NOTE TO THE INSTALLER: Leave these instructions adjacent to the gas meter or with the user
Settled Land Contract Contract
Boiler Size | NF 230 | NF 240 | NF 250 | NF 260 | NF 280 | |||
---|---|---|---|---|---|---|---|---|
Main burner bar |
Aeromatic
AC 19/123 278 |
Aeromatic AC 19/123 278 AC 19/123 279 AC 19/123 276 |
Aeromatic
AC 19/123 277 |
|||||
Gas control | HONEYWE | LL VR 4700 E 1 | 1042, 240 V | |||||
Burner Injector | BRAY |
Cat. 16
size 750 |
Cat. 16
size 1100 |
Cat. 16
size 1400 |
Cat. 16
size 1700 |
Cat. 10
size 2400 |
||
Pilot injector | HONEY | WELL |
459004
STAMPE |
21 - 001
D 38 / 36A |
ST |
45900421 - 002
AMPED 56 / 42 |
2A | |
Gas supply connection | on (in. | BSP) | Rc 1/2 (1/2) | |||||
Flow connection | Compression fi | ittings | 22 mm | 22 mm | ||||
Return connection Compression fittings | 22 mm 28 mm | 28 mm | ||||||
Maximum static water | head | m (ft.) | 30.5 (100) | |||||
Minimum static water | head | m (ft.) | 0.45 (1.5) | |||||
Electrical supply | 240 V ~ 50 Hz Boiler power consumption; 50 W | |||||||
Fuse rating | External; 3 A Internal; F1 A to BS. 4 | BS. 4265 | ||||||
Water content | litre | (gal.) | 1.0 (0 | ).22) | 1.2 (0 | ).27) | 1.5 (0.33) | |
Dry weight | k | g (lb) | 26.3 (58.0) | 27.5 (60.6) | 35.0 (77.2) | |||
Maximum installation weight kg (lb) | 16.0 (35.3) 17.2 (37.9) | 37.9) | 22.9 (50.5) | |||||
Boiler size Height mm (in.) | 700 (27.5) | |||||||
Width mm (in.) | 380 (15) 465 (18) | 465 (18) | ||||||
Depth mm (in.) | . 300 (12) | |||||||
Flue duct diameter mm (in.) | 100 (4) |
Boiler Size | NF 230 | NF 240 | NF 250 | NF 260 | NF 280 | ||
---|---|---|---|---|---|---|---|
Boiler input | MINIMUM | kW | 5.9 | 11.7 | 15.2 | 19.0 | 23.4 |
To obtain gas | (Btu/h) | (20 300) | (40 000) | (51 900) | (64 900) | (80 000) | |
(a) For I/s; divide heat | Gas consumption | 1/s (ft³/h) | 0.15 (19.5) | 0.30 (38.5) | 0.39 (50.0) | 0.49 (62.5) | 0.60 (77.1) |
input (kW) by C.V. of
the gas (MJ/m 3 ). |
MID | kW | 8.6 | 13.3 | 16.9 | 20.7 | 26.6 |
(b) For it 3 /h; divide heat | (Btu/h) | (29 400) | (45 500) | (57 700) | (70 500) | (90 900) | |
of the gas (Btu/ft 3 ). | Gas consumption | l/s (ft³/h) | 0.22 (28.3) | 0.34 (43.8) | 0.44 (55.6) | 0.53 (67. 9 ) | 0.69 (87.6) |
Heat inputs are pre-set to the highest nominal | MAXIMUM | kW | 11.1 | 14.8 | 18.6 | 22.2 | 29.7 |
rating. | (Btu/h) | (38 000) | (50 600) | (63 300) | (75 900) | (101 300) | |
Gas Consumption | l/s (ft³/h) | 0.29 (36.6) | 0.38 (48.7) | 0.48 (61.0) | 0.57 (73.1) | 0.77 (97.6) | |
Boiler output | MINIMUM | kW | 4.4 | 8.8 | 11.7 | 14.7 | 17.6 |
(Btu/h) | (15 000) | (30 000) | (40 000) | (50 000) | (60 000) | ||
MID | kW | 6.6 | 10.3 | 13.2 | 16.1 | 20.5 | |
(Btu/h) | (22 500) | (35 000) | (45 000) | (55 000) | (70 000) | ||
MAXIMUM | kW | 8.8 | 11.7 | 14.7 | 17.6 | 23.4 | |
· | (Btu/h) | (30 000) | (40 000) | (50 000) | (60 000) | (80 000) | |
Burner setting | MINIMUM mba | ır (in.w.g.) | 5.0 (2.0) | 9.2 (3.7) | 9.7 (3.9) | 10.2 (4.1) | 9.5 (3.8) |
pressure (HOT) | MID mbar | (in.w.g.) | 10.1 (4.0) | 11.8 (4.7) | 11.9 (4.8) | 12.0 (4.8) | 12.3 (4.9) |
MAXIMUM mba | r (in.w.g.) | 16.6 (6.7) | 14.6 (5.9) | 14.0 (5.6) | 13.8 (5.5) | 15.2 (6 1) |
The Ideal Elan 2 NF 230, NF 240, NF 250, NF 260 and NF 280 are fully automatically controlled, wall mounted, low water content, balanced flue, fanned gas boilers.
