IMI Cornelius, Inc. Venture Installation Manual

Page 1
VENTURE
CARBONATED & NONCARBONATED
Installation Manual
IMPORTANT:
TO THE INSTALLER. It is the responsibility of the Installer to
ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112. 1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local laws.
POST-MIX DISPENSERS
Part No. 318832000 September 22, 1981 Revised: February 17, 1997 Control Code B
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 1981-97Ó
PRINTED IN U.S.A
Page 2
TABLE OF CONTENTS
SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RECOGNIZE SAFETY INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNDERSTAND SIGNAL WORDS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOLLOW SAFETY INSTRUCTIONS 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 (CARBON DIOXIDE) WARNING 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHIPPING, STORING, OR RELOCATING UNIT 1. . . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL DESCRIPTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT DESCRIPTION 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD UNIT (REQUIRES CONNECTION TO A REMOTE
CARBONATOR) 3. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
UNIT WITH BUILT-IN COLD CARBONATOR 3. . . . . . . . . . . . . . . . . . . . . . . . . .
NONCARBONATED UNIT 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY REFERENCE INFORMATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THEORY OF OPERATION 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATED UNITS 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NONCARBONATED UNITS 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
UNPACKING AND INSPECTION 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SELECTING LOCATION 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLACING UNIT IN OPERATING POSITION 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FILL WATER TANK AND STAR T REFRIGERATION SYSTEM 13. . . . . . . . . . . . . . .
INSTALLATION 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING DRIP TRAY DRAIN HOSE 14. . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING PLAIN WATER SOURCE LINE(S) TO UNIT 14. . . . . . . . . . . . .
CONNECTING CARBONATED WATER SOURCE LINE TO UNIT 15. . . . . . .
CONNECTING CO2 SOURCE LINE TO UNIT 15. . . . . . . . . . . . . . . . . . . . . . . . .
CONNECTING SYRUP SOURCE LINES TO UNIT 15. . . . . . . . . . . . . . . . . . . . .
PREPARATION FOR OPERATION 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD UNIT REQUIRING CONNECTION TO A REMOTE
CARBONATOR 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT WITH BUILT-IN COLD CARBONATOR 16. . . . . . . . . . . . . . . . . . . . . . . . . .
NONCARBONATED UNIT 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT OPERATION 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BLEEDING SYRUP AND APPLICABLE PLAIN OR CARBONATED
WATER SYSTEMS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUST WATER-TO-SYRUP “RATIO” OF DISPENSED PRODUCT 17. . . . .
INSTALL DECALS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERA TOR’S INSTRUCTIONS 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATING CONTROLS 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVE LEVER 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVE WITH WATER LEVER 21. . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSING VALVES KEYED LOCK-OUT SWITCH 21. . . . . . . . . . . . . . . . . .
UNIT POWER SWITCH (IF APPLICABLE) 21. . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
318832000
Page 3
TABLE OF CONTENTS (cont’d)
CARBONATOR WATER PUMP MOTOR POWER SWITCH (UNIT WITH
BUILT-IN COLD CARBONATOR) 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY PRE-OPERATION CHECK 21.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT OPERATION 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING CO2 SUPPLY 22. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
REPLENISHING SYRUP SUPPLY 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND SANITIZING 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY CLEANING OF UNIT 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SANITIZING SYRUP SYSTEMS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHECKING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL
FOR RESTRICTIONS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHECKING ICE WATER BATH 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER
SYSTEM DISRUPTIONS 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT REQUIRING CONNECTION TO A REMOTE CARBONATOR
(STANDARD UNIT) 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT WITH BUILT-IN COLD CARBONATOR 23. . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING CO2 GAS CHECK VALVES 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE AND MAINTENANCE 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
PREPARING UNIT FOR SHIPPING, STORING, OR RELOCATING 25. . . . . . . . . .
HOOD AND FRONT PANEL REMOVAL 25.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
HOOD REMOVAL 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FRONT ACCESS PANEL REMOVAL 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERIODIC INSPECTION 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTMENTS 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CO2 REGULATORS ADJUSTMENTS 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING DISPENSING VALVE WATER FLOW RATE 27. . . . . . . . . . . . . . .
ADJUSTING DISPENSING VALVES FOR WATER-TO-SYRUP “RATIO” (BRIX)
OF DISPENSED PRODUCT 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING AND SANITIZING 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAILY CLEANING OF UNIT 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SANITIZING POST-MIX SYRUP SYSTEMS 28. . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL 30. . . .
CHECKING ICE WATER BATH 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING WATER TANK 31.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER
SYSTEM DISRUPTIONS 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT CONNECTED TO REMOTE CARBONATOR (STANDARD UNIT) 33. . .
UNIT WITH BUILT-IN COLD CARBONATOR 33. . . . . . . . . . . . . . . . . . . . . . . . . .
NO. 3 DISPENSING VALVE CONVERSION FROM STILL TO CARBONATED
DRINK 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD UNIT 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT WITH BUILT-IN COLD CARBONATOR 36. . . . . . . . . . . . . . . . . . . . . . . . . .
REPLENISHING CO2 SUPPLY 36. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
REPLENISHING SYRUP SUPPLY 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYRUP TANK SYSTEM 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
318832000
ii
Page 4
TABLE OF CONTENTS (cont’d)
BAG-IN-BOX SYRUP SYSTEM 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SYRUP FLAVOR CHANGE 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING CO2 SYSTEM CO2 GAS CHECK VALVES 37. . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDARD UNIT (REQUIRES CONNECTION TO A REMOTE CARBONATOR) 43
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH 43. . . . . . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 43. . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 44. . . . . . . . . .
DISPENSED PRODUCT CARBONATION TOO LOW. 44. . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT
FOAMS IN CUP OR GLASS. 44.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING
VALVE. 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NO PRODUCT DISPENSED. 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ONLY CARBONATED WATER DISPENSED. 45. . . . . . . . . . . . . . . . . . . . . . . . . .
ONLY SYRUP DISPENSED. 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT WITH BUILT-IN COLD CARBONATOR 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH 46. . . . . . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 46. . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 46. . . . . . . . . .
DISPENSED PRODUCT CARBONATION TOO LOW. 46. . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR
BUT FOAMS IN CUP OR GLASS. 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES
DISPENSING VALVE. 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES. 47. . . . . . . .
ONLY CARBONATED WATER DISPENSED. 48. . . . . . . . . . . . . . . . . . . . . . . . . .
ONLY SYRUP DISPENSED. 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NONCARBONATED UNIT 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH 49. . . . . . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 49. . . . . . . . . . .
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES
NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”. 49. . . . . . . . . .
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT
FOAMS IN CUP OR GLASS. 49.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES
DISPENSING VALVE. 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES. 50. . . . . . . .
ONLY PLAIN WATER DISPENSED. 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ONLY SYRUP DISPENSED. 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERATION SYSTEM 50.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .
COMPRESSOR DOES NOT OPERATE. 50.. .. .. .. .. .. .. .. .. .. .. .. .. .. .
Page
iii
318832000
Page 5
TABLE OF CONTENTS (cont’d)
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS
PRODUCED.. 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM
SUFFICIENT ICE BANK. 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AGITATOR MOTOR NOT OPERATING. 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARRANTY 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES
FIGURE 1. VENTURE SIX-FLAVOR POST-MIX DISPENSER 4. . . . . . . . . . . . . . .
FIGURE 2. FLOW DIAGRAM (SIX FLAVOR UNIT REQUIRING CONNECTION TO
A REMOTE CARBONATOR) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 3. FLOW DIAGRAM (SIX-FLAVOR UNIT BUILT-IN COLD
CARBONATOR) 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 4. FLOW DIAGRAM (SIX-FLAVOR NON-CARBONATED UNIT) 10. . . . .
FIGURE 5. INLET SUPPLY LINE CONNECTIONS (STANDARD UNIT) 18. . . . . . .
FIGURE 6. INLET SUPPLY LINE CONNECTIONS (UNIT WITH BUILT-IN COLD
CARBONATOR) 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 7. INLET SUPPLY LINE CONNECTIONS (NONCARBONATED UNIT) 20 FIGURE 8. DISPENSER COMPONENTS (UNIT WITH BUILT-IN CARBONATOR
SHOWN) 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 9. WATER TANK (UNIT WITH BUILT-IN COLD CARBONATOR
SHOWN) 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 10. WATER STRAINER SCREEN AND DOUBLE LIQUID CHECK
VALVE 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 11. LIQUID CHECK VALVE ASSEMBLY 34. . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 12. CO2 GAS CHECK VALVE ASSEMBLY 38. . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 13. WIRING SCHEMATIC FOR GERMAN ICE BANK CONTROL
(OPTIONAL) 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 14. WIRING DIAGRAM (60 HZ UNIT WITH 1/3 H.P. REFRIGERATION
ASSEMBLY) 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 15. WIRING DIAGRAM (50 HZ UNIT WITH 1/3 H.P. REFRIGERATION
ASSEMBLY) 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURE 16. WIRING DIAGRAM (60 HZ UNIT WITH 1/4 H.P. REFRIGERATION
ASSEMBLY AND BUILT-IN COLD CARBONATOR) 41. .. .. .. .. .. .. .. .. .. .. .. .
FIGURE 17. WIRING DIAGRAM (50 HZ UNIT WITH 1/4 H.P. REFRIGERATION
ASSEMBLY AND BUILT-IN COLD CARBONATOR) 42. .. .. .. .. .. .. .. .. .. .. .. .
Page
LIST OF TABLES
TABLE 1. DESIGN DATA 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE 2. LOOSE-SHIPPED PARTS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
318832000
iv
Page 6
SAFETY INFORMATION
Recognize Safety Information
This is the safety-alert symbol. When you see this symbol on our machine or in this manual, be alert to the potentially of personal injury.
Follow recommended precautions and safe operating practices.
Understand Signal Words
A signal word - DANGER, WARNING, OR CAUTION is used with the safety-alert symbol. DANGER identi­fies the most serious hazards.
DANGER
Safety signs with signal word DANGER or WARNING are typically near specific hazards.
General precautions are listed on CAUTION safety signs. CAUTION also calls attention to safety mes­sages in this manual.
WARNING
CAUTION
Follow Safety Instructions
Carefully read all safety messages in this manual and on your machine safety signs. Keep safety signs in good condition. Replace missing or damaged safety signs. Learn how to operate the machine and how to use the controls properly . Do not let anyone operate the machine without instructions. Keep your machine in proper working condition. Unauthorized modifications to the machine may impair function and/or safety and affect the machine life.
CO2(Carbon Dioxide) Warning
CO2Displaces Oxygen. Strict Attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Person­nel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
Shipping, Storing, Or Relocating Unit
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must also be purged from the plain and carbonated water systems. A freezing ambient temperature will cause residual water remaining inside the Unit to freeze resulting in damage to internal components of the Unit.
1 318832000
Page 7
Page 8
THIS PAGE LEFT BLANK INTENTIONALLY
318832000
2
Page 9
GENERAL INFORMATION
IMPORTANT: To the user of this manual - This manual is a guide for installing, operating, and main­taining this equipment. Refer to the Table of Contents for page location for detailed information per­taining to questions that arise during installation, operation, service, or maintenance of this equipment.
