IMI Cornelius, Inc. IRC630, IRC830, IRC1030, IRC1030L, IRC1230 Installation Manual

IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234
Telephone (800) 238-3600 Facsimile (800) 535-4231
IMPORTANT:
TO THE INSTALLER. It is the responsibility of
the Installer to ensure that the water supply to the dispensing equipment is provided with protection against backflow by an air gap as defined in ANSI/ASME A112.1.2-1979; or an approved vacuum breaker or other such method as proved effective by test.
Installation Manual
I" Series
“REMOTE”
Ice Cube Machine
Water pipe connections and fixtures directly connected to a potable water supply shall be sized, installed, and maintained according to Federal, State, and Local Codes.
Part No. 166240001 Date of Creation 10/31/94 Revised: 10/8/2003 Control Code A
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment
IMI CORNELIUS INC; 1994–2003
PRINTED IN U.S.A
TABLE OF CONTENTS
GENERAL 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FREIGHT DAMAGE CLAIMS PROCEDURE 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS 2. . . . . . . . . . . . . . . .
REMOTE CONDENSER LOCATION 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION INSTRUCTIONS 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LOCATION OF EQUIPMENT 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EQUIPMENT SET-UP 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISPENSER INSTALLATION 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLUMBING CONNECTIONS 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION CHECK POINTS 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START-UP AND CHECK OUT 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OWNER -OPERATOR 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING PROCEDURES 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREP – CLEANING 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CLEANING THE WATER SYSTEM & EVAPORATOR 15. . . . . . . . . . . . . . . . . .
SANITIZING PROCEDURES 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUMP CYCLE 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WATER PAN LEVEL SETTINGS 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STATUS INDICATOR 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUSTING BRIDGE THICKNESS 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TOTAL ICE CAPACITY 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page
i
166240001
GENERAL
FREIGHT DAMAGE CLAIMS PROCEDURE
The deliverer of your equipment (freight company, distributor or dealer) is responsible for loss or damage of your shipment. All claims must be filed with the deliverer of your equipment. Please follow the steps below to deter­mine if your shipment is satisfactory or if a claim must be filed:
1. Check the number of products delivered against the number of products listed on the delivery receipt. Should the totals not match, have the driver note all errors on both copies and both you and the driver sign and date said notation.
2. Inspect all cartons for visible damage. Open and inspect as required before the driver leaves and have him or her note any damage on the receipts. All damaged claims must be inspected within 15 days of delivery. Notify your carrier immediately if concealed damage is found after delivery.
3. Should concealed damage be found when product is unpacked, retain the packing material and the product and request an inspection from the deliverer.
4. All claims for loss or damage should be filed at once. Delays in filing will reduce the chance of achieving a satisfactory resolution to the claim.
i
166240001
INSTALLATION INSTRUCTIONS REMOTE CONDENSERS
UNIT
LEG
1. Follow the standard installation instructions supplied with cuber. Do not hook cuber into the power source until the remote condenser and line set installation is complete.
2. Assembly of remote condenser (see drawing):
1/4-20 SCREW
LEG
BRACE
A. Assemble legs to base panel. Install leg supports on legs.
B. Locate the remote condenser in a well ventilated area on the roof away from other refrigeration equip-
ments condenser discharge air flow.
C. Use the mounting holes provided to secure the remote condenser to the roof. Seal over heads of bolts
or fasteners with tar or pitch to prevent entrance of moisture.
REMOTE CONDENSER
LEG SUPPORT
LEG
3. Remote condenser electrical hook-up:
A. Connect remote condenser to a power source (208/230VAC, 60 HZ) separate from the cuber. An ex-
ternal disconnect switch must be used.
B. Make sure the electrical connections follow all local and national codes.
C. DO NOT turn condenser on until cuber install and refrigerant line connections are complete!
166240001
ii
NOTE:
a. Never wire condenser into cuber section. The condenser is an independent electrical con-
nection.
b. Fan motor will not start until pressure rises to 205 PSIG [14.07 Bars] closing fan cycling
switch.
c. The condenser fan may cycle off during the harvest cycle - This would be normal.
NOTE: Installing an IMI Cornelius remote cuber with other than an IMI Cornelius remote condenser
and line set may be reason to void the cuber warranty.
LIQUID REFRIGERANT LINE
DISCHARGE LINE
CORRECT
4. Each condenser and cuber is connected with two (2) pre-charged lines.
A. The pre-charged lines are ordered separately from the condenser to suit each individual application.
B. The pre-charged line lengths are 20 feet [6.096 meters], 35 feet [10.66 meters] and 55 feet [16.76 me-
ters].
NOTE: *(Pre-charged is defined as a vapor holding charge - not a portion of the system charge.)
5. Installation of line kits (see drawing) Remove the tubing from the carton. Carefully uncoil the lines so the tubing doesnt become kinked, and route lines to cuber and condenser.
6. Keep line set as short as possible. Place a 3 foot service loop behind cuber to allow for rear service should it ever be required.
