors and garages and installed in false ceilings and walls. Its hidden installation makes it
immune to vandalism.
It can detect objects through non-metallic solids by using radio frequency technology. It is superior to infra-red detectors,
from sensitivity to precision. It is practical, unobtrusive and easy to install and adds elegance to your lighting design.
Applicable power supplies depending on the load*
• Incandescent or halogen lamp 220V .......................................................... 2000W
To manage and monitor devices in the BUSing® installation.
• Slim design with integral front in customizable glass
• 2, 4 or 6 touch areas depending on the model
• LED indicators that can be or not associated to the touch areas
• Ability to manage an independent climate zone
(internal temperature sensor integrated)
• Rear case available in white or black
• Mounted on universal box, screwed on wall
• Size: 88 x 88 x 6mm (square format)
Description
Capacitive touch-button to control devices of a Busing® installation. It is available with 2, 4 or 6 touch areas depending
on the model, being possible to program BUS events for activation/deactivation of each one.
Built-in temperature is added. This, allows reading the measured temperature, setting a set point temperature and variation between winter, summer, mixed or deactivated mode as well as fan-coil control.
Customization
Available within a range of three levels of customization:
[1] basic: front glass and back casing in white or black.
[2] design: print customizable front glass with back casing in white or black.
[3] capriccio: interchangeable and print customizable front glass with back casing in white or black.
Configuration using Development System (SIDE)
• 2, 4 or 6 low voltage touch areas, programable as switch or push button.
• LED low voltage outputs that can be or not associated with the inputs of the device.
Technical Characteristics
Device
Reference
Cubic-SQ
Voltage
Supply
9–16V DC (BUS)
12
Current
Consumption
20mA (BUS)
Temperature
Range
0–51ºC
ingenium
www.ingeniumsl.com
capriccio
!
!
+12V
A
B
Ref.
88mm
80mm
88mm
80mm
60mm
Device
Rear
Wall
Universal box
1mm
Device
Side
The device is installed hanging from the two parallel grooves on its rear.
Two conical head screws are used in wall and/or universal mechanism box.
It is VERY IMPORTANT that the screws head excels 1mm from the wall.
Installation
SURFACE mounted
Glass
2mm
Rear
4mm
Front glass
interchangeable
Exclusively in the capriccio custom
s
eries, the glass is fixed to the rear with
a four magnets system that enables an
easy exchange.
custom series
Consumes
Red
Yellow
Green
Black
· Cubic-SQ
Installation
13
touch-buttons & thermostats
ingenium
· Cubic-V
[
Cubic-V6 · Cubic-V8
]
Vertical thermostat with temperature sensor
To manage and monitor devices in the BUSing® installation.
• Slim design with integral front in customizable glass
• 6 or 8 touch areas depending on the model
• LED indicators that can be or not associated to the touch areas
• Ability to manage an independent climate zone
(internal temperature sensor integrated)
• Rear case available in white or black
• Mounted on universal box, screwed on wall
• Size: 88 x 129 x 6mm (vertical/rectangular format)
Description
Capacitive touch-button to control devices of a Busing® installation. It is available with 6 or 8 touch areas depending on
the model, being possible to program BUS events for activation/deactivation of each one.
Built-in temperature is added. This, allows reading the measured temperature, setting a set point temperature and variation between winter, summer, mixed or deactivated mode as well as fan-coil control.
Customization
Available within a range of three levels of customization:
[1] basic: front glass and back casing in white or black.
[2] design: print customizable front glass with back casing in white or black.
[3] capriccio: interchangeable and print customizable front glass with back casing in white or black.
Configuration using Development System (SIDE)
• 6 or 8 low voltage touch areas, programable as switch or push button.
• LED low voltage outputs that can be or not associated with the inputs of the device.
Technical Characteristics
Device
Reference
Cubic-V
Voltage
Supply
9–16V DC (BUS)
14
Current
Consumption
20mA (BUS)
Temperature
Range
0–51ºC
ingenium
www.ingeniumsl.com
capriccio
+12V
A
B
Ref.
!
!
88mm
80mm
129mm
121mm
60mm
Device
Rear
Consumes
Wall
Universal box
1mm
Device
Side
The device is installed hanging from the two parallel grooves on its rear.
Two conical head screws are used in wall and/or universal mechanism box.
It is VERY IMPORTANT that the screws head excels 1mm from the wall.
Installation
SURFACE mounted
Glass
2mm
Rear
4mm
Front glass
interchangeable
Exclusively in the capriccio custom
s
eries, the glass is fixed to the rear with
a four magnets system that enables an
easy exchange.
custom series
Red
Yellow
Green
Black
· Cubic-V
Installation
15
touch-buttons & thermostats
ingenium
· Cubic-VH
Vertical touch panel for hotel room door - MUR/DND
To monitor the status of hotel rooms by BUSing®.
• Slim design with integral front in customizable glass
• 1 touch area for bell
• 2 signalling icons for room status
• Rear case available in white or black
• Mounted on universal box, screwed on wall
• Size: 88 x 129 x 6mm (vertical/rectangular format)
Description
BUSIng® device for placement in hotel room doors. It incorporates a capacitive touch area for room bell.
It has two signaling icons to distinguish between the room status: Do not disturb / Make up the room.
Customization
This device is available with the second level of customization:
[2] design: print customizable front glass with back casing in white or black.
Technical Characteristics
Device
Reference
Cubic-VH
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
20mA (BUS)
16
ingenium
www.ingeniumsl.com
capriccio
+12V
A
B
Ref.
!
!
88mm
80mm
129mm
121mm
60mm
Device
Rear
Consumes
Wall
Universal box
1mm
Device
Side
The device is installed hanging from the two parallel grooves on its rear.
Two conical head screws are used in wall and/or universal mechanism box.
It is VERY IMPORTANT that the screws head excels 1mm from the wall.
Installation
SURFACE mounted
Glass
2mm
Rear
4mm
Front glassinterchangeable
Exclusively in the capriccio customs
eries, the glass is fixed to the rear witha four magnets system that enables aneasy exchange.
custom series
Red
Yellow
Green
Black
· Cubic-VH
Installation
17
touch-buttons & thermostats
ingenium
· Cubic-T/TH
Square thermostat with temperature/+ humidity sensor
For climate control of a BUSing® installation area.
• Slim design with integral front in customizable glass
• Sensor temperature range 0–51ºC
• PI controller discretized
• Temperature range regulation adjustable by programming
• Incorporates humidity sensor (Ref. Cubic-TH)
• Rear case available in white or black
• Mounted on universal box, screwed on wall
• Size: 88 x 88 x 6mm (square format)
Description
BUSing® thermostat without graphical interface. The device acts as a BUSing® temperature sensor. Incorporates a discretized PI for greater comfort and energy savings.
Includes function modes for summer, winter and allow it to be mixed via modified BUS, and also allows fan coils control
and can be programmed BUS events for different speeds.
This device is available in two versions:
•Cubic-T: with only temperature sensor
•Cubic-TH: with temperature + humidity sensor.
Customization
Available within a range of three levels of customization:
[1] basic: front glass and back casing in white or black.
[2] design: print customizable front glass with back casing in white or black.
[3] capriccio: interchangeable and print customizable front glass with back casing in white or black.
Function Modes
• SUMMER mode: Performing actions before cooling demand.
• WINTER mode: Performing actions before heat demand.
• MIXED mode: Summer and winter mode simultaneously.
• OFF mode: Temperature reading without executing actions.
Technical Characteristics
Device
Reference
Cubic-T/TH
18
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
10mA (BUS)
Temperature
Range
0–51ºC
ingenium
www.ingeniumsl.com
capriccio
!
!
+12V
A
B
Ref.
88mm
80mm
88mm
80mm
60mm
Device
Rear
Wall
Universal box
1mm
Device
Side
The device is installed hanging from the two parallel grooves on its rear.
Two conical head screws are used in wall and/or universal mechanism box.
It is VERY IMPORTANT that the screws head excels 1mm from the wall.
Installation
SURFACE mounted
Glass
2mm
Rear
4mm
Front glass
interchangeable
Exclusively in the capriccio custom
s
eries, the glass is fixed to the rear with
a four magnets system that enables an
easy exchange.
custom series
Consumes
Red
Yellow
Green
Black
· Cubic-T/TH
Installation
19
touch-buttons & thermostats
ingenium
· Cubic-TL
Square thermostat with integrated LEDs indicator
For climate control and monitoring of a BUSing® installation area.
• Sensor temperature range 0–51ºC
• LED indicators for setpoint and ambient temperature
• 5 touch areas panel for climate control
• PI controller discretized
• Temperature range regulation adjustable by programming
• Programmable BUS events for each operating mode
• Rear case available in white or black, print customizable glass
• Mounted on universal box, screwed on wall
• Size: 88 x 88 x 6mm (square format)
Description
BUSing® thermostat with graphical interface. The device acts as a BUSing® temperature sensor. Incorporates a discretized PI for greater comfort and energy savings.
Includes function modes for summer, winter and allow it to be mixed via modified BUS, and also allows fan coils control
and can be programmed BUS events for different speeds.
Customization
Available within a range of three levels of customization:
[1] basic: front glass and back casing in white or black.
[2] design: print customizable front glass with back casing in white or black.
[3] capriccio: interchangeable and print customizable front glass with back casing in white or black.
Function Modes
• SUMMER mode: Performing actions before cooling demand.
• WINTER mode: Performing actions before heat demand.
• MIXED mode: Summer and winter mode simultaneously.
