CAUTION - Only trained and certified electrical, plumbing and refrigeration technicians should
service this unit. ALL WIRING AND PLUMBING MUST CONFORM TO NATIONAL AND LOCAL
CODES.
REQUIREMENTS
Quest 2000 Installation Manual
INSTALLATION MANUAL
Quest 2000
Nameplate Data: Model QST 2000, 115 VAC, 4.5 amps, 1 phase 60 hertz, 6.25 oz. (177g) R-134a
refrigerant. Test press: High side 400 psi (27.6 bar). Low side 100 psi (6.9 bar).
Model QST 2000, 230 VAC, 2.25 amps, 1 phase 50 hertz, 6.25 oz. (177g) R-134a
refrigerant. Test press: High side 400 psi (27.6 bar). Low side 100 psi (6.9 bar).
Concentrate Storage: Two 0.8 gallon (3.0 liter) disposable bottles.
Clearance Recommended: 12” (30.48 cm) on top and 4” (10.16 cm) required in back for air circulation.
Electrical Connection: 6 ft. long (1.83 m) power cord with 3-prong plug attached to dispenser. Export
models have line cord less plug.
Power Supply: 15 amps at 120 volts dedicated power supply.
20 amps at 230 volts dedicated power supply.
Water Connection: 3/8 in. (0.95 cm) SAE male flare fitting on dispenser.
Water Supply Requirements: 80 psi (5.5 bar) maximum static pressure. 20 psi (1.4 bar) minimum
dynamic pressure; i.e., flowing pressure measured at dispenser water inlet with 3.0
ounces (88.7 ml) per second water flow.
Ice Bank/Pull Down: Weight 7-8 lbs. (4.1-4.5 kg.). Pull Down: 3 hours at 75°F (24°C)
Release Date: August 17, 2006 www.cornelius.com Revision: C
© 2004-2006, IMI Cornelius Inc. - 1 - Publication Number: 720529901INS
Quest 2000 Installation Manual
RECEIVING
Each unit is completely tested and inspected before shipment. At time of shipment, the carrier accepts
the unit and any claim for damage must be made with the carrier.
Upon receiving from the carrier, please inspect the carton for visible damage. If damage exists, have the
carrier make a note on the bill of lading and file a claim with the carrier.
UNPACKING
• Remove staples securing carton to pallet.
• Lift carton up and off of unit.
• Remove inserts and shipping bag.
• Open upper cabinet door and remove installation kit.
• Remove bolts securing unit to pallet.
• Lift unit off of pallet.
NOTE: Do not lay the unit on sides or on the back. This may cause vital oils to drain from the
compressor resulting in damage during start-up and consequently voiding the warranty.
COUNTER LOCATION
Select a location in a well ventilated area, close to a
grounded electrical outlet. If possible do not place the unit
close to hot and/or steaming machines.
The minimum airflow clearance is: 4” (10.16 cm) in back
and 12” (30.48 cm) on top and open to the front.
IMPORTANT: Condenser air is drawn in from the bottom of the rear panel and discharged out the top of the
rear panel. Failure to maintain clearance space will
reduce capacity of the unit and cause premature compressor failure.
Typically the dispenser is placed directly on the counter and
a food grade silicone sealant applied around the base. However, supplied with the dispenser is a counter top sealing gasket. This eliminates the need for sealant and
is much easier to use.
FILLING THE ICE BATH
The ice bath holds approximately 2gallons (7.6 liters) of water. The fill
tube is located behind the front splash plate and capped with a 3/8”
(0.95 cm) male flare connector. Prior to attaching the water supply
line to the dispenser, use it to fill the ice bath by attaching it to the
connector on the fill tube
Slowly open the water shut off valve and fill the ice bath until water
trickles from the overflow. This is the quickest and easiest way to fill
the ice bath.
Once the ice bath is full, store the fill tube in the vertically recessed
holder. The fill tube can now be used as a “sight glass” to monitor the water level in the ice bath.
Publication Number: 720529901INS - 2 - © 2004-2006, IMI Cornelius Inc.