Product Manual
SCD1002 Luminaire ControllerExternal
SCLED1002 Luminaire Controller External
SCD1002,SCLED1002 – 347 VAC Luminaire Controller-External
FPRODUCT DESCRIPTION
The AC Smart Connector is a wireless device
which provides electrical connectivity
between the light fixture (load) and
277/347V AC line power and provides on/off
power control and dimming signals to the
load. The information that tells the
connector to power on/off/dim the fixture is
acquired via wireless signals that originate
from a building automation system or from
room controls, based on environmental
conditions and/or predetermined programs.
KEY FEATURES
FCC and IC approved
External fixture mounting
Small form factor 1000
Integrated Wire Antenna
RoHS compliant
PRODUCT CONTENTS
One of the following items is included inside the
package:
Audacy®, Smart Connector® and Smart Switch® are registered trademarks of IDEAL INDUSTRIES.
IDEAL Model SCD1002 347VAC Luminaire Controller - External
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 1
www.idealindustries.com
All other trademarks are the property of their respective owners.
Product Manual
SCD1002,SCLED1002 – 347 VAC Luminaire Controller-External
Installation Instructions
WARNING: This is a current rated device. Use in applications involving
amperage beyond its rating can be dangerous and cause electrical fires.
Wiring must comply with all applicable electrical codes.
Turn off power before removing or installing connector.
TERMINOLOGY
LINE(Black): Smart Connector power feed to be connected to premise wiring
LOAD(Red): Power output from Smart Connector to ballast AC power input
Neutral(White): Incoming Neutral from premise wiring and outgoing ballast
neutral.
DIM (Purple/Grey): 0-10 VDC dimming control output from Smart Connector to
ballast dimming input
CONNECTING THE WIRES
Input Power
The smart connector LINE(Black) and NEUTRAL(White) wires are 18 AWG solid copper
conductors.
1. Strip wires to 1/2”.
2. Connect Smart Connector Line Input to premise line power feed with appropriate sized
wirenut or push-in connector.
3. Connect Smart Connector Neutral Input to premise neutral feed with appropriately sized
wirenut or push-in connector..
4. For feed-through (i.e., “daisy-chain”) installations, connect the LINE hot feed-through
conductor into the wirenut in step 2. Also, connect the NEUTRAL feet-through conductor
connected without re-installing the wires. into the wirenut in step 3.
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 2
www.idealindustries.com
Product Manual
SCD1002,SCLED1002 – 347 VAC Luminaire Controller-External
LOAD
The LOAD(red) and Neutral(White) wire are 18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect Smart Connector LOAD wire to the ballast hot line with appropriate sized wirenut or
push-in connector if necessary.
3. Connect Smart Connector NEUTRAL Output to the ballast neutral with appropriately sized
wirenut or push-in connector if necessary.
4. For feed-through (i.e., “daisy-chain”) installations, connect the LOAD hot feed-through
conductor into the wirenut in step 2. Also, connect the NEUTRAL Output feed-through
conductor into the wirenut in step 3.
DIM Connector
The DIM wires are18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect positive/(+)/purple DIM wire from Smart Connector to positive/(+)/purple wire from
dimming ballast with appropriate sized wirenut or push-in connector if necessary.
3. Connect negative/(-)/grey DIM wire from Smart Connector to negative/(-)/grey wire from
dimming ballast with appropriate sized wirenut or push-in connector if necessary.
Figure 1 – Typical Installation-SCD1002
ND xxxx-1 08/2017Users Manual – SCD1002,SCLED1002 347VAC Luminaire Controller - External Page 3
www.idealindustries.com