• OFF mode: Temperature reading without executing actions.
Technical Characteristics
Device
Reference
Cubic-TL
Voltage
Supply
9–16V DC (BUS)
20
Current
Consumption
35mA (BUS)
Temperature
Range
0–51ºC
ingenium
www.ingeniumsl.com
capriccio
!
!
+12V
A
B
Ref.
88mm
80mm
88mm
80mm
60mm
Device
Rear
Wall
Universal box
1mm
Device
Side
The device is installed hanging from the two parallel grooves on its rear.
Two conical head screws are used in wall and/or universal mechanism box.
It is VERY IMPORTANT that the screws head excels 1mm from the wall.
Installation
SURFACE mounted
Glass
2mm
Rear
4mm
Front glass
interchangeable
Exclusively in the capriccio custom
s
eries, the glass is fixed to the rear with
a four magnets system that enables an
easy exchange.
custom series
Consumes
Red
Yellow
Green
Black
· Cubic-TL
Installation
21
touch-buttons & thermostats
ingenium
· TRMD
Vertical thermostat with 2.8” integrated screen
For climate control and monitoring of a BUSing® installation area.
• 2.8" colour capacitive touch-screen included
• Graphical interface with 6 pre-configured colour combinations
• 8 touch areas panel for climate control
• Sensor temperature range 0–51ºC
• PI controller discretized
• Temperature range regulation adjustable by programming
• Programmable BUS events for each operating mode
• Rear case available in white or black, print customizable glass
• Mounted on universal box, screwed on wall
• Size: 88 x 129 x 4mm (vertical/rectangular format)
(13mm depth)
Description
BUSing® thermostat with graphical interface. The device acts as a BUSing® temperature sensor. Incorporates a discretized PI for greater comfort and energy savings.
Includes function modes for summer, winter and allow it to be mixed via modified BUS, and also allows fan coils control
and can be programmed BUS events for different speeds.
Customization
Available within a range of two levels of customization:
[1] basic: front glass and back casing in white or black.
[2] design: print customizable front glass with back casing in white or black.
Function Modes
• SUMMER mode: Performing actions before cooling demand.
• WINTER mode: Performing actions before heat demand.
• MIXED mode: Summer and winter mode simultaneously.
• OFF mode: Temperature reading without executing actions.
Technical Characteristics
Device
Reference
TRMD
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
35mA (BUS)
Temperature
Range
0–51ºC
22
ingenium
www.ingeniumsl.com
UP
!
!
Ref.
B
A
+12V
!
Device
Rear
Consumes
88mm
73mm
129mm
120mm
Use external mounting box is essential in any type of installation
allows future removal of the device.
To manage and monitor devices in the BUSing® installation.
• 4.3” LCD colour capacitive touch-screen
• Resolution 480 x 800px 4K colours
• Customizable interface appearance
• Supports up to 6 different themes
• Supports up to a total of 32 controls distributed on 4 pages
(8 checks per page)
• Own weather interface
• Ability to manage an independient climate zone
(internal temperature sensor integrated)
• Security options with No. password lock or menu restrictions
• Automatic software updates by Internet
• Mounted on universal box, screwed on wall
• Available in black or white finish
• Size: 88 x 129 x 4mm (13mm depth)
Description
Smart Touch is a vertical 4.3” colour capacitive touch interface that allows control and monitoring a BUSing® installation
by customizable icons on allusive images.
Its appearance is fully editable, from the wallpaper, even the colours of icons and text, controls, etc. You can set up to 6
different themes.
This screen integrates the ability to create a wireless network that will allow to control an installation locally from your
iOS or Android device, simply by downloading the official Ingenium apps.
An advanced version is avalaible, the ST-Plus, extending local connectivity capability to remote/Internet. It also has a
higher quality screen, better contrast and wider viewing angle. Besides it adds Google Home compatibility.
Configuration using Development System (SIDE)
• Choice of 3 custom themes from 9 editable options.
• Configuration of up to 32 controls distributed on 4 pages
• Program up to 16 scenes.
• Setup gestural shortcuts for execution of certain scenes.
Technical Characteristics
Device
Reference
Smart Touch
Voltage
Supply
9–16V DC (BUS)
26
Current
Consumption
380mA (BUS)
Screen
Resolution
480x800px
ingenium
www.ingeniumsl.com
UP
ConectorT
!
!
Ref.
B
A
+12V
!
Device
Rear
BUSing¨
connection
Using
ConnectorT
Consumes
88mm
73mm
129mm
120mm
Use external mounting box is essential in any type of installation
allows future removal of the device.
Device
4mm
8mm
14mm
SURFACE mounted
on universal box
Installation options
Mounting box
When installed
the mounting
box, fit the
device inside
in PLASTERBOARD
in MASONRY WALL
EMBEDDED
Plastic part to remove in EMBEDDED
installation for ConectorT access
Before fitting the device inside
remove external border in
MASONRY WALL installation
Glue connector housing In EMBEDDED installations
Orientation
Arrow should point
to the RIGHT
Ignore UP indication
carved in the box
WiFi connection
To local network
access
Cable BUSing¨
Connection for
crimp connector.
· Smart Touch
Installation
27
visualization
· PPL4-G
4” colour touch-screen
Installation controlling and monitoring through 3D plans.
• 4.3” LCD colour capacitive touch-screen
• Resolution 800 x 480px 4K colours
• All the features of the PPL series in the most
compact size.
• Mounted on universal box, screwed on wall
• Available in black or white finish
• Size: 129 x 88 x 4mm (13mm depth)
Description
The PPL4-G is a 4.3” colour capacitive touch interface to control and monitor a BUSing® installation using 3D drawings
and/or photographs, with alluding icons, custom panels, etc.
Like all models in PPL series, it allows to control thermostats in an installation, including the chrono-thermostat option
and the ability to perform annual time events, the real presence simulation and a weather prediction interface.
It has an integrated web server that allows to control the installation via the Internet using a web browser or through the official Ingenium Apps available for Google Android, Apple iOS and Samsung Smart TV. It is also Google Home compatible.
This display has Wi-Fi connectivity that allows upgrade to the latest software available or control the installation from the
cloud via Smartphone or Tablet.
Configuration using Development System (SIDE)
• Supports up to 100 control planes.
• Program up to 100 scheduled scenes.
• Armed and disarmed intruder alarm with password (4 digits).
• Technical alarm alerts using icons and screen messages,
e-mail messages or push notifications to mobile devices.
Technical Characteristics
Device
Reference
PPC4-G
Voltage
Supply
9–16V DC (BUS)
28
Current
Consumption
380mA (BUS)
Screen
Resolution
800x480px
ingenium
www.ingeniumsl.com
UP
ConectorT
Ref.
B
A
+12V
!
!
Device
Rear
129mm
120mm
88mm
73mm
Device
4mm
8mm
14mm
SURFACE mounted
on universal box
Installation options
Mounting box
WiFi connection
To local network
access
When installed
the mounting
box,
fit the
device inside
in PLASTERBOARD
in MASONRY WALL
EMBEDDED
Plastic part to remove in EMBEDDED
installation for ConectorT access
Before fitting the device inside
remove external border in
MASONRY WALL installation
Use external mounting box is essential in any type of installation
allows future removal of the device.
Glue connector housing In EMBEDDED installations
Consumes
BUSing¨
connection
Using
ConnectorT
Cable BUSing¨
Connection for
crimp connector.
· PPL4-G
Installation
29
visualization
· PPL7-G
7” colour touch-screen
Installation controlling and monitoring through 3D plans.
• 7.1” LCD colour capacitive touch-screen
• Resolution 800 x 480px 4K colours
• Controls thermostats in the installation,
including a chrono-thermostat option
• Executes anual timed events
• Technical alarm alerts using icons and screen
messages, e-mail messages or push notifications
to mobile devices
• Compatibility with Google Home for voice control
• Includes real presence simulation
• Automatic software updates by Internet
• Mounted on universal box, screwed on wall
• Available in black or white finish
• Size: 207 x 140 x 4mm (13mm depth)
Description
The PPL7-G is a 7.1” colour capacitive touch interface to control and monitor a BUSing® installation using 3D drawings
and/or photographs, with alluding icons, custom panels, etc.
It has an integrated web server that allows to control the installation via the Internet using a web browser or through the official Ingenium Apps available for Google Android, Apple iOS and Samsung Smart TV. It is also Google Home compatible.
This display has Wi-Fi connectivity that allows upgrade to the latest software available or control the installation from the
cloud via Smartphone or Tablet.
Configuration using Development System (SIDE)
• Supports up to 16 control planes.
• Program up to 100 scheduled scenes.
• Armed and disarmed intruder alarm with password (4 digits).
• Technical alarm alerts using icons and screen messages,
e-mail messages or push notifications to mobile devices.
Technical Characteristics
Device
Reference
PPC7-G
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
380mA (BUS)
Screen
Resolution
800x480px
30
ingenium
www.ingeniumsl.com
UP
ConectorT
!
!
Ref.
B
A
+12V
207mm
185mm
140mm
107mm
When installed
the mounting
box, fit the
device inside
Device
4mm
8mm
14mm
SURFACE mounted
in PLASTERBOARD
in MASONRY WALL
EMBEDDED
on universal box
Plastic part to remove in EMBEDDED
installation for ConectorT access
Glue connector housing In EMBEDDED installations
Installation options
Mounting box
171mm
119mm
Device
Rear
Before fitting the device inside
remove external border in
MASONRY WALL installation
Use external mounting box is essential in any type of installation
allows future removal of the device.
