Networks & Critical Apps, Industrial Environments
E4 LCD Pro range offers an excellent electrical security level
and the main features for the protection of your essential
and strategic loads.
From 1 to 10 k VA
On Line Double Conversion technology
High Frequency
microprocessor-controlled
The most reliable technology
The microprocessor-controlled On Line Double Conversion
technology, delivers a pure sinewave output current for
applications with an essential role. Models equipped with this
technology have the latest generation IGBT switch on their
inverter and rectifier circuits.
The output power factor is optimal, reaching 0.9 on the whole
range. Monitoring the UPS through a microprocessor offers
a wide input voltage range, a high input power factor, a low
harmonic distortion and a noticeable reduction of noise intensity.
E4 LCD Pro
1-3 k VA
E4 LCD Pro
5-10 k VA
On Line Double
Conversion Technology
LCD
LCD control screen
Features fit for the most demanding needs
E4 LCD Pro range features the requested technical specifications designed to offer an optimal level of
performance that fits to the most varied needs. Service continuity is guaranteed in any circumstance, even
when the UPS is set to Eco mode, or during maintenance operations with the internal manual bypass set during
the interventions (from 5k to 10k VA). The Emergency Power Off feature (from 5k to 10k VA) guarantees the
maintenance staff’s safety and the protection of its environment.
Very low distortion of input current
Input Power Factor correction
up to >0.99%
Output power factor of 0.9
For the most disturbed or
demanding environments:
Extended backup time available
on S models with external Battery Bank
Remote control
software
Extended backup time
available

SECURITY AND SERVICE CONTINUITY
A safe solution
• Protection against any wiring default
ECO functioning mode allowing to
save energy
• Reliability: automatic control of the load, the input voltage and the
internal status of the UPS
• Automatic testing during the initialization of the device
• Protection of the internal power components
Emergency Power Off (EPO) Function
This port is dedicated to the installation of the Emergency
Power Off Function (EPO) for staff’s safety and equipment
protection, allowing to immediately and completely shut
down the UPS (models from 5k to 10k VA).
Cold-start function
In case of an emergency, this feature allows to overcome a total shutdown by
starting the UPS thanks to its batteries.
Eco mode allows to reduce the energy consuming
and costs, thus reaching a 90% efficiency.
This feature allows the unit to supply the connected load directly
from the mains while maintaining the UPS device fully operational in
case a failure or an important voltage fluctuation should occur, thus
guaranteeing a continuous supply of the system.
This functioning mode supplies the UPS through the static bypass
and allows a relevant return to the Online Double Conversion if
necessary.
E4 LCD Pro UPS devices from 1 to 3 kVA also feature an Advanced
Eco mode allowing to reach a 95% efficiency.
USER-FRIENDLY WITH COMMUNICATION FEATURES
Easy to use LCD screen
• Sharp and user friendly: status indicators and real-time parameters information
• Intuitive LCD display on the front panel: direct access to the UPS settings for a quick modification of the operational modes
(output voltage settings…)
• Frequency setting on 50 or 60 Hz or auto-detection (easily set from the LCD screen of the device)
Communication interfaces
Several communication interfaces allow E4 LCD Pro UPS devices to
be remotely controlled thanks to the InfoPower software.
An uninterrupted monitoring of the UPS status and its connected
applicatons is then possible:
• The USB port or RS232 allow to use communication protocols
of IT infrastructures, Data Centers or telecommunication
networks.
• An SNMP port allows to add an SNMP card (as an option)
managed by a software installed on a server.
Remote management software
The Infopower management software is provided as a standard
with the E4 LCD Pro UPS:
• Setting the time of initialization and shutdown of the
device
• Recording of the data and events allowing a daily
maintenance
• E-mail messaging to manage the status of the UPS at any
time from the local network
• Automatic files closing by the UPS when the mains is not
available: protection of the data of all the computers of a
same IT network
• Intuitive graphic interface: allows to monitor the system’s
status, the key indicators, the events history...