They are range rated to provide central heating outputs of 4.4 kW (15 000 Btu/h) to 23.4 kW (80 000 Btu/h).
The boiler casing is of white enamelled mild steel, with a fascia of satinised white glass. The controls pod, also of white enamalled mild steel, has fixed sides and a removable bottom panel.
The glass fascia slides upwards to reveal the boiler thermostat (in the control box mounted on the gas valve) and the programmer (if fitted).
A Programmer Kit , which fits neatly within the casing, is available as an optional extra. Separate fitting instructions are included with this kit.
The boilers are supplied with a standard flue kit suitable for rear or side outlet applications from 114mm (4 1/2 in.) to 406 mm (16 in.).
Up to 3 optional Flue Extension Duct Kits allowing up to 3 m (118 in.), rear or side outlet, are available.
A Vertex Flue Kit, for vertical flue connection is available as an optional extra.
The boilers are suitable for connection to fully pumped, open vented or sealed water systems. Adequate arrangements for completely draining the system by provision of drain cocks, MUST be provided in the installation pipework.
It is the law that all gas appliances are installed by competent persons (e.g. CORGI, identified by 3 ), in accordance with the above Regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure that the law is complied with.
The installation of the boiler MUST also be in accordance with the current I.E.E. Wiring Regulations, the Local Building Regulations, Building Standards (Scotland), the bye laws of the Local Water Undertaking and any relevant requirements of the Local Authority.
Detailed recommendations are contained in the following British Standard Codes of Pratice.
B5. 669 Low pressure installation pit | pes. |
---|
BS. 5546 Installation of gas hot water supplied for domestic purposes (2nd Family Gases).
Manufacturers' notes must not be taken in any way as overriding statutory obligations.
IMPORTANT. These appliances are certificated by the British Standards Institution for safety and performance. It is, therefore, important that no external control devices, e.g. flue dampers, economisers etc., are directly connected to
Any direct connection of a control device not approved by Caradon Heating Ltd. could invalidate the B.S.I. Certification and the normal appliance warranty. It could also infringe the Gas Safety Regulations and the above regulations.
The boiler MUST be installed on a flat and vertical noncombustile wall, capable of adequately supporting the weight of the boiler and any ancillary equipment.
THE BOILER IS NOT SUITABLE FOR EXTERNAL INSTALLTION
IMPORTANT NOTICE. If the boiler is to be fitted in a timber framed building it should be fitted in accordance, with the British Gas publication 'Guide for Gas Installations in Timber Frame Housing', Reference DM2. If in doubt advice must be sought from the local Gas Region of British Gas.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulation and, in Scotland, the electrical provisions of the Building Regulations applicable in Scotland with respect to the installation of the boiler in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower thren the appliance and any electrical switch or appliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
Where installation will be in an unusual location, special procedures may be necessary and BS. 6798 gives detailed guidance on this aspect.
A compartment used to enclose the boiler MUST be designed and constructed specially for this purpose. An existing cupboard or compartment may be used, provided it is modified for the purpose. Details of essential features of cupboards / compartment design, including airing cupboards installation are given in BS. 6798.
In siting the boiler, the following limitations MUST be observed:
The Local Gas Region should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas.
An existing service pipe must NOT be used without prior consultation with the Local gas region.
A gas meter can only be connected by the Local Gas Region, or by a local Gas Region Contractor. An existing meter should be checked, preferably by the Gas Region, to ensure the meter is adequate to deal with the rate of gas supply required.
Installation pipes should be fitted in accordance with BS. 6891. Pipework from the meter to the boiler MUST be of an adequate size. Do NOT use pipes of a smaller size than the object interview that content and content interview.
The flue MUST be installed in accordance with the recommendations of BS 5440: 1.
The following notes are intended for general guidance.
Terminal guards are available from:
Quinnel, Barret & Quinnel Ltd., 884 Old Kent Road, London, SE15 (Model 304),
(Model K1)
Telephone No. 071 6391357,
and from,
Tower Flue Components Ltd., Vale Rise, Tonbridge, Kent, TN9 1TB
Telephone No. 0732 351555.
Ensure that the guard is fitted centrally.
IMPORTANT. It is absolutely ESSENTIAL to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building or any other adjacent building through ventilators, windows, doors, other sources of natural air infiltration, or forced ventilation / air conditioning.
If this should occur, the appliance MUST be turned OFF immediately and the Local Gas Region consulted.