REMOTE CONDENSER LOCATION
NOTE: NOTE: Max. line set length for IMI Cornelius cubers is 55 ft. - Do not confuse line
length with calculated line distance.
1. Physical Line Set Length: 55 Ft. Maximum [16.764 meters]
iii
166240001
The ice machine compressor must have the proper oil return. Line-set rises, drop, or horizontal runs greater than the maximum distance allowed will exceed the compressor start-up and pumping design limits, and will result in poor oil return to the compressor.
Line Set Rise: 35 Ft. Maximum [10.66 meters] Line Set Drop: 15 Ft. Maximum [4.57 meters]
2. Calculated Line Set Distance: 100 Ft. [30.48 meters]
To prevent the combination of rises, drops and horizontal runs exceeding the compressor start-up and pumping design limit, the following calculations should be made:
B
A
C
B
A - (RISE)_ CONDENSER HIGHER THEN EVAP. MAX. 35 B – LINE LENGTH 15: EXAMPLE
B - LINE LENGTH 35: EXAMPLE C - (DROP) CONDENSER LOWER THAN EVAP. 15’: MAX.
Maximum Line Set Distance Formula
3. Measured rise x 1.7=Calculated (Rise 35 ft. Max.) [10.66 meters]
4. Measured drop x 6..6=Calculated (Drop 15ft. Max.) [4.57 meters]
5. Measured Horizontal Distance= actual measurement.
6. Total Calculated distance (A+B+C)=Total Calculated Distance (100 ft. Max.) [30.48 meters]
Examples:
a. Insert measured rise (R) into formula and multiply it by 1.7 to get a calculated rise.
example: A condenser located 15 ft. [4.572 meters] above the ice machine has a 25.5 ft. [8.874 meters]
166240001
calculated total (15 ft. x 1.7 = 25.5).
iv
H
AIR FLOW
R
b. Insert measured drop (D) into formula and multiply by 6.6 to get a calculated drop.
example: A condenser located 8 ft. [2.438 meters] below the ice machine has a 52.8 ft. [16.093 meters] calculated total (8ft. x 6.6 = 52.8 ft.)
COMBIATION OF DROP(S) WITH HORIZONTAL
H
D
AIR FLOW
c. Insert measured horizontal distance into formula. No calculation is necessary. (6 ft.) [1.828 meters].
COMBIATION OF RISE AND DROP(S)WITH HORIZONTAL
H
R
D
AIR FLOW
d. Add the calculated rise, calculated drop, and horizontal distance together to get the total calculated dis-
tance (25.5 + 52.8 + 6) equals 84.3 ft. [25.694 meters]. If 100 ft. [30.48 meters] total calculated distance is exceeded, the condenser must be moved to a new location which permits proper equipment opera­tion..
CAUTION: If a line set rise is followed by a line set drop, a second line set rise cannot be made. or If a line set drop is followed by a line set rise, a second line set drop cannot be made.
7. Lengthening Or Reducing The Line Set Lengths
In most cases, by routing the line set properly, shortening will not be necessary (refer to illustration). How­ever when shortening or lengthening is required, do so before connecting the line set to the ice machine or the remote condenser. This prevents the loss of refrigerant from the ice machine or the condenser.
The quick connect fittings on the line sets are equipped with Schrader Valves. Use these valves to recover any vapor charge from the line set. When lengthening or shortening lines, apply good refrigeration practic­es and insulate new tubing. Do not change the tube sizes. Evacuate the lines and place approximately 5 oz. of vapor refrigerant charge in each line.
v
166240001
SCHRADER
VA LV E
PARENT
METAL
SEAL
INTERMEDIATE
SEAL
8. Connection of Line Set
A. Remove the plastic caps from the line set, the condenser, and the ice machine.
B. Apply refrigeration oil to the threads on the quick connect couplers before connecting them to the con-
denser.
C. Carefully thread the female fitting onto the condenser or ice machine by hand.
D. Using the proper size wrench, tighten the couplings until they bottom out. Turn an additional 1/4 turn
to ensure proper brass-to-brass seating.
E. Check all fittings for leaks.
9. Final Installation:
A. Remove grill from the right hand side panel of cuber.
B. Turn service port on receiver tank to open position releasing refrigerant to the balance of the system.
C. Leak check line set connections at cuber and condenser.
D. Replace grill.
E. Connect cuber to power source.
F. Make sure electrical connections follow all local and national codes.
10. Start Up:
A. Use standard procedures from cuber installation instructions.
B. After the cuber is running, check the remote condenser and verify that the condenser fan is running.
CAUTION: Once the refrigerant lines are connected, the seal is broken in the fittings. If the line are removed or loosened from the cuber or remote condenser, the refrigerant charge will be discharges to the atmosphere. DISCHARGING TO THE ATMOSPHERE IS IN
VIOLATION OF THE CLEAN AIR ACT OF JULY, 1992.
166240001
vi
Loading...
+ 17 hidden pages