GENERAL DESCRIPTION
This section gives the Unit description, theory of operation, and design data for the four-, five-, and six-flavor Venture Post-Mix Dispensers (hereafter referred to as Units).
This Unit must be installed and serviced by a qualified Service Person. This Unit contains no User serviceable parts.
UNIT DESCRIPTION
The Units are compact with high-impact and corrosion-resistant moulded lower housings and may be island­mounted or installed on a front or rear counter. Their refrigeration assemblies are the drop-in type that can be removed for service and maintenance. Adjustable syrup flow regulators, located on dispensing valves, are easily accessible to control Water-To-Syrup “Ratio” of dispensed product. All Units have electric dispensing valves.
NOTE: Optional 4-inch Legs (P/N 314744000) that will elevate the Unit 4-inches above the countertop are available. When ordering legs, order a quantity of four.
STANDARD UNIT (REQUIRES CONNECTION TO A REMOTE CARBONATOR)
This Unit (see Figure 2) is equipped with a 1/3 H.P. refrigeration assembly and requires connection to a remote carbonator. Installation of Unit on a countertop, installation of LOOSE-SHIPPED PARTS, connection of remote carbonator and plain water and syrup supplies, adjustment of CO2regulators, filling water tank with water, and plugging Unit power cord into an electrical outlet is all that is required for operation.
UNIT WITH BUILT-IN COLD CARBONATOR
This Unit (see Figure 3) is equipped with a 1/4 H.P. refrigeration assembly and has a built-in cold carbonator located inside the water tank. Installation of Unit on a countertop, installation of LOOSE-SHIPPED PARTS, connection of plain water and syrup supplies, adjustment of CO2regulators, filling water tank with water, and plugging Unit power cord into an electrical outlet is all that is required for operation.
NONCARBONATED UNIT
This Unit (see Figure 4) is equipped with a 1/3 H.P. refrigeration assembly and dispenses all noncarbonated (still) drinks. Installation of Unit on a countertop, installation of LOOSE-SHIPPED parts, connection of plain wa­ter and syrup supplies, adjustment of CO2regulators, filling water tank with water, and plugging Unit power cord into an electrical outlet is all that is required for operation.
3
318832000
Page 10
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must
also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
WARRANTY REFERENCE INFORMATION
Warranty Registration Date
(to be filled out by customer) Unit Part Number: Serial Number: Install Date: Local Authorized
Service Center:
FIGURE 1. VENTURE SIX-FLA VOR POST-MIX DISPENSER
Table 1. Design Data
CARBONA TED UNITS:
60 HZ Unit:
1/3 HP refrigeration 115 V, 60 HZ (Requires a Remote Carbonator)
Four Flavor 417354XXX Five Flavor 417351XXX
417355XXX 417365XXX 418355XXX 427355XXX
Six Flavor 417356XXX
417366XXX
1/4 HP refrigeration 115V 60 HZ w/built-in Cold Carbonator
Five Flavor 417405XXX Six Flavor 417406XXX
318832000
4
Page 11
Table 1. Design Data (cont’d)
50 HZ Unit:
1/3 HP refrigeration 230V, 50 HZ (Requires a Remote Carbonator)
Four Flavor 497354XXX Five Flavor 497355XXX
497400XXX 498355XXX 498400XXX
Six Flavor 497356XXX
497401XXX 498356XXX
1/4 HP refrigeration 230V 50 Hz w/built-in Carbonator
Four Flavor 497404XXX Five Flavor 497405XXX Six Flavor 497416XXX
NONCARBONA TED CARBONATED UNITS:
60 HZ Unit:
1/3 HP refrigeration 115 V, 60 HZ
Five Flavor 412155XXX
412165XXX
Six Flavor 412156XXX
412166XXX
Overall Dimensions:
Width 16 1/4 inches Height 27 5/8 inches Depth 24 1/2 inches
Weight: Four, Five or Six-Flavor Standard and NonCarbonated Unit with
1/3 HP refrigeration.
Shipping (one carton) approx. 124 Pounds Dry Weight (approx.) 115 Pounds Ice Bank Weight 31 Pounds Drop in Refrigeration Assembly 58 Pounds
Weight: Four, Five, or Six Flavor Unit with 1/4 HP refrigeration and built-in
cold carbonator.
Shipping (one carton) approx. 130 Pounds Dry Weight (approx.) 125 Pounds Ice Bank Weight 24 Pounds Drop in Refrigeration Ass’y 71.6 Pounds
Water Tank Capacity (no ice bank approximate)
Four, Five, or Six-Flavor 9 3/4 Gallons
1/3 H.P. Refrigeration Ass’y Standard Unit 1/3 HP Refrigeration Five, or Six-Flavor Unit with built-in
9 1/4 Gallons
Cold Carbonator and 1/4 HP Refrigeration
Refrigerant Requirement See Unit
Nameplate
Ambient Operating Temperature 40° F to 100° F
5
318832000
Page 12
Table 1. Design Data (cont’d)
Unit Water Inlet Pressure 25-30 PSI
Unit Electrical Requirements See Unit
Nameplate
No. of
Dispens-
ing
Valves
5 4 1/3 HP=650 1/4 HP=252 6 4 1/3HP =520 1/4HP = 248
NOTE: Number of 12-oz drinks dispensed 40° F or below @ 75° F syrup and water inlet temperature and 75° F ambient.
No. of
12 Oz
Drinks/
Min.
No. of Drinks 40° F
Or Below
(see NOTE)
THEORY OF OPERATION
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
CARBONATED UNITS
Standard Units (Requires Connection To a Remote Carbonator).
(see Figure 2) The Unit was set up at the factory to dispense a still (non-carbonated) drink from No. 3 dispensing valve and
carbonated drinks from the remaining dispensing valves. No. 3 dispensing valve may be converted to also dis­pense a carbonated drink. Refer to TABLE OF CONTENTS for conversion instructions.
A CO2cylinder delivers carbon dioxide (CO2) gas through adjustable CO2regulators to the applicable syrup tanks or bag-in-box syrup pumps and also to a remote carbonator. Plain water enters the remote carbonator carbonated water tank and is carbonated by regulated CO2gas pressure also entering the tank.When dispens­ing valve is opened, CO2gas pressure exerted upon the syrup tank or on the bag-in-box system syrup pump, pushes syrup through the Unit syrup cooling coil, and on to the dispensing valve.
Carbonated water is propelled by CO2gas pressure which pushes carbonated water from the carbonated water tank, through the Unit cooling coils, and on to the dispensing valve. Syrup and carbonated water meet simulta­neously at the dispensing valve resulting in a carbonated drink being dispensed. A still (non-carbonated) drink is dispensed from No. 3 dispensing valve in the same manner as the carbonated drink except plain water is substi­tuted for carbonated water.
318832000
6
Page 13
Units With Built-In Cold Carbonators.
(see Figure 3) The Unit was set up at the factory to dispense a still (noncarbonated) drink from No. 3 dispensing valve and car-
bonated drinks from the remaining dispensing valves. No. 3 dispensing valve may be converted to also dis­pense a carbonated drink. Refer to TABLE OF CONTENTS for conversion instructions.
A CO2cylinder delivers carbon dioxide (CO2) gas through adjustable CO2regulators to the applicable syrup tanks or bag-in-box syrup pumps and to a built-in carbonator located inside the Unit. Plain water is pumped into the carbonator carbonated water tank by a water pump and is carbonated by regulated CO2gas pressure also entering the tank. When dispensing valve is opened, CO2gas pressure exerted upon the syrup tank or on the bag-in-box system syrup pump, pushes syrup through the Unit syrup cooling coil, and on to the dispensing valve. Carbonated water is pushed by CO
gas pressure from the carbonated water tank, through the Unit car-
2
bonated water cooling coils, and on to the dispensing valve. Syrup and carbonated water meet simultaneously at the dispensing valve resulting in a carbonated drink being
dispensed. A still (noncarbonated) drink is dispensed from the No. 3 dispensing valve in the same manner as the carbonated drink except plain water is substituted for carbonated water.
The carbonated water tank is replenished when the carbonated water level inside the tank drops, which in turn automatically starts the carbonator water pump. When the carbonated water level inside the tank has been re­plenished, the carbonator water pump will stop.
NONCARBONATED UNITS
(see Figure 4) A CO2cylinder delivers carbon dioxide (CO2) gas through adjustable CO2gas regulators to the applicable syrup
tanks or bag-in-box syrup pumps. When dispensing valve is opened, CO2gas pressure exerted upon the syrup tank or on the bag-in-box system syrup pump, pushes syrup through the Unit syrup cooling coils, and on to the dispensing valve. Plain water enters the Unit and passes through the Unit plain water cooling coils on the way to the dispensing valve. Syrup and plain water meet at the same time at the dispensing valve resulting in a still (noncarbonated) drink being dispensed.
7
318832000
Page 14
PLAIN WATER
CO2 CHECK
VALVE
COOLING COILS (9)
CARBONATED­WATER MANIFOLD
1
2
NON--CARBONATED
DRINK
3
REGULATED CO2 SUPPLY
REMOTE
CARBONATOR
CAPPED
TEE
FITTING
4
5
6
DISPENSER
DISPENSING VALVE (6)
SYRUP SUPPLY (SYRUP TANKS OR BAG-IN-BOX SYSTEM)
LINE LEGEND CO2 PLAIN WATER
SYRUP
FIGURE 2. FLOW DIAGRAM (SIX FLAVOR UNIT REQUIRING CONNECTION TO A REMOTE CARBONATOR)
318832000
8
Page 15
REGULATED CO2 SUPPLY
PLAIN WATER
CO2 CHECK
VALVE
WATER PUMP
DOUBLE LIQUID
CHECK VALVE
BUILT--IN
CARBONATOR
COOLING COILS (9)
1
2
NON--CARBONATED
DRINK
CAPPED CROSS FITTING
DISPENSER
SYRUP SUPPLY (SYRUP TANKS OR BAG-IN-BOX SYSTEM)
LINE LEGEND CO2 PLAIN WATER
SYRUP
3
4
5
6
DISPENSING VALVE (6) CARBONATED­WATER MANIFOLD
FIGURE 3. FLOW DIAGRAM (SIX-FLAVOR UNIT BUILT-IN COLD CARBONATOR)
9
318832000
Page 16
PLAIN WATER SUPPLY
PLAIN WATER COOLING COILS
1
WATER MANIFOLD
SYRUP COOLING COIL (5)
DISPENSER
2
3
4
5
6
SYRUP SUPPLY (SYRUP TANKS OR BAG-IN-BOX SYSTEM)
318832000
LINE LEGEND CO2 PLAIN WATER
SYRUP
FIGURE 4. FLOW DIAGRAM (SIX-FLAVOR NON-CARBONATED UNIT)
10
Page 17
INSTALLATION
This section covers unpacking and inspection, selecting location, installing Unit, preparing for operation, and operation.
UNPACKING AND INSPECTION
NOTE: The Unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it. Any damage or irregularities should be noted at the time of delivery (or not later than 15 days from date of delivery) and immediately reported to the delivering carrier. Request a written inspec­tion report from Claims Inspector to substantiate any necessary claim. File claim with the delivering carrier, not with IMI Cornelius Inc.
