Immergas HYDRO FS Instruction Booklet And Warning

Instruction booklet and
*1.041956ENG*
warning
IE
HYDRO FS
We would first of all like to thank you for having chosen one of our products.
We are sure you will be happy with it because it represents the state of the art in the technology of home air conditioning.
By following the suggestions contained in this manual, the product you have purchased will operate without problems, giving you optimum room temperatures with minimum energy costs.
Symbols
The pictograms in the next chapter provide the necessary information for correct, safe use of the appliance in a rapid, unmistakable way.
Warning The operation described may cause physical harm if not carried out in accordance with safety regulations.
Dangerous electrical current Make personnel aware that the operation described may lead to electrical shocks if not carried out in accordance with safety regulations.
High temperature danger Of safety regulations, the risk of burns caused by contact with components with high temperatures.
Prohibition
Refers to prohibited actions.
2
Summary
1. General ...................................................... 5
1.1 General warnings ............................................ 5
2. Modulating temperature controller kit .. 6
2.1 Assembly, set-up and connection .................... 6
2.2 Assembly ........................................................ 6
2.3 Set-up of auxiliary dip-switch functions B and C 7
2.4 CP presence contact input connection............. 7
2.5 Air temperature probe assembly ....................... 8
2.6 Connections ................................................... 9
3. 4-speed temperature controller kit ..... 10
3.1 Assembly and connections ............................ 10
3.2 Assembly ...................................................... 10
3.3 Air temperature probe assembly ..................... 11
3.4 Connections ................................................. 11
3.5 Water probe kit management ......................... 11
4. Universal card kit for commercial
temperature controller ......................... 12
4.1 Assembly and connections ............................ 12
4.2 Assembly ...................................................... 12
4.3 Connection diagram with 3-speed thermostat 13
4.4 Connections with 3-speed thermostats .......... 13
4.5 LED signals ................................................... 14
4.6 Water probe management with 3-speed
thermostat .................................................... 14
5. 0-10 V demand board kit ....................... 15
5.1 Assembly and connections ............................ 15
5.2 Assembly ...................................................... 15
5.3 LED signals ................................................... 15
5.4 Connection diagram with 0-10V DC
thermostats / signals ..................................... 16
5.5 Connections with 0-10V thermostats.............. 16
6. Feet kit .................................................... 17
6.1 Assembly ...................................................... 17
7. 2-way/3-way valve unit kit ..................... 18
7.1 List of hydraulic accessories .......................... 18
7.2 Pipeline diameter ........................................... 18
7.3 Access to inner parts ..................................... 18
7.4 Mounting the thermostatic head ..................... 19
7.5 Lockshield adjustment ................................... 19
7.6 Way valve with thermo-electric head kit .......... 21
7.7 Way valve with thermo-electric head deviator
valve kit ......................................................... 22
7.8 Connections ................................................. 24
7.9 2-way valve unit kit ........................................ 25
7.10 3-way valve unit kit ........................................ 26
8. Cooler-convector, heating, cooling
and deumidification ............................... 27
8.1 Fundamental safety rules ............................... 27
8.2 Description ................................................... 27
8.3 Identification .................................................. 28
8.4 Charts of Water flow - Pressure drop .............. 29
8.5 Dimensions ................................................... 30
8.6 Product delivery ............................................ 31
8.7 Handling and transportation ........................... 31
8.8 Access to inner parts ..................................... 31
8.9 Installation ..................................................... 32
8.10 Minimum installation distances ....................... 32
8.11 Vertically mounted ......................................... 33
8.12 Hydraulic connections ................................... 34
8.13 Condensation discharge ................................ 35
8.14 Electrical connections .................................... 36
8.15 Filling the system ........................................... 36
8.16 Evacuation of air when filling system ............... 37
8.17 First commissioning ....................................... 37
9. Modulating temperature controller kit . 38
9.1
SMART TOUCH electronic control panel..............38
9.2
Display ................................................................. 38
9.3 Key function .................................................. 38
9.4 General On Switch ........................................ 39
9.5 Activation ...................................................... 39
9.6 Heating/cooling operation modes setting ........ 39
9.7 Stand By ......................................................... 39
9.8 Temperature selection ................................... 40
9.9 Automatic operation ..................................... 40
9.10 Silent operation ............................................ 40
9.11 Night-time operation ..................................... 40
9.12 Operation at maximum ventilation speed ....... 40
9.13 Key lock ........................................................ 41
9.14 Reduce brightness to minimum ...................... 41
9.15 Deactivation .................................................. 41
9.16 Room temperature probe regulation offset ...... 41
9.17 Switching off for long periods ......................... 41
9.18 Error signals .................................................. 42
10. 4-speed temperature controller kit ..... 43
10.1
LCD electronic control panel ...............................43
10.2 LED indications ............................................. 43
10.3 Key function .................................................. 43
10.4 General On Switch ........................................ 43
10.5 Activation ...................................................... 44
10.6 Heating/cooling operation modes setting ........ 44
10.7 Stand By ......................................................... 44
10.8 Temperature selection ................................... 44
10.9 Ventilation speed regulation ............................ 44
10.10 Key lock .......................................................... 45
10.11 Reduce brightness to minimum ...................... 45
10.12 Deactivation .................................................. 45
10.13 Switching off for long periods ......................... 45
10.14 Error signals .................................................. 45
11. Maintenance ........................................... 46
11.1 Cleaning the outside ...................................... 46
11.2 Cleaning air suction filter ................................ 46
11.3 Energy saving tips ......................................... 47
3
12. Troubleshooting ..................................... 48
12.1 Table of anomalies and remedies ................... 48
4
1. GENERAL

