Infosec ICUE4PRO15, ICUE4PRO30, ICUE4PRO10, ICUE4PRO2000 Datasheet

Networks & Critical Apps, Industrial Environments
E4 LCD Pro range offers an excellent electrical security level and the main features for the protection of your essential and strategic loads.
From 1 to 10 k VA
On Line Double Conversion technology
High Frequency
microprocessor-controlled
The most reliable technology
The microprocessor-controlled On Line Double Conversion technology, delivers a pure sinewave output current for applications with an essential role. Models equipped with this technology have the latest generation IGBT switch on their inverter and rectifier circuits. The output power factor is optimal, reaching 0.9 on the whole range. Monitoring the UPS through a microprocessor offers a wide input voltage range, a high input power factor, a low harmonic distortion and a noticeable reduction of noise intensity.
E4 LCD Pro
1-3 k VA
E4 LCD Pro
5-10 k VA
On Line Double
Conversion Technology
LCD
LCD control screen
Features fit for the most demanding needs
E4 LCD Pro range features the requested technical specifications designed to offer an optimal level of performance that fits to the most varied needs. Service continuity is guaranteed in any circumstance, even when the UPS is set to Eco mode, or during maintenance operations with the internal manual bypass set during the interventions (from 5k to 10k VA). The Emergency Power Off feature (from 5k to 10k VA) guarantees the maintenance staff’s safety and the protection of its environment.
Very low distortion of input current
Input Power Factor correction
up to >0.99%
Output power factor of 0.9
For the most disturbed or demanding environments:
Extended backup time available
on S models with external Battery Bank
Remote control
software
Extended backup time
available
SECURITY AND SERVICE CONTINUITY
A safe solution
Protection against any wiring default
ECO functioning mode allowing to save energy
Reliability: automatic control of the load, the input voltage and the internal status of the UPS
Automatic testing during the initialization of the device
Protection of the internal power components
Emergency Power Off (EPO) Function
This port is dedicated to the installation of the Emergency Power Off Function (EPO) for staff’s safety and equipment protection, allowing to immediately and completely shut down the UPS (models from 5k to 10k VA).
Cold-start function
In case of an emergency, this feature allows to overcome a total shutdown by starting the UPS thanks to its batteries.
Eco mode allows to reduce the energy consuming and costs, thus reaching a 90% efficiency.
This feature allows the unit to supply the connected load directly from the mains while maintaining the UPS device fully operational in case a failure or an important voltage fluctuation should occur, thus guaranteeing a continuous supply of the system.
This functioning mode supplies the UPS through the static bypass and allows a relevant return to the Online Double Conversion if necessary.
E4 LCD Pro UPS devices from 1 to 3 kVA also feature an Advanced Eco mode allowing to reach a 95% efficiency.
USER-FRIENDLY WITH COMMUNICATION FEATURES
Easy to use LCD screen
• Sharp and user friendly: status indicators and real-time parameters information
• Intuitive LCD display on the front panel: direct access to the UPS settings for a quick modification of the operational modes (output voltage settings…)
• Frequency setting on 50 or 60 Hz or auto-detection (easily set from the LCD screen of the device)
Communication interfaces
Several communication interfaces allow E4 LCD Pro UPS devices to be remotely controlled thanks to the InfoPower software. An uninterrupted monitoring of the UPS status and its connected applicatons is then possible:
The USB port or RS232 allow to use communication protocols of IT infrastructures, Data Centers or telecommunication networks.
An  SNMP port allows to add an SNMP card (as an option) managed by a software installed on a server.
Remote management software
The Infopower management software is provided as a standard with the E4 LCD Pro UPS:
Setting the time of initialization and shutdown of the device
Recording of the data and events allowing a daily maintenance
E-mail messaging to manage the status of the UPS at any time from the local network
Automatic files closing by the UPS when the mains is not available: protection of the data of all the computers of a same IT network
Intuitive graphic interface: allows to monitor the system’s status, the key indicators, the events history...