BUSing¨
connection
Using
ConnectorT
Consumes
To software actualization,
weather forecast and upload
data from the SIDE (plans and
configuration).
WiFi connection
Cable BUSing¨
Connection for
crimp connector.
· PPL7-G
Installation
31
visualization
· PPL10-G
10,4” colour touch-screen
Installation controlling and monitoring through 3D plans.
• 10.4” LCD colour capacitive touch-screen
• Resolution 640 x 480px 4K colours
• Controls thermostats in the installation,
including a chrono-thermostat option
• Executes anual timed events
• Technical alarm alerts using icons and screen
messages, e-mail messages or push notifications
to mobile devices
• Compatibility with Google Home for voice control
• Includes real presence simulation
• Automatic software updates by Internet
• Mounted on universal box, screwed on wall
• Available in black or white finish
• Size: 307 x 227 x 4mm (24mm depth)
Description
The PPL10-G is a 10.4” colour capacitive touch interface to control and monitor a BUSing® installation using 3D drawings and/or photographs, with alluding icons, custom panels, etc.
It has an integrated web server that allows to control the installation via the Internet using a web browser or through the official Ingenium Apps available for Google Android, Apple iOS and Samsung Smart TV. It is also Google Home compatible.
This display has Wi-Fi connectivity that allows upgrade to the latest software available or control the installation from the
cloud via Smartphone or Tablet.
Configuration using Development System (SIDE)
• Supports up to 100 control planes.
• Program up to 100 scheduled scenes.
• Armed and disarmed intruder alarm with password (4 digits).
• Technical alarm alerts using icons and screen messages,
e-mail messages or push notifications to mobile devices.
Technical Characteristics
Device
Reference
PPC10-G
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
760mA (BUS)
Screen
Resolution
640x480px
32
ingenium
www.ingeniumsl.com
UP
UP
UP
+12V
A
B
Ref.
!
+12V
A
B
GND
+12V
A
B
GND
Device
Rear
Consumes
Device
Wall bracket
120mm
180mm
4mm
24mm
307mm
280mm
227mm
195mm
WiFi connection
To local network
access
The correct
orientation of
the device is
UP arrow.
Use the metal wall bracket included screwing it to wall and/or flushmounted universal box, hanging the device on the 6 slots located
in the rear.
6 hanger slots
Cable BUSing¨
Connection for
crimp connector.
· PPL10-G
Installation
33
visualization
á ETHBUS3
Servidor Web
Web Server
N L
~
+12VAB
Ref.
+12VAB
Ref.
21
ingenium
www.ingeniumsl.com
Ethernet
· ETHBUS3
WEB server to remote control of BUSing® installations
Enables installation controlling via Internet using a conventional Web browser
or by the applications available for iOS, Android and Samsung Smart TV.
• Integrated web server
• Internet control and monitoring of the entire installation
• Java fully graphical interface with 3D planes
• Apps for Android, Apple iOS, Samsung Smart TV and PC for
local or remote control and Google Home compatibility
• Configurable IP with the Development System (SIDE)
• Programming via FTP
• DIN Rail mount (6 modules)
Description
Allows the installation to be controlled from any PC connected to the Internet with a conventional WEB browser through
Ingenium server or using Adroid devices, Apple iOS or Samsung Smart TV locally or remotely.
The device requests a password to control access to the installation and displays the status of the devices installed with
icons on a colour 3D planes or photographs, as configured in the Development System (SIDE).
The entire interface is graphical and intuitive and allows an easy control of the installation: on-off lighting, lighting control, blind control, on-off heating, temperature control of the rooms, programming thermostats, shortcuts available to act
on any part of the installation, perform scenes, etc. It also allows voice control with Google Home.
For remote control using the APPs available for Android, Apple iOS or Samsung Smart TV you need to configure the
router installation (see the device instructions) and use a dynamic DNS service if you do not have a static IP address.
Configuration using Development System (SIDE)
JAVA Application Control:
• Supports up to 100 control planes.
• Program up to 100 scenes.
• Access to the installation locally or via Ingenium server with password (www.ingeniumsl.com).
Android, Apple iOS, Google Samsung Smart TV control apps:
• See instructions.
Technical Characteristics
Device
Reference
EHTBUS3
Voltage
Supply
230V AC
Power
Consumption
2.8VA
Internet
Connection
ETHERNET 10Mbit/s
34
ingenium
www.ingeniumsl.com
SmartPhone
Tablet
á ETHBUS3
Servidor Web
Web Server
NL
~
+12VAB
Ref.
+12VAB
Ref.
21
ingenium
www.ingeniumsl.com
Ethernet
Google
Home
BUS 1
Ethernet
Ethernet
BUS 2
+12V
A
B
Ref.
+12V
A
B
Ref.
á ETHBUS3
Microprocessor
Supply
ETHBUS3 basic wiring
To function as a control
via Internet.
Phase
Neutral
DSL router
DSL connection
PC
Gives
Consumes
BUS 2 wiring
Additional BUS that
can supply power.
BUS 1 wiring
For conventional
installations, use
this BUS only.
Programming via FTP
To upload data from the SIDE
(plans and configuration).
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Wireless connection
Local by the Wi-Fi router
o
r remote by 3G Internet.
Local connection
Exclusive option, by
W
i-Fi or via Ethernet.
DS202000 installation with ADS Router
Via the Ethernet network, Wi-Fi and 3G/4G Internet
Cable BUSing¨
Connection for
crimp connector.
Cable BUSing¨
Connection for
screw terminal.
· ETHBUS3
Installation
35
security
ingenium
www.ingeniumsl.com
á KA
Centralita Alarmas
Alarm Smartbox
NL
~
Ð+
BAT.
BOILER
4
Ref.
Ref.
Ref.
Ref.
+12V
3561
KEY2OFF4PRG
Fire
Water
Intr.
+12VAB
Ref.
EVGAS5EVAGUA6SIREN
3
+12VAB
Ref.
SUPPLY
ingenium
www.ingeniumsl.com
á KCtr-BS
Centralita Alarmas
Alarm Smartbox
NL
~
Ð+
BAT.
+Ð
AUD.TEL.
OUT
BOILER
4
Ref.
Ref.
Ref.
Ref.
+12V
3561
KEY2OFF4PRG
Fire
Water
Intr.
+12VAB
Ref.
EVGAS5EVAGUA6SIREN
3
+12VAB
Ref.
SUPPLY
á GSMing
centralita alarmas GSM
GSM alarm smartbox
NL
~
+12VAB
Ref.
IN 3
IN 4
IN 1
IN 2
Z1 Z2Z3 Z4
sim
ingenium
www.ingeniumsl.com
á RFID-BUS
ingenium
www.ingeniumsl.com
· KA· KCtr-BS
36
· GSMing
· RFiD-BUS
ingenium
www.ingeniumsl.com
KA ...................................................................38
Allows Technical alarms and BUSing® installation components management.
• 6 digital inputs ready for several sensors connections
• 4 digital outputs for direct control of
the installation
• DIN Rail mount (9 modules)
Description
Technical alarms management central (intrusion, flooding, fire, gas…).
This module, combined with a BUSing® interface with integrated web server (PPL10, PPL7, PPL4, ST-Plus or ETHBUS3),
allows to know and control the status of the home automation installation 24/7 and to receive notifications, on mobile
devices, when there is a technical alarm warning.
Inputs
• 6 digital inputs low voltage (SELV) 5V, with a delay of 3 seconds to prevent false alarms.
• Outputs for connection of conventional gas sensors, fire, flood and intrusion.
• Free inputs for magnetic contacts, medical alarm, etc.
Outputs
• 4 digital relay outputs power free for siren, water electrovalve, gas electrovalve and boiler.
• Switching capacity 6A @ 230V AC per output. To control circuits with higher power interlay a contactor.
Technical Characteristics
Device
Reference
KCtr-BS
* only sensors BUS
** potential free outputs to relay
40
Voltage
Supply
230V AC
Max. Power
Consumption
5VA
Current
Given
300mA* (BUS)
No.
Outputs
4**
Switching capacity
of each output
6A
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
BUS
!
Router
+12V
A
B
Ref.
1
2
3
4
Ð+
Ð+
Bat.
Ð+
+Ð
Aud.Tel.
OUT
á DH
Fire/Smoke Sensor
LOOP type
KCtr connection
Max. distance: 30m
Phase
Neutral
N.A. Gas
Electrovalve
(220V AC)
or Siren
Neutral
Phase
Push-Button
Cancel Alarms
Desactivate
Alarms
Ref.
E4: Not Programmed
E2: Unlock Button
E1: Armed Key
S4: Boiler
S5: EV Gas
S6: EV Agua
S3: Siren
E6: Flood Sensors
E5: Fire/Smoke Sensors
E3: Movement Sensors
Microprocessor
Supply
Battery
Battery
Automatic loading
if KCtr with voltage
VERY IMPORTANT
Respect Polarity
Do not connect
batteries over 3A/h
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
DSL installation
A filter must be used for
compatibility.
Tel. line
EXTERNAL
Filter
Cable BUSing¨
Connection for
screw terminal.
Sensors
(Detection)
Gives
· KCtr-BS
Installation of Fire/Smoke Sensors – Loop Type
41
security
+12V
A
B
Ref.
BUS
!
+12V
A
B
Ref.
Bat.
+Ð
Aud.Tel.
OUT
Ð+
Ð+
NANCC
Ð+
á SG
Fire/Smoke sensor
CONTACT type
N.A. Gas
Electrovalve
(220V AC)
or Siren
Neutral
Phase
Push-Button
Cancel Alarms
Desactivate
Alarms
Microprocessor
Supply
Ref.