1.1 General warnings

- This instruction is an integral part of the booklet of the appliance on which the kit is installed. Please consult this booklet for general warnings and fundamental safety rules.
- This manual is designed only for the qualified and authorised installation technician, who must be sufficiently trained and in possession of all psycho­physical requirements as per the law.
- All operations must be carried out with care and according to best practices, and in compliance with workplace safety regulations.
- After unpacking, check that the contents are intact and that all parts are included. If not, contact the agent who sold the appliance to you.
- It is forbidden to modify the safety or adjustment devices without authorisation from and indications of the manufacturer.
- It is forbidden to dispose of, or leave in the reach of children, the packaging materials which could become a source of danger.
- Repairs or maintenance must be performed by the Technical Assistance Service or by qualified personnel in accordance with this manual. Do not modify or tamper with the appliance as this could create dangerous situations and the manufacturer will not be liable for any damage caused.
5
2. MODULATING TEMPERATURE CONTROLLER KIT

2.1 Assembly, set-up and connection

The controllers have two independent clean contacts for controlling a refrigerator unit, a boiler and a presence input. The 2 tube versions have a 230V output to power the summer and winter solenoid valve. The 10 kΩ water temperature probe positioned in the

2.2 Assembly

Slide the control panel into its housing in the upper part of the device and fix it with the two fixing screws (ref. A). To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the fan coil body (ref. M) using the fixing screws (the minimum force that must be applied for tightening screws must be around 2N);
- connect the fast connector of the MOTOR to the other on the board (ref. I) *;
- on the two GRID block terminals (ref. L) there is a bridge which must not be removed.
- For other versions, remove the bridge and connect the two terminals originating on the grill safety microswitch*;
compartment on the battery regulations the minimum level when heating (30°C) and the maximum level when cooling (20°C). The board also has a function when there is no water probe, in such cases the fan stop thresholds are ignored.
- connect the water probe to the H2 connector on the device. The water temperature probe controls the temperature inside the batteries and determines when the fan starts according to pre-set parameters (minimum operation in winder and maximum in summer).** Check that they are correctly inserted into the compartment on the battery.
- Connect the electrics, tidy cables and fix them with the three clevises supplied (ref. G);
- close the box with the 4 screws (ref. H);
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the control panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph
** The regulation also works without a water probe
connected
A
D
B
C
E
G
H
I
L
M
6