The flue terminal assembly can be adapted to accomodate various wall thicknesses and flue lengths. Refer to Frame 3.
Detailed recommendations for air supply are given in BS. 5440: 2. The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in
Refer to Tables 4, 5, 6, 7 & 8 for details of air vent position and sizing.
Table 3 - BAI | .ANCED FL | UE TERMINAL | POSITION |
---|
Ter | minal Position |
Minimum
Spacing |
---|---|---|
1. | Directly below an openable window, air vent or other ventilation opening. | 300 mm (12 in.) |
2. | Below guttering, drain pipes or soil pipes. | 25 mm (1 in.) |
3. | Below eaves. | 25 mm (1 in.) |
4. | Below balconies or a car port roof. | 25 mm (1 in.) |
5. | From vertical drain pipes or soil pipes. | 25 mm (1 in.) |
6. | From internal or external corners. | 25 mm (1 in.) |
7. | Above adjacent ground, roof or balcony level. | 300 mm (12 in.) |
8. | From a surface facing the terminal. | 600 mm (24 in.) |
9. | From a terminal facing a terminal. | 1200 mm (48 in) |
10. | From an opening in a car port (eg. door or window) into dwelling. | 1200 mm (48 in) |
11. | Vertically from a terminal on the same wall. | 1500 mm (60 in) |
12. | Horizontally from a terminal on the wall. | 300 mm (12 in.) |
Position of air | vent |
Air from room/
internal space |
Air direct
from outside |
---|---|---|---|
HIGH LEVEL | cm² | 100 | 50 |
(in²) | (16) | (8) | |
LOW LEVEL | cm² | 100 | 50 |
(in²) | (16) | (8) |
Position of air | vent |
Air from room/
internal space |
Air direct from outside |
---|---|---|---|
HIGH LEVEL |
cm²
(in²) |
133
(21) |
67
(11) |
LOW LEVEL | 0m² |
133
(21) |
67
(11) |
Position of air | vent |
Air from room/
internal space |
Air direct from outside |
---|---|---|---|
HIGH LEVEL | cm² | 166 | 83 |
(in²) | (26) | (13) | |
LOW LEVEL | cm² | 166 | 83 |
(in²) | (26) | (13) |
Position of air | vent |
Air from room/
internal space |
Air direct from outside |
---|---|---|---|
HIGH LEVEL | cm² | 200 | 100 |
(in²) | (30) | (15) | |
LOW LEVEL | cm² | 200 | 100 |
(in²) | (30) | (15) |
Position of air | vent |
Air from room/
internal space |
Air direct from outside |
---|---|---|---|
HIGH LEVEL | cm² | 264 | 132 |
(in²) | (40) | (20) | |
LOW LEVEL | cm² | 264 | 132 |
(in²) | (40) | (20) |
Boiler Size | NF 230 | NF 240 | NF 250 | NF 260 | NF 280 | |
---|---|---|---|---|---|---|
Boiler outpu | t kW | 8.8 | 11.7 | 14.7 | 17.6 | 23.4 |
Btu/h | 30 000 | 40 000 | 50 000 | 60 000 | 80 000 | |
Water flow | l/min | 11.4 | 15.2 | 19.0 | 22.8 | 30.3 |
rate | gai/h | 150 | 200 | 250 | 300 | 400 |
Pressure | mbar | 27 | 45 | - 70 | 102 | 92 |
loss | in.w.g. | 11 | 18 | 28 | 41 | 37 |
The boiler must NOT be used for direct hot water supply. The boiler is suitable for connection to fully pumped open
vented or sealed water central heating systems or central heating combined with indirect domestic hot water systems. The central heating system should be in accordance with
BS. 6798 and in addition, for Smallbore and Microbore systems, BS. 5449
The domestic hot water system, if applicable, should be in accordance with relevant recommendations to BS. 5546.
Copper tubing to BS. 2871: 1 is recommended for water carrying pipework.
The hot water storage cylinder MUST be of the indirect type and should be, preferably, manufactured of copper.
Single-feed indirect cylinders are not recommended and
The hot water cylinder and ancillary pipework, not forming part of the useful heating surface, should be lagged to prevent heat loss and any possible freezing, particularly where pipes run through roof spaces and ventilated under floor spaces.
Draining taps MUST be located in accessible positions, which permit the draining of the whole system, including the boiler and hot water storage vessel.
Draining taps should be at least 1/2 in. nominal size and be in accordance with BS. 2879.
The hydraulic resistances of the boilers, at MAXIMUM OUTPUT with an 11°C (20°F) temperature differential, are shown in Table 9.
Wiring external to the appliance MUST be in accordance with the current I.E.E. Wiring Regulations and any Local Regulations which apply.