+12V
Phase
Neutral
Ref.
E4: Not Programmed
E2: Unlock Button
E1: Armed Key
S4: Boiler
S5: EV Gas
S6: EV Agua
S3: Siren
E6: Flood Sensors
E5: Fire/Smoke Sensors
E3: Movement Sensors
Battery
Tel. line
EXTERNAL
DSL installations > See page: 33
Battery
Automatic loading
if KCtr with voltage
VERY IMPORTANT
Respect Polarity
Do not connect
batteries over 3A/h
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
Sensors
(Detection)
Gives
· KCtr-BS
Installation of fire/smoke sensors – Contact type
41
42
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
BUS
!
+12V
Ref.
+12V
A
B
Ref.
Bat.
+Ð
Aud.Tel.
OUT
Ð+
Ð+
á Sif
Movement sensor
INFRARED type
Microprocessor
Supply
Siren
Switch
Key or Keypad
Activate
Intruder
Ref.
+12V
Phase
Neutral
Ref.
E4: Not Programmed
E2: Unlock Button
E1: Armed Key
S4: Boiler
S5: EV Gas
S6: EV Agua
S3: Siren
E6: Flood Sensors
E5: Fire/Smoke Sensors
E3: Movement Sensors
Battery
Tel. line
EXTERNAL
DSL installations > See page: 33
Battery
Automatic loading
if KCtr with voltage
VERY IMPORTANT
Respect Polarity
Do not connect
batteries over 3A/h
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
Sensors
(Detection)
Gives
· KCtr-BS
Installation of Movement Sensors – Infrared Type
41
43
security
á SIn-2h
+12V
A
B
Ref.
BUS
!
+12V
A
B
Ref.
Bat.
+Ð
Aud.Tel.
OUT
Ð+
Ð+
Push-Button
Cancel Alarms
Desactivate
Alarms
á Sin-2h
Flood sensor
2 wires
Microprocessor
Supply
N.A. Gas
Electrovalve
(220V AC)
Flood
Signal
Neutral
Phase
Phase
Neutral
Ref.
E4: Not Programmed
E2: Unlock Button
E1: Armed Key
S4: Boiler
S5: EV Gas
S6: EV Agua
S3: Siren
E6: Flood Sensors
E5: Fire/Smoke Sensors
E3: Movement Sensors
Battery
Tel. line
EXTERNAL
DSL installations > See page: 33
Battery
Automatic loading
if KCtr with voltage
VERY IMPORTANT
Respect Polarity
Do not connect
batteries over 3A/h
KCtr connection
Max. distance: 30m
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
Sensors
(Detection)
Gives
· KCtr-BS
Installation of flood sensors – 2 wires
41
44
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
BUS
!
+12V
A
B
Ref.
Ð+
Bat.
Ð+
+Ð
Aud.Tel.
OUT
Heater
Air cond.
Neutral
Phase
Conventional
Thermostat
Microprocessor
Supply
Phase
Neutral
Ref.
E4: Not Programmed
E2: Unlock Button
E1: Armed Key
S4: Boiler
S5: EV Gas
S6: EV Agua
S3: Siren
E6: Flood Sensors
E5: Fire/Smoke Sensors
E3: Movement Sensors
Battery
Tel. line
EXTERNAL
DSL installations > See page: 33
Battery
Automatic loading
if KCtr with voltage
VERY IMPORTANT
Respect Polarity
Do not connect
batteries over 3A/h
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
Sensors
(Detection)
Gives
· KCtr-BS
Installation of Temperature Circuit
41
45
security
á GSMing
centralita alarmas GSM
GSM alarm smartbox
NL
~
+12VAB
Ref.
IN 3
IN 4
IN 1
IN 2
Z1Z2Z3Z4
sim
ingenium
www.ingeniumsl.com
· GSMing
Technical alarm BUSing® center with SMS controlling
Allows technical alarms and installation components management by SMS.
• System monitoring by SMS
• Management of up to 5 technical and intrusion alarms
• Setting up for 3 phone numbers
• Ability to perform up to 10 scenes
• DIN Rail mount (6 modules)
Description
This device allows control of alarms and any element of a BUSing® installation by SMS text messages, allowing scenes
run and point to point control of different areas of the facility: on and off lighting, shutter control, thermostats, etc.
No phone line required for operation, only a SIM card (no PIN configured).
Additionally is provided with 4 relay outputs with potential free switching capacity of 10A per output allowing for example
the opening and closing of the gas solenoid or water installation.
Configuration using Development System (SIDE)
• Set up to 3 phone numbers from which you send commands and receive alerts.
• Alerts of up to 5 alarms and intrusion techniques.
• Program up to 10 scenes (command: Run + scene name).
• Up to 16 point to point (commands: On, Off or regulates + output name).
Outputs
• 4 digital relay outputs power free for water electro valve, gas solenoid valve, etc.
• Switching capacity 10A @ 230V AC per output. For controlling circuits of higher power interlay a contactor.
All inputs are SELV.
They are internally referred to 5V and
they are activated when connected to Ref.
Phase
Neutral
GSMing output wiring
Maximum power per output, 10A resistive load.
Key
Light
Plug
Switch
Push-Button
Consumes
Microprocessor
Supply
Phase
Neutral
Electrovalve
Cable BUSing¨
Connection for
screw terminal.
· GSMing
Installation
47
security
á RFID-BUS
ingenium
www.ingeniumsl.com
· RFiD-BUS
BUSing® - RFID smart cards reader
For access control through RFID cards.
• Allows to program 255 identifiers (IDs) per device
• Permission or time restriction for 5 different levels of users
• 3 operational modes: push button, long/short and switch
• Output to transistor (300mA, minimum 30V DC) to connect to the lock
• Screw mounting on universal mechanism box
• Size: 55 x 55 x 10mm
Description
Device designed to be use with smart/intelligent cards (reference: TjRFiD).
Each device allows to read, control, interpret and program up to 255 users with different identification (255 users per device).
The card reader will distinguish the card to read, interpret and execute actions that have been programmed on it.
An specific schedule can be assigned to a each card to allow or restrict access to a particular personal stay level. This
schedule can be programmed easily subdivided at intervals of 30 minutes for each of the seven days of the week to five
user levels 0 through 4.
This device is also used, together with the Software Control for Hotels (reference: SH-PC), to program smart cards and access controls to rooms, common zones, privates areas, etc. You can also use it to activate/deactivate intruder alarms.
Operating Modes
•Push button mode: executes programmed scenes by change of flank.
•Switch mode: executes programmed scenes by level (ascendant flank-descendant flank).
•Long/short mode: distinguishes long/short detection of the RFID card.
• Programmable inputs to work with switches or pushbutton
• 2 programmable BUS events for each input
• Size: 50 x 35 x 25mm
Description
The 2E2S is an on/off actuator equipped with 2 digital outputs with potential free relay with a switching capacity of 10A
per output and 2 digital inputs for low voltage (SELV) referred to the mass of BUS.
From the Development System (SIDE) is possible to assign sequences of 15 characters for each one of the outputs and
entries. You can also set the mode of operation of each of the inputs (button, switch or electric blinds mode), and two
BUS events for each input (one trigger event and one-off), allowing thus acting on any element of the installation from
the device inputs.
Inputs
• 2 digital inputs low voltage (SELV) 5V, minimum activation current 5mA.
• Active when connected to BUS mass.
• Maximum distance from device to switch or push-button, 30m.
• Configurable hardware and software filter through Development System (SIDE).
Outputs
• 2 digital outputs with potential free relay.
• Switching capacity 10A @ 230V AC per output. To control circuits with higher power interlay a contactor.
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
Electrovalve
Phase
+24V~
Cable BUSing¨
Connection for
screw terminal.
· 2E2S
Installation
183
53
á
2E2S-C30A
Z1Z2
IN1
IN2
ingenium
www.ingeniumsl.com
+12VAB
Ref.
input /output
· 2E2S-C30A
2 digital inputs and 2 digital outputs actuator
To control 2 electrical loads or 1 blind/curtain.
• 2 digital inputs low voltage (SELV) referred to the BUS mass
• 2 digital outputs with potential free relay
• Remembers last position when power fails
• Programmable inputs to work with switches or pushbutton
• 2 programmable BUS events for each input
• DIN Rail Mount (2 modules)
Description
The 2E2S-C30A is an on/off actuator equipped with 2 relay outputs with potential free switching capacity of 30A output
and 2 inputs for low voltage (SELV) referred to BUS mass.
From the Development System (SIDE) is possible to assign sequences of 15 characters for each one of the outputs and
entries. You can also set the mode of operation of each of the inputs (button, switch or electric blinds mode), and two
BUS events for each input (one trigger event and one-off), allowing thus acting on any element of the installation from
the device inputs.
This version of 2E2S, is indicated for the control of lighting capacitive outputs, appliances, etc. Not connection available
to 230V AC, so it does not provide power to the BUS, rather uses it. Also the relays incorporate a manual reset.
Inputs
• 2 digital inputs low voltage (SELV) 5V, minimum activation current 5mA.
• Active when connected to BUS mass.
• Maximum wiring distance to switch or pushbutton: 30m.
• Programmable filter hardware and software from the Development System (SIDE).
Outputs
• 2 digital triac outputs.
• Switching capacity 2A @ 230V AC per output. To control circuits with higher power interlay a contactor.