By-pass manuel de maintenance
• Allows to provide connected equipment with a permanent voltage during maintenance through the rotary switch and therefore avoids the IT
network’s shutdown.
• As a standard on the E4 LCD Pro UPS range from 5 to 10 kVA.
• As an external option on E4 LCD Pro UPS devices under 5 kVA.

CONNECTIONS AND BATTERIES
A connectivity designed for several needs
1. Input
2. Input Circuit Breaker
3. USB communication port
4. RS 232 communication port
5. SNMP slot
6. External batteries connection
7. Outlets
8. Input terminal
9. Output terminal
10. EPO connector
11. Maintenance By-pass
3
4
2
1
E4 LCD Pro 1000
OPTIONS
Communication options
SNMP I Pro agent
Using the SNMP I pro
agent with the
E4 LCD Pro UPS devices
makes it easier to
manage the UPS due
to its various special
features:
• Connection to the
Ethernet network and identification by IP address (random
or fixed)
• Setting and programming a system shutdown and restart
on a weekly (or other) basis
• Local or remote UPS configuration
AS400 Dry Contacts Card
The AS400 communication card sends dry contacts to report the
alarms triggered in the UPS (for centralized technical manage
ments for example).
Depending on the applicatons, dry contacts can be normally
open or normally closed.
EMD
This probe is meant for detecting the environmental conditions
of the UPS and allows from a distance
to monitor the temperature and the
moisture rate of the room. This probe
is connected to the SNMP card, and
can also be used to send dry contacts,
this being compatible with security or
alarms systems.
RS485 Card
An RS 485 card can be added as an option in order to allow
the E4 LCD Pro UPS to communicate with installations using
industrial protocols on long distance.
5
6
7
-
2
1
E4 LCD Pro 1500
& 2000
4
3
6
3
4
4
3
6
7
2
1
E4 LCD Pro 3000 E4 LCD Pro 5000 to 10k VA
5
6
7
9
5
10
11
2
8
9
Isolation transformer
An isolation transformer at the input and the output providing the
system a complete galvanic isolation between the upstream and
downstream circuits. The equipment therefore adapts perfectly to
all neutral systems upstream as much as downstream.
BMe
For models from 1000 to 3000 VA,
E4 LCD Pro is compatible with the External
Maintenance Bypasses BMe 1 with IEC or
FR/Schuko outlets.
During maintenance works on a UPS device, BMe1 guarantees, through its independent line, the continuous supply
of the connected equipement.
This option can be installed in a few minutes and guarantees
the staff’s safety without any service interruption.
Extended backup time
In order to benefit from a prolonged backup-time in disturbed
or demanding environments,
external battery modules can be
added to
Several types of battery banks
exist according to the type of
batteries required, and also depending on the place’s configuration.
battery banks offer allows to answer most of the needs.
S versions (Extended Backup Time) are delivered without internal batteries, but with external battery banks.
From 1000 to 3000 VA, an external battery charger can also
be added to a standard model to allow increasing the number
of battery banks that can be configured on the UPS (up to 4).
, E4 LCD Pro (option).
The wide and modular

TECHNICAL SPECIFICATIONS
GENERAL CHARACTERISTICS
Technology
Power (VA)
Power (W)
Power factor
PHYSICAL CHARACTERISTICS
Standard
Long Backup
time (S)
TECHNICAL INPUT CHARACTERISTICS
Low voltage
range
High voltage
range
Frequency range 40 Hz ~ 70 Hz 50 Hz : 46 Hz ~ 54 Hz or 60 Hz : 56 Hz ~ 64 Hz
Power factor > 0,99 at 100% load > 0,99 at 100% load
TECHNICAL OUTPUT CHARACTERISTICS
Voltage 200/208/220/230/240 VAC 208 / 220 / 230 / 240 VAC
AC voltage regulation (Batt mode) +/- 1% +/- 1%
Frequency range (Synchronized range) 50 Hz : 47 ~ 53 Hz or 60 Hz : 57 ~ 63 Hz 50 Hz : 46 Hz ~ 54 Hz or 60 Hz : 56 Hz ~ 64 Hz
Frequency range (Batt mode) 50 Hz +/- 0,5 Hz or 60 Hz +/- 0,5 Hz 50 Hz +/- 0,1 Hz or 60 Hz +/- 0,1 Hz
Current crest ration 3 : 1
Harmonic distorsion <= 3% THD (Linear Load); <= 6% THD (Non-linear Load)
Transfer time
Waveform Pure sinewave
Output outlets IEC 10A
Output terminal block
EFFICIENCY
AC mode 88% 89% 90% 89% 90%
Battery mode 83% 85% 88% 88% 89%
Eco mode
BATTERY
Standard model
Long backup
time model (S)
INDICATORS & ALARMS
LCD screen Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator.
