17 LT6159 issue 7(06/13)
660 PC Installation Instructions
SECTION NINE Checking Operation of Fire
CHECKING FOR COMBUSTION PRODUCTS CLEARENCE
IMPORTANT:-The smoke test must be
carried out with the fire starting from
cold.
Light the fire and leave at maximum
input.
Close all the doors and windows.
After five minutes fit the smoke
match in a holder and position as
illustrated with the head of the
match just inside the test opening
(Within the downdraft diverter slot) .
Run the match along the top edge
All smoke must be drawn into the
test opening if the clearance is
satisfactory.
If spillage occurs wait a further five
minutes and repeat the test.
Repeat the test with doors open and with any extractor fans in other rooms in operation.
If spillage is detected the cause must be discovered and the fault corrected, if the fault cannot be
corrected, disconnect the fire from the gas supply and seek expert advice. Spillage can be caused
by a restriction in the flue system, down draught or insufficient ventilation into the room where the
fire is installed.
FIT STANDARD FASCIA
Offer the decorative fascia up squarely and centrally. The back face of the fascia will have cut out
to give clearance for glass retaining brackets. Use these slots as guides, slide the fascia over the
firebox.
The rear of the fascia as four location studs. Lift the fascia and locate the studs within the slotted
holes two LH and RH within the assembly of the firebox .
ADVISE CUSTOMER THAT:
The glass front of this fire acts as a dress guard, conforming to BS 1945 (1997) and satisfies the
heating appliance regulations (1991) however; a fireguard conforming to BS6539 (1997) must be
used to protect young children, the elderly, or infirm.
The curing effect of heating the logs and other refractory components will cause an initial odour.
This is due to the starch used in the manufacturing process and is non-toxic.
Any debris should be cleaned from the appliance. A vacuum cleaner can be used but only after all
the loose logs have been removed.
The appliance should be serviced annually by a competent person in accordance with these
instructions and the appliance checked for spillage in accordance with the method detailed in
these instructions.
Demonstrate the lighting and extinguishing procedures to the user and the removal and refitting of
the Fascia and glass panel for cleaning. Refer to the user section of this booklet.
If ventilation is fitted for any reason it must be checked regularly to ensure freedom from
obstructions.
Hand these instructions over to the user.