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
+24V
Neutral
Phase
Neutral
2E2S-C30A output wiring
Maximum power per output, 30A resistive load.
Key
Plug
Switch
Push-Button
Consumes
Microprocessor
Electrovalve
Manual reset
Lifting up the device
cover you will find the
relay switches, one per
output
OpenClosed
Cable BUSing¨
Connection for
screw terminal.
· 2E2S-C30A
Installation
55
ingenium
www.ingeniumsl.com
Z1Z2Z3Z4
+12VAB
Ref.
N L
~
á 4E4S
actuador
actuator
IN 3
IN 4
IN 1
IN 2
Ref.
input /output
· 4E4S
4 digital inputs and 4 digital outputs 10A actuator
To control 4 electrical loads or 2 blinds/curtains.
• 4 digital inputs low voltage (SELV) referred to BUS mass
• 4 digital outputs with potential free relay depending on model
• Integrated power supply (depending on model) capable of delivering 150mA
power to other BUS devices
• Remembers last position when power fails
• Programmable inputs to work with switches or pushbutton
• 2 programmable BUS events for each input
• DIN rail mounting (4 modules) or in a distribution box, 70mm depth
Description
The 4E4S is an on/off actuator equipped with 4 relay outputs with potential free switching capacity of 10A output and 4
inputs for low voltage (SELV) referred to BUS mass.
From the Development System (SIDE) is possible to assign sequences of 15 characters for each one of the outputs and
entries. You can also set the mode of operation of each of the inputs (button, switch or electric blinds mode), and two
BUS events for each input (one trigger event and one-off), allowing thus acting on any element of the installation from
the device inputs.
Inputs
• 4 digital inputs low voltage (SELV) 5V, minimum activation current 5mA.
• Active when connected to BUS mass.
• Maximum distance from device to switch or push-button, 30m.
• Configurable hardware and software filter through Development System (SIDE).
Outputs
• 2 digital outputs with potential free relay.
• Switching capacity depending on model. To control circuits with higher power interlay a contactor.
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
Phase
Neutral
4E4S output wiring
Maximum power per output, 10A resistive load.
Key
Light
Plug
Switch
Push-Button
Gives
Microprocessor
Supply
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
· 4E4S
Installation
57
input /output
Z1 Z2 Z3Z6
IN 5
IN 6
Ref.
IN 1
IN 2
IN 3
IN 4
Z4 Z5
+12VAB
Ref.
NL
~
á 6E6S-F2A
actuador
actuator
ingenium
www.ingeniumsl.com
· 6E6S-F2A
6 digital inputs and 6 digital outputs 6A actuator (triac)
To control 6 electrical loads or 3 blinds/curtains.
• 6 digital inputs low voltage (SELV) referred to BUS mass
• 6 digital triac outputs internally connected to phase
• Integrated power supply (depending on model) capable of delivering 150mA
power to other BUS devices
• Remembers last position when power fails
• Programmable inputs to work with switches or pushbutton
• 2 programmable BUS events for each input
• DIN rail mounting (4 modules) or in a distribution box, 70mm depth
Description
The 6E6S-F2A is an on/off actuator equipped with 6 digital triac outputs internally connected to phase with a switching
capacity of 12A (summing all outputs) and 6 digital inputs low voltage (SELV) referred to BUS mass.
This actuator is indicated for the control of fluorescent or LEDs preceded by a transformer, by having triac outputs (not
suitable for DC).
From the Development System (SIDE) is possible to assign sequences of 15 characters for each one of the outputs and
entries. You can also set the mode of operation of each of the inputs (button, switch or electric blinds mode), and two
BUS events for each input (one trigger event and one-off), allowing thus acting on any element of the installation from
the device inputs.
Inputs
• 6 digital inputs low voltage (SELV) 5V, minimum activation current 5mA.
• Active when connected to BUS mass.
• Maximum distance from device to switch or push-button, 30m.
• Configurable hardware and software filter through Development System (SIDE).
Outputs
• 6 digital outputs internally connected to phase.
• Switching capacity depending on model. To control circuits with higher power interlay a contactor.
Maximum power of 12A resistive load,
summing all outputs.
For blinds/curtains wiring
See diagram page 194
Microprocessor
Supply
Light
Switch
Push-Button
6E6S input wiring
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
Gives
Supply
230V AC ~ 50Hz
Optional
110V AC ~ 60Hz
Cable BUSing¨
Connection for
screw terminal.
· 6E6S-F2A
Installation
182
59
input /output
IN 3
IN 4
IN 1
IN 2
á 4E8S
actuador
actuator
Z1Z2Z3Z4Z5Z6
Z8Z7
+12VAB
Ref.
ingenium
www.ingeniumsl.com
· 4E8S
4 digital input 8 digital output actuator
To control 8 electrical loads or 4 blinds/curtains.
• 4 digital inputs Low Voltage (SELV) referred to BUS mass
• 8 digital outputs power free by model
• Remembers last position when power fails
• Programmable inputs to work with switches or pushbutton
• 2 programmable BUS events each entry
• DIN rail mounting (6 modules)
or in a distribution box, 70mm depth
Description
The 4E8S is an on/off actuator equipped with 8 relay outputs power free with a breaking capacity of 10A, 4 low voltage
inputs (SELV) referred to BUS mass.
From the Development System (SIDE) is possible to assign sequences of 15 characters for each one of the outputs and
entries. You can also set the mode of operation of each of the inputs (button, switch or electric blinds mode), and two
BUS events for each input (one trigger event and one-off), allowing thus acting on any element of the installation from
the device inputs.
Inputs
• 4 digital inputs low voltage (SELV) 5V, minimum activation current 5mA.
• Active when connected to BUS mass.
• Maximum wiring distance to switch or pushbutton: 30m.
• Programmable filter hardware and software from the Development System (SIDE).
Outputs
• 8 digital triac outputs.
• Switching capacity 10A @ 230V AC per output. To control circuits with higher power interlay a contactor.
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
4E8S output wiring
Maximum power per output, 10A resistive load.
Key
Light
Plug
Switch
Push-Button
Consumes
Microprocessor
Electrovalve
Phase
NeutralNeutral
Phase
Phase
Neutral
Cable BUSing¨
Connection for
screw terminal.
· 4E8S
Installation
61
ingenium
www.ingeniumsl.com
á MECing
In1
In2
In3
Ref.
+12V
A
B
Ref.
input /output
· MECing
[
MECing · MECing-4
]
Adaptor for mechanical controls to BUSing®
Device with digital low voltage inputs.
• Digital low voltage (SELV) inputs referred to BUS reference
• Up to 60 programmable events per scene and 2 scenes per input
• Remembers last position against power failures
• Programmable inputs to work with switches or push-buttons
• Mounting into universal mechanism box. Size: 45 x 45 x 10mm
Description
Input device designed to be installed in mechanism boxes, behind the mechanisms (switches or push-buttons), being especially useful to distribute the installation and to execute events.
It has 3 or 4 digital inputs, depending on version, being possible to program BUS events for activation and deactivation
of each input.
Supports 3 operating modes: Mode button, Mode switch and repeat mode, selectable for each of the inputs, also providing a configurable delay timer after pressing.
Version available designed for installation on DIN rail (reference: MECing-C, page 64).
Inputs
• Low voltage 5V inputs (SELV), minimum activation current: 15mA
• Activated when connected to Ref.
• Maximum cabled distance to the switch or push-button: 30m.
• Each input has a delay timer once it has been pulsed,
which is configurable through Development System (SIDE).
Technical Characteristics
Device
Reference
MECing
MECing-4
* operating modes of the inputss: button (Pul.), switch (Int.) o repetition (Rep.)
62
Voltage
Supply
9–16V DC (BUS)
9–16V DC (BUS)
Current
Consumption
40mA (BUS)
40mA (BUS)
No.
Inputs
3
4
No.
Scripts/Scene
2
2
No.
Scenes/Input
60
60
Operating
Modes*
Pul./Int./Rep.
Pul./Int./Rep.
ingenium
www.ingeniumsl.com
+5V
In1
In2
In3
Ref.
123
+12V
A
B
Ref.
MECing input wiring
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
Wall mounted
Behind the mechanism.
Key
Switch
Push-Button
Consumes
MECing-4
Available version
with 4 inputs.
(Ref. MECing-4)
Cable BUSing¨
Connection for
screw terminal.
· MECing
Installation
63
input /output
ingenium
www.ingeniumsl.com
á
MECing
INT1
INT2
INT3
Ref.
+12VAB
Ref.
· MECing-C
Adaptor for mechanical controls to BUSing®
Device with 3 digital low voltage inputs.
• 3 digital low voltage (SELV) inputs referred to BUS reference
• Up to 60 programmable events per scene and 2 scenes per input
• Remembers last position against power failures
• Programmable inputs to work with switches or push-buttons
• DIN rail mounted (2 modules) or in distribution box with depth 70mm
Description
Device similar to regular MECing, but designed for DIN rail mounting (2 modules). Especially useful to distribute the installation and to execute events.
It has 3 digital inputs, being possible to program BUS events for activation and deactivation of each.
Supports 3 operating modes: Mode button, Mode switch and repeat mode, selectable for each of the inputs, also providing a configurable delay timer after pressing.
Inputs
• Low voltage 5V inputs (SELV), minimum activation current: 15mA
• Activated when connected to Ref.
• Maximum cabled distance to the switch or push-button: 100m.
• Each input has a delay timer once it has been pulsed,
which is configurable through Development System (SIDE).
Technical Characteristics
Device
Reference
MECing-C
* operating modes of the inputs: button (Pul.), switch (Int.) o repetition (Rep.)