Audible alarms
BYPASS
Static bypass
Manual bypass
MANAGEMENT / COMMUNICATION
Communication
EPO Connector No Yes
ENVIRONMENT
Humidity
Operating Altitude Up to 1000 m above sea level (> 1000 m 1% derating for every 100 m)
Noise level Less than 50dBA @ 1 meter
Heat dissipation max
NORMS
Standard CE RoHS
EMC (Electromagnetic compatibility)
Low voltage (Safety)
SALES INFO
Warranty 2 years
PN - standard versions
PN - Long backup time version (S)
BACKUP MODULES
Dimensions - D x W x H (mm)
Net weight - kg (empty)
PN
10-31-1614 / Cette entreprise a fait certifier sa chaîne de contrôle / pefc-france.or
S models are long-autonomy UPS devices without internal batteries.
E4 LCD Pro UPS devices from 1k to 3k VA are also available in 110V (LV) - Refer to our sales contacts.
Dim. D x W x H (mm) - UPS
Net weight (kg) 9.8 17 27.6 72 82
Dim. D x W x H (mm) - UPS
Net weight (kg) 4.1 6.8 7.4 21 23
Low Line transfer (based on load
percentage : 100%-80% / 80%70% / 70%-60% / 60%-0%)
Low Line comeback 195 VAC / 175 VAC / 155 VAC / 135 VAC +/- 5%
High Line transfer (based on load
percentage : 100%-80% / 80%70% / 70%-60% / 60%-0%)
High Line comeback 290 VAC / 270 VAC +/- 5% 290 VAC +/- 3%
Line mode to battery mode 0 ms 0 ms
Inverter to Bypass 4 ms (Typical) 0 ms
Battery type 12 V / 9 AH 12 V / 9 AH
Number 2 4 6 16
Typical recharge time 4 hours recover to 90% capacity 9 hours recover to 90% capacity
Charging current (max) 1A 1A (max 2A)
Backup time from 5 to 30 minutes depending on the connected load
Battery type Depending on the capacity of external batteries
Charging current (max) 1A/2A/4A/6A 4A (max 6A)
E4 LCD PRO
E4 LCD PRO
1000 (S)
1000 VA 1500 VA 2000 VA 3000 VA 5000 VA 6000 VA 8000 VA 10000 VA
900 W 1350 W 1800 W 2700 W 4500 W 5400 W 7200 W 9000 W
220 x 145
x 282
220 x 145
x 282
180 VAC / 160 VAC / 140 VAC / 120 VAC +/- 5%
300 VAC / 280 VAC +/- 5% 300 VAC +/- 3%
3 4 0
USB & RS232 port and Infopower included software (support Windows family, Linux, Unix and MAC)
Optional SNMP Pro I : power management from SNMP manager (VMware
20 - 90% relative humidity @ 0-40°
141 W /
481,11
BTU/h
EN 62040-2: 2006+AC: 2006 ; EN 61000-3-2: 2014
(EN 61000-4-2: 2009, EN 61000-4-3: 2006+A2:
2010, EN 61000-4-4: 2012, EN 61000-4-5: 2006,
EN 61000-4-6: 2014, EN 61000-4-8: 2010, EN
EN 62040-1:2008 (1
67230
67236
E4 LCD PRO
1000 (S)
220 x 145
x 397
22 27 42 95 115
67277 67279 67281 67283 67284
E4 LCD PRO
1500 (S)
220 x 145 x 397
220 x 145 x 397 318 x 190 x 369 318 X 190 X 442
no yes yes
94%-95%
Option Yes
non condensing
256 W /
873,5 BTU/h
61000-2-2: 2002)
st
Edition) + Am 1:2013
67274
67275
E4 LCD PRO
E4 LCD PRO
1500 (S)
220 x 145 x 397
E4 LCD PRO
E4 LCD PRO
2000 (S)
Battery mode, Low battery, Overload, Fault