The boiler is supplied for 240 V ~ 50 Hz
Single Phase
Fuse Rating is 3 A
The method of connection to the mains electricity supply MUST facilitate complete electrical isolation of the boiler, preferably by the use of a fused, unswitched three pin plug and a shuttered socket outlet, both complying with the requirements of BS. 1363.
Alternatively, a fused double pole switch, having at least a 3 mm (1/8 in.) contact separation in both poles and servicing only the boiler, may be used.
The point of connection to the mains should be readily accessible and adjacent to the boiler, except that for bathroom installations, the point of connection to the mains MUST be situated outside of the bathroom.
Note. Where a room sealed appliance is installed in a room containing a bath or shower then the appliance and any electrical switch or apppliance control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
16. Flue outlet sealing plate
13
The following minimum clearances must be maintained for operation and servicing. Additional space will be required for installation depending upon site conditions. In addition a minimum of 450 mm MUST be available at the front of the boiler for servicing. Side and Rear Flue Installations.
3. Once the boiler has been installed, the clearance on the non-flue side may be
Release the 2 bottom captive screws and lift the casing off the boiler. Place the casing safely to one side, taking care not to damage the glass fascia panel. (Slide the glass panel down in the casing for safe keeping.)
5 in. diameter
flue hole
SECTION SHOWING
Note. Check all of the hole
positions BEFORE drilling.
WALL THICKNESS, 'X'
Note. If the terminal is to
be sited within 25 to 40 mm
of a corner or vertical pipe
(refer to Table 3.) then the
hole MUST be accurately
cut and the rubber weather
seal trimmed around the
The terminal wall plate
aroove provided.
need not be fitted.
IMPORTANT. Ensure that, during the cutting operation, masonry falling outside of the building does not cause damage or personal injury.
5. Cooste two No. 10 x 2 in. screws in the wall mounting plate top fixing holes and screw home to within 6 mm (1/4 in.) of the wall sur face.
Check with a spirit level that the plate is vertical.
Align the holes in the sliding collar flange with the 3 cut-outs in the wall plate. Insert 3 of the self-tappers and rectangular washers to retain the ascence
FOR WALL THICKNESSES ABOVE 406 mm, REFER TO FRAMES 27 & 28 - FLUE EXTENSION DUCTS.
This plate is provided to allow the neat concealment and full compression of the rubber seal. If the flue hole and flue ducts have been accurately cut and the outside wall face is flat then its use is not essential except that this plate must be used on wall thicknesses over 610 mm (24 in.) .
ane 9
APPLIANCES FITTED WITH A REAR OUTLET FLUE: PROCEED DIRECT TO FRAME 29
IMPORTANT. Ensure that, during the cutting operation, masonry failing outside of the building does not cause damage or, personal injury.
plus 50 mm (2 in
position
washers, provided, to retain the flue assembly
rectangular washers, provided, to retain the assembly
Refer to the detail in Frame 22
____Self tapping screws. 6 off The flue assembly is shown locked in plate, insert 3 of the self tapping screws and rectangular
the rubber seal. Its use is not essential if the flue hole and flue ducts have been accurately cut and the outside wall face is flat except that this plate must be used on wall thickness over 610 mm (24 in.).
Secure the plate with four of the No. 10 x 2in. screws provided.
Note. If the terminal is less than 2 m (6.6 ft.) above ground level, an approved terminal guard should be fitted. Refer to Page 4.
(d) Reconnect the electrical leads and the pressure sensing tube to the fan.
PROCEED TO FRAME 29
Note. If the flue duct assembly locking screws restrict the sliding collar then use the collar locking screws to lock the whole assembly.
APPLIANCES FITTED WITH A REAR OUTLET FLUE: PLEASE REFER TO FRAME 11 (PAGE 9). APPLIANCES FITTED WITH A SIDE OUTLET FLUE: PLEASE REFER TO FRAME 21 (PAGE 12).
6. Using the sliding collar as a template at the joins of any ducts
mark the positions the fixing screws (3 screws for each joint).
Page 15
the meter to the boiler is greater than 3 m (10 ft.), it is recommended that 22 mm O.D. pipe is used.
3. To facilitate connection, it
is recommended that the
das service cock is not
removed from the gas
control valve. A 1/2 in. BSP x 15 mm connector prefitted with a short stub connection should be screwed into the cock using a suitable sealant. Ensure that the gas supply pipe does not foul the boiler casing when fitted.
IMPORTANT. The gas service cock contains a non-metallic seal, so must not be overheated when making capillary connections.
4. Test the gas installation for soundness and purge in accordance with BS. 6891.
1. Connect the system flow and return pipework to the two water connections at the top of the boiler.
Note. When the required output exceeds 16.1kW (55 000 Btu/h) 28mm (1in.) flow and return pipes should be used, both to and from the boiler. On the NF 260 boiler only connect to the boiler in 22mm (4/,in.) pipe and increase to 28 mm (1in.) as soon as is practicable.
