Product Manual
SRC2100– 120/277 VAC Single Room Controller
ND xxxx-1 08/2017 Users Manual – SRC2100 Single Room Controller
Page 1
www.idealindustries.com
FPRODUCT DESCRIPTION
The Single Room Controller is a wireless
device which provides electrical connectivity
between the light fixture (load) and
120V/277V AC line power. The SRC2100
provides on/off power control as well as 010V dimming control via dimming signals to
the load. The information which tells the
controller to power on/off/dim the fixture is
acquired via wireless signals that originate
from a system gateway, room controls, and
integrated switches/PIR sensor.
KEY FEATURES
FCC and IC approved
Switch replacement with integrated PCB
antenna.
RoHS compliant
PRODUCT CONTENTS
One of the following items is included inside the
package:
SRC2100 Single Room Controller
Audacy®, Smart Connector® and Smart Switch® are registered trademarks of IDEAL INDUSTRIES.

Product Manual
SRC2100– 120/277 VAC Single Room Controller
ND xxxx-1 08/2017 Users Manual – SRC2100 Single Room Controller
Page 2
www.idealindustries.com
All other trademarks are the property of their respective owners.
IDEAL Model SRC2100 Single Room Controller Instructions
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires.
Wiring must comply with all applicable electrical codes.
Turn off power before removing or installing connector.
TERMINOLOGY
LINE(Black): Single Room Controller power feed to be connected to premise
wiring
LOAD(Red): Power output from Single Room Controller to AC lighting load
power input
Neutral(White): Incoming Neutral from premise wiring and outgoing lighting load
neutral.
DIM (Purple/Grey): 0-10 VDC dimming control output from Single Room
Controller to lighting load analog dimming input
CONNECTING THE WIRES
Input Power
The smart connector LINE(Black) and NEUTRAL(White) wires are 18 AWG solid copper
conductors.
1. Strip wires to 1/2”.
2. Connect Controller Line Input to premise line power feed with appropriate sized wirenut or
push-in connector.
3. Connect Controller Neutral Input to premise neutral feed with appropriately sized wirenut or
push-in connector..
4. For feed-through (i.e., “daisy-chain”) installations, connect the LINE hot feed-through
conductor into the wirenut in step 2. Also, connect the NEUTRAL feet-through conductor
connected without re-installing the wires. into the wirenut in step 3.

Product Manual
SRC2100– 120/277 VAC Single Room Controller
ND xxxx-1 08/2017 Users Manual – SRC2100 Single Room Controller
Page 3
www.idealindustries.com
LOAD
The LOAD(red) and Neutral(White) wire are 18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect Controller LOAD wire to the ballast hot line with appropriate sized wirenut or push-
in connector if necessary.
3. Connect Controller NEUTRAL Output to the ballast neutral with appropriately sized wirenut
or push-in connector if necessary.
4. For feed-through (i.e., “daisy-chain”) installations, connect the LOAD hot feed-through
conductor into the wirenut in step 2. Also, connect the NEUTRAL Output feed-through
conductor into the wirenut in step 3.
DIM Connector
The DIM wires are18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect positive/(+)/purple DIM wire from Controller to positive/(+)/purple wire from dimming
ballast with appropriate sized wirenut or push-in connector if necessary.
3. Connect negative/(-)/grey DIM wire from Controller to negative/(-)/grey wire from dimming
ballast with appropriate sized wirenut or push-in connector if necessary.