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
40mA (BUS)
64
No.
Inputs
3
No.
Scripts/Scene
2
No.
Scenes/Input
60
Operating
Modes*
Pul./Int./Rep.
ingenium
www.ingeniumsl.com
123
BUS
+12V
A
B
Ref.
In1
In2
In3
Ref.
MECing input wiring
Low voltage inputs (SELV), sepa rated
by an optical isolator; they are
activated when connected to Ref.
Regulator to control adjustable, electronic ballasts
Regulates fluorescent lighting, or adjustable electronic ballast lighting.
• 1 channel regulation
• Protection against circuit overload in output 1–10V
• Output to relay for turning ballasts on/off (not circuit overload protected)
• Digital control using a 200 regulation points Micro-Controller
• DIN rail mounted (4 modules) or in distribution box with depth 70mm
Description
This actuator is indicated for achieving a fine and precise digital control receiving orders only via the bus, whether it is
wired or wireless, so you can control these devices from conventional buttons (using MECing), from remote controls,
touch-screens, PC, etc.
Is possible to configure the ramp control, ie the progressive on-off lighting and assign 15 characters strings to identify
its output, using the Development System software (SIDE).
Outputs
On/Off Relay
• Maximum current 10A
• The number of ballasts that can be connected will depend on their activation peaks.
• To control circuits with higher power interlay a contactor.
1–10V tension
• This device can provide up to 35mA in the 1-10V voltage outputs.
• To calculate the maximum number of supported ballasts, consult the technical information provided by the ballast
manufacturer.
Technical Characteristics
Device
Reference
RBF10A
* without connection to 230V AC
** triac output internally connected to phase
Voltage
Supply
85–265V AC
9–16V DC (BUS)
68
Max. Power
Consumption
2.8VA @ 230V AC
Current
Given
50mA (BUS)
Current
Consumption
250mA* (BUS)
Max. Current
Output 1–10 V
35mA
No.
Outputs
1**
ingenium
www.ingeniumsl.com
BUS
+12V
A
B
Ref.
+
Ð
+
Ð
1-10V d.c
NF
Phase
Neutral
Fluorescent
Fluorescent
RBF10A output wiring
Maximum cut-off capacity 10A
Key
Ballast/Transformer
Adjustable 1Ð10V
Microprocessor
Supply
Phase
Control
Gives
Supply
85Ð265V AC
50~60Hz
Cable BUSing¨
Connection for
screw terminal.
· RBF10A
Installation
69
dimmers
á RU1S200
regulador universal
universal dimmer
ingenium
www.ingeniumsl.com
+12VAB
Ref.
NC
NC
~L1~N~N~
L1
· RU1S200
1-channel universal regulator, triac dimmer with BUSing® control
To regulate LED, incandescent or halogen lighting, with or without incorporated transformer.
• 1-channel regulation
• Protection against overloads
• Digital control using a 200 regulation points Micro-Controller
• Luminaire or ceiling intregration mounting
• Size: 37 x 77 x 17mm
Description
RU1S200 is a proportional universal actuator to regulate 1 channel with a maximum of 200W. This device allows the
regulation of any type of load, be it halogen, incandescent or LED, with or without incorporated transformer. It is prepared
to avoid the problems of flickering, incompatibilities or other inconsistencies resulting from lighting regulation.
This actuator is designed for achieving a fine and precise digital control receiving orders only via the bus, whether it is
wired or wireless. So this device can be controlled from conventional push-buttons (using MECing), from remote controls,
touch-screens, etc.
Using the Development System software (SIDE) is possible to configure the ramp control (progressive on-off lighting), or
lower limit and upper limit.
Applicable power supplies depending on the load
• LED lighting load .................................................................................................. 200W
• Incandescent or halogen loads 230V AC ................................................................. 200W
• Low Voltage loads with a conventional transformer
• Low Voltage loads with a electronic transformer
(1) Estimated power calculated with the losses of each type of lighting.
(2) When using transformers, they must be LEADING EDGE or TRAILING-LEADING EDGE type.
2-channel universal regulator, triac dimmer with BUSing® control
To regulate LED, incandescent or halogen lighting, with or without incorporated transformer.
• 2-channel regulation
• Protection against overloads
• Digital control using a 200 regulation points Micro-Controller
• DIN rail mounted (4 modules) or in distribution box with depth 70mm
Description
RU2S200 is a proportional universal actuator to regulate 2 channels with a
maximum of 200W each. This device allows the regulation of any type of load,
be it halogen, incandescent or LED, with or without incorporated transformer.
It is prepared to avoid the problems of flickering, incompatibilities or other inconsistencies resulting from lighting regulation.
Designed for achieving a precise digital regulation, receiving commands via the bus or from conventional push buttons
connected to its inputs, using standard control long/short keystroke.
Using the Development System software (SIDE) is possible to configure the ramp control (progressive on-off lighting), or
lower limit and upper limit.
Applicable power supplies depending on the load
• LED lighting load .................................................................................................. 200W
• Incandescent or halogen loads 230V AC ................................................................. 200W
• Low Voltage loads with a conventional transformer
• Low Voltage loads with a electronic transformer
(1) Estimated power calculated with the losses of each type of lighting.
(2) When using transformers, they must be LEADING EDGE or TRAILING-LEADING EDGE type.
Inputs
• 2 digital inputs low voltage (SELV) 5V,
minimum activation current 5mA.
• For pushbutton (non-programmable input
linked to the output of the device).
All inputs are SELV.
They are internally referred to 5V
and they are activated when
connected to Ref.
RU2S200 output wiring
Maximum power per output 200W.
Key
Switch
Consumes
Microprocessor
Supply
85Ð265V AC
50~60Hz
Phase
Neutral
Supply
Phase
Control 2
Phase
Control 1
Supply
Light/LED
Cable BUSing¨
Connection for
screw terminal.
· RU2S200
Installation
73
dimmers
á RGBL
regulador LED
LED dimmer
ingenium
www.ingeniumsl.com
GND
B GR
+12 +24
+12VAB
Ref.
+12 +24
ingenium
www.ingeniumsl.com
+12VAB
Ref.
á RGBW-C
GND
B GR
+12 +24
W
· RGBL
[
RGBL · RGBL-C
]
3-channel dimmer to regulate RGB LED modules with BUSing® control
Allows control of RGB LED strips to create different shades of environment.
• 3 independent regulation channels
(Red, Green, and Blue)
• Individual programming control values
for each channel
• Digital regulation control based on microcontroller with more than 200 regulation points
• PWM dimming metod
· RGBL
Luminaire or ceiling intregration
mounting version.
• Size:
37 x 77 x 17mm
Description
RGBL is a three channels lighting regulator. Each channel can be individually controlled or simultaneously the four of
them. They are controlled via other BUSing® devices. It is recommended for controlling RGB LED strips, creating different
atmospheres thanks to their RGB colours combination.
It is designed to achieve a precise digital regulation. It receives the commands from other BUSing® devices.
Using the Development System Software (SIDE), different parameters can be configured for each channel, for instance
the ramp speed or the maximum and minimum regulation values.
Installation Details
• To connect the RGB module, it has 4 regulation channels (red, green, blue and white) and an output supply
(+12V DC - +24V DC) from RGB unit.
• The output voltage for feeding the LED strip will be the same as the one the device receives in the input; two wires
+12V DC - +24V DC and reference (GND).
• It is not necessary to connect +12V DC–Ref to the BUSing socket terminal of the RGBL device. It is only needed to connect A and B and the power supply plugs from the upper part (+12V DC - + 24V DC) as well as GND in order to feed and
control the device.
· RGBL-C
DIN rail mounted version
(2 modules)
Technical Characteristics
Device
74
Reference
RGBL, RGBL-C
* power supplied by the LED transformer
Voltage
Supply*
12–24V DC
Output Power
(10V DC)
3x30W
Output Power
(24V DC)
3x78W
No of
channels
3 (R-G-B)
Max. Operating
Output Current
6A
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
GND
BGR
+12 +24
+12 +24
Consumes
Output
To LED modules
Supply
12Ð24V DC (SELV)
Cable BUSing¨
Connection for
screw terminal.
· RGBL
Installation
75
dimmers
á RGBWL
regulador LED
LED dimmer
ingenium
www.ingeniumsl.com
GND
B GR
+12 +24
+12VAB
Ref.
W
ingenium
www.ingeniumsl.com
+12VAB
Ref.
á RGBW-C
GND
B GR
+12 +24
W
· RGBWL
[
RGBWL · RGBWL-C
]
4-channel dimmer to regulate RGBW LED modules with BUSing® control
Allows control of RGB+White LED strips to create different shades of environment.
• 4 independent regulation channels
(Red, Green, Blue and White)
• Individual programming control values
for each channel
• Digital regulation control based on microcontroller with more than 200 regulation points
• PWM dimming metod
· RGBWL
Luminaire or ceiling intregration
mounting version.
• Size:
37 x 77 x 17mm
Description
RGBWL is a four channels lighting regulator. Each channel can be individually controlled or simultaneously the four of
them. They are controlled via other BUSing® devices. It is recommended for controlling RGBW LED strips, creating different atmospheres thanks to their RGBW colours combination.
It is designed to achieve a precise digital regulation. It receives the commands from other BUSing® devices.
Using the Development System Software (SIDE), different parameters can be configured for each channel, for instance
the ramp speed or the maximum and minimum regulation values.