2. Ensure that all valves are open, fill and vent the system and check for water soundness. Note:- This appliance is NOT suitable for use with a direct hot water cylinder.
When venting the heat exchanger using the manual ar vent on the flow header, protect the electrical controls with a waterproof sheet or similar.
Boiler size | NF 230 | NF 240 | NF 250 | NF 260 | NF 280 | |
---|---|---|---|---|---|---|
Boiler output | kW (Btu/h) | 8.8 (30 000) | 11.7 (40 000) | 14.7 (50 000) | 17.6 (60 000) | 23.4 (80 000) |
Water flow rate for 11 C differential | l/min. (gal./h) | 11.4 (150) | 15.2 (200) | 19.0 (250) | 22.8 (300) | 30.3 (400) |
Pressure loss for 11° C differential | mbar (in.w.g) | 27 (11) | 45 (18) | 70 (28) | 102 (41) | 92 (37) |
Water flow rate for 9 C differential | l/min. (gal./h) | 13.8 (183) | 18.5 (244) | 23.2 (306) | 27.8 (367) | 37.0 (488) |
Pressure loss for 9° C differential | mbar (in.w.g) | 40 (16.4) | 67 (26.9) | 105 (41.8) | 152 (61.2) | 138 (55) |
T NOT be more th
When the NF 260 (with output above 16.1kW [55 000 Btu/h]) and NF 280 units are used, 28mm (1in.) flow and return pipes MUST be used - both to and from the boiler.
The control system used with the boiler MUST provide a load in circuit with the boiler of at least 10% of the boiler output whenever the boiler fires. In order to achieve this load it may be necessary to provide 'uncontrolled' radiator(s) which cannot be manually turned off by the use
A by-pass MUST be fitted as far from the boiler as possible, consisting of the following:
(a) 15 mm pipe not more than 1 metre long for boilers up to 50 000 Btu/h output. (b) 22 mm pipe for boilers of over 60 000 Btu/h output. The by-pass should incorporate a balancing valve which CANNOT be adjusted by the househ
ξ
5. The circulating pump used should have adequate performance to give a maximum temperature differential across the boiler of 9°C when the by-pass & the 'uncontrolled' radiator(s) (when fitted) are closed, with either the heating or the dom etic bot water controls call
Thermostatic Radiator Valves
Caradon Heating Ltd. support the recommendations made in BS. 5449 and by leading manufacturers of domestic heating controls that heating systems utilising the full thermostatic radiator valve control of temperature in individual rooms should also be fitted with a roor thermostat controlling the temperature in a space served by radiators not fitted with such a valve.
Such an arrangement will provide for a potentially more efficient control of the environment and will also avoid the continuous running of the circulation pump during programmed heating 'ON' periods - thus saving electrical energy. It is therefore strongly recommended that, when thermostatic radiator valves are used, space heating temperature control over a living / dining area or a hallway having a heating requirement of at least 10 % of the boiler heat output is achieved using a room thermostat whilst other rooms are individually controlled by thermostatic radiator valves. If a rcom thermostat is not fitted as described above then it is recommended that the system includes in concerce of radiator has seen a melon in heat (see of 10% of the boiler heat output under design conditions.
A spring loaded safety valve complying with the relevant requirements of BS. 6759 must be fitted in the flow pipe as close to the boiler as possible and with no intervening valve or restriction. The valve should have the following features:
A pressure gauge covering at least the range 0 - 4 bar (0 - 60 lb.ft. / in2) must be fitted to the system. The gauge should be easily seen from the fitting point and should preferably be connected at the same point as the expansion vessel.
The cylinder must be either of the indirect coil type or a direct cylinder fitted with an immersion calorifier, which is suitable for operating on a gauge pressure of 0.35 bar (5 lb.ft. / in2) in excess of the safety valve setting. Single feed indirect cylinders are not suitable for sealed systems.
Provision must be made for replacing water loss from the system either,
There must be no direct connection to the mains water supply or to the water storage tank supplying domestic water, even through a non-return valve, without the approval of the Local Water Authority.
The system may be filled by one of the following methods:
(a) Through a cistern, used for no other purposes, via a ball valve permanently connected directly to a service pipe and / or a cold water distributing pipe.
The static head available from the cistern should be adequate to provide the desired initial system design pressure. The cold feed pipe from the cistern should include a non-return valve & a stop valve with an automatic air vent connected between them, the stop valve being located between the system & the automatic air vent. The stop valve may remain open during normal operation of the system if automatic water make-up is required.
(b) Through a self-contained unit comprising a cistem, pressure booster pump if required, and if necessary, an automatic pressure reducing valve and flow restrictor. The cistern should be supplied through a temporary connection from a service pipe or cold water distributing pipe.
This unit may remain permanently connected to the heating system to provide limited automatic water make-up. Where the temporary connection is supplied from a service pipe or distributing pipe which also supplies other 'draw-off' points at a lower level then a double check valve shall be installed upstream of the draw off point.