By-pass manuel de maintenance
Allows to provide connected equipment with a permanent voltage during maintenance through the rotary switch and therefore avoids the IT network’s shutdown.
As a standard on the E4 LCD Pro UPS range from 5 to 10 kVA.
As an external option on E4 LCD Pro UPS devices under 5 kVA.
CONNECTIONS AND BATTERIES
A connectivity designed for several needs
1. Input
2. Input Circuit Breaker
3. USB communication port
4. RS 232 communication port
5. SNMP slot
6. External batteries connection
7. Outlets
8. Input terminal
9. Output terminal
10. EPO connector
11. Maintenance By-pass
3 4
2
1
E4 LCD Pro 1000
OPTIONS
Communication options
SNMP I Pro agent
Using the SNMP I pro agent with the E4 LCD Pro UPS devices makes it easier to manage the UPS due to its various special features:
• Connection to the Ethernet network and identification by IP address (random or fixed)
• Setting and programming a system shutdown and restart on a weekly (or other) basis
• Local or remote UPS configuration
AS400 Dry Contacts Card
The AS400 communication card sends dry contacts to report the alarms triggered in the UPS (for centralized technical manage ments for example).
Depending on the applicatons, dry contacts can be normally open or normally closed.
EMD
This probe is meant for detecting the environmental conditions
of the UPS and allows from a distance to monitor the temperature and the moisture rate of the room. This probe is connected to the SNMP card, and can also be used to send dry contacts, this being compatible with security or alarms systems.
RS485 Card
An RS 485 card can be added as an option in order to allow the E4 LCD Pro UPS to communicate with installations using industrial protocols on long distance.
5
6
7
-
2
1
E4 LCD Pro 1500
& 2000
4 3
6
3 4
4 3
6
7
2
1
E4 LCD Pro 3000 E4 LCD Pro 5000 to 10k VA
5
6
7
9
5
10
11
2
8
9
Isolation transformer
An isolation transformer at the input and the output providing the system a complete galvanic isolation between the upstream and downstream circuits. The equipment therefore adapts perfectly to all neutral systems upstream as much as downstream.
BMe
For models from 1000 to 3000 VA, E4 LCD Pro is compatible with the External Maintenance Bypasses BMe 1 with IEC or FR/Schuko outlets.
During maintenance works on a UPS device, BMe1 gua­rantees, through its independent line, the continuous supply of the connected equipement.
This option can be installed in a few minutes and guarantees the staff’s safety without any service interruption.
Extended backup time
In order to benefit from a pro­longed backup-time in disturbed or demanding environments, external battery modules can be added to
Several types of battery banks exist according to the type of batteries required, and also de­pending on the place’s configu­ration. battery banks offer allows to answer most of the needs.
S versions (Extended Backup Time) are delivered without in­ternal batteries, but with external battery banks.
From 1000 to 3000 VA, an external battery charger can also be added to a standard model to allow increasing the number of battery banks that can be configured on the UPS (up to 4).
, E4 LCD Pro (option).