1. After Unit has been unpacked, remove shipping tape and other packing material.
2. Lift hood straight up and off Unit.
3. Remove four shipping nuts that secure drop-in refrigeration assembly in Unit.
4. Remove two screws (if applicable) securing front access panel to Unit, then remove panel.
5. Unpack LOOSE-SHIPPED PARTS. Make sure all items are present and in good condition.
CARBONA TED UNITS WITH 1/3 H.P. REFRIGERATION
(REQUIRES CONNECTION TO A REMOTE CARBONATOR)
Table 2. Loose-Shipped Parts
Item
No. Part No. Name 4-FL 5-FL 6-FL
1 317659039 Drip Tray 1 1 1 2 317660000 Cup Rest 1 1 1 3 317792000 Line Outlet Plug 1 1 1 4 176193000 Fitting, 7/16-20 (2) 5 6 7
NONCARBONA TED UNITS WITH 1/3 H.P. REFRIGERATION
Item
No. Part No. Name 5-FL 6-FL
1 317659039 Drip Tray 1 1 2 317660000 Cup Rest 1 1 3 317792000 Line Outlet Plug 1 1 4 176193000 Fitting, 7/16-20 (2) 6 7 5 318523088 Test Baffle Ass’y, Dispensing Valve (see Note below) 1 1
NOTE: Temporarily used to adjust dispensing valves for Water-To -Syrup “Ratio” of dispensed product.
11
318832000
Page 18
UNITS WITH 1/4 H.P. REFRIGERATION AND BUILT-IN COLD CARBONATOR
Item
No. Part No. Name 4FL 5FL 6FL
1 317659039 Drip Tray 1 1 1 2 317660000 Cup Rest 1 1 1 3 317792000 Line Outlet Plug 1 1 1 4 77070402 Fitting, Stainless Steel, 5/8-18 (2) 1 1 1 5 176017000 Swivel Nut, 7/16-20 1 1 1 6 311304000 Tapered Gasket, Black 3 3 3 7 77010400 Nipple, 7/16 Nut (for .265 Tube) 1 1 1 8 300200000 Tubing Clamp 1 1 1
SELECTING LOCATION
CAUTION: This Unit is intended for indoor installation only. Do not install this Unit in an outdoor environment which would expose it to the outside elements.
This Unit may be island-mounted or installed on a front or rear counter. Locate the Unit so the following require­ments are satisfied:
WARNING: To avoid possible fatal electrical shock or serious injury to the operator, it is highly recommended that a GFCI (ground fault circuit interrupt) be installed in the electrical circuit for the domestic Units. It is required that an ELCB (earth leakage circuit
breaker) be installed in the electrical circuit for the export Units
1. The Unit must be installed near a properly grounded electrical outlet with proper electrical require­ments.The electrical circuit must be properly fused (slow-blow type fuse) or the circuit must be connected through an equivalent HACR circuit breaker.The electrical outlet must be accessible for ease of connecting and disconnecting the Unit power cord. No other electrical equipment should be connected to this circuit.
REFER TO UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE, HZ, AND THE MINIMUM CIRCUIT AMPACITY OF THE UNIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES.
CAUTION: Do not place or store anything on top of the Unit.
2. A minimum of 15-inches clearance must be maintained above the Unit to the nearest obstruction (shelf, cupboard, ceiling, etc.) and 6-inches clearance between back-side of the Unit and the wall. The front grille of the Unit must be unobstructed to allow air to enter the hood.
3. Close to a permanent drain to route drip tray drain hose and water tank drain hose.
4. The top of the unit is to remain free of all objects. Do not place anything on top of unit.
318832000
12
Page 19
PLACING UNIT IN OPERATING POSITION
NOTE: Some of the Units are manufactured with water and syrup inlet lines that are to be routed to out­side of the Unit and be connected to water and syrup source lines. Some Units are also assembled at the factory not equipped with water and syrup inlet lines and require water and syrup source lines to be routed to inside of the Unit and be connected to labeled stainless-steel inlet tubes on front of the Unit. For Units not equipped with factory installed water and syrup inlet lines, the water and syrup source lines may be routed in through Unit back access hole or up through hole cut in the countertop to inside of the Unit to be connected to labeled stainless-steel inlet tubes on front of the Unit.
Proceed as follows to place Unit manufactured with water and syrup inlet lines in operating position.
The Unit inlet supply lines, power cord, water tank drain hose, and drip tray drain hose must either be routed out Unit base back access hole, under drip tray at front of the Unit, or if island-mounted, through hole cut in counter­top under the Unit. Proceed to applicable installation procedure.
1. Unit Base Access Panel- Place Unit in location on the countertop. Route Unit inlet supply lines, power cord, water tank drain hose, and drip tray drain hose out base back access hole. Area around inlet supply lines at flanged hole behind front access panel must be closed and sealed.
Under Drip Tray At Front Of Unit- Place Unit in location on the countertop with drip tray extended over the edge of the countertop approximately one inch. Route Unit inlet supply lines, power cord, water tank drain hose. and drip tray drain hose out back access hole. Area around inlet supply lines at flanged hole behind front access panel must be closed and sealed. Install LINE OUTLET PLUG, pro­vided with the Unit, in Unit base back access hole.
Island-Mounted- Place Unit in location on the countertop flush with the countertop edge. Mark Unit center line on edge of the countertop, then move Unit off to one side. Starting at center line mark on edge of the countertop, measure back 12-inches for location of 2-inch hole to be cut in the countertop. Cut a 2-inch hole in countertop where indicated. Place Unit in position over the hole. Route Unit inlet supply lines, power cord, water tank drain hose, and drip tray drain hose down through hole in countertop. Install LINE OUTLET PLUG, provided with the Unit, in Unit base back access hole. Area around inlet supply lines at flanged hole behind front access panel must be closed and sealed.
2. To comply with NSF International (NSF) requirements within the United States, Unit base must be sealed to countertop and all access holes to base must be sealed. Proceed as follows to seal Unit base.
NOTE: An alternate arrangement to avoid sealing the Unit base to the countertop as described, would be to install four 4-inch Legs ( Leg P/N 314744000).
A. Tilt Unit up to expose bottom of base. B. Liberally apply silastic sealant such as Dow Corning RTV 731 or equivalent on base bottom edges.
NOTE: Do not move Unit after positioning or seal from base to countertop will be broken.
C. Lower Unit into operating position on counter top to complete seal from base to countertop. D. Apply additional sealant around bottom of base. Seal must have a minimum radius of 1/2-inch to pre-
vent crevices and to ensure a complete seal.
E. All access holes to inside of the Unit base must be closed and sealed.
FILL WATER TANK AND START REFRIGERATION SYSTEM
1. Make sure plug in water tank drain hose is secure.
NOTE: Use low -mineral-content water where a local water problem exists.
2. Remove plug from drop-in refrigeration assembly platform water fill hole. Fill water tank with clean water to top of stainless steel coils located in coil basket.
3. Install plug in water fill hole.
13
318832000
Page 20
4. 60 HZ Units Place Unit power switch (if applicable) in “OFF” Position. ON UNIT WITH BUILT-IN COLD CARBONATOR,
MAKE SURE CARBONATOR WATER PUMP MOTOR SWITCH, LOCATED ON REFRIGERATION AS-
SEMBLY CONTROL BOX, IS IN “OFF” POSITION.
50 HZ Units On Units with built-in cold carbonator (see Figure 8) make sure carbonator water pump motor switch,
located on refrigeration assembly control box, is in “OFF” position.
WARNING: The Unit must be electrically grounded to avoid possible fatal electrical shock or serious injury to the operator. The Unit power cord is equipped with a three-prong plug. If a three-hole (grounded) electrical outlet is not available, use an approved method to
ground the Unit.
5. 60 HZ Units A. Plug Unit power cord into an accessible properly grounded electrical outlet with GFCI (ground fault
circuit interrupt).
B. Place Unit power switch (if applicable) in “ON” position. Compressor, condenser fan motor, and agita-
tor motor will start and begin forming an ice bank. When full ice bank has been formed, compressor and condenser fan motor will stop but agitator motor will continue to operate circulating ice water bath in water tank. ON UNIT WITH BUILT-IN COLD CARBONATOR (see Figure 8), DO NOT PLACE CAR-
BONATOR WATER PUMP MOTOR SWITCH IN “ON” POSITION AT THIS TIME.
50 HZ Units
C. Plug Unit power cord into an accessible properly grounded electrical outlet with ELCB (earth leakage
circuit breaker).
D. Compressor, condenser fan motor, and agitator motor will start and begin forming an ice bank. When
full ice bank has been formed, compressor and condenser fan motor will stop but agitator motor will continue to operate circulating ice water bath in water tank. ON UNIT WITH BUILT-IN COLD CARBO-
NATOR (see Figure 8), DO NOT PLACE CARBONATOR WATER PUMP MOTOR SWITCH IN “ON” POSITION AT THIS TIME.
INSTALLATION
CONNECTING DRIP TRAY DRAIN HOSE
NOTE: Connection of the drip tray drain hose to a permanent drain is recommended. Drip tray drain hose routed to waste container is not recommended due to sanitation and cleaning problems.
1. Route lower end of drip tray drain hose to and connect to a permanent drain.
2. Install DRIP TRAY in position on the Unit, then place CUP REST in drip tray.
CONNECTING PLAIN WATER SOURCE LINE(S) TO UNIT
NOTE: IMI Cornelius Inc. recommends that a water shutoff valve and water filter be installed in plain water inlet supply line. A Cornelius Water Filter (P/N 313860000) and Quick Disconnect Set (P/N 313867000) are recommended. The plain water source to the equipment shall be installed with ade­quate backflow protection to comply with applicable Fereral, State, and local codes.
318832000
14
Page 21
CAUTION: Check the minimum flow rate and maximum pressure of plain water inlet supply line. MINIMUM FLOW RA TE MUST BE AT LEAST 100-GALLONS PER HOUR. If flow rate is
less than 100-gallons per hour, starving of carbonator water pump will occur. Starving will allow water pump to overheat and will damage the pump. Overheating could occur if plain water inlet supply line flow rate drops below 100-gallons per hour. CARBONATOR CO2OPERA TING PRESSURE MUST EXCEED WATER PRESSURE BY 10-PSI. (Example: CO2operating pressure is 80-psi, maximum water pressure can be no more than 70-psi, etc.) Water over pressure (higher than CO2operating pressure) can cause carbonator flooding, malfunction, and leakage through carbonator relief valve. If water is exceeding maximum pressure specifications, a Water Pressure Regulator Kit (P/N 317589000) or equivalent must be installed in plain water inlet supply line.
Standard Unit Requiring Connection to a Remote Carbonator. (see Figure 2)
1. Install ADAPTOR FITTING, provided with the Unit, in end of Unit labeled plain water inlet line.
2. Connect plain water source supply line to Unit labeled plain water inlet line.
Unit With Built-In Cold Carbonator. (see Figure 3)
Connect plain water source line to Unit labeled plain water inlet lines. NonCarbonated Unit. (see Figure 4)
(see Figure 4) Connect plain water source lines to Unit labeled plain water inlet lines.
CONNECTING CARBONATED WATER SOURCE LINE TO UNIT
Standard Unit Requiring Connection to a Remote Carbonator. (see Figure 2)
Connect carbonated water source line from remote carbonator to labeled Unit carbonated water inlet line.
CONNECTING CO2SOURCE LINE TO UNIT
Unit With Built-In Cold Carbonator. (see Figure 3)
Connect CO2source line to Unit labeled CO2inlet line.