Installation Details
• To connect the RGBW module, it has 4 regulation channels (red, green, blue and white) and an output supply
(+12V DC - +24V DC) from RGBW unit.
• The output voltage for feeding the LED strip will be the same as the one the device receives in the input; two wires
+12V DC - +24V DC and reference (GND).
• It is not necessary to connect +12V DC–Ref to the BUSing socket terminal of the RGBWL device. It is only needed to connect A and B and the power supply plugs from the upper part (+12V DC - + 24V DC) as well as GND in order to feed and
control the device.
· RGBWL-C
DIN rail mounted version
(2 modules)
Technical Characteristics
Device
76
Reference
RGBWL, RGBWL-C
* power supplied by the LED transformer
Voltage
Supply*
12–24V DC
Output Power
(10V DC)
4x30W
Output Power
(24V DC)
4x78W
No of
channels
4 (R-G-B-W)
Max. Operating
Output Current
6A
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
GND
BGR
+12 +24
W
Consumes
Output
To LED modules
Supply
12Ð24V DC (SELV)
Cable BUSing¨
Connection for
screw terminal.
· RGBWL
Installation
77
dimmers
á DMXBUS
DMX +DMX
Ð
ingenium
www.ingeniumsl.com
+12VAB
Ref.
· DMXBUS
Gateway DMX512 - BUSing®
Allows digital lighting control by DMX512 protocol.
• Gateway for digital controllers with DMX 512 protocol
• Emulation up to 255 channels
• DIN rail mounted (2 modules)
Description
The DMXBUS is a device that acts as a control interface for controlling DMX 512 protocol colour LEDs regulation through
BUSing® devices.
With this device it is possible to emulate each and every one of the channels available within a digital DMX dimmer 512.
The number of channels depends on the type of dimmer used, being usually 3 (RGB). Being able to control the level of
brightness of each of the LEDs, a complete chromatic circle can be configured.
Like any other regulator can be controlled from any control system, from touch-screens, buttons, PC, etc., Achieving different intensities of light and colour tones.
Technical Characteristics
Device
Reference
DMXBUS
78
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
100mA (BUS)
No. of
Emulable Channels
255
ingenium
www.ingeniumsl.com
BUS
+12V
A
B
Ref.
A (DMX+)
B (DMXÐ)
Consumes
DMX station connection
DMX-512 protocol
Cable BUSing¨
Connection for
screw terminal.
· DMXBUS
Installation
79
+12VAB
Ref.
á DALing
pasarela BUSing-DALI
BUSing-DALI gateway
NL
~
ingenium
www.ingeniumsl.com
dimmers
· DALing
Gateway BUSing® - DALI
Allows digital control of lighting with DALI protocol.
• Gateway control for luminaires with DALI protocol
• DALI power supply built
• DIN rail mounting (6 modules)
Description
The DALing gateway is a device that acts as a control interface for luminaires with DALI protocol through BUSing® teams.
With this device you can control up to 64 DALI luminaires + 16 luminaires groups, providing power required to include an
integrated source.
As with any other controller, you can control the DALI lighting control system from anywhere, from touch-screens, buttons,
PC, etc. On the other hand it is possible to make a more complete control, and address and direct parameters of each
fixture using the DALI master (reference: iDALing) along this gateway.
Allows the detection of water leaks in the installation.
· Sin-2h
Vertical contact detector 2 wires type
to be connected to the KA/KCtr.
• For KA or KCtr smartbox connection
• Vertical mount
• Size: 34 x 70 x 14mm
Description
These devices have terminals with sensors that detect water. They are to be installed vertically with the bottom flap
touching the ground. For an alarm to sound, the water must be in contact with both metal terminals.
• They should be located in areas of water leaking risk.
• On sloping ground, should be placed at the points where, by fall, the water tends to accumulate.
• Can be installed hidden, because its function is to send information to the automation system.
· Sin-3h
Vertical contact detector 3 wires type
to be connected to the KA/KCtr.
• For KA or KCtr smartrbox connection
• Vertical mount
• Size: 34 x 70 x 14mm
Technical Characteristics
Device
Reference
Sin-2h
Sin-3h
* maximum recommended distance between sensor and KA/KCtr
84
Voltage
Supply
9–16V DC (KCtr)
9–16V DC (BUS)
Current
Consumption
Negligible
Negligible
Max. Recommended
Distance
30m*
30m*
ingenium
www.ingeniumsl.com
á Sin-2h
á Sin-3h
+12V
Ref.
KCtr
+12V
Ref.
KCtr
KA/KCtr
KA/KCtr
6
á Sin-2h
á Sin-3h
6
Floor
Wall installation
These devices must be installed in vertical
position on the wall, with the sensor downside
and lapel of the housing stuck to the floor.
Connection to KA/KCtr
E6: Flood Sensors
Max. distance: 30m
See KCtr diagram > Page 36
Installation of Flood Sensors (2 wires type).
Connection of additional Sin-2h sensors
Floor
Wall installation
These devices must be installed in vertical
position on the wall, with the sensor downside
and lapel of the housing stuck to the floor.
Connection to KA/KCtr
E6: Flood Sensors
Max. distance: 30m
Connection of additional Sin-3h sensors
· Sin
Installation
44
85
sensors > flooding
á SIn-BUS
Ref.
B
A
+12V
ingenium
www.ingeniumsl.com
· Sin-BUS
BUSing® flood sensor
Allows the detection of water leaks in the installation.
· Sin-BUS
Vertical detector to be connected
to BUSing®via cable.
• BUSing® connection
• Vertical mount
• Size: 34 x 70 x 14mm
Description
These devices have terminals with sensors that detect water. They are to be installed vertically with the bottom flap
touching the ground. For an alarm to sound, the water must be in contact with both metal terminals.
• They should be located in areas of water leaking risk.
• On sloping ground, should be placed at the points where, by fall, the water tends to accumulate.
• Can be installed hidden, because its function is to send information to the automation system.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the sensor.
• Up to 60 programmable BUS events for each scene.
Technical Characteristics
86
Device
Reference
Sin-BUS
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
40mA (BUS)
ingenium
www.ingeniumsl.com
á Sin-BUS
Ref.
B
A
+12V
+12V
A
B
Ref.
+12V
A
B
Ref.
á Sin-BUS
Floor
Consumes
Wall installation
These devices must be installed in
vertical position on the wall, with
the sensor downside and lapel of
the housing stuck to the floor.
Cable BUSing¨
Connection for
crimp connector.
· SinBUS
Installation
87
sensors > fire/smoke
· DTV
[
DTV · DTV-BUS
]
Thermovelocimetric fire detector
To detect fires indicated by sharp temperature changes.
· DTV
Contact detector 2 wires type
to be connected to the KA/KCtr.
• For KA or KCtr connection
• Mounted on the ceiling (surface)
• Size: Ø74 x 26mm
Description
These types of detectors are mounted on ceilings and detect fires by measuring the rise in temperature produced in the
room where they are installed.
• The thermovelocimetric detectors are designed to be placed in areas where smoke might exist or occur, such as kitchens,
garages etc.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the BUSing® sensor (reference: DTV-BUS).
• Up to 60 programmable BUS events for each scene.
Technical Characteristics
Device
Reference
Voltage
Supply
Current
Consumption
Max. Recommended
Distance
· DTV-BUS
Detector to be connected to
wired BUSing®.
• BUSing® connection
• Mounted on the ceiling (surface)
• Size: Ø74 x 26mm
DTV
DTV-BUS
* maximum recommended distance between sensor and KA/KCtr
9–16V DC (KCtr)
9–16V DC (BUS)
Negligible
40mA (BUS)
88
30m*
–
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
+12V
A
B
Ref.
5
KA/KCtr
á DTV
á DTV-BUS
Ð+
+
Ð
See KCtr diagram > Page 33
Installation of Fire/Smoke Sensors
LOOP type
Connection of additional DTV sensors
U
p to 3 sensors can be connected directly
to the KA or KCtr input.
Connection to KA/KCtr
E5: Fire/Smoke Sensors
Max. distance: 30m
Consumes
Cable BUSing¨
Connection for
crimp connector.
· DTV
Installation
41
89
sensors > fire/smoke
· DH
[
DH · DH-BUS
]
Optical smoke detector
Allows detection of fire by the presence of smoke.
· DH
Contact detector prepared for KA
or KCtr by smartbox connection.
• For direct connection to KA/KCtr
• Mounted on the ceiling (surface)
• Size: 60 x 85 x 58mm
Description
This kind of detectors are mounted on the ceiling and detect the presence of smoke in the room where are located.
• Optical detectors are designed to be placed in areas where there is usually the presence of smoke, ie. hallways, rooms, etc.
• They are also installed when you cannot install thermovelocimetric detectors, being areas where although there is smoke,
you cannot wait, in case of a fire, for the temperature to rise above the critical thermovelocimetric value.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the BUSing® sensor (reference: DH-BUS).
• Up to 60 programmable BUS events for each scene.
Technical Characteristics
Device
Reference
Voltage
Supply
Current
Consumption
Max. Recommended
Distance
· DH-BUS
Detector prepared for KCtr by
wire connection.
• For BUSing® connection
• Mounted on the ceiling (surface)
• Size: 60 x 85 x 58mm
DH
DH-BUS
* maximum recommended distance between sensor and KA/KCtr
9–16V DC (KCtr)
9–16V DC (BUS)
20mA
160 µA (off) / 25mA (on)
90
30 m*
–
ingenium
www.ingeniumsl.com
· DH
Installation
KA/KCtr
á DH
5
Connection to KA/KCtr
Ð+
E5: Fire/Smoke Sensors
Max. distance: 30m
See KCtr diagram > Page 33
Installation of Fire/Smoke Sensors
LOOP type
41
Connection of additional DH sensors
Up to 3 sensors can be connected directly
3
to the KA or KCtr input.