2.3 Set-up of auxiliary dip-switch functions B and C

There are two dip switches on the controller circuit board for configuring unit operation as per requirements.
- The night-time heating operation logic is modified by using dip switch C:
- in the ON position, the fan is always off, and heats the room using radiation and natural convection, as with traditional radiators; in the off position it operates as a normal fan.
- By positioning dip switch B to ON, when cooling, the fan operates at the minimum speed even after having

2.4 CP presence contact input connection

On closing the contact connected to the CP input (ref. A) the panel is placed in stand-by mode. If the contact is open the unit is active, if the contact is closed it is deactivated when a key is pressed the symbol flashes.
reached the set point, to allow for more uniform operation of the temperature probe and to avoid layering in the air. With the cursor in the OFF position, the functions are cycled (4 minutes ON, 10 minutes OFF).
The input cannot be connected in parallel to that of other electronic boards (use separate contacts).
MOTOR
LED
ON
C
B
C
BA
D
ASCII
RTU
H4 H2 AIR
COMM
GRIDGRIDCP
A
N EV1 N EV2
LN
CHILLER BOILER
7

2.5 Air temperature probe assembly

- To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
A
D
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
C
B
8

2.6 Connections

H2* water temperature probe 10 kΩ AIR air temperature probe 10 kΩ M1 DC inverter fan motor S1 grill safety micro-switch
Y1
L-N
water solenoid valve (230V/ 50Hz 1A output voltage)
electrical power supply 230V/50Hz
BO boiler consent output (free contact max 1A) CH chiller consent output (free contact max 1A)
CP
* If after switching the power on the board detects
presence input sensor (if closed, the fan coil unit is placed in standby)
the probe, start-up occurs in normal conditions with the minimum water temperature when heating (30°C) and maximum when cooling (20°C). The board also has a function when there is no probe, in such cases the fan stop minimum and maximum thresholds are ignored.
9
3. 4-SPEED TEMPERATURE CONTROLLER KIT

3.1 Assembly and connections

The on-board controller with speed selector and ON/OFF key, room thermostat adjustable from 5 to 40°C, winter summer selector and minimum winter temperature function

3.2 Assembly

Slide the control panel into its housing in the upper part of the device and fix it with the two fixing screws (ref. A). To install the board:
- connect the grounding cable to the unit structure (ref. M) using the fixing screws (the minimum force that must be applied for tightening screws must be around 2N);
- connect the fast connector of the MOTOR to the other on the board (ref. I) *; N.B.: should the board not be fitted in the factory, the fan motor must be rotated 180° due to the length of the standard fan coil cable.
- on the two GRID block terminals (ref. L) there is a bridge which must not be removed.
- For other versions, remove the bridge and connect the two terminals originating on the grill safety microswitch; N.B.: should the two brown terminals on the unit be too short, replace them with those included in the kit packaging.
- connect the water probe connector H2 (ref. F) on the
(30°C) and maximum summer temperature (20°C) is suitable for fitting on board the unit and has a 230V - 1A output for controlling a solenoid valve.
unit. The water temperature probe controls the temperature inside the batteries and determines when the fan starts according to pre-set parameters (minimum operation in winter and maximum in summer). Check that they are correctly inserted into the compartment on the battery.
- make the electrical connections, tidy the cabling;
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the control panel;
- * For versions with hydraulic connections on the right, refer to the relevant paragraph.
A
M
10
L
F

3.3 Air temperature probe assembly

- To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
A
D

3.4 Connections

H2 water temperature probe 10 kΩ M1 DC inverter fan motor S1 grill safety micro-switch
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
C
B
Y1
L-N 230V/50Hz electrical power supply AIR air temperature probe 10 kΩ
water solenoid valve (230V/ 50Hz 1A output voltage)