CONNECTING SYRUP SOURCE LINES TO UNIT
(see applicable Figure 2, 3, or 4)
Connect syrup source lines to Unit labeled syrup inlet lines.
PREPARATION FOR OPERATION
CAUTION: Before opening CO2cylinder shutoff valve, turn secondary CO2regulators
adjusting screws to the left (counterclockwise) until all tension is relieved from adjusting
screws springs.
15
318832000
Page 22
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
STANDARD UNIT REQUIRING CONNECTION TO A REMOTE CARBONATOR
(see Figure 2)
1. Open (counterclockwise) CO2cylinder shutoff valve slightly to allow lines to slowly fill with gas, then open valve fully to back-seat valve. (back-seating valve prevents leakage around valve shaft). Check for CO leaks.
2. Adjust primary CO2regulator (regulator controls carbonator CO2pressure) as instructed in manual pro­vided with the carbonator. Check for CO2leaks.
3. Open plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose connections.
4. Plug remote carbonator power cord into electrical outlet. Carbonator will start and continue to operate until carbonated water tank is full.
5. Adjust syrup tanks system or bag-in-box syrup system syrup pumps secondary CO2regulator as instructed in SERVICE AND MAINTENANCE section of this manual.
2
6. Sanitize all syrup systems as instructed in SERVICE AND MAINTENANCE section of this manual.
7. Install syrup tanks or bag-in-boxes containing syrup into syrup systems.
UNIT WITH BUILT-IN COLD CARBONATOR
(see Figure 3)
1. Open (counterclockwise) CO2cylinder shutoff valve slightly to allow lines to slowly fill with gas, then open valve fully to back-seat valve. (back-seating valve prevents leakage around valve shaft). Check for CO leaks.
2. Adjust primary CO2regulator (regulator controls Unit built-in cold carbonator CO2pressure) as instructed in SERVICE AND MAINTENANCE section of this manual. Check for CO2leaks.
3. Open plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose connections.
4. Flip carbonator water pump motor power switch (located on refrigeration assembly control box) to “ON” position. Carbonator water pump will start and continue to operate until carbonator tank has been filled, then pump motor will stop. Check for CO2, plain water, and carbonated water leaks and tighten any loose connections.
5. Adjust syrup tanks system or bag-in-box syrup system syrup pumps secondary CO2regulator as instructed in SERVICE AND MAINTENANCE section of this manual.
6. Sanitize all syrup systems as instructed in SERVICE AND MAINTENANCE section of this manual.
2
7. Install syrup tanks or bag-in-boxes containing syrup into syrup systems.
NONCARBONATED UNIT
(see Figure 4)
1. Open plain water inlet supply line shutoff valve. Check for water leaks and tighten any loose connections.
318832000
16
Page 23
2. Adjust syrup tanks system or bag-in-box syrup system syrup pumps secondary CO2regulator as instructed in SERVICE AND MAINTENANCE section of this manual.
3. Sanitize all syrup systems as instructed in SERVICE AND MAINTENANCE section of this manual.
4. Install syrup tanks or bag-in-boxes containing syrup into syrup systems
UNIT OPERATION
BLEEDING SYRUP AND APPLICABLE PLAIN OR CARBONATED WATER SYSTEMS
1. Make sure Unit keyed lock-out switch is in “ON” (vertical) position.
2. Dispense from each dispensing valve until air is bled from systems and until syrup and applicable plain or carbonated water are dispensed.
3. Check for syrup and water leaks and tighten any loose connections.
4. Install Unit hood and secure with screw.
ADJUST WATER-TO-SYRUP “RATIO” OF DISPENSED PRODUCT
1. On dispensing valves equipped with adjustable water flow regulators, adjust for water flow rate as instructed in SERVICE AND MAINTENANCE section of this manual.
2. Adjust dispensing valves for Water-to-Syrup “Ratio” of dispensed drinks as instructed in SERVICE AND MAINTENANCE section of this manual.
3. Install Unit front access panel.
INSTALL DECALS
Install DECALS (provided with Unit) on dispensing valve covers.
17
318832000
Page 24
DISPENSING VALVE BLOCK
DISPENSING VALVE RELEASE LATCH
6
5
3
24
1
* This CAPPED TEE is used when converting No. 3 dispensing valve from a still ( noncarbonated ) to a carbonated drink. Refer to TABLE OF CON­TENTS for conversion instructions.
FIGURE 5. INLET SUPPLY LINE CONNECTIONS (STANDARD UNIT)
318832000
18
LABELED UNIT INLET LINES
*CAPPED TEE
(CARBONATED WATER)
Page 25
DISPENSING VALVE BLOCK
DISPENSING VALVE RELEASE LATCH
6
*CAPPED CROSS FITTING (CARBONATED WATER)
5
4
3
2
1
LABELED UNIT INLET LINES
* This CAPPED CROSS FITTING is used when converting No. 3 dispensing valve from a still ( noncarbonated ) to a carbonated drink. Refer to TABLE OF CONTENTS for con­version instructions.
FIGURE 6. INLET SUPPLY LINE CONNECTIONS (UNIT WITH BUILT-IN COLD CARBONATOR)
19
318832000
Page 26
DISPENSING VALVE BLOCK
DISPENSING VALVE RELEASE LATCH
6
5
4
3
2
1
318832000
LABELED UNIT INLET LINES
FIGURE 7. INLET SUPPLY LINE CONNECTIONS (NONCARBONATED UNIT)
20
Page 27
OPERATOR’S INSTRUCTIONS
This section covers operating controls, daily pre-operation check, Unit operation, adjustments, replenishing CO2and syrup supplies, cleaning and sanitizing, checking drop-in refrigeration assembly condenser coil for restrictions, checking ice water bath, water pump yearly maintenance on Unit with built-in carbonator and peri­odic cleaning of CO2gas check valves.
WARNING: Disconnect electrical power to the Unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or electrical wiring.
CAUTION: Do not place or store anything on top of the Unit.
OPERATING CONTROLS
(see Figure 8)
DISPENSING VALVE LEVER
The dispensing valve lever, located on bottom of the valve, needs only to be pressed with a cup or glass to dis­pense product.
DISPENSING VALVE WITH WATER LEVER
The water lever, located on the side of No. 3 dispensing valve cover, will dispense only plain water when actu­ated.
DISPENSING VALVES KEYED LOCK-OUT SWITCH
The dispensing valves keyed lock-out switch, must be in the “ON” (vertical) position to operate the electric dis­pensing valves. The keyed lock-out switch in the “OFF” (horizontal) position turns off electrical power to the dis­pensing valves only, but the refrigeration system will continue to operate.
UNIT POWER SWITCH (IF APPLICABLE)
The Unit power switch (if applicable) must be in the “ON” position before the Unit will operate.
CARBONATOR WATER PUMP MOTOR POWER SWITCH (UNIT WITH BUILT-IN COLD CARBONATOR)
The carbonator water pump motor power switch (see Figure NO TAG) must be in the “ON” position before the carbonator water pump motor will operate. The purpose of the switch is to turn off the carbonator water pump motor for service and maintenance. THE WATER SUPPLY TO THE CARBONATOR WATER PUMP MUST BE
TURNED ON BEFORE RESTARTING. STARVING WATER PUMP OF WATER WILL DAMAGE THE PUMP.
DAILY PRE-OPERATION CHECK
1. Check CO2cylinder regulator assembly 1800-psi gage and if gage indicator is in shaded (“change CO2cyl­inder”) portion of dial, CO2cylinder is almost empty and must be replaced.
31883200021
Page 28
2. Make sure there is a sufficient syrup supply . If not, replenish syrup supply as instructed.
3. Make sure the drip tray and the cup rest are clean and are properly installed on the Unit.
UNIT OPERATION
1. Make sure the Unit dispensing valves keyed lock-out switch is in the “ON” (vertical) position.
2. Press a cup or glass against the dispensing valve lever and dispense until the cup or glass is full of prod­uct, then release the lever.
3. If water only is desired, hold a cup or glass under the dispensing valve with a lever on it’s side, then actuate the lever to dispense water.
REPLENISHING CO2SUPPLY
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
CO2supply should be checked daily and replenished if necessary. Refer to SERVICE AND MAINTENANCE section of this manual for instructions.
REPLENISHING SYRUP SUPPLY
Syrup supply should be checked daily and replenished if necessary . Refer to SERVICE AND MAINTENANCE section of this manual for instructions.
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT
Daily cleaning procedure for Unit should be performed at end of daily operation. Refer to SERVICE AND MAIN­TENANCE section of this manual for instructions.
SANITIZING SYRUP SYSTEMS
Syrup systems should be sanitized as instructed every 90-days. Refer to SERVICE AND MAINTENANCE sec­tion of this manual for instructions.
CHECKING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL FOR RESTRICTIONS
NOTE: Circulating air required to cool the refrigeration assembly condenser coil is drawn in through grille on front and is exhausted through grille on top of hood. Restricting air in or out of Unit will de­crease its cooling efficiency .
Area on top of the hood must be kept free of obstructions at all times. Make sure nothing is stored on top of the hood. The refrigeration assembly condenser coil must be cleaned every 30-days as instructed in the SERVICE AND MAINTENANCE section of this manual to maintain proper cooling of the condenser coil. The condenser coil cleaning procedure should be performed by a qualified Service Person.
318832000 22
Page 29
CHECKING ICE WATER BATH
A “gurgle” heard from the Unit indicates the water level in the water tank is low and more water should be added to the tank for maximum product cooling. Water should be added to the water tank as instructed in the SER­VICE AND MAINTENANCE section of this manual. This procedure should be performed by a qualified Service Person.
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER SYSTEM DISRUPTIONS
UNIT REQUIRING CONNECTION TO A REMOTE CARBONATOR (STANDARD UNIT)
The remote carbonator water pump water inlet strainer screen and the double liquid check valve must be in­spected and cleaned by a qualified Service Person at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.) Refer to manual provided with the remote carbo­nator for the double liquid check valve inspection and cleaning procedure.
UNIT WITH BUILT-IN COLD CARBONATOR
The water pump water strainer screen and double liquid check valve must be inspected and cleaned as instructed by a qualified Service Person at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.). Refer to SERVICE AND MAINTENANCE section of this manual for inspection and cleaning procedure.
CLEANING CO2GAS CHECK VALVES
The CO2gas check valves must be inspected and serviced as instructed at least once a year under normal conditions and after any CO2system servicing or disruption. Servicing of CO2gas check valves should be performed by qualified Service Personnel. Refer to SERVICE AND MAINTENANCE section in this manual for inspection and servicing procedures.
31883200023
Page 30
318832000
2
4
THIS PAGE LEFT BLANK INTENTIONALLY
Page 31
318832000
SERVICEANDMAINTENANCE
This section describes service and maintenance procedures to be performed on the Unit.
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
WARNING: Disconnect electrical power to the Unit to prevent personal injury before attempting any internal maintenance. Only qualified personnel should service the internal components or electrical wiring.
PREPARING UNIT FOR SHIPPING, STORING, OR RELOCATING
CAUTION: Before shipping, storing, or relocating this Unit, the syrup systems must be sanitized and all sanitizing solution must be purged from the syrup systems. All water must
also be purged from the plain and carbonated water systems. A freezing ambient environment will cause residual water in the Unit to freeze resulting in damage to internal components.
