FPRODUCT DESCRIPTION
The AC Smart Connector is a wireless device which provides electrical connectivity between the light fixture (load) and 277/347V AC line power and provides on/off power control and dimming signals to the load. The information that tells the connector to power on/off/dim the fixture is acquired via wireless signals that originate from a building automation system or from room controls, based on environmental conditions and/or predetermined programs.
KEY FEATURES
FCC and IC approved External fixture mounting Small form factor 1000 Integrated Wire Antenna RoHS compliant
PRODUCT CONTENTS
One of the following items is included inside the package:
Audacy®, Smart Connector® and Smart Switch® are registered trademarks of IDEAL INDUSTRIES.
IDEAL Model SCD1002 347VAC Luminaire Controller - External
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 1 www.idealindustries.com
All other trademarks are the property of their respective owners.
Product Manual
SCD1002,SCLED1002 – 347 VAC Luminaire Controller-External
Installation Instructions
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires.
Wiring must comply with all applicable electrical codes. Turn off power before removing or installing connector.
TERMINOLOGY
LINE(Black): Smart Connector power feed to be connected to premise wiring LOAD(Red): Power output from Smart Connector to ballast AC power input Neutral(White): Incoming Neutral from premise wiring and outgoing ballast neutral. DIM (Purple/Grey): 0-10 VDC dimming control output from Smart Connector to ballast dimming input
CONNECTING THE WIRES
Input Power The smart connector LINE(Black) and NEUTRAL(White) wires are 18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect Smart Connector Line Input to premise line power feed with appropriate sized wirenut or push-in connector.
3. Connect Smart Connector Neutral Input to premise neutral feed with appropriately sized wirenut or push-in connector..
4. For feed-through (i.e., “daisy-chain”) installations, connect the LINE hot feed-through conductor into the wirenut in step 2. Also, connect the NEUTRAL feet-through conductor connected without re-installing the wires. into the wirenut in step 3.
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 2 www.idealindustries.com
Product Manual
SCD1002,SCLED1002 – 347 VAC Luminaire Controller-External
LOAD The LOAD(red) and Neutral(White) wire are 18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect Smart Connector LOAD wire to the ballast hot line with appropriate sized wirenut or push-in connector if necessary.
3. Connect Smart Connector NEUTRAL Output to the ballast neutral with appropriately sized wirenut or push-in connector if necessary.
4. For feed-through (i.e., “daisy-chain”) installations, connect the LOAD hot feed-through conductor into the wirenut in step 2. Also, connect the NEUTRAL Output feed-through conductor into the wirenut in step 3.
DIM Connector The DIM wires are18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect positive/(+)/purple DIM wire from Smart Connector to positive/(+)/purple wire from dimming ballast with appropriate sized wirenut or push-in connector if necessary.
3. Connect negative/(-)/grey DIM wire from Smart Connector to negative/(-)/grey wire from dimming ballast with appropriate sized wirenut or push-in connector if necessary.
Figure 1 – Typical Installation-SCD1002
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 3 www.idealindustries.com