3.5 Water probe kit management

If the board detects the water temperature detecting probe on the device positioned in the relevant compartment of the battery, it starts in normal conditions. If the probe is not connected, its absence is indicated by the blue and red LEDs flashing together, and operation stops. To confirm operation without the probe, press and hold the summer/winter button for 5 seconds (ref. A). This condition is saved by the board for future start-ups.
C A D
In any case, as and when the probe is connected, the unit returns to normal operation with temperature thresholds. If the unit operates with the probe connected and the water temperature is not suitable for active functioning (over 20°C when cooling, under 30°C when heating) the fan will stop and the anomaly will be indicated by the corresponding LED flashing (cooling: blue C or heating: red D).
11
4. UNIVERSAL CARD KIT FOR COMMERCIAL TEMPERATURE CONTROLLER

4.1 Assembly and connections

Assembled on-board the unit, this card allows the regulation of the motor with fixed speeds; it can be combined with control panels with thermostat and with all control panels

4.2 Assembly

Slide the blanking panel into its housing in the upper part of the device and fix it with the two fixing screws (ref. A). To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of
the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the unit body (ref. M)
using the fixing screws (the minimum force that must be applied for tightening screws must be around 2N);
- on the two SW GRL block terminals (ref. L) there is a
bridge which must not be removed.
available in the market. It has a 230 V output to pilot the summer and winter solenoid valve.
- For other versions, remove the bridge and connect the two terminals originating on the grill safety microswitch*;
- connect the fast connector of the MOTOR to the other on the board (ref. I);
- Connect the electrics, tidy cables and fix them with the three clevises supplied
- close the box with the 4 screws
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the blanking panel;
- place the screw head covers in their housing on the blanking panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph.
(ref. G)
;
(ref. H)
;
A
L
D
B
I
C
E
G
H
M
12

4.3 Connection diagram with 3-speed thermostat

Make the electrical connections to a thermostat fit for use according to the diagram.
L-N electrical supply 230V-50Hz EV solenoid valve permission input V1 maximum fan speed V2 medium fan speed V3 minimum fan speed V4 supersilent speed
E
Y2
Y1
heating selection input, cooling See paragraph on Water Probe Management output for mobile suction panel servo (power output 230V/ 50Hz 1A) water solenoid valve (230 V/ 50 Hz 1A output voltage)
M1 DC inverter fan motor S1 safety micro-switch for grill
3-speed room thermostat (to be purchased,
TA
CV thermostat permission SV speed selector H2* water temperature probe (10 kΩ)
*
installation and connection to be made by installer)
positioned in the on-board battery. See paragraph on Water Probe Management

4.4 Connections with 3-speed thermostats

The CV input is the board ON/OFF which when open puts the board in stand-by. It must be bridged to the L terminal on the 230V power supply to activate solenoid valve Y1. The 4 speed inputs V1, V2, V3 and V4, when bridged to the L terminal on the 230V power supply, activate the fan if the S1 input to which the grill safety microswitch is connected is closed. The sequence is: maximum speed (1400 rpm on terminal V1), medium speed (1100 rpm on terminal V2), minimum speed (680 rpm on terminal V3) and supersilent speed (400 rpm on terminal V4). Connect the three thermostat speeds to 3 out of the 4 available inputs as per the characteristics and use of the
room: connect, for example, medium speed V2, minimum V3 and supersilent V4 for residential applications, when greater silence is required, whereas V1, V2 and V3 can be connected for commercial applications where the thermal yield is more important. If multiple inputs are simultaneously closed, the motor will run at a number of revs equal to that of the connection with the highest speed. Multiple cards can be connected in parallel to a single thermostat, also using different speeds.
13

4.5 LED signals

The LED (ref. A) is off if the CV input is not closed (stand-by condition). It turns on when the CV contact is closed and indicates normal operation.
• Flashes frequently if the grille microswitch S1 is activated due to the filter cleaning operation
• 1 flash + pause indicates a fan stoppage alarm due to unsuitable water (with H2 water probe connected).
• 2 flashes + pause due to a motor alarm (e.g. blockage caused by foreign objects, faulty rotation sensor).