HOOD AND FRONT PANEL REMOVAL
(see Figure 8)
HOOD REMOVAL
CAUTION: Do not place or store anything on top of the Unit.
Loosen screw on top of hood, then lift hood straight up and off the Unit.
FRONT ACCESS PANEL REMOV AL
Remove two screws (if applicable) securing front access panel to Unit, then remove panel..
PERIODIC INSPECTION
1. Clean the drop-in refrigeration assembly condenser coil every 30-days as instructed in this manual section. Cleaning the condenser coil should be performed by a qualified Service Person. DO NOT place objects on
top of or on back side of the Unit hood. Restricting circulating air in or out of the Unit hood will cause the refrigeration system to overheat.
2. Check dispensing valves for dripping that indicates leaking and repair as necessary.
3. Periodically , pull up on carbonated water tank relief valve momentarily on units with built in carbonators.
ADJUSTMENTS
CO2REGULATORS ADJUSTMENTS
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
Page 32
318832000
2
6
DISPENSING
VALVE
LEVER
WATER FILL HOLE PLUG
CARBONATOR
WATER PUMP
POWER SWITCH
DISPENSING VALVES
KEYEd LOCK -OUT
SWITCH
FIGURE 8. DISPENSER COMPONENTS (UNIT WITH BUILT-IN CARBONATOR SHOWN)
Page 33
318832000
NOTE: To readjust CO2regulator to a lower setting, loosen adjusting screw lock nut, then turn screw to the left (counterclockwise) until pressure gage reads 5-psi lower than new setting will be. Turn adjust­ing screw to the right (clockwise) until gage registers new setting, then tighten lock nut.
Adjusting Carbonator CO2Regulator UNIT REQUIRING CONNECTION TO A REMOTE CARBONATOR (see Figure 2) Refer to manual provided with remote carbonator and adjust CO2regulator operating pressure as instructed. UNIT WITH INTEGRAL (BUILT-IN) CARBONATOR (see Figure 3) Adjust CO2regulator for integral carbonator to nominal 80-psig. INLET CO2PRESSURE TO CARBONATOR
MUST NOT EXCEED 125-PSIG.
Adjusting Syrup Supplies CO2Regulator SUGAR SYRUP TANKS CO2REGULATOR Adjust sugar syrup tanks CO2regulator to a minimum of 45-psi. LOW-CALORIE (DIET) SYRUP TANK CO2REGULATOR Adjust low-calorie (diet) syrup tank secondary CO2regulator to 10-psi for syrup lines up to 30-feet in length.
Syrup lines longer than 30-feet in length may require a slightly higher setting of 12-psi maximum. Excessive CO2pressure may cause low-calorie syrup carbonation resulting in foam.
SYRUP PUMPS (BAG-IN-BOX SYSTEM) CO2REGULATOR Adjust the syrup pumps CO2regulator to 70-psi. DO NOT EXCEED MAXIMUM CO2PRESSURE SPECIFIED
ON THE SYRUP PUMPS.
ADJUSTING DISPENSING VALVE WATER FLOW RATE
The dispensing valves adjustable water flow regulators are factory adjusted and should require no futher adjust­ment. If readjustment should become necessary, consult the dispensing valve manufacturer for the proper ad­justment procedure.
ADJUSTING DISPENSING VALVES FOR WATER-TO-SYRUP “RATIO” (BRIX) OF DISPENSED PRODUCT
The dispensing valves are each equipped with adjustable syrup flow regulators. The Water-To-Syrup “Ratio” (Brix) of the dispensed product is controlled by adjustment of these syrup flow regulators. Consult the dispens­ing valve manufacturer for the proper adjustment procedure.
CLEANING AND SANITIZING
DAILY CLEANING OF UNIT
1. Remove cup rest from the drip tray .
2. Wash drip tray in place on the Unit, then rinse drip tray with hot water allowing water to drain out through the drain hose.
3. Wash cup rest, then rinse the cup rest with clean water. Install cup rest in the drip tray.
4. Clean all external surfaces of the Unit with a sponge. Rinse out the sponge with clean water, then wring excess water out of the sponge and wipe off all external surfaces on the Unit. Wipe Unit dry with a clean soft cloth. DO NOT USE ABRASIVE CLEANERS.
Page 34
318832000
2
8
5. Remove nozzle and syrup diffusers from the dispensing valves. Place nozzles and syrup diffusers in sani­tizing solution.
6. Wash the nozzles and syrup diffusers in sanitizing solution, then rinse them with potable water.
7. Re-install nozzles and syrup diffusers back on the dispensing valves.
SANITIZING POST-MIX SYRUP SYSTEMS
IMPORTANT: Only qualified Service Personnel should perform sanitizing procedure on the post-mix syrup systems.
The post-mix syrup systems should be sanitized every 90-days using a non-scented household liquid bleach containing a 5.25 % sodium hypochlorite concentration. Proceed as follows to sanitize the post-mix syrup sys­tems.
1. Disconnect syrup supplies from syrup systems.
2. Rinse quick disconnects (syrup tanks systems) or bag-in-box connectors (syrup bag-in-box systems) in warm potable water.
STEP 1. WASH SYRUP SYSTEMS
3. Using a clean syrup tank (syrup tank system) or a five-gallon container (bag-in-box system), prepare a full tank or container of liquid dishwasher detergent by using 70_ F (21_ C) to 100_ F (38_ C) potable water and 0.5 oz. (15 ml) of liquid dishwasher detergent to one gallon of potable water. Stir detergent solution to thoroughly mix the solution.
4. Syrup Tank Systems. A. Observe and note CO2pressure setting on the syrup tanks CO2regulator, then re-adjust CO2regula-
tor to 60 to 80-psi. Pressurize syrup tank containing detergent solution to 60 to 80-psi.
B. Connect detergent solution tank, pressurized at 60 to 80-psi, into one of the syrup systems.
Bag-in Box Syrup Systems.
C. Install bag valves, cut from empty bag-in-box syrup containers, on ends of syrup containers syrup
outlet tubes connectors.
D. Place all syrup outlet tubes, with bag valves on their ends, in container containing detergent solution.
5. Flush the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all syrup and flush out the syrup system. C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
6. Connect detergent solution to the remaining syrup systems and flush syrup out of the syrup systems as instructed in step 5 preceding.
7. Remove detergent solution source from the syrup system.
STEP 2. FLUSH SYRUP SYSTEMS
8. Syrup Tank Systems. Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems.
Bag-in-Box Syrup System. Fill five-gallon container with potable water, then place all bag-in-box syrup containers syrup outlet tubes in
container containing potable water.
Page 35
318832000
9. Flush detergent solution out of the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all detergent solution and flush out the syrup
system.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
10. Connect potable water source to the remaining syrup systems and flush detergent solution out of the syrup systems as instructed in step 9 preceding.
11. Remove potable water source from the syrup system.
STEP 3. SANITIZE SYRUP SYSTEMS
12. Using a clean syrup tank (syrup tanks system) or a five-gallon container (bag-in-box system), prepare sani­tizing solution using 70_ F (21_ C) to100_ F (38_ C) potable water and 0.5 oz. (15 ml) of non-scented household liquid bleach that contains a 5.25 % sodium hypochlorite concentration to one gallon of potable water. This mixture must not exceed 200 PPM of chlorine. Stir sanitizing solution to thoroughly mix.
13. Syrup Tank Systems.
Connect sanitizing solution tank, pressurized at 60 to 80-psi, into one of the syrup systems. Bag-in-Box Syrup System. Place all bag-in-box syrup containers syrup outlet tubes in container containing sanitizing solution.
14. Sanitize the syrup system and dispensing valve as follows: A. Place waste container under applicable dispensing valve. B. Activate the dispensing valve for one minute to purge all water from and install sanitizing solution in
the syrup system and dispensing valve.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
15. Repeat steps13 and 14 to flush water out of and install sanitizing solution in the remaining syrup systems and dispensing valves.
16. Remove sanitizing solution source from the syrup system.
17. Allow sanitizing solution to remain in the syrup systems for not less than 10 or no more than 15-minutes (max.) contact time.
STEP 4. WATER FLUSH SYRUP SYSTEMS
WARNING: Flush sanitizing solution from the syrup systems as instructed. Residual sanitizing solution left in the syrup systems could create a health hazard.
18. Fill syrup tank (syrup tank system) or a five-gallon container (bag-in-box system) with potable water.
19. Syrup Tank Systems.
Connect syrup tank containing potable water, pressurized at 60 to 80-psi, into one of the syrup systems. Bag-in-Box Syrup System. Place all bag-in-box syrup containers syrup outlet tubes in container containing potable water.
20. Flush sanitizing solution from the syrup system and the dispensing valve as follows: A. Place waste container under applicable dispensing valve.
Page 36
318832000
3
0
B. Activate the dispensing valve for one minute to purge all sanitizing solution out of the syrup system
and the dispensing valve.
C. Continue to activate the dispensing valve in cycles (“ON” for 15-seconds, “OFF”, then “ON” for
15-seconds). Repeat “ON” and “OFF” cycles for 15-cycles.
21. Repeat steps 19 and 20 preceding to purge sanitizing solution out of the remaining syrup systems and dispensing valves.
22. Remove potable water source from the syrup system.
STEP 5. PURGE WATER OUT OF SYRUP SYSTEMS (RESTORE OPERATION)
23. Syrup Tank Systems. A. Noting syrup tanks CO2regulator pressure setting observed in step 4 preceding, readjust CO2regula-
tor to the observed pressure setting,
B. Connect tanks containing syrup into syrup systems.
Bag-in-Box Syrup System. C. Remove all bag valves from bag-in-box syrup containers outlet tubes connectors. D. Connect bag-in-box syrup containers into the syrup systems.
24. Place waste container under dispensing valves. Dispense from all dispensing valves to permit syrup to purge all potable water from the syrup systems and the dispensing valves. Continue to dispense from the dispensing valves until only syrup is dispensed from the syrup systems and valves.
WARNING: To avoid possible personal injury or property damage, do not attempt to remove the syrup tank cover until CO2pressure has been released from the tank.
25. Dispose of waste sanitizing solution in a sanitary sewer, not in a storm drain, then thoroughly rinse the in­side and the outside of the container that was used for sanitizing solution to remove all sanitizing solution residue.
CLEANING DROP-IN REFRIGERATION ASSEMBLY CONDENSER COIL
(see Figure 8) Excessive accumulation of dust, lint, and grease on the drop-in refrigeration assembly condenser coil will restrict
air flow through the coil and cause a loss of cooling. Perform the following procedure to clean the condenser coil.
1. Unplug Unit power cord from electrical outlet.
2. Remove hood by loosening screw on top of hood, then lift hood straight up off Unit.
3. Vacuum or use a soft brush to clean condenser coil. If available, use low-pressure compressed air.
4. Clean dust and dirt from around top of refrigeration assembly .
5. Install hood on Unit and secure with screw.
6. Plug Unit power cord into electrical outlet.
CHECKING ICE WATER BATH
A “gurgle” heard from Unit indicates water level in the water tank is low and more water should be added to the tank for maximum cooling. Before adding more water, ice water bath and ice bank should be checked for clean­liness and water tank coils checked for excessive mineral deposit build-up.