The wide and modular
TECHNICAL SPECIFICATIONS
g
GENERAL CHARACTERISTICS
Technology Power (VA) Power (W) Power factor
PHYSICAL CHARACTERISTICS
Standard
Long Backup time (S)
TECHNICAL INPUT CHARACTERISTICS
Low voltage range
High voltage range
Frequency range 40 Hz ~ 70 Hz 50 Hz : 46 Hz ~ 54 Hz or 60 Hz : 56 Hz ~ 64 Hz Power factor > 0,99 at 100% load > 0,99 at 100% load
TECHNICAL OUTPUT CHARACTERISTICS
Voltage 200/208/220/230/240 VAC 208 / 220 / 230 / 240 VAC AC voltage regulation (Batt mode) +/- 1% +/- 1% Frequency range (Synchronized range) 50 Hz : 47 ~ 53 Hz or 60 Hz : 57 ~ 63 Hz 50 Hz : 46 Hz ~ 54 Hz or 60 Hz : 56 Hz ~ 64 Hz Frequency range (Batt mode) 50 Hz +/- 0,5 Hz or 60 Hz +/- 0,5 Hz 50 Hz +/- 0,1 Hz or 60 Hz +/- 0,1 Hz Current crest ration 3 : 1 Harmonic distorsion <= 3% THD (Linear Load); <= 6% THD (Non-linear Load)
Transfer time
Waveform Pure sinewave Output outlets IEC 10A Output terminal block
EFFICIENCY
AC mode 88% 89% 90% 89% 90% Battery mode 83% 85% 88% 88% 89% Eco mode
BATTERY
Standard model
Long backup time model (S)
INDICATORS & ALARMS
LCD screen Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator. Audible alarms
BYPASS
Static bypass Manual bypass
MANAGEMENT / COMMUNICATION
Communication
EPO Connector No Yes
ENVIRONMENT
Humidity
Operating Altitude Up to 1000 m above sea level (> 1000 m 1% derating for every 100 m)
Noise level Less than 50dBA @ 1 meter
Heat dissipation max
NORMS
Standard CE RoHS
EMC (Electromagnetic compatibility)
Low voltage (Safety)
SALES INFO
Warranty 2 years PN - standard versions PN - Long backup time version (S)
BACKUP MODULES
Dimensions - D x W x H (mm)
Net weight - kg (empty) PN
10-31-1614 / Cette entreprise a fait certifier sa chaîne de contrôle / pefc-france.or
S models are long-autonomy UPS devices without internal batteries. E4 LCD Pro UPS devices from 1k to 3k VA are also available in 110V (LV) - Refer to our sales contacts.
Dim. D x W x H (mm) - UPS
Net weight (kg) 9.8 17 27.6 72 82
Dim. D x W x H (mm) - UPS
Net weight (kg) 4.1 6.8 7.4 21 23
Low Line transfer (based on load
percentage : 100%-80% / 80%­70% / 70%-60% / 60%-0%)
Low Line comeback 195 VAC / 175 VAC / 155 VAC / 135 VAC +/- 5%
High Line transfer (based on load
percentage : 100%-80% / 80%­70% / 70%-60% / 60%-0%)
High Line comeback 290 VAC / 270 VAC +/- 5% 290 VAC +/- 3%
Line mode to battery mode 0 ms 0 ms Inverter to Bypass 4 ms (Typical) 0 ms
Battery type 12 V / 9 AH 12 V / 9 AH Number 2 4 6 16 Typical recharge time 4 hours recover to 90% capacity 9 hours recover to 90% capacity Charging current (max) 1A 1A (max 2A) Backup time from 5 to 30 minutes depending on the connected load Battery type Depending on the capacity of external batteries Charging current (max) 1A/2A/4A/6A 4A (max 6A)
E4 LCD PRO
E4 LCD PRO
1000 (S)
1000 VA 1500 VA 2000 VA 3000 VA 5000 VA 6000 VA 8000 VA 10000 VA
900 W 1350 W 1800 W 2700 W 4500 W 5400 W 7200 W 9000 W
220 x 145
x 282
220 x 145
x 282
180 VAC / 160 VAC / 140 VAC / 120 VAC +/- 5%
300 VAC / 280 VAC +/- 5% 300 VAC +/- 3%
3 4 0
USB & RS232 port and Infopower included software (support Windows family, Linux, Unix and MAC)
Optional SNMP Pro I : power management from SNMP manager (VMware
20 - 90% relative humidity @ 0-40°
141 W /
481,11
BTU/h
EN 62040-2: 2006+AC: 2006 ; EN 61000-3-2: 2014