4.6 Water probe management with 3-speed thermostat

If the board is used with electromechanical thermostats, or with other commercial controllers with water probe, the on-board probe H2 should not be connected and the fan is controlled by the remote control. If on the other hand the controller is not set up for managing the water probe, this function can be performed by the board, by connecting the 10 kΩ probe on the battery to the H2 connector on the board (ref. B). In this case the board carries out the minimum temperature function for heating operations and maximum temperature function for cooling. Therefore, if the water temperature is not suitable for active operation (above 20°C when cooling, under 30°C when heating) the fan is stopped and the anomaly is signalled by a single flash + pause of the LED (ref. A).
• 3 flashes + pause indicates a disconnected or faulty water probe alarm.
The discrimination between heating/cooling is actuated via the Summer-Winter (ref. C) input of the board: leaving it open the board activates heating, closed activates cooling. If after having connected the probe it is disconnected or measures incorrect values (e.g. installation of 2 kΩ probe in the place of the 10 kΩ probe) the anomaly is signalled by 3 flashes + pause of the LED (ref. A) and operation is stopped. To confirm operation without a probe, turn the power to the board off and then on again. This condition is saved by the board for future start-ups. In any case, as and when the probe is connected, the unit returns to normal operation with temperature thresholds.
A
B
C
14
5. 0-10 V DEMAND BOARD KIT

5.1 Assembly and connections

When fitted on board the machine it allows for managing the motor, with modulated speed; motor regulation can be made using an analogue 0-10V DC input with 25 kΩ impedance.

5.2 Assembly

Slide the blanking panel into its housing in the upper part of the device and fix it with the two fixing screws (ref. A). To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the unit structure using the fixing screws (the minimum force that must be applied for tightening screws must be around 2N);
- on the two GRID block terminals (ref. I) there is a bridge which must not be removed.
A
For board control outputs these impedance values must be considered, especially when controlling more than one unit in parallel. It has a 230 V output to pilot the solenoid valve.
- For other versions, remove the bridge and connect the two terminals originating on the grill safety microswitch;*
- connect the fast connector of the MOTOR to the other on the board (ref. H);
- Connect the electrics, tidy cables and fix them with the three clevises supplied
- close the box with the 4 screws
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the blanking panel;
- place the screw head covers in their housing on the blanking panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph.
(ref. F)
;
(ref. G)
;
D
C
E

5.3 LED signals

The LED (ref. L) is off is the input signal is less than 0.9V. It turns on with values greater than 1V and indicates normal operation.
• Flashes frequently if the grille microswitch S1 is activated due to the filter cleaning operation
L
H
I
B
F
G
• 2 flashes + pause due to a motor alarm (e.g. blockage caused by foreign objects, faulty rotation sensor).
15
Y2
)

5.4 Connection diagram with 0-10V DC thermostats / signals

Make the electrical connections to a thermostat fit for use according to the diagram
L-N Electrical power supply 230V-50 Hz 10V Appliance piloting input 0÷10 V
Y1
water solenoid valve (230V/ 50Hz 1A output voltage)
Input impedance 25 kΩ
Y2
M1 S1 safety micro-switch for grill
output for mobile suction panel servo (power output 230 V/ 50Hz 1A) DC inverter fan motor
OUTPUT FEATURES
MAX rpm
M1
MIN rpm

5.5 Connections with 0-10V thermostats

The 10V input, if the S1 input which the grill safety micro switch is connected to is closed, activates solenoid valve Y1 and regulations fan revolutions. The speed "ramp" provides for linear regulation from the minimum value (400 rpm) to the maximum value (1,400 rpm)
ON
Y1
OFF
0
1
1,1
0,9
for voltage values ≥ 1.1V÷10 V DC. The motor is off when values are lower than 1V DC. The Y1 solenoid valve is activated for power values > 1V DC and switches off then the power drops below 0.9V DC.
10
10 V INPUT (V DC
16
Loading...
+ 36 hidden pages