4
3
2
1
Cable BUSing¨
Consumes
+12V
+12V
Ref.
Ref.
Connection for
crimp connector.
A
A
B
B
Ð
2
+
1
3
4
4
22
1
3
4
1
á DH-BUS
91
sensors > movement
· Sif
Infrared movement detector
Allows detection of presence in the installation.
• For direct connection to KA or KCtr smartbox
• Normally closed output
• Mounted on the ceiling (embedded)
• Size: Embedded Ø23mm - Seen Ø34mm - Length 52mm
Description
This detector have a passive infrared sensor which detects movements caused by intruders. They have a high level of
immunity from false alarms, electromagnetic fields and temperature variations.
• This type of detectors are indicated to be placed inside homes, buildings, etc.
• Avoid installation in places exposed to direct sunlight and drafts. Also, avoid placing these detectors behind large objects
as these will reduce their detection reach.
• It has no BUS connection, being ready to be directly connected to a KA or KCtr alarm smartbox.
Technical Characteristics
Device
Reference
Sif
Voltage
Supply
9–16V DC
92
Current
Consumption
25mA @ 12V DC
Detection
Angle
90º
Max. Detection
Distance
15m
ingenium
www.ingeniumsl.com
+12V
Ref.
+12VRef.+12VRef.
Ref.
+12V
3
KA/KCtr
á Sif
Connection to KA/KCtr
E3: Movement Detectors and E6
See KCtr diagram > Page 35
Installation of Movement Detectors
INFRARED Type
Connection of additional SIf sensors
Ceiling
Connection to KA/KCtr
E3: Movement Detectors and E6
· Sif
Installation
43
93
sensors > movement
· SifBUS
[
SifBUS-E · SifBUS-S
]
BUSing® infrared movement detector
Allows detection of presence in the installation.
· SifBUS-E
Detector to be connected to wired BUSing®
• BUSing® connection
• Mounted on the ceiling (embedded)
• Size: Embedded Ø23mm - Seen Ø34mm - Length 52mm
· SifBUS-S
Detector to be connected to wired BUSing®.
• BUSing® connection
• Mounted on the ceiling (surface)
• Size: Ø74 x 26mm
Description
These movement detectors have a passive infrared sensor which detects movements caused by intruders. They have a
high level of immunity from false alarms, electromagnetic fields and temperature variations.
• This type of detectors are indicated to be placed inside homes, buildings, etc.
• Avoid installation in places exposed to direct sunlight and drafts. Also, avoid placing these detectors behind large objects
as these will reduce their detection reach.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the sensor.
• Up to 60 programmable BUS events for each scene.
Technical Characteristics
Device
Reference
SifBUS · SIfBUS-E
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
40mA (BUS)
Detection
Angle
360º
Detection Area
at 2.5m height
Ø5m
94
ingenium
www.ingeniumsl.com
Ref.
B
A
+12V
+12V
A
B
Ref.
+12V
A
B
Ref.
á SifBUS-S
á SifBUS-E
Ceiling
Consumes
Consumes
Cable BUSing¨
Connection for
crimp connector.
Cable BUSing¨
Connection for
crimp connector.
· SifBUS
Installation
95
sensors > movement
· SifBUS-L
[
SifBUS-L · SifBUS-LS
]
BUSing® infrared movement detector with light level sensor
Allows detection of presence and lighting in the installation.
· SifBUS-L
• BUSing® connection
• Movement and light level sensor integrated
• Mounted on the ceiling (embedded)
• Size: Embedded Ø23mm - Seen Ø34mm - Length 52mm
· SifBUS-LS
• BUSing® connection
• Movement and light level sensor integrated
• Mounted screwed to the ceiling or interior wall (surface)
• Size: Ø48 x 27mm
Description
Infrared sensor for movement detection (intrusion, lighting) and brightness level. Designed for wired BUSing® connection. Possibility to program the desired events both in detection and when it finishes, or in the absence of light.
These detectors have a passive infrared sensor which detects movements caused by intruders. They have a high level of
immunity from false alarms, electromagnetic fields and temperature variations.
• Indicated to be placed inside homes, buildings, etc.
• Avoid installation in places exposed to direct sunlight and drafts. Also, avoid placing these detectors behind large objects
as these will reduce their detection reach.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the sensor.
(2 for the movement sensor and 2 for the light sensor)
• Up to 30 programmable BUS events for each scene.
Technical Characteristics
Device
Reference
SIfBUS-L/LS
Voltage
Supply
9–16V DC (BUS)
96
Current
Consumption
40mA (BUS)
Detection
Angle
360º
Detection Area
at 2.5m height
Ø5m
ingenium
www.ingeniumsl.com
Ref.
B
A
+12V
Ref.
B
A
+12V
á SifBUS-L
á SifBUS-LS
Ceiling
Consumes
Consumes
Ceiling or wall surface mounting
The base of the device is screwed
to the surface.
The equipment and its housing
is fixed to the base by preasure.
Ceiling
Cable BUSing¨
Connection for
crimp connector.
Cable BUSing¨
Connection for
crimp connector.
· SifBUS-L
Installation
97
ingenium
www.ingeniumsl.com
+12V
A
B
Ref.
á SRBUS
ngulo de deteccin
detection angle
360¡
9-16 Vdc
100 mA @ 12 Vdc
Patentado
Patented
DETECTION
SIDE
sensors > movement
· SRBUS
BUSing® hidden 360º radiofrequency detector
For movement detection with concealed installation.
• Detects movement through solid, non-metallic objects
• Detects minimum movements
• Hidden installation in false ceiling, wall or waterproof case
• Automatic reset after each detection
• Adjustable timer from pulse to 17min.
• Adjustable sensitivity up to 12m
• Size: 65 x 25 x 45mm
Description
The SR-BUS is a radio frequency detector for hidden installation can detect movement through walls and ceilings of any
non-metallic material. It is designed to replace passive 360° sensors, surpassing its performance.
Its installation hidden behind walls, partitions, ceilings, junction boxes or waterproof casings, ensure safety unwanted intrusions or vandalism to not be accessible.
By being able to detect the slightest movement, it is possible to link the lighting of a room to the presence of people or
trigger the intrusion alarm.
From Development System (SIDE) you can set the sensitivity, the sampling period, the response time and the delay after
detection, and a list of events BUS to send at the time in which detection occurs and when the timer expires.
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the sensor.
• Up to 60 programmable BUS events for each scene.
• Timing adjustment seconds after detection.
• Sensitivity adjustment and damping.
• Configuration control cycles and number of detections for activation.
Technical Characteristics
Device
Reference
SR-BUS
* approx. area at 2.5m height
98
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
100mA (BUS)
Detection
Angle
360º
Maximum
Detection Area
12 x 6m*
Secure
Detection Area
6x3m*
ingenium
www.ingeniumsl.com
BUS
SRBUS
+12V
A
B
Ref.
Direction of the device
Place lengthwise, with the length of the
device parallel to the length of the room.
Together with the programming, this will
ensure optimal detection.
Detection adjustments
The detector emits a detection beam of high
intensity, being of greater or lesser scope
depending on the sensitivity for which it has been
programmed from the Development System.
Detection angles
The beam in the longitudinal direction
of the device has an angle of 140¼ and
in transversal, 70¼.
Detection area
The detection area must face the room,
with the silk screened part of the device
face-down.
SRBUS output wiring
Supply absorbed 100mA
Installation in a false ceiling
Guaranteed area 6x3m
Maximum area 12x6m
Length side of the room
Microprocessor
Detection
Consumes
Floor
Detection area at
2.5m from the floor:
Guaranteed: 6x3m
Maximum: 12x6m
The device can be partially
blinded with metal tape to
cancel detection in a
zone/direction.
Do NOT install:
á In locations susceptible to vibrations.
á Over fluorescent lights.
Cable BUSing¨
Connection for
screw terminal.
· SRBUS
Installation
99
sensors > contact
ingenium
www.ingeniumsl.com
Ref.
B
A
+12V
á DM-BUS
Deteccin / Detection
· DM-BUS
BUSing® magnetic detector
Allows detection of open windows or doors.
• Detector designed to be connected to BUSing®.
• Surface mount
• Size:
Detector: 58 x 27 x 10mm
Magnet: 23 x 14 x 6mm
Description
The magnetic detectors have two physically separate pieces. The smaller one has a magnet and the bigger one has an
integrated circuit which can detect the presence or absence of the smaller piece.
They can be used for the following functions:
• Anti-intruder security device: that detects when an unwanted door or window opening.
• Air control devices for energy saving: on detecting that a window has been opened, it will (having been programmed) cut
off the air conditioning or heating accordingly.
They are installed in zones close to door or window openings in the moving part, so that the sensor detects the slightest
movement or displacement.
The smaller piece is installed on the edge of the window which is closest to the window opening.
• The smaller piece (magnet) is installed on the edge of the window which is closest to the window opening.
The bigger piece is installed on the window frame and with its detecting side facing the magnet.
•
Configuration using Development System (SIDE)
• 2 programmable scenes for activation and deactivation of the sensor.
• Up to 60 programmable BUS events for each scene.
Technical Characteristics
Device
Reference
DM-BUS
100
Voltage
Supply
9–16V DC (BUS)
Current
Consumption
40mA (BUS)
Loading...