(EN 61000-4-2: 2009, EN 61000-4-3: 2006+A2:
2010, EN 61000-4-4: 2012, EN 61000-4-5: 2006,
EN 61000-4-6: 2014, EN 61000-4-8: 2010, EN
EN 62040-1:2008 (1
67230 67236
E4 LCD PRO
1000 (S)
220 x 145
x 397
22 27 42 95 115
67277 67279 67281 67283 67284
E4 LCD PRO
1500 (S)
220 x 145 x 397
220 x 145 x 397 318 x 190 x 369 318 X 190 X 442
no yes yes
94%-95%
Option Yes
non condensing
256 W /
873,5 BTU/h
61000-2-2: 2002)
st
Edition) + Am 1:2013
67274 67275
E4 LCD PRO
E4 LCD PRO
1500 (S)
220 x 145 x 397
E4 LCD PRO
E4 LCD PRO
2000 (S)
Battery mode, Low battery, Overload, Fault
67231 67232 67266 67267 67237 67238 67270 67271
2000 (S)
3000 (S)
On Line Double Conversion
0,9
318 x 190
x 421
Yes
and web browser
348 W /
1187,41
BTU/h
E4 LCD PRO
3000 (S)
318 x 190
x 421
E4 LCD PRO
5000 (S)
6000 (S)
369 x 190 x 688 442 X 190 X 688
110 VAC +/- 3% at 50% load
176 VAC +/- 3% at 100% load
120 VAC +/- 3% at 50% load
186VAC +/- 3% at 100% load
0 - 95% relative humidity @ 0-40°
Less than 55dBA @ 1
meter
667 W / 2276,45 BTU/h 960 W / 3276,45 BTU/h
EN 62040-2 : 2006 ; EN 61000-2-2 : 2002; EN61000­4-2 : 2009; EN61000-4-3:2006 +A1:2008 +A2:2010;
EN61000-4-4:2004+A1:2010; EN61000-4-5:2006;
E4 LCD PRO
E4 LCD PRO
5000 (S)
6000 (S)
688 x 190 x 442 688 x 190 x 442
E4 LCD PRO
8000 (S)
-
©,
Hyper V
non condensing
Less than 58dBA @ 1
EN61000-4-8:2010
EN62040-1 : 2008
67268 67272
E4 LCD PRO
8000 (S)
E4 LCD PRO
10000 (S)
20
TM
compatible)
meter
67269 67273
E4 LCD PRO
10000 (S)
From 1 to 10 k VA
Communications solutions and remote management
USB & RS232, SNMP & EPO communication ports
Software :
• Simple user interface
• UPS startup and shutdown programming
• Data and events record enabling daily maintenance
• E-mail messaging to manage UPS status at all times via the local network
• Free download from the website
Package content
• 1 UPS
• 1 input cable (1 to 3 kVA models)
• IEC 10A output cable (1 to 3 kVA models)
• 1 RS 232 cable
• 1 USB cable
• 1 battery cable (5k to 10kVA and S models)
• 1 user manual
• Infopower Software
Options
Désignation Réf
SNMP Pro I Card 61156
SNMP vm Minislot Card 61142
Dry contacts card 61454
RS 485 card 61439
BMe 1 IEC 1 to 3k 61440
BMe 1 FR 1 to 3k 61441
Additional battery banks
EMD detector 61452
External isolation transformer NC
Warranty
2-year warranty against manufacturing defects under normal conditions and compliance with precautionary measures.
Warranty to be taken out on our website within 10 days of purchase.
Maintenance contract
A Maintenance contract is highly recommended: contact hotline@infosec.fr
Infosec Communication
15, Rue du Moulin
44880 SAUTRON - FRANCE
Sales Contact
Tel: 02 40 76 11 77
commercial@infosec.fr
See
chart
©2017 Infosec Communication SAS, all rights reserved. Infosec UPS System is a trademark or registered trademark of Infosec Communication. All other trademarks or registered trademarks belong to their respective owners. Photos are not binding. Specifications are subject to change without prior notice. Backuptime is only a guide: actual duration may vary depending on the temperature, battery condition and peripherals added. UPS are part of electronic and electric equipments category. At the end of their lives, they have to be collected separately. 04 17 AA 80 111 80
Loading...