(c) Through a temporary hose connection from a draw off tap supplied from a service pipe under mains pressure. Where the mains pressure is excessive a pressure reducing valve shall be used to facilitate filling.
The following fittings shall form a permanent part of the system and shall be fitted in the order stated.
A stop valve complying with the requirements of BS. 1010 Part 2 (the hose from the draw off tap shall be connected to this fitting). A test cock.
A double check valve of an approved type.
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be less than that given by the table below multiplied by a factor of 0.8 (for flow temperatures of less than 88° C).
Safety valve setting | 3.0 bar | 3.5 bar | 3.5 bar | ||||||
---|---|---|---|---|---|---|---|---|---|
Vessel charge and initial system pressure |
0.5
bar |
1.0
bar |
1.5
bar |
0.5
bar |
1.0
bar |
1.5
bar |
0.5
bar |
1.0
bar |
|
Total water content of sy | ystem | Exp | ansion vesse | l volume (litr | res) | r | |||
25 ( | (litres) | 2.1 | 2.7 | 3.9 | 2.3 | 3.3 | 5.9 | 2.8 | 5.0 |
50 | 4.2 | 5.4 | 7.8 | 4.7 | 6.7 | 11.8 | 5.6 | 10.0 | |
75 | 6.3 | 8.2 | 11.7 | 7.0 | 10.0 | 17.7 | 8.4 | 15.0 | |
100 | 8.3 | 10.9 | 15.6 | 9.4 | 13.4 | 23.7 | 11.3 | 20.0 | |
125 | 10.4 | 13.6 | 19.5 | 11.7 | 16.7 | 29.6 | 14.1 | 25.0 | |
150 | 12.5 | 16.3 | 23.4 | 14.1 | 20.1 | 35.5 | 16.9 | 30.0 | |
175 | 14.6 | 19.1 | 27.3 | 16.4 | 23.4 | 41.4 | 19.7 | 35.0 | |
200 | 16.7 | 21.8 | 31.2 | 18.8 | 26.8 | 47.4 | 22.6 | 40.0 | |
225 | 18.7 | 24.5 | 35.1 | 21.1 | 30.1 | 53.3 | 25.4 | 45.0 | |
250 | 20.8 | 27.2 | 39.0 | 23.5 | 33.5 | 59.2 | 28.2 | 50.0 | |
275 | 22.9 | 30.0 | 42.9 | 25.8 | 36.8 | 65.1 | 31.0 | 55.0 | |
300 | 25.0 | 32.7 | 46.8 | 28.2 | 40.2 | 71.1 | 33.9 | 60.0 | |
Multiplying factors for o
system volumes |
ther | 0.0833 | 0.109 | 0.156 | 0.094 | 0.134 | 0.237 | 0.113 | 0.20 |
WARNING. This appliance MUST be efficiently earthed
A mains supply of 240V ~ 50 Hz is required.
All external controls & wiring MUST be suitable for mains voltage. Wiring should (Green/yellow) be 3-core PVC insulated cable, NOT LESS than 0.75 mm2 (24 x 0.2 mm) and to BS. 6500, Table 16. Wiring external to the boiler MUST be in accordance with the current I.E.E. Wiring Regulations and any Local Regulations.
The supply connection may be made via a removable plug to an unswitched shuttered socket/ outlet, preferably adjacent to the boiler, & should such a plug be used for connection to the mains, it must be of the 3-pin type-wired as shown, fused at 3A & comply with the requirements of BS. 1363. Alternatively, a fused double-pole switch, having a 3mm contact separation in both coles, parving poly the boiler & its external controls may be used.
External wiring MUST be in accordance with the current I.E.E. Wiring Regulations.
The wiring diagrams illustrated in Frames 40 to 42 cover the systems most likely to be used with this appliance.
For wiring external controls to the Ideal Elan 2 NF boiler, reference should be made to the systems wiring diagram supplied by the relevant Manufacturer in conjunction with the wiring diagrams shown in Frame 39.
Difficulty in wiring should not arise, providing the following directions are observed:
Advice on required modifications to wiring may be obtained from the component Manufacturers.
1. Connections between a frost thermostat and the time control should be made without disturbing other wiring.
.......................................
2. A frost thermostat should be sited in a cool place in the house, but where it can sense heat from the system.
WIRING DIAGRAMS
Page 22
WARNING. Whilst effecting the required gas soundness test & purging air from the gas installation, open all windows & doors, extinguish naked lights & DO NOT SMOKE.
F Gas sevice cock.
IMPORTANT. This appliance MUST NOT be operated with the casing removed.
Slide the fascia up until it locates in the retaining
Secure the bottom two captive screws.