67231 67232 67266 67267
67237 67238 67270 67271
2000 (S)
3000 (S)
On Line Double Conversion
0,9
318 x 190
x 421
Yes
and web browser
348 W /
1187,41
BTU/h
E4 LCD PRO
3000 (S)
318 x 190
x 421
E4 LCD PRO
5000 (S)
6000 (S)
369 x 190 x 688 442 X 190 X 688
110 VAC +/- 3% at 50% load
176 VAC +/- 3% at 100% load
120 VAC +/- 3% at 50% load
186VAC +/- 3% at 100% load
0 - 95% relative humidity @ 0-40°
Less than 55dBA @ 1
meter
667 W / 2276,45 BTU/h 960 W / 3276,45 BTU/h
EN 62040-2 : 2006 ; EN 61000-2-2 : 2002; EN610004-2 : 2009; EN61000-4-3:2006 +A1:2008 +A2:2010;
EN61000-4-4:2004+A1:2010; EN61000-4-5:2006;
E4 LCD PRO
E4 LCD PRO
5000 (S)
6000 (S)
688 x 190 x 442 688 x 190 x 442
E4 LCD PRO
8000 (S)
-
©,
Hyper V
non condensing
Less than 58dBA @ 1
EN61000-4-8:2010
EN62040-1 : 2008
67268
67272
E4 LCD PRO
8000 (S)
E4 LCD PRO
10000 (S)
20
TM
compatible)
meter
67269
67273
E4 LCD PRO
10000 (S)
From 1 to 10 k VA
Communications
solutions and remote
management
USB & RS232, SNMP & EPO communication
ports
Software :
• Simple user interface
• UPS startup and shutdown
programming
• Data and events record enabling daily
maintenance
• E-mail messaging to manage UPS status
at all times via the local network
• Free download from the website
Package content
• 1 UPS
• 1 input cable (1 to 3 kVA models)
• IEC 10A output cable (1 to 3 kVA models)
• 1 RS 232 cable
• 1 USB cable
• 1 battery cable (5k to 10kVA and S models)
• 1 user manual
• Infopower Software
Options
Désignation Réf
SNMP Pro I Card 61156
SNMP vm Minislot Card 61142
Dry contacts card 61454
RS 485 card 61439
BMe 1 IEC 1 to 3k 61440
BMe 1 FR 1 to 3k 61441
Additional battery banks
EMD detector 61452
External isolation transformer NC
Warranty
2-year warranty against
manufacturing defects
under normal conditions
and compliance with precautionary
measures.
Warranty to be taken out on our website
within 10 days of purchase.
Maintenance contract
A Maintenance contract is highly
recommended: contact hotline@infosec.fr
Infosec Communication
15, Rue du Moulin
44880 SAUTRON - FRANCE
Sales Contact
Tel: 02 40 76 11 77
commercial@infosec.fr
See
chart
©2017 Infosec Communication SAS, all rights reserved. Infosec UPS System is a trademark or registered trademark of Infosec Communication. All other trademarks or registered trademarks belong to their respective owners. Photos
are not binding. Specifications are subject to change without prior notice. Backuptime is only a guide: actual duration may vary depending on the temperature, battery condition and peripherals added. UPS are part of electronic and electric
equipments category. At the end of their lives, they have to be collected separately. 04 17 AA 80 111 80