1. Unplug Unit power cord from electrical outlet.
Page 37
318832000
2. Remove Unit hood by loosening screw on top of hood, then lift hood straight up off Unit.
3. Remove plug from drop-in refrigeration assembly platform water fill hole (see Figure 8).
4. Using a flashlight, inspect ice water bath and ice bank for cleanliness. Ice water bath should be clear and ice bank free of foreign particles.
5. If cleaning of water tank is necessary , refer to CLEANING WATER TANK in this section.
6. Fill water tank with clean water to top of stainless steel coils located in coil basket. USE LOW-MINERAL-
CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.
7. Install plug in water fill hole.
8. Install Unit hood and secure with screw.
9. Plug Unit power cord into electrical outlet.
CLEANING WATER TANK
1. Unplug Unit power cord from electrical outlet.
2. Remove two screws (if applicable) securing Unit front access panel, then remove panel.
3. Route water tank drain hose to a drain. Remove plug from end of drain hose and allow water tank to drain.
4. Remove Unit hood by loosening screw on top of hood, then lift hood straight up off Unit.
5. Unplug drop-in refrigeration assembly power cord and electric dispensing valves power cord.
Unit Equipped with Built-in Cold Carbonator.
A. Disconnect built-in cold carbonator power cord (see Figures 8 and 9). B. Loosen screw on water pump-to-motor coupling (see Figure 10), then slide water pump off motor
shaft. Lay water pump, with attached lines, off to one side.
6. Lift drop-in refrigeration assembly up and out of Unit.
CAUTION: Never use an ice pick or other instrument to remove ice from drop-in refrigeration assembly evaporator coils. Such practice can result in punctured refrigeration circuit.
7. Allow ice bank to melt. Hot water may be used to speed melting.
8. Use fiber brush and carefully clean mineral deposit build-up from agitator motor shaft and ice bank sensing bulb.
9. Wash inside of water tank and drop-in refrigeration assembly evaporator coils, then rinse with clean water.
10. Install plug in end of water tank drain hose.
11. Install drop-in refrigeration assembly in Unit by reversing removal procedure.
Page 38
318832000
3
2
CARBONATOR
SENSOR LEADS
FIGURE 9. WA TER TANK (UNIT WITH BUILT-IN COLD CARBONATOR SHOWN)
12. Remove plug from drop-in refrigeration assembly platform water fill hole.
13. Fill water tank with clean water to top of stainless steel coils located in coil basket. USE LOW-MINERAL-
CONTENT WATER WHERE A LOCAL WATER PROBLEM EXISTS.
14. Install access plug in water fill hole.
15. Install hood on Unit by reversing removal procedure.
16. Install Unit front access panel by reversing removal procedure.
17. Plug Unit power cord into electrical outlet.
CARBONATOR WATER PUMP YEARLY MAINTENANCE OR AFTER WATER SYSTEM DISRUPTIONS
WARNING: The carbonator water pump water inlet strainer screen and double liquid check valve must be inspected and cleaned at least once a year under normal circumstances, and
after any disruptions (plumbing work, earthquake, etc.) to the water supply system that might cause turbulent (erratic) flow of water through the system. A carbonator water pump with no screen or a defective screen in the strainer would allow foreign particles to foul the double liquid check valve. CO2gas could then back flow into the water system and create a health hazard.
Page 39
318832000
UNIT CONNECTED TO REMOTE CARBONATOR (STANDARD UNIT)
The remote carbonator water pump water inlet strainer screen and double liquid check valve must be inspected and cleaned at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.). Refer to manual provided with the remote carbonator for servicing procedure.
UNIT WITH BUILT-IN COLD CARBONATOR
Carbonator water pump water inlet strainer screen and double liquid check valve must be inspected and cleaned at least once a year under normal circumstances and after any water system disruption (plumbing work, earthquake, etc.).
Servicing Water Pump Water Inlet Strainer Screen
(see Figures 3 and 10)
1. Unplug unit power cord from electrical outlet.
2. Remove Unit hood by loosening screw on top of hood, then lift hood up and off Unit.
3. Close water inlet supply line shutoff valve.
4. Note pressure setting on primary CO2regulator, then turn regulator adjusting screw to the left (counter­clockwise) until gage reads 0-psig.
5. Pull up on carbonator tank relief valve until carbonator tank CO2pressure has been released, then release valve.
6. Loosen screen retainer, then pull screen retainer and strainer screen from the water pump.
7. Pull screen from screen retainer. Clean any sediment from screen retainer and the water pump screen retainer port.
8. Inspect screen for holes, restrictions, corrosion, and other damage. Discard damaged screen.
9. Check O-Ring on screen retainer. Replace worn or damaged O-Ring (P/N 315349000).
NOTE: A screen should always be used, otherwise particles could foul the double check valve.
10. Install screen (P/N 315348000) in screen retainer, then screw retainer into water pump and tighten securely .
11. Service double liquid check valve, (refer to next paragraph, Servicing Double Liquid Check Valve) as instructed.
Servicing Double Liquid Check Valve.
(see Figures 3 and 10)
1. Service water inlet strainer screen as instructed in previous paragraph before servicing double liquid check valve.
2. Disconnect water line from double liquid check valve, then remove double check valve from water pump outlet.
Page 40
318832000
3
4
WATER LINE TO TANK
DOUBLE LIQUID
CHECK VALVE
WHITE TAPERED GASKET
PUMP TO MOTOR COUPLING
WATER PUMP
WATER
STRAINER SCREEN
(P/N 315348000)
O-RING (P/N 315349000)
SCREEN RETAINER
FIGURE 10. WA TER STRAINER SCREEN AND DOUBLE LIQUID CHECK VALVE
ELBOW
SAFETY THERMOSTAT
(P/N 318040000)
*INSTALL NEW BALL SEAT AT EACH SERVICING
INDEX
NO.
1 317963000 Housing 2 312415000 Flat Washer, Stainless Steel 3 *312418000 Ball Seat (quad ring) 4 312419000 Ball 5 312196000 Spring 6 317965000 Retainer
PART
NO.
DUAL CHECK VALVE P/N 311765000 SINGLE CHECK VALVE P/N 311764000
FIGURE 11. LIQUID CHECK VALVE ASSEMBLY
Page 41
318832000
3. Disassemble each check valve as shown in Figure 11.
4. Wipe each part with clean lint-free cloth. Inspect each part, especially the ball for burrs, nicks, corrosion, deterioration, and other damage. Discard ball seat and any damaged or suspicious parts and replace with new parts during reassembly.
5. Reassemble check valves as shown in Figure 11. ALWAYS INSTALL NEW BALL SEAT (QUAD RING) P/N
312418-000.
NOTE: Make sure when assembling check valves together, check valve female end with white tapered gasket inside is on inlet side of double liquid check valve assembly.
6. Assemble check valves together as shown in Figure 11.
7. Make sure white tapered gasket is in place inside female end of double check valve, then install double check valve on water pump outlet.
8. Connect water line to double check valve.
9. Turn primary CO2regulator adjusting screw to the right (clockwise) until gage indicates pressure setting noted in step NO TAG of Servicing Water Pump Water Inlet Strainer Screen.
10. Open water inlet supply line shutoff valve.
11. Install Unit hood and secure with screw.
12. Plug Unit power cord into electrical outlet.
13. Test dispense Unit for proper operation.
14. Activate relief valve momentarily .
NO. 3 DISPENSING VALVE CONVERSION FROM STILL TO CARBONATED DRINK
STANDARD UNIT
(see Figure 2 and Figure 5)
Unit New Installation.
The Unit plain water inlet line is intended for connection to a plain water source to dispense a still (non-carbon­ated) drink from No. 3 dispensing valve as shown in Figure 2. To dispense a carbonated drink from No. 3 dis­pensing valve, the Unit plain water inlet line must be connected to the capped tee fitting on the Unit carbonated water inlet line.
Unit Already in Service.
1. Unplug remote carbonator power cord from electrical outlet.
2. Close remote carbonator water inlet supply and CO2source shutoff valves.
3. Relieve CO2gas pressure on carbonated water system by pulling up on carbonator tank relief valve.
4. Disconnect Unit plain water inlet line (No. 3 dispensing valve) from plain water source. Cap plain water source where line was disconnected.
5. Connect Unit plain water inlet line (No. 3 dispensing valve) to capped tee fitting on the Unit carbonated water inlet line (see Figures 2 and 5).
6. Open remote carbonator CO2source shutoff valve, then open remote carbonator water inlet supply line shutoff valve.
Page 42
318832000
3
6
7. Plug remote carbonator power cord into electrical outlet.
8. Open No. 3 dispensing valve and dispense until carbonated water is dispensed.
UNIT WITH BUILT-IN COLD CARBONATOR
One of the Unit plain water inlet lines is intended for connection to a plain water source to dispense a still (non­carbonated) drink from No. 3 dispensing valve as shown in Figure 3. To dispense a carbonated drink from No. 3 dispensing valve, it’s plain water inlet line must be connected to the capped cross fitting (carbonated water) lo­cated behind the Unit front access panel as shown in Figure 6.
Unit New Installation.
1. Remove two screws (if applicable) securing front access panel to Unit, then remove panel.
2. Locate the No. 3 dispensing valve plain water inlet line that was intended for connection to a plain water source.
3. Install SWIVEL NUT and NIPPLE on the plain water line and secure with TUBING CLAMP.
4. Remove cap from the cross fitting in the carbonated water line (see Figure 6), then connect plain water line to the cross fitting. The No. 3 dispensing valve will now be capable of dispensing a carbonated drink.
5. Install Unit front access panel.
Unit Already in Service.
1. Unplug Unit power cord from electrical outlet.
2. Remove two screws (if applicable) securing front access panel on Unit, then remove panel.
3. Shut off CO2and water inlet supply line sources.
4. Relieve CO2gas pressure on carbonated water system by pulling up on carbonator tank relief valve.
5. Disconnect No. 3 dispensing valve plain water inlet line from the plain water source.
6. Extend plain water inlet line to capped cross fitting, in carbonated water line behind the front access panel (see Figure 6), then cut off the plain water line.
7. Install SWIVEL NUT and NIPPLE on plain water line and secure with TUBING CLAMP.
8. Remove cap from cross fitting in the carbonated water line, then connect No. 3 dispensing valve plain wa­ter inlet line to the cross fitting.
9. Cap off plain water source line.
10. Open CO2shutoff valve, then open water inlet supply line shutoff valve.
11. Plug Unit power cord into electrical outlet.
12. Open No. 3 dispensing valve and dispense until carbonated water is dispensed.
13. Install Unit front access panel.
REPLENISHING CO2SUPPLY
WARNING: CO2displaces oxygen. Strict attention must be observed in the prevention of CO2(carbon dioxide) gas leaks in the entire CO2and soft drink system. If a CO2gas leak is
suspected, particularly in a small area, immediately ventilate the contaminated area before attempting to repair the leak. Personnel exposed to high concentration of CO2gas will experience tremors which are followed rapidly by loss of consciousness and suffocation.
NOTE: When indicator on CO2cylinder primary CO2regulator assembly 1800-psi gage is in shaded (‘‘change CO2cylinder’’) portion of dial, CO2cylinder is almost empty and should be changed.
Page 43
318832000
1. Fully close (clockwise) CO2cylinder main shutoff valve.
2. Slowly loosen primary CO2regulator assembly coupling nut allowing CO2pressure to escape, then remove regulator assembly from empty CO2cylinder.