The casing MUST seat correctly and compress the sealing strip to make an airtight joint. If side the clearance is limited then this may be checked by ensuring that the top and bottom edges of the casing are correctly located
Check that the pilot flame envelops the igintion / detection electrode. If the pilot flame appears incorrect then refer to Frame 8 'Servicing', Note. The pilot flame is factory set and no adjustment is possible
Continued from Frame 45.
burner or circulating pump, as the case may be, responds.
Knob Setting | Flow Te | mperature |
---|---|---|
°C | ۴ | |
1 | 54 | 130 |
2 | 60 | 140 |
3 | 66 | 150 |
4 | 71 | 160 |
5 | 77 | 170 |
6 | 82 | 180 |
Advise the User of the precautions necessary to prevent damage to the system and to the building, in the event of the system remaining inoperative during frosty conditions.
To ensure the continued safe and efficient operation of the appliance, it is recommended that it is checked at regular intervals and serviced as necessary. The frequency of servicing will depend upon the installation condition and usage, but should be carried out at least annually. It is the law that any service work must be carried out by a competent person.
The servicing procedures are covered more fully in Frames 2 to 8 and must be carried out in sequence.
WARNING. Always turn off the gas supply at the gas service cock and and switch off & disconnect the electricity supply to the appliance before servicing.
IMPORTANT. After completing the servicing or exchange of components always test for gas soundness and carry out functional checks as appropriate.
Note. In order to carry out either servicing or replacement of components, the boiler casing must be removed (Frame 2). IMPORTANT. When work is complete the casing MUST be
correctly refitted, ensuring that a good seal is made. DO NOT OPERATE THE BOILER IF THE CASING IS NOT FITTED.
1. Remove the wing nut securing the burner front support bracket. Remove the M5 pozi screw situated at the left hand, bottom rear of the burner & pull the burner downwards in
3. Remove the two securing screws, slide the bottom panel forward slightly, and then sideways to remove from the casing.
1. Stacken the 4 wing nuts, disengage the tie rods and remove the flue collector hood.
Place a plastic sheet, or similar, beneath the boiler and remove all loose deposits from the heat exchanger finned block and copper skirt using a suitable brush and / or clearing rod - brushing from above and below.
Re-assemble the boiler in the following order:
1. Refit the flue collector hood - renewing any damaged or deteriorating sealing gasket.
Note. Enter the horizontal tie rods, with the hooks vertical, through the collector hood slots and engage in the holes in the retention angle.
IMPORTANT. When work is complete the casing MUST be correctly re-fitted. Ensure that a good seal is made.
PILOT Light the boiler and check that the pilot flame envelopes the ignition / detection electrode.
The pilot is factory set to maximum and no further adjustment is possible. However, if the pilot flame length is incorrect then remove and inspect the pilot injector. Refer to Frame 13. Relight in accordance with 'Initial Lighting'. Refer to Frame 46 'Installation'.
After any servicing, reference should be made to Table 2 which quotes details of the rated output with the related burner setting pressure and the heat input. Any required adjustments should be made by using the pressure adjustment screw. Refer to 'Initial Lighting', Frame 46 'Installation'.
9 GENERAL | When replacing any component: | Note. In ore | er to assist fault finding the control box printed circuit board is | |
---|---|---|---|---|
1. Isolate the electricity supply. | fitted with 4 indicator lights which represent the following boiler conditions: | |||
2. Turn OFF the gas supply | Neon i1. | Air pressure switch made. | ||
3. Remove the boiler casing. Refer to Frame 2. | Neon 12. | Boiler thermostat calling for heat. | ||
IMPORTANT. When work is complete the casing MUST be
correctly refitted, ensuring that a good seal is made. |
Neon 13. | Mains electricity ON. | ||
Neon SG1 | Flashes to indicate spark operation (stops after detection). | |||
τ | he boiler MUST NOT be | operated | if the casing is not fitted. |
REPLACEMENT OF PARTS
ate. Also refer to Frame 26 of 'Exploded Views' for illustration of the procedure detailed below.
9. Check the boiler operation.
Pressure switch
REPLACEMENT OF PARTS
Front nanel
ol box lid
Thermostat switch
Page 30
1. Refer to Frame 9.
2. Drain down the system and heat exchanger.
. Daar ar
Note. Ensure that the casing is correctly sealed -compressing the sealing strip to make an airtight joint. If side clearances are limited, then this can be checked by ensuring that top and bottom edges of the casing are correctly located.
11. Sat the ornorammer to the desired occoramme & test its indigits
EXPLODED VIEWS
_____
The following list comprises parts commonly required as replacement components due to damage, expendability, or such that their failure or absence is likely to affect safety or performance. The list is extracted from the British Gas List of Parts, which contains all available spare parts.
Details of the British Gas Lists are held by Gas regions, CARADON Distributors and by Merchants.