3. Unfasten safety chain and remove empty CO2cylinder.
WARNING: To avoid personal injury and/or property damage, always secure CO2cylinder in upright position with safety chain to prevent it from falling over. Should valve become accidentally damaged or broken off, CO2cylinder can cause serious personal injury.
4. Position full CO2cylinder and secure with safety chain.
5. Make sure gasket is in place inside primary CO2regulator coupling nut, then install regulator on CO2cylin­der.
6. Open (counterclockwise) CO2cylinder main shutoff valve slightly to allow lines to slowly fill with gas, then open valve fully to back-seat valve. (Back-seating valve prevents leakage around valve shaft).
REPLENISHING SYRUP SUPPLY
NOTE: The following instructions are applicable only when replenishing same flavor syrup. Refer to SYRUP FLAVOR CHANGE when changing syrup flavor.
SYRUP TANK SYSTEM
1. Disconnect empty syrup tank from syrup system.
2. Check syrup drink quick disconnects for sticky or restricted operation. Wash disconnects in warm water.
3. Connect full tank of syrup into syrup system.
BAG-IN-BOX SYRUP SYSTEM
1. Disconnect empty bag-in-box container from syrup system.
2. Check bag-in-box connecter for sticky or restricted operation. Wash bag-in-box connecter in warm water.
3. Connect full bag-in-box container into syrup system.
SYRUP FLAVOR CHANGE
1. Perform sanitizing procedure (as instructed in this section of the manual) on syrup system syrup flavor change will be made on.
2. Connect new flavor syrup into the syrup system.
CLEANING CO2SYSTEM CO2GAS CHECK VALVES
(see applicable Figure 2, 3, or 4) The CO2regulators and CO2manifold CO2gas check valves must be inspected and serviced at least once a
year under normal conditions and after any servicing or disruption of the CO2system. ALWAYS REPLACE BALL SEAT (QUAD RING SEAL) EACH TIME GAS CHECK VALVES ARE SERVICED.
Page 44
318832000
3
8
*QUAD RING 183294000
BALL 183296000
SPRING 183297000
RETAINER 183298000
BODY 183295000
*Quad ring seal must be replaced each time check valve is serviced.
FIGURE 12. CO2GAS CHECK VALVE ASSEMBLY
THE GERMAN ICE BANK CONTROL IS FOR
INTERNATIONAL USE ONLY.
FIGURE 13. WIRING SCHEMA TIC FOR GERMAN ICE BANK CONTROL (OPTIONAL)
Page 45
FIGURE 14. WIRING DIAGRAM (60 HZ UNIT WITH 1/3 H.P. REFRIGERATION ASSEMBLY)
39
318832000
Page 46
FIGURE 15. WIRING DIAGRAM (50 HZ UNIT WITH 1/3 H.P. REFRIGERATION ASSEMBLY)
318832000
40
Page 47
*60 HZ UNITS ONLY
41
FIGURE 16. WIRING DIAGRAM (60 HZ UNIT WITH 1/4 H.P. REFRIGERATION ASSEMBLY AND BUILT-IN COLD CARBONATOR)
318832000
Page 48
FIGURE 17. WIRING DIAGRAM (50 HZ UNIT WITH 1/4 H.P. REFRIGERATION ASSEMBLY AND BUILT-IN COLD CARBONATOR)
318832000
42
Page 49
TROUBLESHOOTING
IMPORTANT: Only qualified personnel should service internal components or electrical wiring.
WARNING: If repairs are to be made to a product system, remove quick disconnects from the applicable product tank, then relieve the system pressure before proceeding. If repairs
are to be made to the CO2system, stop dispensing, shut off the CO2supply , then relieve the system pressure before proceeding. If repairs are to be made to the refrigeration system, make sure electrical power is disconnected from the unit.
STANDARD UNIT (REQUIRES CONNECTION TO A REMOTE CARBONATOR)
Trouble Probable Cause Remedy
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
A. Dispensing valve syrup flow
control not properly adjusted.
B. Syrup Tanks System.
CO2gas pressure to syrup tanks insufficient to push syrup out of tanks
Bag-in-Box System.
CO2gas pressure to syrup pumps insufficient to operate pumps.
A. No syrup supply. A. Replenish syrup supply as
B. Syrup Tanks System.
Syrup tanks CO2regulator out of adjustment.
Syrup Bag-in-Box System.
Syrup pumps CO2regulator out of adjustment.
A. Adjust Water-to-Syrup “Ratio” as
instructed.
B. Adjust syrup tanks CO2regulator
as instructed.
Adjust syrup pumps CO regulator as instructed.
instructed.
B. Adjust CO2regulator for syrup
tanks as instructed.
Adjust syrup pumps CO regulator as instructed.
2
2
C. Dispensing valve syrup flow
control or syrup line restricted. D. Improper Baume of syrup. D. Replace syrup supply. E. Inoperative dispensing valve
syrup flow control. F. Tapered washer inside tube
swivel nut connection distorted
from being overtightened
restricting syrup flow.
43
C. Sanitize syrup system as
instructed.
E. Repair dispensing valve syrup
flow control.
F. Replace tapered gasket. Make
sure it seats properly .
318832000
Page 50
STANDARD UNIT (REQUIRES CONNECTION TO A REMOTE CARBONATOR) CONT’D
Trouble Probable Cause Remedy
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
DISPENSED PRODUCT CARBONATION TOO LOW.
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP OR GLASS.
A. Dirty or inoperative dispensing
valve syrup flow control.
A. Disassemble and clean
dispensing valve syrup flow control.
A. Carbonator CO2regulator out
of adjustment for existing
A. Adjust carbonator CO2regulator
as instructed. water conditions or temperature.
B. Air in carbonator tank. B. Vent air out of carbonator tank
through relief valve. Open
dispensing valve to make
carbonator pump cycle on.
C. Water, oil, or dirt, in CO
supply .
2
C. Remove contaminated CO2.
Clean CO2system (lines,
regulator, etc.) using a mild
detergent. Install a clean CO
supply .
A. Oil film or soap scum in cups
A. Use clean cups or glasses.
or glasses.
2
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE.
B. Ice used for finished drink is
subcooled.
B. Do not use ice directly from
freezer. Allow ice to become “wet”
before using. (Refer to following
NOTE)
NOTE: Crushed ice also causes dispensing problems. When dispensed drink hits sharp edges of ice, carbonation is released from drink.
A. Recovery rate of refrigeration
A. Allow ice bank to recover. unit exceeded, ice bank depleted.
CAUTION: The drop -in refrigeration assembly condenser coil must be cleaned every 30-days. Excessive accumulation of dust, lint, and grease on coil will restrict cooling air flow through coil and cause refrigeration system to overheat.
B. Carbonator CO2regulator
pressure adjusted too high for
B. Reduce Carbonator CO2regulator
pressure settings. existing water conditions or temperature.
C. .Condenser coil plugged. C. Clean condenser coil as
instructed..
D. Dispensing valve restricted or
dirty .
D. Sanitize syrup system as
instructed.
318832000
44
Page 51
STANDARD UNIT (REMOTE REQUIRES CONNECTION TO A REMOTE CARBONATOR) CONT’D
Trouble Probable Cause Remedy
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE. (cont’d)
NO PRODUCT DISPENSED. A. Dispensing valves keyed
E. Tapered gasket inside
carbonated water line swivel nut connector distorted restricting carbonated water flow.
F. Dirty water supply. F. Check water filter. Replace
NOTE: If water supply is dirty, be sure to flush lines and carbonator completely . It may be necessary to remove lines to carbonator tank, invert tank, and flush tank and all inlet lines to remove any foreign particles or dirt.
lock-out switch in “OFF” position.
B. No electrical power to Unit. B. Plug in Unit power cord or check
C. Disconnected dispensing
valves power cord.
D. Disconnected or broken wiring
to dispensing valve.
E. Replace tapered gasket. Make
sure it is properly seated.
cartridge (see NOTE).
A. Place keyed lock-out switch in
“ON” position.
for blown power fuse or tripped circuit breaker.
C. Connect dispensing valves power
cord.
D. Connect or replace wiring.
E. Inoperative transformer or
valve solenoids.
ONLY CARBONATED WATER DISPENSED.
ONLY SYRUP DISPENSED. A. Water inlet supply line shutoff
A. Out of syrup. A. Replenish syrup supply as
B. Inoperable dispensing valve. B. Repair dispensing valve. C. Dispensing valve syrup flow
control not properly adjusted.
D. Dispensing valve syrup flow
control or syrup lines restricted.
valve closed.
B. Carbonator power cord
unplugged from electrical outlet.
C. Carbonator CO2regulator not
properly adjusted.
E. Replace inoperative part.
instructed.
C. Adjust dispensing valve syrup
flow control (Water-to-Syrup “Ratio”) as instructed.
D. Sanitize syrup system as
instructed.
A. Open water inlet supply line
shutoff valve.
B. Plug carbonator power cord into
electrical outlet.
C. Adjust carbonator CO2regulator
as instructed.
45
318832000
Page 52
UNIT WITH BUILT-IN COLD CARBONATOR
Trouble Probable Cause Remedy
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
A. Dispensing valve syrup flow
control not properly adjusted.
B. Syrup Tanks System.
CO2gas pressure to syrup
A. Adjust Water-to-Syrup “Ratio” as
instructed.
B. Adjust CO2regulator for syrup
tanks as instructed. tanks insufficient to push syrup out of tanks.
Bag-in-Box Syrup System.
CO2gas pressure to syrup
Adjust syrup pumps CO
regulator as instructed.
2
pumps insufficient to operate pumps.
A. No syrup supply. A. Replenish syrup supply as
instructed.
B. Syrup Tanks System.
Syrup tanks CO2regulator out
B. Adjust syrup tanks CO2regulator
as instructed. of adjustment.
Syrup Bag-in-Box System.
Syrup pumps CO2regulator
Adjust syrup pumps CO
regulator as instructed.
2
out of adjustment.
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
DISPENSED PRODUCT CARBONATION TOO LOW.
C. Dispensing valve syrup flow
control, or syrup line restricted.
C. Sanitize syrup system as
instructed.
D. Improper syrup Baume. D. Replace syrup supply as
instructed.
E. Inoperative dispensing valve
syrup flow control.
F. Tapered gasket inside tube
swivel nut connection distorted
E. Repair dispensing valve syrup
flow control.
F. Replace tapered gasket. Make
sure it is properly seated. from being overtightened restricting syrup flow.
A. Dirty dispensing valve syrup
flow control.
A. Disassemble and clean
dispensing valve syrup flow
control.
A. Carbonator CO2regulator out
of adjustment for existing
A. Adjust carbonator CO2regulator
as instructed. water conditions or temperature.
B. Air in carbonator tank. B. Vent air from carbonator tank by
dispensing from dispensing valve
to make carbonator pump motor
cycle on.
318832000
C. Water, oil, or dirt in CO
supply .
46
2
C. Remove contaminated CO2.
Clean CO2system (lines,
regulators, etc.) using mild
detergent. Install clean CO
2
supply .
Page 53
UNIT WITH BUILT-IN COLD CARBONATOR (CONT’D)
Trouble Probable Cause Remedy
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP OR GLASS.
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE.
A. Oil film or soap scum in cups
A. Use clean cups or glasses.
or glasses.
B. Ice used for finished drink is
subcooled.