When ordering spares please quote:
Key No. | G.C. Part No. | Description | No. Off | Product Code No. |
---|---|---|---|---|
З | 319 493 | Sightglass assembly kit. | 1 | 079 333 |
5 | Main burner. | |||
386 235 | 386 235 AEROMATIC No. AC 19/123 278; NF 230 | 113 207 | ||
386 236 AEROMATIC No. AC 19/123 279; NF 240 | 1 | 113 208 | ||
386 233 AEROMATIC No. AC 19/123 276; NF 250 & NF 260 | 1 | 113 209 | ||
386 234 | AEROMATIC No. AC 19/123 277; NF 280 | 1 | 113 210 | |
6 | Main burner injector. | |||
398 315 | BRAY Cat. 16 - size 750; NF 230 | 1 | 002 773 | |
398 339 | BRAY Cat. 16 - size 1100; NF 240 | 1 | 003 279 | |
398 329 | BRAY Cat. 16 - size 1400; NF 250 | 1 | 003 962 | |
398 332 | BRAY Cat. 16 - size 1700; NF 260 | 1 | 003 213 | |
398 066 | BRAY Cat. 10 - size 2400; NF 280 | 1 | 004 444 | |
8 | 308 347 | Pilot burner. HONEYWELL Q 359 A 1124 | 1. | 079 599 |
9 | Pilot burner injector. | |||
386 131 | HONEYWELL 45900421 - 001; NF 230 & NF 240 | 1 | 004 981 | |
386 150 | HONEYWELL 45900421 - 002; NF 250, NF 260 & NF 280 | 1 | 004 982 | |
10 | 308 359 | Gas control valve. | ||
HONEYWELL VR 4700 E 1042, 240 V | 1 | 079 600 | ||
11 | 308 281 | Control box, including control thermostat potentiometer, | ||
control thermostat, sensor lead, control thermostat knob | ||||
40 | and mains ON / OFF switch. | 1 | 137 656 | |
12 | 308 317 | Ignition electrode. VERNITRON No. 1414 | 1 | 113 172 |
15 | 386 149 | Automatic ignition printed circuit board. | ||
PACTROL P.C.B. No. 25B | 1 | 079 716 | ||
16 | 386 802 | Control thermostat ON / OFF switch. | 1 | 004 882 |
17 | 308 285 | Pressure switch, BECK 911.81 L | 1 | 137 990 |
18 | 397 910 | Control thermostat potentiometer. | 1 | 137 661 |
. 18 A | 308 357 | Control thermostat sensor lead. | 1 | 137 658 |
18 B | 308 283 | Control thermostat knob. | 1 | 079 601 |
20 | 386 675 | Overheat thermostat, RANCO LM 7. | 589 930 056 | |
21 | 386 686 | Fan assembly. | 009 930 036 | |
SIFAN FFB 0224 - 004 or SEL RL 108/0034 - 3030 L H | 1 | 126 729 | ||
26 | Boiler casing assembly - white stove enamel with | · 1 | 130720 | |
sightglass, foil insulation & bottom panel (less glass fascia). | · | |||
308 372 | Ideal Elan 2 NF 230, NF 240, NF 250 & NF 260. | 198 934 035 | ||
308 408 | ideal Elan 2 NF 280. | 1 | 137,989 | |
27 | Controls casing bottom panel. | |||
308 373 | Ideal Elan 2 NF 230, NF 240, NF 250 & NF 260. | 1 | 079.612 | |
308 409 | Ideal Elan 2 NF 280. | 1 | 079 613 | |
28 | 308 374 | Glass fascia. Ideal Elan 2 NF 230, NF 240, NF 250 & NF 260. | 1 | 137 900 |
· | 308 383 | Ideal Elan 2 NF 280. | 1 | 137 904 |
30 | 308 058 | Casing seal. Ideal Elan 2 NF 230 NF 240 NF 250 2 NF 260 | 070 520 | |
308 059 | Ideal Elan 2 NF 280. | 079 532 | ||
1 | 019 233 |
These appliances are designed for use with Natural Gas only. They have been tested and conform with the provisions of BS. 6332 and BS. 5258.
Products bearing this Kitemark are made to a safety and performance standard under a stringent scheme of supervision and control monitored by the British Standards Institute.
CARADON IDEAL Ltd. pursues a policy of continuing improvement in the design and performance of its products. The right is therefore reserved to vary specification without notice.
P.O. Box 103, National Avenue,
Registration No. London 322 137.
Kingston upon Hull.
North Humberside. HU5 4JN.
Telephone: 01482 492 251
Fax: 01482 448 858
Registered Office; National Avenue, Kingston upon Hull, North Humberside. HU5 4JN.
A subsidiary of Caradon p.I.c
August 1994 116 799 A07
Please use the following numbers for speedy assistance.
Spares Tel: 01482 498 643 |
---|
Customer Care & |
Technical Support Tel: 01482 498 610 |
Publications/literature Tel: 01482 498 467 |