B. Do not use ice directly from
freezer. Allow ice to become “wet” before using. (Refer to following NOTE.)
NOTE: Crushed ice also causes dispensing problems. When dispensed drink hits sharp edges of ice, carbonation is released from drink.
A. Recovery rate of refrigeration
A. Allow ice bank to recover. unit exceeded, ice bank depleted.
CAUTION: The drop -in refrigeration assembly condenser coil must be cleaned every 30-days. Excessive accumulation of dust, lint, and grease on coil will restrict cooling air flow through coil and cause refrigeration system to overheat.
B. Condenser coil plugged. B. Clean condenser coil as
instructed.
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES.
C. Carbonator CO2regulator
pressure adjusted too high for
C. Adjust carbonator CO2regulator
pressure as instructed. existing water conditions or temperature.
D. Dispensing valve restricted or
dirty .
E. Tapered gasket inside
carbonated water line swivel
D. Sanitize syrup system as
instructed.
E. Replace tapered gasket. Make
sure gasket is properly seated. nut connector distorted restricting carbonated water flow.
F. Dirty water supply. F. Check water filter. Replace
cartridge (see NOTE).
NOTE: If water supply is dirty, be sure to flush lines and carbonator completely . It may be necessary to remove lines to carbonator tank, invert tank, and flush the tank and all inlet lines to remove any foreign particles or dirt.
A. Dispensing valves keyed
lock-out switch in “OFF”
A. Place keyed lock-out switch in
“ON” position. position.
B. Power switch (if applicable) in
“OFF” position.
B. Place power switch in “ON”
position.
47
318832000
Page 54
UNIT WITH BUILT-IN COLD CARBONATOR (CONT’D)
Trouble Probable Cause Remedy
NO PRODUCT DISPENSED
C. No electrical power to Unit. C. Plug in Unit power cord or check FROM ALL DISPENSING VALVES. (cont’d)
D. Inoperative power switch (if
applicable).
E. Dispensing valves power cord
disconnected.
F. Disconnected or broken wiring
to dispensing valve.
G. Inoperative transformer or
valve solenoids.
ONLY CARBONATED WATER
A. Out of syrup. A. Replenish syrup supply as DISPENSED.
B. Inoperable dispensing valve. B. Repair dispensing valve.
C. Dispensing valve syrup flow
control not properly adjusted.
D. Dispensing valve syrup flow
control or syrup lines restricted.
ONLY SYRUP DISPENSED. A. Water inlet supply line shutoff
valve closed.
for blown power fuse or tripped circuit breaker.
D. Replace power switch.
E. Connect dispensing valves power
cord.
F. Connect or replace wiring.
G. Replace inoperative part.
instructed.
C. Adjust dispensing valve syrup
flow control as instructed.
D. Sanitize syrup system as
instructed.
A. Open water inlet supply line
shutoff valve.
B. Carbonator power cord (under
hood) unplugged.
C. Carbonator CO2regulator not
properly adjusted.
D. Inoperative carbonator liquid
level control assembly.
E. Inoperative water pump, water
pump motor, or water pump power switch.
B. Remove hood and plug in
carbonator power cord.
C. Adjust carbonator CO2regulator
as instructed.
D. Replace carbonator liquid level
control assembly.
E. Replace inoperative component.
318832000
48
Page 55
NONCARBONATED UNIT
Trouble Probable Cause Remedy
WATER-TO-SYRUP “RATIO” TOO LOW OR TOO HIGH
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT INCREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
A. Dispensing valve syrup flow
control not properly adjusted.
B. Syrup Tanks System.
CO2gas pressure to syrup
A. Adjust Water-to-Syrup “Ratio” as
instructed.
B. Adjust syrup tanks CO2regulator
as instructed. tanks insufficient to push syrup out of tanks.
Bag-in-Box Syrup System.
CO2gas pressure to syrup
Adjust syrup pumps CO
regulator as instructed.
2
pumps insufficient to operate pumps.
A. No syrup supply. A. Replenish syrup supply as
instructed.
B. Syrup Tanks System.
Syrup tanks CO2regulator out
B. Adjust syrup tanks CO2regulator
as instructed. of adjustment.
Syrup Bag-in-Box System.
Syrup pumps CO2regulator
Adjust syrup pumps CO
regulator as instructed.
2
out of adjustment.
ADJUSTMENT OF DISPENSING VALVE SYRUP FLOW CONTROL DOES NOT DECREASE TO DESIRED WATER-TO-SYRUP “RATIO”.
DISPENSED PRODUCT COMES OUT OF DISPENSING VALVE CLEAR BUT FOAMS IN CUP OR GLASS.
C. Dispensing valve syrup flow
control or syrup line restricted.
D. Dirty or inoperative dispensing
valve syrup flow control.
E. Tapered washer inside tube
swivel nut connection distorted from being overtightened restricting syrup flow.
A. Dirty dispensing valve syrup
flow control.
A. Oil film or soap scum in cups
or glasses.
B. Ice used for finished drink is
subcooled.
C. Sanitize syrup system as
instructed.
D. Disassemble and clean syrup flow
control.
E. Replace tapered gasket. Make
sure it seats properly .
A. Disassemble and clean
dispensing valve syrup flow
control.
A. Use clean cups or glasses.
B. Do not use ice directly from
freezer. Allow ice to become “wet”
before using. (Refer to following
NOTE.)
NOTE: Crushed ice also causes dispensing problems. When dispensed drink hits sharp edges of ice, carbonation is released from drink.
49
318832000
Page 56
NON-CARBONATED UNIT (CONT’D)
Trouble Probable Cause Remedy
DISPENSED PRODUCT PRODUCES FOAM AS IT LEAVES DISPENSING VALVE.
NO PRODUCT DISPENSED FROM ALL DISPENSING VALVES.
A. Recovery rate of refrigeration
unit exceeded, ice bank depleted.
CAUTION: The drop -in refrigeration assembly condenser coil must be periodically cleaned. Excessive accumulation of dust, lint, and grease on coil will restrict cooling air flow through coil and cause refrigeration system to overheat.
B. Dispensing valve restricted or
dirty .
C. Tapered gasket inside
carbonated water line swivel nut connector distorted restricting carbonated water flow.
A. Dispensing valves keyed
lock-out switch in “OFF” position.
B. No electrical power to Unit. B. Plug in Unit power cord or check
C. Disconnected dispensing
valves power cord.
A. Allow ice bank to recover.
B. Sanitize syrup system as
instructed.
C. Replace tapered gasket. Make
sure gasket is properly seated.
A. Place keyed lock-out switch in
“ON” position.
for blown power fuse or tripped circuit breaker.
C. Connect dispensing valves power
cord.
D. Disconnected or broken wiring
to dispensing valve.
E. Inoperative transformer or
valve solenoids.
ONLY PLAIN WATER DISPENSED.
ONLY SYRUP DISPENSED. A. Water inlet supply line shutoff
A. Out of syrup. A. Replenish syrup supply as
B. Inoperable dispensing valve. B. Repair dispensing valve. C. Dispensing valve syrup flow
control not properly adjusted.
D. Dispensing valve syrup flow
control or syrup lines restricted.
valve closed.
REFRIGERATION SYSTEM
Trouble Probable Cause Remedy
COMPRESSOR DOES NOT OPERATE.
A. Ice bank sufficient. A. Refrigeration not called for.
D. Connect or replace wiring.
E. Replace inoperative part.
instructed.
C. Adjust dispensing valve syrup
flow control (Water-to-Syrup “Ratio”) as instructed.
D. Sanitize syrup system as
instructed.
A. Open water inlet supply line
shutoff valve.
318832000
B. Unit power cord unplugged,
power switch (if applicable) in “OFF” position, or drop-in refrigeration assembly power cord unplugged.
50
B. Plug in power cord(s) or place
Unit power switch (located behind front panel) in “ON” position.
Page 57
REFRIGERATION SYSTEM (CONT’D)
Trouble Probable Cause Remedy
COMPRESSOR DOES NOT OPERATE. (cont’d)
C. No power source (blown fuse
or tripped circuit breaker).
C. Replace fuse or reset circuit
breaker. (NOTE: Fuse or circuit
breaker are not part of unit).
D. Inoperative Unit power switch
(if applicable) or power cord
D. Replace power switch or plug Unit
power cord into electrical outlet. unplugged.
E. Low voltage. E. Voltage must be at least 103 volts
(115 VAC unit) or 208 (230 VAC
unit) at compressor terminal when
compressor is trying to start.
F. Loose, disconnected, or
broken wiring.
G. Overload protector cut out;
overheated compressor. Condenser fan motor not operating as required.
F. Tighten connections or replace
broken wiring.
G. Compressor will cool enough to
restart. Do not overdraw cooling
capacity of Unit. Refer to
“CONDENSER FAN MOTOR
NOT OPERATING” in this
section.
H. Inoperative overload protector
H. Replace inoperative part.
or start relay.
I. Inoperative ice bank control
I. Replace ice bank control.
probe.
COMPRESSOR WILL NOT STOP AFTER SUFFICIENT ICE BANK IS PRODUCED. (NOTE: ICE BANK SHOULD JUST COVER CONTROL BULB).
COMPRESSOR OPERATES CONTINUOUSLY BUT DOES NOT FORM SUFFICIENT ICE BANK.
AGITATOR MOTOR NOT OPERATING.
J. Inoperative compressor. J. Call service person. A. Ice bank control cap tube
A. Replace ice bank control.
kinked or broken.
B. Ice bank control stuck in
B. Replace ice bank control.
closed position.
A. Cooling capacity is exceeded
by over-drawing.
B. Unit located in excessively hot
area or air circulation through condenser coil is restricted.
A. Reduce amount of drinks drawn
per given time.
B. Relocate unit or check and if
necessary , clean condenser coil
as instructed.
NOTE: Ice bank freezes from bottom of evaporator upward. A refrigerant leak or insufficient charge might show an ice bank at bottom and not at top of evaporator.
A. Power switch (if applicable) in
“OFF” position.
A. Place power switch in
“ON” position.
B. Unit power cord or
refrigeration assembly power cord unplugged.
51
B. Connect power cord(s).
318832000
Page 58
REFRIGERATION SYSTEM (CONT’D)
Trouble Probable Cause Remedy
AGITATOR MOTOR NOT OPERATING. (cont’d)
C. No power source (blown fuse
or tripped circuit breaker).
C. Replace fuse or reset circuit
breaker. (NOTE: Fuse or circuit breaker are not part of Unit).
D. Agitator motor propeller
D. Remove obstruction.
obstructed.
E. Low voltage. E. Voltage must be at least 103 volts
(115 VAC unit) or 208 (230 VAC unit) at compressor terminals when compressor is trying to start.
F. Loose, disconnected, or
broken wiring.
F. Tighten connections or replace
broken wiring.
G. Inoperative agitator motor. G. Replace agitator motor.
318832000
52
Page 59
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un­der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire prod­uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the equipment model number, serial number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166 AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930 BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307 BRAZIL D RUA IT AOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829 ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644 FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201 GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438 GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491 HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222 ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, IT ALY D (39) 39 608 0817 D FAX (39) 39 608 0814 NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361 SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604 SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379 USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255
LD004
4/21/98
53 318832000
Page 60
Page 61
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place Anoka, Minnesota 55303-6234 (612) 421-6120 (800) 238-3600
Loading...